Digital Inputs:
On Command FOR STARTERS: For each motor (from local push button station)
Off Command FOR STARTERS: For each motor (from local push button station)
1) Zero speed
Total No of Conveyors:
1) Bc-13-11 KW-11m
2) BC-14-30 KW-78m
3) BC-15-15 KW-70m
4) BC-16-15 KW -70m
5) BC-17-37 KW-103m
6) SC-5-55 KW-22m
30 KW and above for starting using a star delta starter. For BC-16 & SC-5 for
starting using IP42 class drive and starter by pass arrangement.
Each 15m once the pull chord switch will be fixed in both sides.
EMERGENCY SWITCH:
For BC-16 AND SC-5 using a logical operation to avoid operates the VFD and starter
at a same time.
Before starting the motor should monitor the MCCB healthy condition.
IF any fault (pull cord, zero speed, emergency, temp fault) is occurs based on this
the motor should off.
The local & Field selector switch input for operates the motor from MCC and from
field also.