Fault Analysis

Symmetrical Components

Fault Analysis
The cause of electric power system faults is
insulation breakdown
This breakdown can be due to a variety of
different factors:
Lightning.
wires blowing together in the wind.
animals or plants coming in contact with the
wires.
salt spray or pollution on insulators.

Fault Types
There are two main types of faults

Symmetric faults: system remains balanced; these faults


are relatively rare, but are the easiest to analyze so well
consider them first.
Un-symmetric faults: system is no longer balanced; very
common, but more difficult to analyze.

The most common type of fault on a three phase system by


far is the single line-to-ground (SLG), followed by the line-toline faults (LL), double line-to-ground (DLG) faults, and
balanced three phase faults.

Fault Analysis
Fault currents cause equipment damage due to both

thermal and mechanical processes.


Goal of fault analysis is to determine the magnitudes
of the currents present during the fault.
need to determine the maximum current to insure
devices can survive the fault.

need to determine the maximum current the circuit


breakers (CBs) need to interrupt to correctly size the
CBs.

Fault Analysis Solution Techniques

Circuit models used during the fault allow the network to be

represented as a linear circuit

There are two main methods for solving for fault currents:
1.

Direct method: Use pre-fault conditions to solve for the


internal machine voltages; then apply fault and solve
directly.

2.

Superposition: Fault is represented by two opposing


voltage sources; solve system by superposition.

Analysis of Un-Symmetric Systems


Except for the balanced three-phase fault, faults result in
an unbalanced system.
The most common types of faults are single line-ground
(SLG) and line-line (LL). Other types are double lineground (DLG), open conductor, and balanced three phase.
System is only unbalanced at point of fault!

The easiest method to analyze unbalanced system


operation due to faults is through the use of Symmetrical
Components

Symmetric Components
The key idea of symmetrical component analysis is to
decompose the system into three sequence networks.
The networks are then coupled only at the point of the
unbalance (i.e., the fault)
The three sequence networks are known as the
positive sequence (this is the one weve been using).
negative sequence.
zero sequence.
7

Positive Sequence Sets


The positive sequence sets
have three phase
currents/voltages with
equal magnitude, with
phase b lagging phase a by
120, and phase c lagging
phase b by 120.
Weve been studying
positive sequence sets.

Positive sequence sets


have zero neutral current
8

Negative Sequence Sets


The negative sequence sets
have three phase
currents/voltages with
equal magnitude, with
phase b leading phase a by
120, and phase c leading
phase b by 120.
Negative sequence sets are
similar to positive
sequence, except the phase
order is reversed

Negative sequence sets


have zero neutral current

Zero Sequence Sets


Zero sequence sets have three
values with equal magnitude and
angle.
Zero sequence sets have neutral
current

Zero Sequence vectors with


Zero phase shift.

Sequence Set Representation


Any arbitrary set of three phasors, say Ia, Ib, Ic can be
represented as a sum of the three sequence sets

I a I a0 I a I a
I b I b0 I b I b
I c I c0 I c I c
where
I a0 , I b0 , I c0 is the zero sequence set
I a , I b , I c is the positive sequence set
I a , I b , I c is the negative sequence set

11

Conversion from Sequence to Phase


Only three of the sequence values are unique,
I0a , I a , I a ; the others are determined as follows:

= 1120
0
0
0
Ia I b Ic
I b 2 I a

2 3 0

3 1

(since by definition they are all equal)


I c I a

I b I a

I c 2 I a

1
1
1
1
I

a
1
Ia
1

0
+
2

I I 1 I I 1
Ia
b
a
a
a


2 1 2 I
I c
1


a

12

Conversion Sequence to Phase


Define the symmetrical components transformation
matrix
1
1 1

2
A 1

1 2

0
0

I
I
a
Ia

Then I I b A I a A I A I s



I c
I a
I

13

Conversion Phase to Sequence


By taking the inverse we can convert from the
phase values to the sequence values
1

Is A I
1
1 1
1 1
2
with A 1
3
1 2

Sequence sets can be used with voltages as well


as with currents
14

Example
Va 0
Let V Vb

Vc
Then
1 0 0
1 1
1
1
2
Vs A V 1

3
1 2 6.12

15

Example
I 0 100

Let I s I 10

I
Then
1 100
1 1

2
I AI s 1
10

1 2

16

Power in Symmetrical Components


The total power in a three-phase network is given in
terms of phase variables by

where the asterisk denotes complex conjugation. We can show that the
corresponding expression in terms of sequence variables is given by

The total power is three times the sum of powers in individual


sequence networks.
17

Use of Symmetrical Components


Consider the following wye-connected load:

I n I a Ib I c
Vag I a Z y I n Z n
Vag ( ZY Z n ) I a Z n I b Z n I c
Vbg Z n I a ( ZY Z n ) I b Z n I c
Vcg Z n I a Z n I b ( ZY Z n ) I c

Vag
Z y Zn

Vbg Z n
V
Z
n
cg

Zn
Z y Zn
Zn

Ia

Z n Ib

Z y Z n I c
Zn

18

Use of Symmetrical Components


Vag
Z y Zn
Zn

Z y Zn
Vbg Z n
V
Z
Zn
n
cg

V
Z I V A Vs
A Vs Z A I s

Z y 3Z n

1
A ZA
0

Ia

Z n Ib

Z y Z n I c
I A Is
Zn

Vs A
0
Zy
0

0
Z y

Z A Is

19

Networks are Now Decoupled


V 0
Z y 3Z n 0

0
Zy
V

0
0
V

Systems are decoupled


V 0 ( Z y 3Z n ) I 0

0
0 I

0 I

Z y I

Zy I

V Zy I
20

Grounding
When studying unbalanced system operation how a
system is grounded can have a major impact on the fault
flows
Ground current only impacts zero sequence system
In previous example if load was ungrounded the zero
sequence network is (with Zn equal infinity):

21

Grounding, contd

Voltages are always defined as a voltage difference.


The ground is used to establish the zero voltage
reference point

ground need not be the actual ground (e.g., an


airplane)

During balanced system operation we can ignore the


ground since there is no neutral current

There are two primary reasons for grounding electrical


systems
1. safety
2.

protect equipment

22

Sequence diagrams for generators


Key point: generators only produce positive sequence voltages; therefore
only the positive sequence has a voltage source.

During a fault Z+ Z Xd. The zero sequence impedance is


usually substantially smaller. The value of Zn depends on
whether the generator is grounded.
23

Sequence diagrams for Transformers


The positive and negative sequence diagrams for transformers are similar to those for
transmission lines.
The zero sequence network depends upon both how the transformer is grounded and
its type of connection. The easiest to understand is a double grounded wye-wye

24

Transformer Sequence Diagrams

25

Unbalanced Fault Analysis


The first step in the analysis of unbalanced faults is to assemble
the three sequence networks.

For example, for the following power system lets develop the
sequence networks.

26

Sequence Diagrams
Positive Sequence Network

Negative Sequence Network

27

Negative Sequence Network

28

Zero Sequence Network

29