Professional Documents
Culture Documents
Medium Volt Xple Ins Cab h37 TB 35 20kv
Medium Volt Xple Ins Cab h37 TB 35 20kv
xls
PT. KABELINDO MURNI Tbk
TECHNICAL DATA
SPEC
STD Specification : SPLN 43-5, IEC 60502 Cu Conductor Shape : Copper or aluminium ( compacted circular stranded )
APL Application : Used for primary underground distribution installation direct burial in wet or dry location.
ELECTRICAL DATA
Cross Max.DC Resistance DC Insulation Current Carrying Capacity Current Carrying Capacity Max.Short Max.Short Circuit
Capacitance Inductance
Section at 20° C Conductor Resistance at 30° C - in Air at 30° C - in Ground Circuit Current Current of Conductor
per phase per phase
Nominal Cu Al at 20° C Cu Al Cu Al of Screen Cu Al
( mm2 ) ( ohm / km ) ( ohm / km ) M.Ohm.km A A A A uF / km mH / km kA / Sec kA / Sec kA / Sec
35 0.524 0.868 1.400 173 139 171 132 0.161 0.408 2.92 5.18 3.45
50 0.387 0.641 1.300 206 161 202 154 0.175 0.389 3.08 7.36 4.89
70 0.268 0.443 1.100 257 199 246 191 0.197 0.367 3.31 10.26 6.81
95 0.193 0.320 1.000 313 242 295 228 0.219 0.348 3.56 13.88 9.19
120 0.153 0.253 360 280 335 260 0.237 0.335 3.75 17.49 11.58
900
150 0.124 0.206 410 318 376 292 0.252 0.327 3.92 21.81 14.43
185 0.0991 0.164 800 469 365 425 331 0.277 0.314 4.20 26.86 17.76
240 0.0754 0.125 553 425 492 385 0.307 0.302 4.53 34.78 22.98
700
300 0.0601 0.100 629 481 554 437 0.334 0.292 4.84 43.41 28.67
400 0.047 0.0778 600 760 593 625 495 0.368 0.282 5.23 57.79 38.14