Tablero F
MOTOR
Ind.
Ind.
Ind.
R.D
R.D
R.D
R.D
10 HP
10 HP
10 HP
5 HP
5 HP
15 HP
1 5 HP
I nominal
(Amp)
14
14
14
7.6
7.6
21
21
Desconectador
(1.15 x In)
16.1
16.1
16.1
9
9
24.1
24.1
30
30
30
20
20
30
30
Overload
(1.15 x In)
1.25xIn
17
17
17
10
10
25
25
18
18
18
10
10
27
27
Circuito Ramal
Conductores
3C#12 THHN + 1C#10AWG 1 tubo PVC de
3C#12 THHN + 1C#10AWG 1 tubo PVC de
3C#12 THHN + 1C#10AWG 1 tubo PVC de
3C#12 THHN + 1C#10AWG 1 tubo PVC de
3C#12 THHN + 1C#10AWG 1 tubo PVC de
3C#10 THHN + 1C#10AWG 1 tubo PVC de
3C#10 THHN + 1C#10AWG 1 tubo PVC de
Protecciones De 3p
T.I
2.5 x In 35
40
2.5 x In 35
40
2.5 x In 35
40
1.5 x In 12
20
1.5 x In 12
20
1.5 x In 32
40
1.5 x In 32
40
40 + 78.2 = 118.2
104.5 A 3 C# 2 THHN + 1 C# 6 AWG 1 tub PVC de 1 de dimetro
118.2A
110 A/3p
PROT DE
3P T.I.
1.25 X In
In (Amp)
TA
752
TF
99.2
IP
851.2
TX
P=1.73VI
I=851.2
940 A
(21X1.25 + 78.2)=
104.5 A
851.2X1.25 =
1064 A
800
104.5
110
899.2
1000
V=480
Corriente en el tablero TA es 940 A..........utilizando un cable de 500 kcmil que maneja 380 A, 940/380= 2.47 cables......se
utilizaran 3 cables 500 kcm
Corriente del IP es 1064 A..........utilizando un cable de 500 kcmil que maneja 380 A, 1064/380= 2.8 cables......se utilizaran 3
cables 500 kcm
Calculo en la proteccin 800+99.2= 899.2 A 1000 A /3P
CARGAS In (Amp)
TB
92
TC
41
IP
133
TX
P=1.73VI
I=133
PROT DE 3P
T.I.
V=208
100
50
141 A
150
CAIDAS DE VOLTAJE
Vc= 2IL/1000
Resistividad:
Resistividad:
CORRIENTE DE CORTOCIRCUITO
Se puede utilizar tableros de 20 000 (todos los elementos con capacidades de 20 000)
BANCO DE CAPACITORES
BANCO DE CAPACITORES
DIAGRAMA UNIFILAR