izing Separators
e speed with which operators can
rect upsets is included in these
jesign considerations
SEPARATORS AND ACCUMULATORS should be sized on the
sis of the minimum possible volume consistent with
easonable operating flexibility. The term “reasonable”
related to the time in which operating personnel can
nse and correct a process upset around a fractionator
x other processing equipment. The lag time between
snsing and correcting trouble is dependent upon the
yype of operating personnel in the unit and the degree
f sophistication of the instrumentation.
LIQUID ACCUMULATORS
Hower Reflux-Distillate Accumlators. The manner in
which certain factors influence a design is shown in the
following examples which are based on Fig. 1. The
jtower is operating on flow controlled reflux with prod-
luct withdrawal on level control. A temperature recorder
provided at a tray below the top tray for reference
in operating. If there is a failure of the reflux pump, the
required surge time will be different due to the various
types of instrument schemes utilized. Consider the fol-
lowing
Primary Element Alarm, The low flow alarm will
found almost immediately. The operator will check the
FRC module on the panel to confirm low flow or will
lcheck the pump running light if one has been provided,
This should take about 30 seconds. He will then go to
the equipment and start the spare pump. Assuming that
the control room is immediately adjacent to the unit,
this operation will take about two minutes. Since the
latter time will be greatly dependent upon the plot plan
and/or the physical condition of the operator, this point
will require careful study with each design.
November 1967, Vol. 46, No. 11
and Accumulators
Since two and one-half minutes have been used in
this operation, the minimum vessel volume is five min-
utes volume (of reflux plus distillate) based on half-
full normal operation. It is necessary to design for half
full operation to provide flexibility for the case of loss
of level as well as level increase.
Secondary Element Alarm. The instrumentation func-
tions in such a way that there will be a short lag be-
tween the beginning of an upset condition and the
sounding of an alarm. This arrangement is necessary to
mo)
Fig. 1—There is a short lag between the beginning of an
upset and the sounding of some alarms.
Fig. 2—A bridlemounted controller saves vessel nozzles
and gives control over full vessel volume.
253SIZING SEPARATORS AND ACCUMULATORS . .
avoid constant alarms due to minor fluctuations. As an
approximation, the condition should exist for about 30
seconds before reaching the alarm point. For this ex-
ample, pump failure results in a level increase. Thirty
seconds after failure, the alarm sounds, giving the op-
erator 30 seconds t0 locate the trouble on the board
‘The time required for field remedial action will be the
same as discussed under “primary element alarm.”
If the secondary clement were a temperature alarm
at some tray below the reflux tray, an even greater
lag time before alarm will exist. Normally, the control
point will be within five trays from the top. Allowing
a lag of 10-15 seconds per tray, about 60 seconds will
ppass between inception of upset and sound of alarm,
‘Another 30 seconds will be required to identify trouble
fon the board followed by field remedial action.
‘These two cases clearly show the influence of instru-
mentation and labor factors on the actual design of
equipment and clearly point out the fallacy behind any
arbitrary rules in reference to surge volumes. For the
cease of high level alarm, the vessel size should be seven
minutes full.
Note that the word “full” means total vessel volume,
heads excluded, and does not refer to the control range
of a level control element. Use of the latter standard to
define volumes will result in excessively large vessels.
This definition does not preclude level control over
the full vessel volume. This can be accomplished by use
of bridle-mounted controllers which, in addition, saves
vessel nozzles. A typical installation is shown in Fig. 2.
‘The most difficult factor to evaluate here is labor.
Sharp, conscientious personnel can easily meet the re-
quirements outlined above, On the other hand, lazy or
untrained personnel will require considerably more time
to locate and remedy trouble. If a unit is unattended,
TABLE 1—Design Criteria for Refex Distillate Accomulators
Minutes
These design times represent adequate surge volume and
2ctually are somewhat fat. Ina highly competitive situation,
Ris recommended that the labor factors be cut by 80%
TABLE 2—Operating Factors for Externol Uni
Operating Characteristics Factor
Under good control 20
Under fair contrat 30
Under poor contro! 40
Feed to or from storage 125
Note: These factors assume that there is @ board-mounted
level recorder. i this ts not s0, the following additional
multiplying factor must be ‘applied:
‘Level indicator on board 15
Gauge glass at equipment only 20
254
these criteria do not apply and must be evaluated on
an individual basis.
‘Table 1 illustrates the recommended design surge times
for these vessels.
As an example, size an accumulator for a butane
splitter in a grass roots gasoline plant in North Dakota
Column control is reflux on FRC and distillate with
drawal on LG with high level alarm.
Inst, factor = 1 min.
Labor factor = (likely to be inexperienced but also
probably eager.) = 3 min,
Vessel size = 4 min., half-full.
Surge Volumes for Unit Feed and Product Streams.
To provide for smooth operation, it is advisable to pro-
Vide surge capacity for feed and product streams be-
cause of the degree of uncertainty in the operation of
other units, These volumes are determined by the labor
and instrument factors which were discussed in the pre-
‘vious section but also by an additional operating factor
which considers the reliability of the external unit either
from an operating or control viewpoint.
This operating factor must consider the external unit
and its operation, its instrumentation and response to
control, the efficiency of its labor, any chronic mechan-
ical problems, possibility of short or long term interrup-
tions, and any other information that may be available,
‘The procedure for sizing this type of surge drum con-
sists of estimating the proper parent unit instrument and
ig a multiplier which re~
factors for continuously operating extemal units which
are under the control of separate operators are given in
‘Table 2. Note that the vessel surge volume subject to the
‘mechanical factor is the product stream only and is not
to be applied to any internal streams within the parent
For an example, size a reflux accumulator for a de-
propanizer to be installed in an existing large refinery
gas plant. Assume 900 gpm of reflux is pumped back
fon temperature control, Also, 500 gpm of product pro-
pane is fed to a new ethylene unit. Product flow is on
level control with unit alarm,
From Table 1,
Inst. factor
Labor factor
From Table 2,
External operating factor (good control) = 20
Volume = 4 min. reflux +20 (4 min. of produet)
3600 + (20% 2000) = 7600 gal., half-full
For cases where the external unit is subject to wide
variations in rates or is a batch operation, special case-
by-case judgment must be applied,
2 min., half-full
2min., half-full (good labor)
VAPOR-LIQUID SEPARATORS
‘These vessels usually serve two functions. The primary
job is to separate vapor and liquid but they may also
serve as liquid surge drums. The basic principle of design
Hyprocarnow Processinvoo6
0.4
oz
0.08
0.06
0.04
0.02
0.006 8 0.01 2 a) e001
(Wa Wo ) VP v/Pp
Fig. 3—Design vapor velocity factor for vertical vaporiiquld separators at 85% of flooding.
is to provide a sufficiently low velocity so that vapor and
liquid will separate. The designer must also design the
surge volume properly. As a general rule, a vessel which
is to provide a large surge volume such as an atmospheric
tower accumulator will be a horizontal drum. A vessel
which provides only a small surge volume such as a com-
pressor interstage knockout drum will be a vertical vessel.
‘The vapor velocity factor chart is based on five percent
of the liquid being entrained with the vapor. This is ade-
quate for normal design. For design where entrainment
must be less, the use of a demister section is recom
mended. ‘These will guarantee a maximum entrainment
of one percent. The principal use of these devices is in
compressor suction drums and product gas separator
Calculation Method—Vertical Drum.
‘Step 1. Calculate the vapor-liquid separation factor
(WW) Voi
Step 2. From Fig. 3 find the design vapor velocity fac-
tor Ky, and calculate the maximum design vapor velocity
(0) mae = Ky Vi = 6) ft. /s00
and should not be
Note that this is a design veloci
derated.
Step 3. Calculate the minimum vessel cross sectional
Amin = Wel (He) ae 0M
‘Step 4. Set vessel diameter based on 6-inch increments.
Pain = V opin? ft
D=Dig 19 next largest Ginches
100/,/ Pais f/s0:
60 Pa fee
Step 6. Make preliminary vessel sizing as in Fig. 4
Step 7. From Table 1 or Table 2, select the appropriate
full surge volume in seconds. Calculate the required ves-
sel volume
V = Qj/ design time to fl), cw. fe.
‘Then liquid height is
H,=V (4/4 D8)
Step 8. Check geometry
(H,-4H,)/D must be between 3 and 5.
For small volumes of liquid, it may be necessary to pro
vide more liquid surge than is necessary to satisfy the
L/D > 3. Otherwise, this criteria. should be observed.
If the required liquid surge volume is greater than that
possible in a vessel having L/D <5, a horizontal drum
must be provided.
Calculation Methed—Horizontal Drum.
Step 1. Calculate
(WW dV Pe
Step 2. For horizontal vessels using Fig. 3
Ky =125 KySIZING SEPARATORS AND ACCUMULATORS . ..
36"++ (FEED NOZZLE 0.0)
48° MIN.
FEED NOZZLE
(FEED NOZZLE 0.0)
Is" MIN.
MAX. LEVEL,
Fig. 4—An example is given to show how to calculate the
‘dimensions of a vertical separator.
Step 3.
(46) mae = Ky Vy — Pe) Pe ft. /s0e.
‘Step 4. Calculate the required vapor flow area
(Ae) nin = Qo/ (te) maa 84
‘Step 5. From Table 1, select the appropriate design
surge time and calculate full liquid volume. The remain
der of the sizing procedure is done by trial and error as
in the following steps.
Step 6. When the vessel is full,
Arotat nin = (Ap) nn/ 02
Dayin = V WA cota nin Mt.
Step 7. Calculate vessel length
Fall Liquid Volume
(H/F
D=Dyig to the next largest G-inches.
Step 8.15 < (L/D) < 3, resize
About the author
RN. Warxins ia a process engineer
for The Fluor Corp., Lta., Houston,
Texas, where he does process design of
petroleum, petrochemical and natural
asoline processing plants. He holds
B. 8. degrees in chemistry and. chemi-
cal’ engineering. Br. Watkine aloo has
worked for Monsanto Coy Celanese
Chemical Co. and Bechtel Corp. He is a
registered professional engineer and a
member of AICKE.
MECHANICAL DESIGN ASPECTS
To this point, the discussion has been devoted to de-
termining the required volume of a vessel and rough
ing its dimensions. The principle physical criterion
specified has been that length-to-diameter ratio shall be
between 3 and 5. It is possible for the process engincer
to make some simple vessel design calculations and opti-
mize the accumulator dimensions. This is based on the
fact that, as diameter decreases, shell thickness decreases
and vessel length increases. At some point between L/D
ratios of 3 and 5, a minimum vessel weight will occur
and this will result in minimum cost,
The following example is based on a depropanizer ac-
ccumulator:
Operating conditions: 100° F and 200 psig
Design conditions: 650° F and 225 psig
Material of construction: SA-285C
Allowable stress: 13,750 psi
{Joint efficiency: 85’ percent
Corrosion allowances: -inch
Total volume: 2,157 en. f.
va =DL/s
Use 30 ft.
Shell thickness = (press. (radius) /[ (stress ~ 0.6(press.)}
“+ corrosion factor.
= (225) (57)/[(0.85) (18,750) — (0.6) (225)]
+0.125
= 1.295 in. Use 16-inch plate
Shell weight
We, = 56,880 Ib.
ALL/D:
D=AB? he Use 9 ft
177 in, Use 1%4 in, plate
7,798 Tb.
13 ft. Use. 8 ft.6 in
38.01 fe. Use 38 ft.
1.118 in. Use 1% in. plate
We. = 53,802 Ib.
‘Thus the design with L/D = gives the lowest cost
NOMENCLATURE
Vessel crow-secton area, sq
Vessel diameter, fe
Yeret height
fspor velocity factor
Wesel length, te
Flow rate, ev. fe/tec,
‘Vesel thickness, in.
Fluid velocity, fe /tec.
Vessel volume, cw. fe
Flow rate, Ib./ste
‘Vessel welght, Ib,
Density, Is/eu. fe
SUBSCRIPTS
> Sexe .onazea.
Rae
Diameird, Es
Shine Sain