“Annexure to lr, No.CEIG/TS/EHV/HV/D.No. 201 dated - -201
Drawing provisionally approved subject to the compliance of the
following conditions,
1 FP COMMEN orsi -
1. The erection of all electrical equipments shall be strictly as pe:
Approved drawings, Indian Electricity Rules, 1956, Indian
Standards and National Electric Code.
2, The width of the plinth shall be just sufficient to take the base of
the transformer,
3, A'separate entrance for the supplier to their metering equipment
‘shall be provided.
4, Circuit breaker of appropriate capacity shall be installed at the
point of commencement of supply:
tl. TRANSFORMER :=
1. Inter locks shail be provided between the isolators and their
respective circuit breakers and earth switches
2, Tremaformers in parallel shall have interlocks such that when
the primary circuit breaker of the transformer is tripped, the
Corresponding secondary circuit breaker also to be tripped.
43, bent electrodes of the Transformers, Generators and Lightning
‘Aarestors normally shall not be connected as earth grid.
4, Copper flat shall used for Neutral of Transformers, Generators
‘and Lightning Arrestors
5, Baltic sail shall be constructed between the Transformers if oil
content is 2000 litres and above.
6. Souk pits shall be constructed for the Transformers of il content
each of 9000 litres and above.
7, Another Circuit Breaker shall be installed, if distance is more
than 15Mirs of walking distance.
8, Ban duct shall be provided on the secondary side of the
Transformers for 750KVA and above capacity up to PCC panel
Ill, CONTROL ROOM ==
1. The cables shall be dressed properly and fixed with inverted
‘U'clamps on to the racks run in the cables trenches
2. Gables of different voltages shall be run on different levels.
Cable of A.C. and D.C. shall be separated.
Contd. 2.2
3. Two separate earth flats shall be run on the either side of the
cable tray and connected to two separated earth electrodes.
4, All the hinged doors shall be earthed to their respective frames
with Rexible wires.
5, Identification such as cable size, length and load on the cable
shall be noted at their respective control switches on the panel
board,
IV, MACHINERY SECTIONS:-
1. Two parallel earth bus shall be run all through the machinery
sections with raiges at cach equipment or machine. All the
motors, starters,
2. switches on the machines and frame shall be provided with
double earth flats each directly tapped from the two parallel
earth bus. The earth wire so connected shall be less than 15°
in length and the size shall be as per capacity of the motor /
equipment
3. Normally bare copper or G.l. shall be used for body earthing.
4, Externally earthing is normally to be carried in preference to the
4% wire of the cable.A.C. earth system,
5. The long and cross travel motors of the E.O.T crane shall be
provided with earths of sufficient size and continuous earth wire
Shall be provided all along the rails earth earthed at the both
ends,
6. Automatic P.F. controls shall be installed for the capacitor
oR
Capacitor of appropriate capacity shall be connected in shunt for
each motor of motor 20HP and above, For motor of lesser
capacity the consolidated capacitor bank shall be connected at
the nearest distribution panels.
7. For motors which are more than 15° away or out of sight from
the control panel, 2%! isolator shall be fixed locally nearer to
such motor. In case of local emergency switches, the ‘OFF”
Dutton switches shall be provided with lock and key
arrangement
8. The cable and cable trenches shall be laid as per provisions of
18 2272-66
V, GENERATOR
1. An automatic arrangement shall be made such that only one
neutral contact is closed when the generators are running,
coma 3,3
parallel among themselves. Due to any fault ifthe generator
fwhen neutral) contact is closed to carth goes out of
synchronism neutral contact ofthe other generator shall be
closed automatically
2. If the generators are to be run parallel with the grid of the
DISCOM or APTRANSCO arrangement shall be made such that
pone of the neutral earth links of the generators are closed. Due
to any reason if supply from the DISCOM fails arrangement shall
be made such that neutral links of the generators shall be closed
automaticaly.
GENERAL:
1. The location of D.Bs should conform to Rule 51 of Indian
Electricity Rules, 1956.
. installation of Transformer shall be as per 1S — 1886.
Suitable provisions shall be made for immediate and automatic
discharge of every static condenser on disconnection of supply.
‘nil plug sockets shall be three pin type and the third pin shall be
permanently and efficiently earthed.
5, Local controls Isolation shall be provided for the motors
wherever necessary. Any instruction is issued in this regard at
the time of inspection shall be complied with.
6. Earth pits should be constructed as per IS 3043 -87 and the
arth electrode of 100mm in diameter of CI pipe and 2.5 Mtrs. in
length.
‘The Electrical Installation work shall be got executed through
only a Licensed Electrical Contractor as per the provisions of
Rule 45 of Indian Electrical Rules, 1956.
& The Licensed Electrical Contractor shall submit | a
commencement report to this Office immediately after
Commencing the electrical installation work. This should indicate
the names of the permit holders supervising and executing the
work.
9, The licensed Blectrical Contractor shall submit his completion —
cum _ test report in the prescribed proforma after completion of
the work.
40, The installation should conform to relevant provisions of Indian
Blectricity Rules, 1956.
11. Approved drawings shall be displayed in the factory premises.
sal-3 Tononcng LY
HEF ELECTRICAL INSPECTOR
£20 'T0 GOVERNMENT