08
Single Core PVC Insulated Cables in Conduit Or Trunking at an Air Temperature of 45 C
mm
Current Rating
Amperes
2 Cables Single
Phase
Voltage Drop Per
Ampere Per Meter
Mv
Current Rating
Amperes
3 Or 4 Cables Three
Phase
Voltage Drop Per
Ampere Per Meter
Mv
1.5
2.5
10
16
25
35
50
70
95
120
150
185
240
300
400
14
19
25
33
44
60
80
100
114
150
182
205
250
277
350
402
486
27
16
10
6.8
4.0
2.6
1.6
1.2
0.97
0.71
0.56
0.48
0.41
0.38
0.37
0.36
0.34
12
17
23
30
41
53
70
90
100
140
170
200
215
250
300
350
407
23
14
8.8
5.9
3.5
2.2
1.4
1.0
0.84
0.62
0.48
0.42
0.39
0.36
0.35
0.34
0.33
All cables to be of 600/1000 Volts grade. Solid conductors permitted only in the case of 1.5 mm and 2.5 mm cable.