You are on page 1of 8

DOE/GO-102001-1113

FS143
June 2001

Air-Source
Heat Pumps
There are two common types of heat An air-source heat pump can provide effi-
pumps: air-source heat pumps and geot- cient heating and cooling for your home,
hermal heat pumps (GHPs). Either one especially if you live in a warm climate.
can keep your home warm in the winter When properly installed, an air-source
and cool in the summer. An air-source heat pump can deliver one-and-a-half to
heat pump pulls its heat indoors from the three times more heat energy to a home
outdoor air in the winter and from the compared to the electrical energy it con-
indoor air in the summer. A GHP extracts sumes. This is possible because a heat
heat from the indoor air when it's hot out- pump moves heat rather than converting
side, but when it's cold outside, it draws it from a fuel, like in combustion heating
heat into a home from the ground, which systems.
maintains a nearly constant temperature
of 50˚ to 60˚F. This fact sheet focuses on How They Work
air-source heat pumps, which comprise You might be wondering how an air-
the majority of all residential heat pump source heat pump uses the outdoor winter
applications. air to heat a home. Believe it or not: heat
can be harvested from cold outdoor air

Sara Farrar, NREL/PIX05420

This home in Austin, Texas, features an air-source heat pump.

This document was produced for the U.S. Department of Energy (DOE) by the National Renewable Energy Laboratory (NREL), a DOE national laboratory. The
document was produced by the Information and Outreach Program at NREL for the DOE Office of Energy Efficiency and Renewable Energy. The Energy Efficiency
and Renewable Energy Clearinghouse (EREC) is operated by NCI Information Systems, Inc., for NREL / DOE. The statements contained herein are based on
information known to EREC and NREL at the time of printing. No recommendation or endorsement of any product or service is implied if mentioned by EREC.

Printed with a renewable-source ink on paper containing at least 50% wastepaper, including 20% postconsumer waste
down to about 40°F. And this can Types of Air-Source Heat Pumps
be accomplished through a process You can use a central heat pump to heat
you're probably already familiar and cool a whole house. Most central heat
with—refrigeration. pumps are split-systems—that is, they
Basically, a heat pump's refrigeration sys- each have one coil indoors and one out-
tem consists of a compressor, and two doors (see Fig. 1 below). Supply and
coils made of copper tubing, which are return ducts connect to a central fan,
surrounded by aluminum fins to aid heat which is located indoors. The fan, often
transfer. The coils look much like the radi- called an air handler or blower, circulates
ator in your car. Like in a refrigerator or air throughout the house. The fan also
air-conditioner, refrigerant flows continu- usually contains electric resistance coils
You can use a ously through pipes, back and forth from (some units now have a gas-fired furnace
the outdoor coils. In the heating mode, liq- option). The heated or cooled air circulates
central heat pump to uid refrigerant extracts heat from the out- from the fan to the supply ducts, and open-
side coils and air, and moves it inside as it ings in the home called supply registers.
heat and cool a whole evaporates into a gas. The indoor coils Return registers and ductwork return the
transfer heat from the refrigerant as it con- air to the fan to be heated.
house. denses back into a liquid (see Fig. 1 Some heat pumps are packaged systems.
below). A reversing valve, near the com- These usually have both coils and the fan
pressor, can change the direction of the outdoors. Heated or cooled air is delivered
refrigerant flow for cooling as well as for to the interior from ductwork that
defrosting the outdoor coils in winter (see protrudes through a wall or roof.
Fig. 2 on page 3).
Another packaged system is the ductless
When outdoor temperatures fall below room heat pump. These pumps will effi-
40°F, a less-efficient panel of electric resis- ciently heat or cool a room or small house
tance coils, similar to those in your toaster, with an open floor plan. They are much
kicks in to provide indoor heating. This is more common for apartments and motel
why air-source heat pumps aren't always rooms than homes. They can be installed
very efficient for heating in areas with in a window or through a hole in the
cold winters. Fuel-burning furnaces gener- wall—wall installations being preferable
ally can provide a more economical way for appearances sake. Through-the-wall
to heat homes in cooler U.S. climates.

Compressor

Fan
Liquid Gas
evaporates condenses
into gas into a liquid
Expansion
Valve
Outdoor Indoor
Coils Coils

Fig. 1 A split-system heat pump heating cycle

2
Compressor

Gas Liquid
condenses Fan evaporates
into a into gas
liquid
Expansion
Valve
Indoor
Coils
Outdoor
Coils

Fig. 2 A split-system heat pump cooling cycle

installations, however, sometimes aren't The Seasonal Energy Efficiency Ratio


well insulated from inside to outside and (SEER) rates a heat pump's cooling effi-
can have infiltration problems. When ciency. In general, the higher the SEER, the
When selecting a new used, mini-split systems can solve these higher the cost. However, the energy sav-
problems. ings can return the higher initial invest-
heat pump, ment several times during the heat
Selecting a Heat Pump pump’s life. Replacing a 1970s vintage,
it’s important that When selecting an air-source heat pump, central heat pump (SEER = 6) with a new
consider the following three characteris- unit (SEER=12) will use half the energy to
you determine the tics carefully: the energy efficiency rating, provide the same amount of cooling, cut-
sizing, and the system's components. ting air-conditioning costs in half. The
proper size needed for most efficient heat pumps have SEERs of
Energy efficiency rating
between 14 and 18.
your home. In the United States, we rate a heat
pump's energy efficiency by how many You'll find the Energy Star® label—spon-
British thermal units (Btu) of heat it moves sored by the U.S Department of Energy
for each watt-hour of electrical energy it (DOE) and the U.S. Environmental Protec-
consumes. Every residential heat pump tion Agency (EPA)—on heat pumps with
sold in this country has an EnergyGuide an HSPF of at least 7 and a SEER of at
Label, which features the heat pump's least 12. Many new heat pumps exceed
heating and cooling efficiency perfor- these ratings, but looking for this label is a
mance rating, comparing it to other avail- good way to start shopping for one.
able makes and models.
The Heating Seasonal Performance Factor
(HSPF) rates both the efficiency of the
compressor and the electric-resistance ele-
ments. The HSPF gives the number of Btu
harvested per watt-hour used. The most
efficient heat pumps have an HSPF of
between 8 and 10.

3
Sizing efficiency not only depend on the selection
New Energy-Efficient Heat Pumps When selecting a new heat and planning of the equipment but also on
pump, it's important that you careful installation.
The efficiency and performance of
determine the proper size Consumers and home builders alike tend
today’s air-source heat pumps is one-
and-a-half to two times greater than
needed for your home. Bigger to accept the lowest bid for heating and
those available 30 years ago. This is not better. Oversizing air-conditioning work. This unfortunate
improvement in efficiency has resulted causes the heat pump to start choice can often leave a system lacking 10
from technical advances and options and stop more frequently, to 30 percent in the materials and labor
such as: which is less efficient and necessary to optimize heat-pump
• Thermostatic expansion valves for harder on the components performance. Rather than just accepting
more precise control of the refriger- than letting it run for longer the lowest bid, it's best to research the
ant flow to the indoor coil cycles. A properly sized heat performance records of local contractors,
• Variable speed blowers, which are pump also will provide you and get involved in the planning and
more efficient and can compensate with better comfort and decision-making about your new heat
for some of the adverse effects of humidity control than an
restricted ducts, dirty filters, and pump system.
oversized one.
dirty coils You can avoid most of the common com-
• Improved coil design The heating and cooling fort and performance problems from
• Improved electric motor and two- capacity of heat pumps is improper installation by following these
speed compressor designs measured in Btu per hour. The guidelines:
• Copper tubing, grooved inside to cooling capacity is commonly • Make your home as energy-efficient as
increase surface area. expressed in "tons" of cooling you can with proper insulation, energy-
capacity—each ton equaling efficient windows, and an effective air
12,000 Btu per hour. Correct barrier, etc. Then your contractor can
sizing procedures involve complex calcu- install a smaller pump system with
lations, which are best performed by an shorter duct lengths. In an energy-
experienced contractor, who uses sizing efficient home, it isn’t necessary to run
methods accepted by the heat pump ducts all the way out to exterior walls to
industry. Don't employ a contractor who install registers near the exterior walls.
guesses the size of the heat pump needed. • Install the ducts inside your home’s
Rule-of-thumb sizing techniques are gen- insulation and air barrier, if possible.
erally inaccurate, often resulting in higher Research shows that this strategy is a
than necessary purchase and annual major energy saver.
energy costs. • Insulate your ducts to R-8 if they
System components must be located in an attic or crawl
space beyond the home’s air barrier
You and your contractor should discuss
and insulation.
options that will help improve your
You and your home's comfort and the economy of your
• Locate the outdoor unit on the northside
of your home if possible. If not, pick a
heat pump. Regarding ducts, for example,
contractor should dis- it's important to carefully consider their
shady spot. There should be no obstruc-
tions within 10 feet of the sides with
design and materials, as well as the proper
cuss options amount of space they require. Check your
openings and the top.
• Specify that the measured air leakage
home's blueprints to see if the architect
that will help improve and builder have planned adequate space
through your new ducts be less than
10 percent of your system’s airflow.
for ducts and fans. Heating and cooling
your home’s comfort contractors complain that they often have
Air leakage of 5 percent or less is possi-
ble with careful workmanship.
to squeeze heating and cooling systems
and the economy of into spaces that are too small, resulting in
• Tell your contractor that you want a
return register in every room.
constricted ducts and inadequate airflow.
your heat pump. • Don’t use building cavities as ducts.
Except for packaged systems, you'll also Building-cavity return ducts are notori-
need to select the proper type of indoor ously leaky and often cause comfort,
coil for adequate summer moisture energy, and moisture problems.
removal. • Pull on ductwork after installation to
make sure it is fastened and sealed well.
Installing a New Heat Pump (Seal duct joints with mastic.)
A heat pump's performance and energy

4
Improving Performance Air-sealing ducts
Poor installation, duct losses, and inade- Measurements of heat pump performance
quate maintenance are more of a problem indicate that duct leakage wastes 10 to 30
for heat pumps than for combustion fur- percent of the heating and/or cooling
naces. A growing body of evidence sug- energy in a typical home. It's one of the
gests that most heat pumps have most severe energy problems commonly
significant installation or service problems found in homes because the leaking air is
that reduce performance and efficiency. 20° to 70°F warmer than indoor air in win-
According to a report on research funded ter and 15° to 30°F cooler in the summer.
by Energy Star‚ more than 50 percent of all Duct leakage may cause some minor com-
heat pumps have significant problems fort problems when ducts are located in
with low airflow, leaky ducts, and incor- conditioned areas. But when leaky ducts
rect refrigerant charge. are located in an attic or crawl space, the
Increasing airflow in central energy loss is often large. Some of the
worst duct leakage occurs at joints
Measurements heat pumps
between the air handler, and the main
The capacity and the efficiency of a heat
supply and return air ducts.
of heat pump pump depend upon adequate airflow.
There should be about 400 to 500 cubic Some main return ducts use plywood or
performance feet per minute (cfm) airflow for each ton fiberglass duct-board boxes. These boxes
of the heat pump’s air-conditioning capac- frequently leak because their joints are
indicate that duct ity. Efficiency and performance deteriorate exposed to the duct system’s highest air
if airflow is much less than 350 cfm per pressures. Heating and air-conditioning
leakage waste 10 to 30 ton. contractors often use wall, floor, and ceil-
ing cavities as return ducts. These build-
percent of the An ideal duct system has both a supply
ing-cavity return ducts are often
register and a return register for every
accidentally connected to an attic, crawl
room. Most homes, however, have only
heating and/or cool- one or two return registers for the entire
space, or even the outdoors, creating seri-
ous air leakage. Fiberglass ducts and flex
house. Air from other rooms must find its
ing energy in way back to these registers to be reheated
ducts are often installed improperly. These
ducts may also deteriorate with age, lead-
or re-cooled. Obstructions in return air are
a typical home. a common air circulation problem, partic- ing to significant supply-duct leakage.
ularly from closed interior doors to rooms The best heating and cooling contractors
with no return-air register. have equipment to test for duct leakage.
Blockage of supply or return air ducts and Testing helps locate duct leaks and indi-
registers can pressurize or depressurize cates how much duct sealing is necessary.
portions of the home, resulting in poor Do not use duct tape for sealing—its lifes-
performance and increased air leakage pan is very short, often less than 6 months.
through the building envelope. Restric- Adjusting refrigerant charge
tions to airflow have the greatest impact
Room heat pumps and packaged heat
on the return-air side of the system, so
pumps are charged with refrigerant at the
repairs should start with the return ducts.
factory. They are seldom incorrectly
Air from every supply register must have
an unobstructed pathway back to a return charged. Split-system heat pumps, on the
register. You can install louvered grilles other hand, are charged in the field, which
through walls or doors, ducts between can sometimes result in either too much or
rooms, and/or additional return ducts and too little refrigerant.
registers to improve air circulation. Split-system heat pumps that have the
Technicians can increase the airflow by correct refrigerant charge and airflow usu-
cleaning the evaporator coil, increasing fan ally perform very close to manufacturer’s
speed, or enlarging the ducts—especially listed SEER and HSPF. Too much or too
return ducts. Enlarging ducts may seem little refrigerant, however, reduces heat-
drastic but in some cases, might be the pump performance and efficiency.
only remedy for poor comfort and high
energy costs.

5
For satisfactory performance and effi- A defrost control tells the reversing valve
ciency, a split-system heat pump should when to send hot refrigerant outdoors to
be within a few ounces of the correct thaw the outdoor coil during the winter.
charge, specified by the manufacturer. During the 2-to-10-minute defrost cycle,
When the charge is correct, specific refrig- auxiliary heat takes over, reducing the
erant temperatures and pressures listed by heat pump’s overall efficiency up to 10
the manufacturer will match temperatures percent. The two most common types of
and pressures measured by your service defrost controls are time-temperature
technician. Verify these measurements and demand-defrost. Time-temperature
with the technician. defrost controls activate defrost at regular
time intervals for set time periods,
If the manufacturer’s temperatures and
whether there is ice on the outdoor coil or
pressure’s don’t match the measured ones,
not. A demand-defrost control senses coil
refrigerant should be added or with-
temperature or airflow through the coil,
drawn, according to standards specified
and only activates defrost if it detects the
by the EPA. Refrigeration systems should
presence of ice. Obviously, choosing a heat
be leak-checked at installation and during
pump with demand-defrost will pay a sig-
each service call.
nificant efficiency dividend.
Manufacturer’s say that a technician
For greater efficiency, don't locate a ther-
must measure airflow prior to checking
mostat near a heat source or cold draft
The difference refrigerant charge because the refrigerant
because they can cause a heat pump to
measurements aren’t accurate unless air-
operate erratically. This includes shading
between the energy flow is correct.
thermostats from direct sunlight. Also, do
Operating a heat pump not turn the thermostat beyond the
consumption of a Like combustion heating systems, you desired temperature. It will not make the
control heat pumps using thermostats. heat pump heat or cool your home any
well-maintained heat faster. It will only waste energy. Residents
If you leave and return at regular times who duel one another over the thermostat
pump and a neglected everyday, you'll save money by using settings, moving it up and down to suit
automatic thermostats, which minimize their different comfort levels, cause heat
one ranges from 10 energy use during the times the home is pumps to operate erratically and ineffi-
unoccupied. However, choosing an auto- ciently.
to 25 percent. matic thermostat’s reactivation time
requires considering the duration of heat- Maintaining and Servicing
pump operation necessary to restore a Heat-pump performance will deteriorate
comfortable temperature. During the heat- without regular maintenance and service.
ing season, some homeowners also set The difference between the energy con-
their thermostats back 10°F, manually or sumption of a well-maintained heat pump
automatically, when they leave home or and a severely neglected one ranges from
go to bed. 10 to 25 percent.
A two-stage thermostat controls the heat- Regular Maintenance
ing. The first stage activates the refrigera-
Either the homeowner or service techni-
tion system. If it’s too cold outside for the
cian can perform the following routine
refrigeration system to counteract the
maintenance tasks:
home’s heat loss, then the thermostat’s
second stage activates the electric resis- • Clean or replace filters regularly (every
tance coils. An outdoor thermostat will 2 to 6 months, depending on operating
prevent the less efficient electric resistance time and amount of dust in the environ-
heat from coming on until the outdoor ment).
temperature falls below 40°F. An outdoor
• Clean outdoor coils as often as
thermostat also will prevent auxiliary heat
necessary (when dirt is visible on the
from activating when an automatic ther-
outside of the coil).
mostat is warming the house after a set-
back period. Use setback thermostats that • Remove plant life and debris from
are only for heat pumps. around the outdoor unit.

6
• Clean evaporator coil and condensate • Verify correct refrigerant charge by mea-
pan every 2 to 4 years. surement.
• Clean the blower’s fan blades. • Check for refrigerant leaks.
• Clean supply and return registers and • Inspect electric terminals, and if neces-
straighten their fins. sary, clean and tighten connections, and
apply nonconductive coating.
Professional Service
• Lubricate motors, and inspect belts for
You should have a professional technician
tightness and wear.
service your heat pump at least every year.
The technician can: • Verify correct electric control, making
sure that heating is locked out when the
• Inspect ducts, filters, blower, and indoor
thermostat calls for cooling and vice
coil for dirt and other obstructions.
versa.
• Diagnose and seal duct leakage.
• Verify correct thermostat operation.
• Verify adequate airflow by measurement.

Resources Fax: (703) 575-4449


E-mail: info@ms.acca.org
The following are sources of additional information on Web site: www.acca.org/
heat pumps. This list is not exhaustive, nor does the
mention of any resource constitute a recommendation A national, trade association of heating, ventilation,
or endorsement. air-conditioning, and refrigeration contractors.

Ask an Energy Expert Air-Conditioning and Refrigeration Institute (ARI)


DOE’s Energy Efficiency and Renewable Energy 4301 N. Fairfax Drive, Suite 425
Clearinghouse (EREC) Arlington, VA 22203
Phone: (703) 524-8800
P.O. Box 3048
Fax: (703) 528-3816
Merrifield, VA 22116
E-mail: ari@ari.org
1-800-DOE-EREC (363-3732)
Web site: www.ari.org/
E-mail: doe.erec@nciinc.com
Online submittal form: A national trade association representing manufacturers of
www.eren.doe.gov/menus/energyex.html U.S. produced central air-conditioning and commercial refriger-
Consumer Energy Information Web site: ation equipment.
www.eren.doe.gov/consumerinfo/
Consortium for Energy Efficiency (CEE)
Energy experts at EREC provide free general and One State Street, Suite 1400
technical information to the public on many topics Boston, MA 02109-3507
and technologies pertaining to energy efficiency and Phone: (617) 589-3949
renewable energy. Fax: (617) 589-3948
DOE’s Energy Efficiency and Renewable Energy Web site: www.ceeformt.org/
Network (EREN) A national, nonprofit, benefits corporation that promotes
Web site: www.eren.doe.gov the manufacture and purchase of energy-efficient products
and services.
Your comprehensive online resource for DOE’s energy
efficiency and renewable energy information.

Organizations
Air Conditioning Contractors of America (ACCA)
2800 Shirlington Rd., Suite 300
Arlington, VA 22206
Phone: (703) 575-4477 (Continued on page 8)

7
(Continued from page 7) Further Reading
Consumer Guide to Home Energy Savings, Wilson A.,
Eastern Heating & Cooling Council (EH-CC) Thorne J., Morrill J, American Council for an Energy-
20,000 Horizon Way, Suite 260 Efficient Economy (ACE3), Washington, DC.
Mt. Laurel, NJ 08054 Available from ACE3 at (202)429-8873,
E-mail: info@eh-cc.org ac3pubs@ix.netcom.com, or online at www.aceee.org.
Web site: www.eh-cc.org/
Energy Savers: Tips on Saving Energy and Money
Educates consumers and contractors on properly designed at Home, DOE. Available from EREC (see Ask an Energy
and installed high-efficiency heating and cooling systems. Expert above) or online in PDF and HTML at
Energy Star® www.eren.doe.gov/consumerinfo/energy_savers/.
DOE and EPA Geothermal Heat Pumps Make Sense for Homeowners,
Phone: (888) STAR-YES (782-7937) DOE Office of Geothermal Technologies, 1998.
E-mail: info@energystar.gov/ Available from EREC (see Ask an Energy Expert above)
Web site: www.energystar.gov/ or online in PDF at www.eren.doe.gov/
Provides lists of energy-efficient, Energy Star®-qualified geothermal/pdf/26161b.pdf or in HTML at
products, including heat pumps. www.eren.doe.gov/erec/factsheets/
ghp_homeowners.html.
Home Energy Magazine
2124 Kittredge Street, #95 Residential Energy: Cost Savings and Comfort for
Berkeley, CA 94704 Existing Buildings , Krigger J., Saturn Resource
Phone: (510) 524-5405 Management, Helena, MT 2000. Available from Saturn
E-mail: contact@homeenergy.org, at (406) 443-3433.
Web site: www.homeenergy.org/
A source of information on reducing energy
consumption in the home.

Web Sites
Heat Pumps
The Energy Outlet
Web site: www.energyoutlet.com/res/heatpump/

Heat Pumps for Heating and Cooling


DOE Office of Building Technology, State and
Community Programs
Web site: www.eren.doe.gov/buildings/
ee_heatpump.html

International Energy Agency Heat Pump Centre


Web site: www.heatpumpcentre.org/

Top-Rated Energy-Efficient Appliances


American Council for an Energy-Efficient Economy
Web site: www.aceee.org/consumerguide/2000enef.htm

Why Buy Energy-Efficient Appliances?


DOE Office of Codes and Standards
Web site: www.eren.doe.gov/buildings/
consumer_information/

You might also like