Undervoltage release
This release is used to:
Trip the Compact NSX circuit breaker when the supply voltage is less than 0.35 times
nominal voltage Un.

If the voltage is between 0.35 and 0.7 times the rated voltage Un, opening is possible but
not guaranteed. Above 0.7 times the rated voltage Un, opening is impossible.
Close the circuit breaker again once the voltage reaches 0.85 times the rated voltage.
This type of voltage release is used for failsafe emergency stops.

MX release

This release causes the Compact NSX circuit breaker to open on the appearance of a voltage
exceeding 0.7 times the rated voltage.