Relief Cases
When determining the relief requirements for atmospheric storage tanks there are seven independent
cases. They are:
1.
1.
1.
1.
1.
1.
1.
Inflow
Outflow
External Fire
Steam Coil Rupture
Liquid Overfill
Chemical Reaction
Steam Out
The following are contributions that are used in combination to determine the loads required for each
case:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
Liquid Movement In
Liquid Movement Out
Thermal Out Breathing
Thermal In Breathing
Fire Exposure
Pressure Transfer Blow-through
Fail Open the Nitrogen Padding System
Failure or loss of Control of Heat Transfer Devices; loss of heating/cooling utility or instrument air.
Failure of Internal/External Heating/Cooling Coils
Failure of Vent Vapor Collection System
Chemical Reaction
Steam Out
Table 1 shows which contributions need to be considered when calculating each Case.
Page 1 of 11
Art Montemayor
Relief Devices
1. Conservation Vents - These are Pressure Vacuum breather valves. They may be used as final
pressure and/or vacuum relief or for normal pressure control on atmospheric tanks.
1. Emergency Vents - These devices are like conservation vents except that they only have the
pressure side. They may be used to supplement the conservation vent(s) when additional capacity is
needed to meet a large pressure relief load while additional vacuum relief is not needed. They can
take the inexpensive form of simple, weighed blind flanges on top of a tank roof nozzle; the blind
cover flange is often hinged or chained in order to avoid a hazard with the cover being expelled.
1. Fire Hatches - These devices may be used in the same cases as Emergency Vents. These devices are
usually weighed down and swing open when over-pressured. They will not re-seal after the relief
venting is complete. Because of this feature, their relief capacity is restricted to mitigate the Fire,
Coil Failure, and Chemical Reaction contributions. Other devices must be available to provide relief
for all of the other contributions.
4. Pipe Away Vent Valves - These are like Emergency or Conservation Vents with a piping flange on
the outlet. They are used to connect tanks to environmental control devices where the pressure in the
tank is the driving force pushing the vapors through the piping and environmental control device.
These devices are usually not considered as relief devices; however, their capacity can be considered
as contributing to a relief scenario if there are no block valves or control valves between the Pipe
Away Vent Valve and the atmosphere or all block valves are locked open and there are no control
valves. If their capacity is considered, calculations will need to be made to de-rate the capacity due
to back pressure effects of the down stream piping and other equipment.
Page 2 of 11
Art Montemayor
Table 1
Pressure Relief Cases for Atmospheric Storage Tanks
1
Inflow
(Pressure)
Contributions:
1. Liquid / Vapor In
1. Liquid Out
1. Out Breathing
1. In Breathing
1. Fire Exposure
1. Pressure Transfer
1. N2 Regulator Failure
1. Loss Heat Transfer
1. Coil Failure
1. Vent System Failure
1. Chemical Reaction
1. Steam Out
2
Outflow
(Vacuum)
3
Fire
Case:
4
Coil
Rupture
5
Liquid
Overfill
6
Chemical
Reaction
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Note 3
9.a)
9.b)
11.b)
11.b)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
8.b) & c)
8. a) & d)
10.b)
10.a)
Yes
Note 1
Note 2
11.a)
11.c)
Yes
Notes:
1.
2.
3.
7
Steam Out
(Vacuum)
Page 3 of 11
Art Montemayor
Factor, SCFH/GPM
17.14
8.57
Page 5 of 11
Art Montemayor
Factor, SCFH/MGAL
23.81
14.29
4. Thermal In-Breathing
Per API 2000. Table 2 in API-2000 is used to determine the thermal in breathing based on the capacity
of the tank. For tanks less than 840,000 gal capacity, the factor is 23.81 SCFH / MGAL. For tanks
larger than 840,000 gal, refer to Table 2 in API-2000.
5. Fire Exposure
Per API 2000
6. Pressure Transfer Blow-through
a) For tanks that are not expected to be unloaded into, the vapor rate is the flow capacity of two
(2) 1 by 20 foot utility hoses with a pressure drop of the maximum nitrogen header gauge
pressure. One 1 (3/4 ID) by 20 utility hose can pass 18,825 SCFH of nitrogen.
b) For tanks where unloading is expected, use the greater of (a) above or the sum of one (1) 1
by 20 foot long utility hoses with a pressure drop of the maximum nitrogen header gauge
pressure and the unloading line size with the pressure drop as the maximum gauge pressure
rating of the shipping container to be used.
7. The Nitrogen Padding System Fails Open
Calculate the flow capacity of the flow limiting device using the maximum nitrogen header gauge
pressure for the pressure drop. For padding systems that have a step down regulator, the step down
regulator will almost always be the flow limiting device.
Page 7 of 11
Art Montemayor
8. Failure or loss of Control Heat Transfer Devices; loss of heating/cooling utility or instrument
air.
This contribution covers loss of heating, excessive heating, loss of cooling, or excessive cooling and
must be determined on a tank by tank basis. These failures can be caused by failures in the control
systems, measurement instruments, control valves, instrument air, and the loss of the heating or cooling
utility.
a) Loss of heating - determine the in breathing required if heating were lost. This will probably
be a transient inflow until equilibrium is reached.
b) Excessive heating - determine the out breathing required at full heating. The steam control
valve usually limits this. This will probably be a continuous condition.
c) Loss of Cooling - determine the out breathing required if cooling were lost. This could be a
transient and continuous condition.
d) Excessive Cooling - determine the required in breathing if the cooling were to fail to
maximum. This will probably be a transient inflow until equilibrium is reached.
9. Failure of Internal/External Heating/Cooling Coils
This contribution covers a mechanical failure of a heat transfer device.
a) For tanks with heating coils, determine the flow capacity of the flow-limiting device fully
open. If the flow-limiting device is a control valve, use the largest trim available for the
valve body. Also, add the capacity of any bypass valves. An alternate to using the largest
trim for a control valve is to use the actual trim size and affix a metal tag to the valve
indicating that a safety device rating is dependent on the trim size. Determine the vapor
generated by vaporization of the product or by the steam itself - whichever is greater.
b) For tanks with cooling coils, determine the flow capacity of any flow-limiting devices. If
there are no flow-limiting devices perform a reasonable pipe pressure drop calculation,
taking into consideration that the return line can potentially contribute to the inflow.
10. Failure of Vent Vapor Collection System
a) For vacuum relief, this pertains to any failure in a vapor collection system that can cause the
system to pull excessive vapors from the tank. Calculate the flow capacity of the flowlimiting device. For systems that vent through a vacuum device that can pull down below the
vacuum rating of the tank, calculate the vapor flow at the pressure where the capacity of the
vacuum device equals the full open capacity of the vent valve. Use Atmospheric pressure for
the upstream pressure of the vent valve. Do not take credit for pressure losses in the piping
or any nitrogen from a padding system.
b) For pressure relief, if the vacuum-producing device discharges into a header that can have a
pressure higher than the pressure rating of the tank, the back flow case must be considered in
the event of the failure of the vacuum-producing device. For this case calculate the capacity
of the vent valve using the maximum anticipated vacuum producing device discharge header
gauge pressure as the pressure drop. Do not take credit for check valves or piping losses.
Page 9 of 11
Art Montemayor