Professional Documents
Culture Documents
Yes No
1. Cables on reels must be isolated and meggered before unreeling.
Yes No
4. Erect safety barriers and post safety man at cable end remote from the
test equipment.
5. Check the insulation resistance of the cable using a megger tester. The
test voltage should be 5000 volts for 5000 volt and above cables. Measure
the insulation resistance of each core and any metallic armor or sheath
grounded at one end only.
6. Each cable shall be high potential tested as follows: each core to
ground, with the shield, other cores and any metallic armor or sheath
grounded at one end only.
7. For commissioning new cables, the final D. C. test voltage is the 80%
test voltage in the tables below.
8. For commissioning new cables that are spliced to old cables, and for
testing old cables, the final D. C. test voltage shall be determined by the
proponent of the cables, and should not exceed the 65% test voltage in the
tables below( 40% of these values is recommended after 5 years ). A
voltage equal to 1.7 X the operating voltage is recommended for extremely
old cables with low megger readings.
9. The D. C. high voltage shall be applied in a minimum of four steps
(each step approximately equal to the rated rms voltage of the cable) of
one (1) minute duration each except for the final test voltage which shall
be maintained for fifteen (15) minutes.
10. On completion of tests the cable shall be left with all cores and shields
grounded for one hour to allow the residual charge to dissipate.
RECOMMENDED TEST VALUES
NOTES: 80% and 65% refer to percentages of the factory test voltages specified in AEIC CS5
and CS6. AEIC CS5 and CS6 permit testing at the 65% test voltage "at anytime during the period
of the guarantee. "
Maximum test values for cables older than 5 years are listed in the 40% column.
CABLE TEST RECORD