Table No.

08
Single Core PVC Insulated Cables in Conduit Or Trunking at an Air Temperature of 45 C
mm
Current Rating
Amperes
2 Cables Single
Phase
Voltage Drop Per
Ampere Per Meter
Mv
Current Rating
Amperes
3 Or 4 Cables Three
Phase
Voltage Drop Per
Ampere Per Meter
Mv

1.5

2.5

10

16

25

35

50

70

95

120

150

185

240

300

400

14

19

25

33

44

60

80

100

114

150

182

205

250

277

350

402

486

27

16

10

6.8

4.0

2.6

1.6

1.2

0.97

0.71

0.56

0.48

0.41

0.38

0.37

0.36

0.34

12

17

23

30

41

53

70

90

100

140

170

200

215

250

300

350

407

23

14

8.8

5.9

3.5

2.2

1.4

1.0

0.84

0.62

0.48

0.42

0.39

0.36

0.35

0.34

0.33

All cables to be of 600/1000 Volts grade. Solid conductors permitted only in the case of 1.5 mm and 2.5 mm cable.