the ceiling at 32°C and 70% relative humidity (airstream 2). Determine the relative humidity and
temperature of the resultant airstream 3 if the outside flow rate is 40m³/min and the inside flow rate is
20 m³/min.
Solution
An energy and mass balance of the mixing of airstream 2 to produce airstream 3 would reveal the
following facts relative to the paychrometric chart:
98.3
∴ ⍴a 1= =1.19 kg/m ³
(0.287)(288)
9 5 .2
∴ ⍴a 2= =1.0 9 kg/m ³
(0.287)(305)
kg
∴ ṁ a1 =( 40 ) ( 1.19 )=47.6
min
kg
∴ ṁ a 2=( 2 0 )( 1. 0 9 ) =21. 8
min
State 3 is located by the ratio d2-3 / d3-1 = ṁa 1 / ṁa 2 = 47.6 / 21.8 = 2.18, where d2-3 is the
distance from state 2 to state 3.
State 3 is positioned on the psynchrometric chart, and we find Ø = 63% and T3 = 20.2°C.