Professional Documents
Culture Documents
Gosh Presentation-16-12-2010
Gosh Presentation-16-12-2010
FREQUENTLY
MISUNDERSTOOD PROVISIONS
Inc.
IBC/ASCE 7 STRUCTURAL
S. K. Ghosh Associates
I www.skghoshassociates.com I
1---------------_-1-_---~--------.
-_.
__ .__
...
_---_ .._---------------------------_----_.-----
All sections referenced are from ASCE 7-05, unless otherwise noted.
••••
www.skghoshassociates.com
s. K. Ghosh
Associates Inc.
.s.i~~;;_;;:
I
SKG
.C
.R.
!!! '''.'II__
..
.rom!
,h;g; hA~"o&Ia1~~
~-----• HOflilo!' J'~(Jl1U(l
51:_'/SAllL
(, /HlII/)[Sc,
CO"SmTlN(;~r'l
lit,
'III 0. I"" I Pro I' , I
.f.;.~iLn"t=",,1 H • 1•
---
,I, d~1
",,111111011
1,.l(,olr-:I.J.I,uU
-~----
St:u::tLoIIl'- -A
I•
,II'
.~.Iil W II
to.seE
Errata
Click
here
for more
us.efu!
Hnks
MISUNDERSTOOD
PROVISION #1
-4-
www.skghoshassociates.com
soc
A
B&C 0, E & F
NA
1.0 1.0 or 1.3
YH1 Si~S~
Note that p = 1.0 when the SIMPLIFIED PROCEDURE of Section 12.14 is used.
- 6-
www.skghoshassociates.com 3
S. K. Ghosh Associates
Inc.
1. Structures assigned to SOC ~ and C. 2. Drift calculation and P-delta effects. components. not similar to
3. Design of nonstructural
5. Design of collector elements, splices and their connections for which load combinations with overstrength are used. 6. Design of members or connections where load combinations with overstrength are required for design. 7. Diaphragm loads determined using Eq. 12.10-1. 8. Structures with damping systems designed in accordance with Chapter 18.
- 8-
www.skghoshassociates.com
\
CONDITION #1 and CONDITION #2 only need to be checked at each story resisting more than 35% of the base shear.
www.skghoshassociates.com
TABLE 12.3-3 REQUIREMENTS FOR EACH STORY RESISTING MORE THAN 35% OF THE BASE SHEAR
Lateral Force-.Re$ittillg Element Req_nt
Braced Frames
Removal of an individual brace. Of connection tllereto, would nOI result ill more than a 33% reducuon ill story strengUl. nor does IIIe resulling system haw an extreme torsional irregularity (horizontal 'Im<mral irregularity Type U}), Loss-of moment resistance ar Ihe beam-to-column connections at bolh ends of a ,ingle beam would uot result in more titan a 33<;<reduction in story strength. nor does the resulting system have an extreme torsional irregularity (horizontal stroetor.1 irregularity TYiX'lh). Removal of fi shear wall or wall pier with a heigltHo-lenglh ratio greater than 1.0 within any story. or collector cennections tbereto. w(tuld not resul! in more than a 33'/i reduction in story srrength, nor doe, tile resulting system have an extreme torsional irregularity Ihori1.Ontai structural irregularity Type tb). Loss or moment resistance at the base connections or any single cantilever column would not result in more than a 33~cfreduction in story strength. nor docs the resulting system have an extreme torsional irregularity thoraontal.lruclural irre"ularily'!YiX' lbl·
Moment Fnunes
Cantilever Colttmn.~
Other
No requirements -12 -
www.skghoshassociates.com
6
CONDITION #2 :
If a structure is regul?r in plan and there are at least 2 bays of seismic force-resisting perimeter framing on e?9tl§ige of the structure in each orthogonal direction at each story resisting> 35% of the base shear.
-~~'_-*'{>'_~;~"'~~'h~'>~"';_~
'"'
·13·
o
1,
--~~----~------------------------
1
·14·
Two Bays
www.skghoshassociates.com 7
Q: A: for Redundancy
Q:
wall?
Q: A: for Redundancy
Q:
design of foundations?
A: Yes.
·16·
www.skghoshassociates.com
s. K. Ghosh Associates
Inc.
Q: A: for Redundancy
Q:
for a wood-frame building. All of the shear walls are relatively long; in other words, the height of each shear wall (2.45 m) is less than its length (2.75 m, 3.05 m, 3.65 m). Can I assign p = 1.0 because there are no shear walls with a hit' ratio> 1.0?
A:
Yes.
_.
-~---••lsflng ReqUltemet"
'__"1_R
Braced Frames
Removal of an individual brace, or connection thereto. would not result in more than a 33% reduction in story strength. nor does the resulting system have an extreme (orsional irregularity (horizontal ,truc-tural irregularity Type lb). Loss of moment resistance at Ille beam-to-column connecuons at both ends of a single beam would not result in more than a 33% reduction in 'tory strength. nor does the resulting system have an extreme torsional irregularity thorizontal strucrural irregularity Type Ih). Removal of a snear wall or wall pier with a beigbt-!~1I8th ratio greater than 1.0 within any stoty. or collector conoecuons therelO. would 001 result in more than a 33'", reduction in story strength. nor does the resulting systv'lll have an extreme to",ionru irregularity tboriZoolal structural irregularity'lYpe 11», Los, of molllCtll resistance at the base connecuoas or any sin0'" canulever column would Ill)! result in more than a 33% redecnon in story Mrength. nor doe the resulting system bave an extreme torsional jrr~ltularitl' tltorizmual >lnit'lural incgulanty Type 1M,
No reqUifl!tllents
Moment Frames
Shear Walls or Wall Pie! with a height-tolength ratio of greater than 1.0
Cantilever
Cohnnns
Other - 18-
lilt
www.skghoshassociates.com 9
s. K. Ghosh
Associates Inc.
Q: A: for Redundancy
Q: We
(31 stories) with shear walls. When Table 12.3-3 uses the phrase "height-to-Iength" ratio, is that the height-to-Iength height-to-Iength ratio "within any story"? Or is it referring to the overall ratio which, for our building, would mean a height of 100 meters.
Q: A: for Redundancy
A: The
height-to-Iength ratio .
_.-_
... ...
\ I I
I
_.,
........
...
,.,'"
I I \
~,;.-n-rr. .....
....
__
,.,'"
- 20-
www.skghoshassociates.com 10
Q: A: for Redundancy
·21.
Q: A: for Redundancy
A:
levels of the same building. However, depending on the structural system, p can be different in the two orthogonal directions of the same building if Condition #1 is used.
·22·
www.skghoshassociates.com
11
Q: A: for Redundancy
Q:
systems?
) ~ '>
't e. »v-;
1\
",~J.i(
- 23-
A: No .....
FEMA
- 24-
www.skghoshassociates.com
12
Q: A: for Redundancy
'Braced frame, moment frame and shear wall systems have to conform to redundancy requirements. Dual systems are also included, but in most cases are in_h~r~n!JX"E~Q~l:!n£jant. walls with a height-toShear length aspect ratio greater than 1.0 have been included, even though the issue has been essentially solved by requiring collector elements and their connections to be designed for 00 times the design force."
Q: A: for Redundancy
Q:
- 26-
www.skghoshassociates.com 13
Q: A: for Redundancy
A:
factor. If the code did not intend that the redundancy factor be determined for "Nonbuilding structures similar to buildings", there would have been an exception to Section 15.5.1 as is the case with Section 15.6.
Q: A: for Redundancy
Q:
A:
Yes.
www.skghoshassociates.com
14
s. K. Ghosh
Associates Inc.
Redundancy Example
Wall E Wall F
Wall B Stiffness
x, U
Il
www.skghoshassociates.com 15
Redundancy Example
o
soc
o~=~=~=~=~=~=~=~=K
o All walls have the same nominal shear strength,
v;
Redundancy Example
CONDITION #1 CONDITION #2
~:t,
::~
Step 1: Remove shear wall and see if story strength is reduced by more than 33%.
Step 2: Are there at least 2 bays of.. ..on each side in each orthogonal direction?
- 32-
~.
www.skghoshassociates.com 16
Redundancy Example
Check Condition #2 first (it's easier)
Q:
How many bays are there in a shear wall? of shear wall/ story height. .. or for 2 x length of shear
A: Length
I.mt
~
Redundancy Example
CONDITION #1 : Removal of a shear wall or wall pier with a heightto-length ratio greater than 1.0 within any story, or collector connections thereto, would not result in more than a 33% reduction in story strength, nor does the resulting system have an extreme torsional irregularity (horizontal structural irregularity Type 1b).
- 34-
www.skghoshassociates.com 17
Redundancy Example
CONDITION #1
Step 1: Remove shear wall and see if story strength is reduced by more than 33%.
Redundancy Example
Wall E Wall F
WallA Stiffness K,
!)
Wall C Stiffness K,
Wall D Stiffness Kd I
L
I
a
WallH
www.skghoshassociates.com
18
Redundancy Example
Definition of Extreme Torsional Irregularity in ASCE 7-05 Table 12.3-1 : Extreme Torsional Irregularity exists where the maximum story drift, computed including accidental torsion, at one end of the structure transverse to an axis is more than f;f~:!r}imesthe average of the story drifts at the two ends of the structure.
~,~~;</
- 37-
__
1II1
Redundancy Example
The determination of extreme torsional irregularity requires the evaluation of the story drifts ~ and Jh, as shown below.
f
2aJ3
- 38-
www.skghoshassociates.com 19
Redundancy Example
The torsional stiffness about the center of rigidity (CR) is determined as:
Kt
= K[( -at
33'
,1 ')
1." 2 ') 1 ') 1 ') 1 " 1 ') at + at + (-a)'" +{-a}"" +(-a)'" +(-a)'"]
222
- 39-
Redundancy Example
According to ASCE 7-05 Table 12.3-1, extreme torsional irregularity does not exist when ()b < 1.4( ba + bb)
6a
< 2.33
- 40-
www.skghoshassociates.com
20
Redundancy Example
Assume that the story drift caused only by the lateral force V is equal to J, and that 8 is the rotation caused by the torsion T, then
8b
°a
c-
2 8+-a8 3 1 0- a8 3
82 +a8 3 81 a8 3
This ratio is less than 2.33 only if <5/(a8)is larger than 1.08.
Redundancy Example
1V
Kt
S-"'-----
Kt
Therefore, no extreme torsional irregularity is created and p = 1.0. (Note that the term 0.05a is for accidental torsion) Thus, horizontal structural irregularity Type 1b does not exist and the configuration qualifies for a p factor of 1.0.
-42-
_Ks2 3
_ 3
www.skghoshassociates.com
21
MISUNDERSTOOD
PROVISION
#2
Qe
~./ 1
v
- 44-
__..
www.skghoshassociates.com
22
where ()xe is the lateral deflection at floor level x determined by elastic analysis under codeprescribed seismic forces.
Step 2:
Multiply
s.,
by
c, given
in Table
8x
= 8xeCd
II
Step 4:
-46 -
www.skghoshassociates.com 23
s. K. Ghosh
Associates Inc.
Story Drift
Cd
= deflection
amplification factor
- 48-
www.skghoshassociates.com
24
Allowable Drift
ASCE 7-05 Table 12.12-1
Occupancy Category Structure lor II Structures, other than masonry shear wall structures, 4 stories or less with interior walls, partitions, ceilings, and exterior wall systems that have been designed to accommodate the story drift. Masonry cantilever shear wall structures Other masonry shear wall structures All other structures
- 49-
III
IV
i<t:=
For seismic force-resisting systems comprised solely of moment frames in structures assigned to Seismic Design Categories 0, E, orF, the
_::__"'-=>M'''~~~A,"'"",,*Xi"~~'~ ~_~.~
design story drift shall not exceed L1a li:rf()r any story. p shall be determined in accordance with Section 12.3.4.2.
- 50-
www.skghoshassociates.com
25
s. K. Ghosh
Associates Inc.
Q:
Why is drift divided by the Importance Factor? Because the forces under which ()xe are
A:
computed are already amplified by I, and the drift limits set forth in Table 12.12-1 are more restrictive for higher occupancy category buildings.
Q:
A:
••••••
www.skghoshassociates.com 26
Q:
A:
the requirements of Section 12.8 be satisfied for the purpose of computing drift.
----_~
-53-
~_~
_J_
~
- '~-------------------~'------~---~----
-------------------
----_------ -----------~------------.~
-.-
--
,"" 4
- --------,,----------_
Q:
A:
period to be subject to the upper limit of CuT a for the purpose of drift determination.
- 54-
www.skghoshassociates.com 27
- 55-
www.skghoshassociates.com 28
PORTIONS OF THE SAME STRUCTURE: All portions of the structure shall be designed and constructed to act as an integral unit in resisting seismic forces unless separated structurally by a distance sufficient to avoid damaging contact under total deflection (C5x) as determined in Section 12.8.6.
-_ ...._
Code Requirement BUILDING SEPARATIONS (paraphrased): All structures shall be separated from adjoining structures. Separations shall allow for the maximum inelastic displacement OM {including torsion}. Adjacent buildings on the same property shall be separated by at least OMT where ~T
= ~(ijMl)2
+ (6M2i
When a structure adjoins a property line not common to a public way, that structure shall also be set back from the property line by at least the displacement, OM, of that structure. Exception: Smaller separations or property line setbacks shall be permitted when justified by rational analyses based on maximum expected ground motions.
......
_ ...................................
_ .....................................
.....•....................
........................
.........
_ .....
- 58-
···l~
www.skghoshassociates.com 29
= c, bxel
I (Equation 16-44)
bmax
= the
assuming Ax
1 (12.8.4.3)
tlj.... C ,
0f"'i/'-..-e'>--
www.skghoshassociates.com ,
~,,,\;
30
r~M=200mm
~M=150mm
,__
Q:
ASCE 7-05 Section 12.12.3 contains the language contact? any contact at all, the separation sum of
OM1
A: To avoid
and
OM1 0M2'
To avoid damaging contact, ASCE 7 allowsr-,.__ distance to be the statistical sum of sum. which is less than the arithmetic
-62-
www.skghoshassociates.com 31
Q:
less separation between two buildings on the same property than between two identical buildings on different sides of the property line.
A:
The first provision is concerned with to the same owner. is that one owner
damaging contact from pounding of buildings belonging presumably based on consideration The property line setback requirement
·64·
www.skghoshassociates.com 32
MISUNDERSTOOD
PROVISION
#3
-65 -
--------.
www.skghoshassociates.com
33
Q:
in ASeE 7-05?
A:
0.551
Rl (Tj
where 81
;:::
0.6g.
- 67-
> :;.c
fI)
CI) CI)
V-~w ~ (RlIlT
a:t
:g
'iii
CI)
til
Period, T
- 68-
www.skghoshassociates.com
34
s. K. Ghosh
Associates Inc.
Q:
A:
minimum of
where S1 ~ 0.6g.
-70 -
www.skghoshassociates.com 35
2009 IBC Section 1613.1 references ASCE 7 Chapter 35 entry for ASCE 7 reads as follows:
ASCE 7-05 Minimum Design Loads for Buildings and Other Structures including Supplements No.1 and 2, excluding Chapter 14 and Appendix 11A
---------------
·71 •
---
www.skghoshassociates.com 36
s. K. Ghosh
Associates Inc.
to
= ().Q3
nonbuilding
structures _
-------------_._----.
not similar to
i I
en
>
..
<It
D -e 5'j
j.._
h....e, s
s h.e ._"
www.skghoshassociates.com
37
0
E
T~; I) 0.04450sl
! < 0.044R
T T>
50S 501
-
22.73 5 01 R 50S
= 0.4
-76 -
~.~ ..
-.
www.skghoshassociates.com
38
T(R/I)
1.19(8/1)
0.40
0.042
C
s
s;
R/I
8/1
c, 2: 0.044Sos'
Cs
2:
0.044
Governs
0.01
www.skghoshassociates.com
39
Q:
ASCE's website?
A:
1. Go to http://www.seinstitute.org/ 2. From the drop-down menu under "Publications," select "Supplement No.2 to ASCE 7-05."
-79 -
Q:
A:
the requirements of Section 12.8 be satisfied for the purpose of computing drift.
- 80-
www.skghoshassociates.com 40
MISUNDERSTOOD
PROVISION
#4
Table 1607.1: Minimum Uniformly Distributed Live Loads, Lo, and Minimum Concentrated Live Loads
CJ
Based on, but not identical to, ASCE 7-05 Table 4-1 (same title)
- 82-
www.skghoshassociates.com 41
Alternate floor live load reduction, based on tributary rather than influence areas, retained from UBC and other model codes.
Applies to slab systems, beams, girders, columns, piers, walls and foundations 1. Reduction not permitted in Group A (assembly) occupancies 2. Reduction not permitted when live load exceeds 100 pst, except design live load for columns may be reduced by 20%
- 84-
www.skghoshassociates.com
42
S. K. Ghosh Associates
Inc.
.LA.
For use other than storage, where approved, additional live load reductions shall be permitted where shown by the registered design professional that a rational approach has been used and such reductions are warranted.
- 85-
2009 IBC 1607.9.2 Alternate Floor Live Load Reduction (co nt' d)
3. A reduction shall not be permitted in passenger vehicle parking garages except that the live loads for members supporting two or more floors are permitted to be reduced by a maximum of 20 percent
- 86-
www.skghoshassociates.com 43
2.40 to 1.92 kN/m2. The same value is in 2009 IBC Table 1607.1.
- 87-
www.skghoshassociates.com 44
live loads for any member supporting 13.94 m2 or more may be reduced by
R (%)
= r (A -
13.94)
where r = 0.86 percent for floors Such reduction shall not exceed 40% for horizontal members, 60% for vertical members, nor
R (%)
1------------.
= 23.1
(1 + D/Lo)
....• ~
8-9 .--~~~----.-.----.~.-
100
..J
C
i'5
60
- -I--------
o,
a; 40
1 I 1
-1- - - 1 1 1
14
60
Tributary Area, A (rn'') Floor Members
84
·90·
www.skghoshassociates.com 45
10
L
=:
Reduced design live load shall be not less than 50% of La for members supporting one floor nor less than 40% of La for members supporting two or more floors
-92 -
www.skghoshassociates.com 46
Influence Areas
II
•
Interior supporting
member
member
- 94-
www.skghoshassociates.com
47
~W////////~
~//////////k
L..-J!
"""-1
- 95-
KLL
4 4
3 2
2 2
_,,=s=h=e=a=r=tr=a=ns=f=er=n=o=r=m=a=' t=?=t=he=i=r_==sp==a=n=======,==~
-96-
..
1_
~
www.skghoshassociates.com 48
'I
_______________ ~
-97-
I.m1_
~
- 98-
www.skghoshassociates.com 49
- 99-
- 100-
www.skghoshassociates.com 50
-102 -
www.skghoshassociates.com
51
The minimum uniformly distributed roof live load, Lo, is now given in Table 1607.1.
R1 = 1
= =
for At ~ 18.58 m2 for 18.58 m2 < At < 55.74 m2 for At ~ 55.74 m2 for F ~ 4 for 4 < F < 12 for F ~ 12
1.2 - 0.011 At
0.6 1
R2
= 1.2 - 0.05F
= 0.6
where, for a pitched roof, F expressed
I__
in percentage
=_
rise-t()=~Ei3.nrati()f!1~I!iPI~~~
~~y?2_~__
_.
www.skghoshassociates.com
52
S. K. Ghosh Associates
Inc.
to be landscaped, the uniform design live load in the landscaped area shall be 0.96 kN/m2. The weight of the landscaping materials shall
be considered as dead load and shall be computed on the basis of saturation of the soil.
·106·
www.skghoshassociates.com
53
1607.11.4 Awnings and canopies. Awnings and canopies shall be designed for uniform live loads as required in Table 1607.1 as well as for snow loads and wind loads as specified in Sections 1608 and 1609.
= 3.65 m
= 2.40
kN/m2 (for a typical office building, see 2009 IBe Table 1607.1)
www.skghoshassociates.com
54
lifI----I I I I
III
III
:T
f I
I
6m
II
I I
+t
Tributary area for comercolumn Plan
-109 -
:1
6m
lliecVsl ~
www.skghoshassociates.com
55
s. K. Ghosh
Associates Inc.
Ar
La
KLL
KLL x
Ar
R (%)
R (max) (%)
Reduction (%)
L (kN/m2)
2 1
4 4
42 84
4.5 25 R = 1- LILa
50 60
4.5 25
2.29 1.80
- 111 -
Ar-
Lo 2.40 2.40
R (%) 0 6.07
R (max) (%) 60 60
0.86
www.skghoshassociates.com
56
S. K. Ghosh Associates
Inc.
Ar Level (m2)
2 84 168
Lo
2.40 2.40
KLL
KLL)(
Ar
R
('Yo) 25 40
R (max)
('Yo) 50 60
Reduction
('Yo) 25 40
84 168
R = 1- LILa
- 113 -
Ar
Lo
R (%)
R (max) (%)
R (max)' (%)
Reduction ('Yo)
L (kN/m2)
2 1 *
84 168
2.40 2.40
0.86 0.86
60.3 132.5
60 60
78.5 78.5
60 60
0.96 0.96
www.skghoshassociates.com 57
Q:
A:
partition loads cannot be reduced. However, there is an unofficial ICC interpretation out there, which says it cannot be reduced because it is not listed in Table 1607.1.
- 115 -
(Equation 16-1) (Equation 16-2) (Equation 16-3) (Equation 16-4) (Equation 16-S) (Equation 16-6) (Equation 16-7)
1.2(0 + F + T) + 1.6(L + H) + O.S(Lror S or R) 1.20 +1.6(Lr or S or R) + (f1Lor 0.8W) 1.20 + 1.6W + f1L + O.S(Lror S or R)
n,)
-r
)1.-
0.90 + 1.6W + 1.6H 0.90 + 1.0E + 1.6H f1 = O.Sexcept in special circumstances f2 = 0.2 except in special situations
- 116 -
--III
www.skghoshassociates.com
58
s. K. Ghosh
Associates Inc.
different from live load reduction based on loaded area typically allowed in general building code. • The live load reduction adjusts the nominal load, L. • The smaller load factor reflects the reduced probability of simultaneous occurrence of maximum values of multiple transient loads. • Both may be used at the same time.
--~----11-7 :-----------------------
---III
MISUNDERSTOOD
PROVISION #5
~-::_~M ~~--.~~
A A~-e:===-
-118 -
III
www.skghoshassociates.com
59
STATIC ANALYSIS PROCEDURES Simplified Design Procedure Equivalent Lateral Force Procedure
- 119-
-III
DYNAMIC ANALYSIS PROCEDURES Modal Response Spectrum Analysis Linear Response History Analysis Nonlinear Response History Analysis
www.skghoshassociates.com
60
S. K.
Ghosh Associates
Inc.
- 121-
Category I or II
Site Class A, B, C, or 0 Three stories or less in height Bearing wall system or building frame system
4.
5. through 12 ......
-122·
www.skghoshassociates.com
61
Design
A:
• p = 1, no = 2.5.
• No period (T) determination. • No triangular distribution of seismic forces. • Determination of Fa simplified; Ss need not exceed 1.5g. • Drift need not be calculated
- 123-
* 12.3-1 ** 12.3-2
-124 -
www.skghoshassociates.com
62
(Ts is the period at which the flat-top portion of the response spectrum transitions to the descending (period-dependent) branch.)
fs
www.skghoshassociates.com 63
-128 -
www.skghoshassociates.com
64
MOVer
All structures of light frame construction, irrespective of height - Dynamic analysis never required
Occupancy Category I or II buildings of other construction not exceeding two stories in height - Dynamic analysis not required
-130 -
www.skghoshassociates.com
65
Q:
with T < 3.5Ts and all structures of light frame construction" are permitted to use an Equivalent Lateral Force Analysis. Does this mean that the building must meet both conditions (regular with T < 3.5Ts and light frame construction), or does only one of these two characteristics need to be satisfied?
·131.
A:
Regular Structures with T < 3.5Ts are permitted to use Equivalent Lateral Force Analysis. All structures of light frame construction, irrespective of height, are also permitted to use Equivalent Lateral Force Analysis.
·132·
www.skghoshassociates.com 66
MISUNDERSTOOD
PROVISION
#6
(can experience
.:. Enclosed
-134 -
www.skghoshassociates.com
67
Internal Pressure
-135 -
OPEN
A building having each wall at least 80% open.
Ao ~ 0.8 Ag
for EACH side of the building
-136 -
www.skghoshassociates.com
68
, .'
"'..
'.'
. ....
'I
,I
i
~.
www.skghoshassociates.com
69
~U.5L
____...
c~'W
,~~
Roof Angle
ra()·E~
e
7.;1' IS'
A A
Wind Direction
¢=
y=180·
11177777777777)717
7/
111171/11
Clear Wmd fl.", 1.2 -1.1 O.? 1.6 13 1& O.l .0.1 1.5 OJ 1.6 0.6
J.Ij
WmclDirectioo • .,,,,.rf Clear Wind Flow Ob!I1ll<t<!dWind Flow 1.2 -1.1 0.6 ·U ·0.9 ·1.9 ·1.5 -1.8 0.3 .0.1 ·1 0
.1.)
Ob!U"lCkd Wlud flow -OS .1.1 -0.2 0.8 0.. 1.2 -1.2 -lk6 .1.2 -0.3 ·1.1 -0.3
0 ·1.6
.rs
-OJ .1.8 .0.6
.ll
·2.5
A
45'
B A B
·1.3 .2,4
-t.s
-2.2
-1.5 -2.l
·1.6
·2.3
·I.~
-0.1
-u
·1.9
·1.1 .0.6 .J.S -0.8 .1.5 -0.6 ·1.7 -0.9 -1.8 .1.1 ·1.8 -1.1 ·1.8 -12
1.7
2.2 2.1 1.6 2.1 2.1 1.2 2.6
0.5
I.J 0.6 1.6 0.1 1.9 0.8 2.1
-I
0 ·1 0.1 ~).9 OJ -0.9 M
·140·
www.skghoshassociates.com 70
Notes: I. C.w and denote RC! pressures (contribution, from top and bottolll surfaces) fur windward and leeward half of roofsurfioces, respectively. 2. Clear wind flow denotes relatively unebstmcted wind flow with blockage less than or equal to 50%. Obstructed wind flow denotes objeclt below roof inhibiting wind flow (>50% blockage). 3. For values Of between 7.S· and 45', linear interpolalion is permitted. for values of 9 less than 7.5·, usc load coeffIcients forO·. 4. ?lUll and minw; signs signifY pressures acting towards and away from the top roof surface, respectively. 5. AlIluadc.,.,. shown for each roofangluhall be ilIvestlgated. 6. Notation: L : horizomal dimension (If roof, measured in the along wind direedon, ft. (m) h : 01_ roofbeight, ft. (III) '( :di""'ri.onOfwind,dc~ D : angle ofplanc of roof from horizontal. ~
em
- 141 -
PARTIALLY ENCLOSED
1. Ao ;:: 1.1 OAoi 2. Ao > 0.37 m2 AND> 0.01 Ag 3. Ao/ Agi
s 0.20
-142 -
www.skghoshassociates.com 71
-144 -
www.skghoshassociates.com
72
A:
NO.
-146 -
www.skghoshassociates.com
73
ENCLOSED
A building that does not qualify as OPEN or PARTIALLY ENCLOSED.
-147 -
------1[111
--_._-_._-_
__ ._._-_._._--j
···~-148-~·-·~ .. -
--.-.-.- -...... . .
--
····111
www.skghoshassociates.com
74
Enclosure Classification
Figure 6-5 Internal Pressure Coefficients, GCpi
Enclosed Buildings
1------------_ - --_
1 49
-----------1tI
p = qGCp
qGCpi
- 150-
www.skghoshassociates.com 75
WI
Net·-O.3
INTERNAL SUCTION
1.1
www.skghoshassociates.com
76
Q:
A:
tables. In a simple diaphragm building, internal pressures cancel out for the walls but not for the roof.
doors and
A:
·154 -
www.skghoshassociates.com
77
MISUNDERSTOOD
PROVISION
#7
1.20 + f1 L + Em
0.90 + Em
•••
78
www.skghoshassociates.com
-157 -
2006 IBC Section 1605.4 had one set of "special seismic load combinations" applicable to both ASD and strength design. ASCE 7-05 has two sets of "load combinations with overstrength factors" ... one for ASD and one for strength design.
CJ
-158 -
www.skghoshassociates.com 79
-159 -
~H
www.skghoshassociates.com
80
- 161 -
-162 -
www.skghoshassociates.com 81
1.7 ....
-163 -
------
-164 -
www.skghoshassociates.com 82
3. The load combinations with overstrength factor specified in Section 12.4.3.2 of ASCE 7 where required by Section 12.2.5.2, 12.3.3.3 or 12.10.2.1 of ASCE 7. With the simplified procedure of ASCE 7 Section 12.14, the load combinations with overstrength factor of 1~ _ _::s:=,:,e===c=ti::;:on::,:-::,:::12=.=-,1=4:=:::.3=.2:::.::0=f=A:=:::~=1?::;;::5 ~::::7=s=h:,::"a="=b::::e=u=se:::d":::.. ~_~ __
r---~~-------~~.~
Q: Section
and other structures and portions thereof to be designed to resist the load combinations with overstrength factor specified in Section 12.4.3.2 of ASCE 7-05 where required by Section 12.2.5.2, 12.3.3.3, or 12.10.2.1. Can you elaborate?
·166·
www.skghoshassociates.com
83
A: Cantilever
Column Systems
Foundation and other elements used to provide overturning resistance at the base of cantilever column elements shall have the strength to resist the load combinations with over strength factor of Sectio n 12.4.3.2.
I--------.-
iiiiiiiiiiiiiiiiiiiilli .....
-167-
IIIlIll••
~
.... -~--.--.--------------_l~
A:
walls or
www.skghoshassociates.com 84
-----------
·169·
·170·
www.skghoshassociates.com
85
Collector elernents .
r V Sh&~J~ t..JJJ:;
www.skghoshassociates.com
lv<v:>
86
-173 -
MISUNDERSTOOD
PROVISION
#8
~~
-174 -
www.skghoshassociates.com
87
o In different directions
u In the same direction
-175-
www.skghoshassociates.com
88
R =5 Cd = 5 no = 2%
R = 8, Cd = 5 %,
-177 -
no = 3
-178 -
www.skghoshassociates.com 89
s. K. Ghosh
Associates Inc.
R: Cannot increase as you go down Cd and .0.0: Cannot decrease as you go down
Vertical combinations
R: Cannot increase as you go down Cd and .0.0: Always correspond to R ASCE 7-10 Section 12.2.3.1 Vertical Combinations
...•-
--
-180 -
-.
www.skghoshassociates.com
90
s. K. Ghosh
Associates Inc.
- 181 -
www.skghoshassociates.com 91
-183 -
www.skghoshassociates.com 92
www.skghoshassociates.com
93
which is extremely unlikely in view of the large design forces that would result from an R = 1.5, large inelastic displacements possible. do not seem to be
~\e would
automatically
result from the low value of R used in design. These, multiplied by the Cd of 5.5 would yield unrealistically large total displacements. Cd of 1.75 appears to be much more logical. This second interpretation was implicit in the 1997 Uniform Building Code, where O.7R was used in place of Cd'
-188 -
www.skghoshassociates.com 94
-189 -
-.~-----
..... -~.~-.-------- ..
no Values
~~~-~.~--
---
...
--.----------~-~~-~.~-.-~.-.~ ~-~-~.
...
systems used. In the case where two or more systems have the same least value of R, the largest of the corresponding values of Cd shall be used.
f\
value
to the system with the least value of R for any of the values of 00 shall be used .
systems used. In the case where two or more systems have the same least value of R, the largest of the corresponding
I·
- 190-
www.skghoshassociates.com 95
t--------------------------------I~·191·
Q: A: for Combinations
Q: I am designing
reinforced masonry shear walls and special steel braced frames in the same direction. R values are 5.5 and 6, respectively. I understand that I should design the building with the smaller R
=
masonry shear walls and steel braced frames in this direction for seismic design in accordance with ASCE 7-05 Section 12.2.3.2. But someone told me that the building should be designed by analyzing the entire building twice: use R
=
and design the masonry shear walls and use R = 6 for the entire building to design the steel frames. I don't think this is right. What is
-192 -
www.skghoshassociates.com 96
Q: A: for Combinations
A:
MISUNDERSTOOD
PROVISION #9
-194 -
www.skghoshassociates.com 97
...... __
wp
for 80S = 1.00, Fp = 0.30 IpWp for 80S = 1.00, Fp = 1.60 IpWp
...
- . -- -_---- .- •....-
----
.---~-.---.-
- 196-
www.skghoshassociates.com
98
2. 3.
-198 -
www.skghoshassociates.com 99
ASCE 7-05
Rp
2.5
Explanation of Fp Equation
1.2SDS
=h
--~--- ---------------
-200 -
www.skghoshassociates.com 100