Professional Documents
Culture Documents
Membrane Action of Composite Floor Slabs in Fire Condition
Membrane Action of Composite Floor Slabs in Fire Condition
*
Tongji University, China
**
State University of New York at Buffalo
Abstract
A new method to predict the membrane action for simply supported steel-concrete composite floor slab is presented in
this paper. In the analysis model, the slab is divided into one elliptical paraboloid reinforcement tensile mesh in the
center and four concrete rigid plates at the boundary of the slab which will form a compressive concrete ring to
provided anchorage for the reinforcement. According to force and bending moment equilibrium equation, the load
capacity offered by membrane action is obtained.
4 full-scale composite floor slab test are performed at Tongji University, for the purpose to observe the membrane
action and to verify the validity of the new method. Comparison of the tests’ result and the prediction by the method
proposed is presented and analyzed.
Keywords: Composite floor slab, fire-resistance, membrane action, analysis method, full-scale test
(e)); 4) finally, most of the load will be carried by or short edge of the slab, which satisfies 0<K<0.5;
membrane action with the reinforcement acting as a
mesh, and being anchored in a concrete compression ring
formed in the peripheral part of the slab (Fig. 1(f)).
2 ⎧ ⎡ 1⎛ B ⎞ ⎤
tan ϕ y =
∂z
=
2w ⎛ x ⎞
1− ⎜
(8) ⎪M q12 + M Tvx + M Thx − 2C ⋅ cos α ⋅ ⎢h0 x − ⎜ − y 0 ⎟ ⋅ θ x ⎥ − (15)
⎟ ⎪ ⎣ 3 ⎝ 2 ⎠ ⎦
∂y KB ⎝ KL ⎠
z =0 ⎪ ⎡ 1⎛B ⎞ ⎤
So the horizontal and vertical component forces of ⎪2 S ⋅ sin α ⋅ ⎢h0 x − ⎜ − y 0 ⎟ ⋅ θ x ⎥ − M xu = 0
⎪ ⎣ 2⎝ 2 ⎠ ⎦
reinforcement in Y direction are obtained by Eq. (9) and ⎨
⎪ M + M + M − 2C ⋅ sin α ⋅ ⎡h − 1 ⎛⎜ L − x ⎞⎟ ⋅ θ ⎤ +
Eq. (10). ⎪ q 34 Tvy Thy ⎢ 0y 3 2 0 y⎥
⎣ ⎝ ⎠ ⎦
⎪
(9) ⎪
⋅ α ⋅
⎡
−
1⎛L
−
⎞
⋅ θ
⎤
− =
⎪ 2 S cos ⎢ 0y 2 ⎜ 2
h x 0 ⎟ y⎥ M yu 0
KB ⎩ ⎣ ⎝ ⎠ ⎦
Tyh( x ) = Tyu ⋅
⎡ 2
⎤ where M12 and M34 are the bending moments induced by
(KB )2 + 4w2 ⎢1 − ⎛⎜ x ⎞
⎟ ⎥
⎢⎣ ⎝ KL ⎠ ⎥⎦ q12 and q34 respectively; MThx and MTvx are the bending
2
(10) moments induced by horizontal and vertical component
⎛ x ⎞
2w 1 − ⎜ ⎟ forces of reinforcement in plates 1 and 2 respectively;
⎝ KL ⎠
Tyv ( x ) = Tyu ⋅ MThy and MTvy are the bending moments induced by
⎡ x ⎞ ⎤
2
(KL )2 + 4w2 ⎢1 − ⎛⎜ ⎟ ⎥ ⎪
⎛ f ⎞
⎣⎢ ⎝ KB ⎠ ⎦⎥ ⎪ M ux = Asx f yT ⎜ hcx − 0.59 Asx yT ⎟ ⋅ ( L − 2 x0 )
⎪⎩ ⎝ f cT ⎠
At the limit state, the membrane forces in each rigid plate
of the slab are shown in Fig.7. The force equilibrium in (16)
⎧ M q 34 = q34 ⋅ A34 ⋅ dx
X and Y direction can be expressed as ⎪
⎧ 2C ⋅ cos α + 2S ⋅ sin α = 2 x T dx ⎪ y0 ⎡ ⎛L ⎞ ⎤
∫0 yh( x ) (13) M Thy = 2∫ Txh ⋅ ⎢ h0 y − ⎜ − x0 ⎟ ⋅ θ y ⎥ ⋅ dy
0
⎪ ⎪ ⎝ 2 ⎠ ⎦
⎨
0
⎣
y0
⎪
⎪⎩2C ⋅ sin α = 2S ⋅ cos α + 2∫0 Txh( y )dy ⎪ ⎡L ⎛ y ⎞ ⎥⎤
2
⎨ y0 KL ⎛L ⎞
⎪ M Tvy = 2∫0 Txv ⋅ ⎢ 2 − KL 1 − ⎝⎜ KB ⎠⎟ ⎥ ⋅ dy + 2 ∫x0 Txv ⋅ ⎝⎜ 2 − x ⎠⎟ ⋅ dx
⎢
which leads to
⎪ ⎣ ⎦
⎧ x0 y0
sin α ⋅ 2∫ Tyh ( x )dx − cos α ⋅ 2∫ Txh( y )dy ⎪
⎪S = 0 0 (14) ⎪ ⎛ f ⎞
⎪ 2 M uy = Asy f yT ⎜ hcy − 0.59 Asy yT ⎟ ⋅ ( B − 2 y0 )
⎨ x0
⎪⎩ ⎝ f cT ⎠
⎪ 2∫ Tyh( x )dx − 2S ⋅ sin α
⎪ C= 0 (17)
⎩ 2 cos α where A12 and A34 are the area of the rigid plates 1 or 2
and plate 3 or 4 respectively; dy and dx are the distances
between gravity center of rigid plate 1 or 2 and axis O’
and between plate 3 or 4 and axis O respectively; hcx and
hcy are the distances between reinforcement and the
upper side of the slab in Y and X direction respectively.
Fig.7 Membrane forces in rigid plates 1 and 3 Fig.8 Forces on rigid plate 1 and 3
At the limit state, the force on each rigid plate are shown 2.5. Ultimate load capacity of the slab
in Fig.8, where q12 is the loading capacity of plates 1 and The load capacity of the elliptic part is contributed by the
2, and q34 is the loading capacity of plates 3 and 4.The vertical component force of reinforcement in the elliptic
bending moment equilibriums equations about O’ and O paraboloid, which can be obtained by Eq. (18).
4 ⎡ ∫ Tyv ( x ) ⋅ dx + ∫ Txv ( y ) ⋅ dy ⎤
KL KB
axis can be expressed as
⎢0 ⎥⎦
qe = ⎣ (18)
0
π ⋅ (KL ) ⋅ (KB )
The ultimate load capacity of the slab can be obtained by
5
averaging the load capacity of the rigid plates and that of reinforcement. Taking the smaller one of Kx, Ky and K
the central elliptical part by using Eq. (19). and substitute into the equations (15), (18) and (19), the
2q12 ⋅ A12 + 2q34 ⋅ A34 + 4⎡ ∫ Tyv ( x ) ⋅ dx + ∫ Txv ( y ) ⋅ dy ⎤
KL KB
revised ultimate load capacity of the slab can be obtained.
⎢⎣ 0 0 ⎥⎦ (19)
q=
LB
Max deflection
Effective Reinft Reinft Steel yield
Test Slab size recorded in the Test load
Reference thickness dia. spacing strength fy
No. (m) test (kN/m2)
(mm) (mm) (mm) (N/mm2)
(mm)
1 1.6*1.1 26 3 30 263 127 45.13
Sawczuk
2 2.0*1.0 26 3 60 263 76 17.14
3 1.829*1.829 43.6 4.8 76.2 376 81 42.9
4 Taylor etal 1.829*1.829 37.3 4.8 63.5 376 98 39.03
5 1.829*1.829 69 4.8 122 376 84 38.13
6 Ghoneim& 2.745*1.829 68.2 6.36 120 450 106 45.5
7 MacGregor 1.829*1.829 67.8 6.35 120 450 100 75
8 Cardington 9.98*7.57 6 200 460 390 5.48
U76-305-
9 Guoqiang Li 3*2 4 150 300 90 10
610
9 90 127 1.4
Test load Predicted by Predicted by Guo- Predicted by the qBailey qG.Q Li qnew
Test
qtest Bailey et al Qiang Li method proposed
No. qtest qtest qtest
(mm) qBailey (kN/m2) qG.Q Li (kN/m2) qnew (kN/m2)
1 45.13 45.24 44.18 34.4 1.002 0.979 0.762
2 17.14 14.21 14.63 17.85 0.829 0.854 1.041
3 42.9 35.27 33.60 41.18 0.822 0.783 0.960
4 39.03 40.03 35.51 48.75 1.026 0.910 1.249
5 38.13 31.22 31.22 31.18 0.819 0.819 0.818
6 45.5 41.89 0.897
7 75 58.3 0.735
8 5.48 5.318 0.970
9 10 7.13 0.713
Tests 1-7 were performed at ambient temperature, and 70mm. The reinforcing mesh of the slabs was made by
Test 8, 9 were performed at high temperatures. The limit smooth reinforcement bar with the gird size of
elongation is reduced by 30% for test 1-7 because the 150mm*150mm. The diameter of the reinforcement bar
limit elongation of the reinforcement at ambient was 8mm, and the steel grade was Q235. The thickness
temperature is less than that at high temperature based on of the protective layer of reinforcement was 21mm for S-
statistical regression analysis. 1 and 30mm for S-2 to S-4. S-1 and S-2 had an
The comparisons shown that the method proposed in this unprotected secondary beam supporting the slabs in the
paper can well predict to the maximum deflection and middle, while S-3 and S-4 did not have. The cross
load-bearing capacity of slabs exposed to fire. section of the secondary beam was I25b, and the grade of
steel was Q235. The slabs, the primary beams and
3. Experimental study on full-scaled test secondary beams were designed in according with the
Chinese Code GB50017-2003 and YB 9238-92. The
4 full-scaled composite slab tests were performed in ISO general information of the specimens was shown in Table
834 standard fire at Tongji University to observe the 4. The arrangement of the specimens and the cross
membrane action and verify the presented method. section of the composite slab are shown in the Fig.10 and
Fig.11 respectively. The grade of the reinforcement was
3.1. General information of the tests Q235 and the grade of the concrete was C25. The
The test specimens were 4 pieces of 5.232m*3.72m material property of reinforcement and concrete are
composite floor slabs numbered from S-1 to S-4 with the shown in Table 5 and Table 6 respectively (Where fy, fu
secondary beam and steel decks unprotected. The slabs and δ are the yield strength, ultimate strength and the
were contributed with the profiled steel sheet YX76-344- ultimate elongation of the reinforcement respectively. fcu
688 which is commonly used in China. The thickness of is the cubic compressive strength of concrete).
the deck was 1mm, and its strength was larger than The reinforcement in the test was not anchored at the
270N/mm2 (270 N/mm2 was considered in the boundary of the slab, but exceeded the edge of the slab
calculation, GB/T 2518-2004). The decks were fixed on for 150mm, because the reinforcement would fracture at
the primary beams and secondary beams (if existed) by the boundary of the slab according to the phenomena of
shear connector with a diameter of 16mm and a height of Cardington test. The anchorage condition of the
125mm.Total depth of the slabs was 146mm and the reinforcement is shown in Fig.12.
thickness of the concrete on the top of the decks was
(b) specimens S-3 and S-4 Fig.13 The planform of loading system
Fig.10 Arrangement of the specimens
400
3.3. Test result and analysis
350
1. Temperature
300
ISO 834 standard fire was used in the test. According to
the inspection of the temperature in the furnace, the 250
Temperature(℃)
furnace temperature coincided well with the ISO834 fire 200
curve.
150
Fig.27 shows the bottom temperature curve in the middle
S-1
of the slabs. It can be seen that at the beginning of the 100
S-2
test, the temperature of the slab at the bottom was low, 50 S-3
and then it increased along with time. At the time of 75 S-4
0
minutes, the temperature can reach to 700 or 800℃. At 0 1000 2000 3000 4000 5000 6000 7000
the time of 90 minutes to 100 minutes, the bottom of the Time(s)
slab can be heated up to around 800℃ or 900℃.
Fig.28 is surface temperature curve in the middle of the Fig.29 Average temperature of the reinforcement
slabs. It shows that surface temperature of the slab is of S-1 to S-4
about 100℃ at 90 minutes, which is much lower than
that of bottom. 2. The strains of reinforcement and concrete
Fig.29 is the average temperature curves of the Fig.30 and Fig.31 show the strains of the reinforcement
reinforcement. It can be found that the distance between along the short edge and long edge respectively. Since
the reinforcement and the bottom of the slab has a great the effective working temperature of the strain gauges is
impact to the temperature of the reinforcement. less than 60℃, the data when the temperature was higher
than 60 ℃ are taken off in the figures. Since the
1000 reinforcement located at the compression zone in the
900 cross section of the slabs, according to the yield line
800 theory, the reinforcement should be under compression.
700 However, the data show that the reinforcement was
Temperature(℃)
600 under tension during most of the test except for the
500 beginning. This phenomenon proves the occurrence of
400 tensile membrane action in the test.
300
Fig.32 is the strains curve of the concrete at the boundary
S-1
200 S-2
of S-4. It can be found that the concrete in the middle of
100 S-3 the boundary was under compression. It validates the
0
S-4 existence of the concrete compressive ring which can
0 1000 2000 3000 4000 5000 6000 7000 provide the anchorage for the reinforcement.
Time(s)
2500
#1 #2 #3
Fig.27 Bottom temperature in the middle of the slabs #4 #5 #6
2000
#7 #8 #9
1500
120
Strain (με)
1000
100
500
80
0
Temperature(℃)
40 -1000
S-1
S-2 Time(s)
20
S-3
S-4
0
0 1000 2000 3000 4000 5000 6000 7000 Fig.30 The strains of the reinforcement
Time(s) along short edge in S-1
3500
#10 #11
3000 #12 #13
#14 #15 160
2500 #16 #17
140
2000
120
Strain (με)
Deflection (mm)
1500
100
1000
80
500
60
0
0 500 1000 1500 2000 2500 40
-500
20 S-3
-1000
S-4
Time(s) 0
0 1000 2000 3000 4000 5000 6000 7000
Time(s)
Fig.31 The strains of the reinforcement
along long edge in S-1 Fig.34 The deflection of S-3 and S-4
4. Verification
300
Table 8 shows comparison of the deflection at the center
200
of the slab predicted by the method proposed in section 2
100 and measured in the tests in section 3.
Strain (με)
0
0 1000 2000 3000 4000 5000 Table 8 Comparison of deflection of tests and prediction
-100
-200
Test Deflection Prediction #1* Prediction #2*
-300
#44 #45 #46 # in tests Defl. % Defl. %
-400 #47 #48 #49 S-1 171 161 -5.85 192 12.28
#50
-500 S-2 141 178 26.24 212 50.35
Time(s) S-3 133 192 44.36 212 59.40
S-4 148 198 33.78 213 43.92
*The average temperature of reinforcement measured in
Fig.32 The strains of the concrete at the boundary of S-4 the test was used in prediction #1, and the reinforcement
temperature obtained by Eq. (5) was used in prediction
3. Deflection in the middle of the slabs #2.
Fig.33 and Fig.34 show the deflections in the middle of
the slabs. It is found that after 90min fire exposure the From Table 8, it can be seen that the deflection predicted
deflection of slabs can arrive at 1/25 of the short edge of by the new method presented in this paper is higher than
the slabs. Therefore, it is reasonable to deduce that the that in tests yielding the following reason.
load-bearing mechanism of the slabs has been changed 1) The thermal elongation of the reinforcement was
from bending mechanism to membrane action under such over predicted by Eq. (4) because the confinement
large deflection in the tests. effect of concrete is ignored. In fact, most of the
concrete in the center of slab did not crack in the test,
180 which can provide good confinement and resist the
160
elongation of the reinforcement.
2) The strength decline of the reinforcement and
140
concrete cannot be exactly obtained in the test.
Deflection (mm)
120
3) Strain hardening of the reinforcement was not
100 considered in the prediction.
80 4) Although the catenary effort of secondary beam and
60 the membrane action of steel deck is small, ignoring
40 these efforts made the prediction conservative.
20 S-1 5) The average of top and bottom temperature of
S-2 concrete was used in prediction. However the real
0
0 1000 2000 3000 4000 5000 6000
temperature of the concrete should be lower because
Time (s) the temperature gradient in concrete is significant
large.
Fig.33 The deflection of S-1 and S-2
12
6. Acknowledgement
The work reported in this paper was financially
supported by the National Natural Science Foundation of
China under contract 50621062, 50738005 and
50728805. The support is gratefully acknowledged.
References
Bailey C.G. and Moore D.B. (2000) The structural
behaviour of steel frames with composite floor slabs
subjected to fire: Part 1: Theory, The Structural
Engineer 2000, Vol. 78(11), pp.19-27.
Bailey C.G. (2001) Membrane action of unrestrained
lightly reinforced concrete slabs at large displacements,
Engineering Structure 23(2001), pp. 470-483.
Bailey C.G. (2004) Membrane action of slab/beam
composite floor systems in fire, Engineering Structure
26(2004), pp.1691-1703.
Code for design of steel structures. GB50017-2003,
China.
Continuously Hot-Dip Zinc-Coated Steel Sheet and Strip.
GB/T 2518-2004, China.
Eurocode 2: Design of concrete structures. Technical
Report ENV 1992-1-1, Brussels, European Committee
for Standardisation, 1992.