Line # 2 Line #1
Bus Bar Protection Zone
BUS
x Breakers x AL : Alarm relay (CT open Ckt Detection )
IL 2 RXTLA
IL 1
R
Line 1 Bkr trip
BF junction
L /O Line 2 Bkr trip
Box
RXID
Bkr Trip
C Bkr Trip
NL AL RXTCA
Rst R.
STB
AL
Diff. CT Ckt is Shorted
BUS BAR PROTECTION
MEDIUM IMPEDANCE B/F RELAYS
a) RADSS
b) SIEMENS NUMERICAL RELAY.
ADVANTAGES OF % BIASED DIFFERENTIAL RELAY:
FREE OF ANY NEED FOR MATCHED CT
CHARACTERISTIC OR RATIOS.
OTHER PROTECTIVE RELAYS CAN BE INCLUDED IN
THE SAME CIRCUIT.
STABLE FOR INFINITE FAULT LEVEL.
MAX. PERMISSIBLE CT LOOP RESISTANCE IS MUCH
HIGHER THAN CONVENTIONAL PROTECTIONS.
INSENSITIVE TO CT SATURATION.
CHECK FEATURE IN THE FORM OF O/C START.
ALARM FOR CT SECONDARY OPEN CIRCUIT.
DETECTS FAULTS WITH IN 1-2 m sec AND INITIATES
TRIPPING WITH IN 5-7 m sec.
Bus Fault Protection : RADSS Relay
SR : Start Relay
AL
dR : Diff. relay
SR
RS : Restraining resistor
Rd11 : Diff. resistor
Rd3
IL 2 Tmd
IL 1 Ud3
Trip Logic
dR Line 2 Bkr
Rd11
TC 1
LO
RS/2 Line 2 TC 2
Us
RXMVB 2
RS/2
SR Line 1 Bkr
Trip O/P
& LO TC 1
dR ( 10 -13 ms)
Line 1
TC 2
AL
Diff. Ckt is bypassed
BUS BAR PROTECTION
BREAKER FAIL PROTECTION:
IN MODERN NETWORKS CRITICAL FAULT CLEARANCE
TIME IS APPROXIMATELY 200 m sec. HENCE, NEED FOR
FAST ACTING B/U WHEN PRI PROTECTION OR BKR
FAILS.
REMOTE BACK-UP: REMOTE END ZONE-II OF
DISTANCE REL.
LOCAL BACK-UP: BKR BACK UP.