KW

51 N

KW

Out Supply

400 A, 400 V

81 O

400 Volts, Unit Protection Panel 01

51

F
400/110 V

OPEN CLOSE

M
150 A

200/5

3 x 150
1 x 95

G1

200/5

150 KVA, 400 V, 3 , 50 Hz.

11 KV Feeder Out

400/11000 V, 300 KVA, 3

25 SYNCHROCHECK

400/110 V

DC EXCITATION

Generator Protection:
i. In built: Earth Fault, Short Circuit,
Thermal Overload, Under voltage 400 Volt
panel for generator 2 is identical to that of
Generator 01.
ii. G1 and G2 are identical.
iii. Number of radial feeders to be taken out
shall be determined later.

G1

Implementing Agency

Azad Jammu & Kashmir


Power Development
Organization

Project Name

Development &
Dissemination of
Small Hydropower
Stations (Phase-I)

Figure

Single Line Diagram for


240 KW Kharigam Micro
Power Station

Drawn By:
Jawad Usmani
Assistant Engineer

Designed By:
Shafiq Ahmed Usmani
Dy.Director (O&M)
Neelum Valley

Note:This single line diagram is meant only for


conceptual purpose and may not be used for
installation.