You are on page 1of 1

Grounding Sistem

Daya Total Trafo = 100KVA


Arus yg mengalir = 100/

3 .400 = 144 A

Re2 < 50/2x144 = 0,17 ohm (yang diinginkan)

Misalkan Re1 = 2 ohm


Ig = E 3/
= 400/

3 (Re1+Re2+Rsaluran/3)
3 ( 2+0,17)

= 106,4 A
R = P/ 2 l ((ln 4l/A)-1)
R = 100/ 2 x 1,5 (( ln (4x1,5/0,01) -1)
= 128,84
Agar sesuai maka dibuat konfigurasi
Konfigurasi segitiga
X = (l/ln 48l/a -1)/D
X = (1,5/ln 48x1,5/0,01 -1)/10
X = 0,019

R = 1+2x/N
R = 1+2 x 0,019/3
R = 0,346 (memenuhi)

You might also like