You are on page 1of 1

TABEL MEDIUM VOLTAGE XPLE INSULATED CABLE Hal 37 Tab 35.

xls
PT. KABELINDO MURNI Tbk

N2XSEFGbY / NA2XSEFGbY 12/20 (24) kV


Copper or Aluminium Conductor , XLPE Insulated
Copper wire / tape screened, Zinc-coated flat steel wire armoured, PVC Sheathed Cable

1. Conductor : Copper or aluminum ( compacted circular stranded )


2. Conductor screen : Extruded semi conductive compound
3. Insulation : Extruded Cross Linked Polyethylene (XLPE)
4. Insulation screen : Extruded Strippable semiconductive compound
5. Metalic Screen : Helically Overlapped copper tape
6. Inner Sheath : Extruded PVC 90° C grade
7/8. Armour : Galvanized Flat Steel and Steel tape
9. Outer Sheath : Extruded PVC 90° C grade

MEDIUM VOLTAGE XPLE INSULATED CABLE

TECHNICAL DATA

SPEC
STD Specification : SPLN 43-5, IEC 60502 Cu Conductor Shape : Copper or aluminium ( compacted circular stranded )

APL Application : Used for primary underground distribution installation direct burial in wet or dry location.

DIMENSIONAL DATA 3 CORES

Cross Conductor Insulation Insulation Armour Sheath Min. Overall Std.


Cable Net Weight (Approx)
Section Diameter Thickness Diameter Thickness Thickness Bending Cable Length
Nominal (Approx) Nominal (Approx) Nominal Nominal Cu Al Radius Diameter per reel
( mm2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( mm ) ( kg / km ) ( kg / km ) ( mm ) ( mm) (m)
35 7.1 19.7 2.7 5.000 4.400 480 57
50 8.25 20.9 2.8 5.700 4.800 510 60
500
70 9.9 22.5 2.9 6.800 5.400 550 64
95 11.7 24.3 3.1 8.000 6.200 600 68
120 13.1 25.7 3.2 9.100 6.800 630 71
5.5 0.80
150 14.3 26.6 3.3 10.300 7.500 660 74 350
185 16.3 28.9 3.4 11.900 8.400 720 79
240 18.7 31.3 3.6 14.300 9.600 780 85
300 20.9 33.5 3.7 16.700 10.900 830 90 300
400 23.7 36.3 4.0 20.100 12.700 910 97

ELECTRICAL DATA

Cross Max.DC Resistance DC Insulation Current Carrying Capacity Current Carrying Capacity Max.Short Max.Short Circuit
Capacitance Inductance
Section at 20° C Conductor Resistance at 30° C - in Air at 30° C - in Ground Circuit Current Current of Conductor
per phase per phase
Nominal Cu Al at 20° C Cu Al Cu Al of Screen Cu Al
( mm2 ) ( ohm / km ) ( ohm / km ) M.Ohm.km A A A A uF / km mH / km kA / Sec kA / Sec kA / Sec
35 0.524 0.868 1.400 173 139 171 132 0.161 0.408 2.92 5.18 3.45
50 0.387 0.641 1.300 206 161 202 154 0.175 0.389 3.08 7.36 4.89
70 0.268 0.443 1.100 257 199 246 191 0.197 0.367 3.31 10.26 6.81
95 0.193 0.320 1.000 313 242 295 228 0.219 0.348 3.56 13.88 9.19
120 0.153 0.253 360 280 335 260 0.237 0.335 3.75 17.49 11.58
900
150 0.124 0.206 410 318 376 292 0.252 0.327 3.92 21.81 14.43
185 0.0991 0.164 800 469 365 425 331 0.277 0.314 4.20 26.86 17.76
240 0.0754 0.125 553 425 492 385 0.307 0.302 4.53 34.78 22.98
700
300 0.0601 0.100 629 481 554 437 0.334 0.292 4.84 43.41 28.67
400 0.047 0.0778 600 760 593 625 495 0.368 0.282 5.23 57.79 38.14

You might also like