You are on page 1of 1

ROOM PRESSURE [Pa]

AIR CHANGES [1/h]


SUPPLY AIR [CMH]
RETURN AIR [CMH]
TRANSFER AIR IN [CMH]
LEAKAGE AIR OUT [CMH]
EXHAUST AIR [CMH]
-

4
129
115
14
-

10
407
319
87
-

4
124
113
11
-

21
REX-GF-05
0022

23
AHU-GF-07
0
0024

EXH
7.6
2.80
NC
12
255
255
-

22
AHU-GF-07
REX-GF-05
0023
FEM CNC CHANGE
RM
AC
18.1
2.80
NC
<25
7
365
21
192
152
-

31
AHU-GF-01
EAU-01
0032

32
AHU-GF-01
EAU-01
0033

33
AHU-GF-01
EAU-01
0034

CLEAN LAUNDRY

OFFICE

IPQC

AC
11.6
2.80
C
223
30
59
1,919
1,893
347
74
300
-

AC
6.6
2.80
C
223
30
35
647
763
174
57
-

AC
4.8
2.80
C
223
<65
30
35
470
610
174
34
-

41
AHU-GF-04
EAU-01
0042

42
AHU-GF-04
EAU-01
0043

43
AHU-GF-04
EAU-01
0044

ROOM NAME

PH-1 BLENDING

CIP/SIP

MOBILE LAF
CHARGING ROOM

HVAC MODE

AC

AC

AC

SN
AHU Tagging
REX Tagging
ROOM NUMBER
ROOM NAME
HVAC MODE
AREA [m2]
CHT [m]
CLASSIFICATION
TEMPERATURE [C]
HUMIDITY [%]
ROOM PRESSURE [Pa]
AIR CHANGES [1/h]
SUPPLY AIR [CMH]
RETURN AIR [CMH]
TRANSFER AIR IN [CMH]
LEAKAGE AIR OUT [CMH]
EXHAUST AIR [CMH]
SN
AHU Tagging
REX Tagging
ROOM NUMBER
ROOM NAME
HVAC MODE
AREA [m2]
CHT [m]
CLASSIFICATION
TEMPERATURE [C]
HUMIDITY [%]
ROOM PRESSURE [Pa]
AIR CHANGES [1/h]
SUPPLY AIR [CMH]
RETURN AIR [CMH]
TRANSFER AIR IN [CMH]
LEAKAGE AIR OUT [CMH]
EXHAUST AIR [CMH]
SN
AHU Tagging
REX Tagging
ROOM NUMBER

FEMALE TOIL/SH

A/L (MALE)
AC
9.6
2.80
NC
<25
5
136
20
116
-

You might also like