Multizone air handlers, for a long time, were considered the Cadillacs of air conditioning. With the rapid increase in energy prices, the multizone has virtually eliminated the multizone. Advances in multizone energy conservation include the use of high-low pressure selectors. Another control strategy that is acknowledged to save energy is the "deadband thermostat"
Multizone air handlers, for a long time, were considered the Cadillacs of air conditioning. With the rapid increase in energy prices, the multizone has virtually eliminated the multizone. Advances in multizone energy conservation include the use of high-low pressure selectors. Another control strategy that is acknowledged to save energy is the "deadband thermostat"
Multizone air handlers, for a long time, were considered the Cadillacs of air conditioning. With the rapid increase in energy prices, the multizone has virtually eliminated the multizone. Advances in multizone energy conservation include the use of high-low pressure selectors. Another control strategy that is acknowledged to save energy is the "deadband thermostat"
Advanced multizone
control concepts
Maintenance of desired temperatures
and energy savings are available with
advanced multizone control concepts
BALFREDEGUNTERMANN PE &8shown in Fig. 4. (The mechanical
Renee a ANS PE cooling cold deck temperature is
‘Technical Services Die, usually held constant at-60 F or be-
‘The Avatin,Co, Cleveland, Ohio low to provide dehumidfieation.)
———$_ Tre resetting of the hot and cold
deck temperatures from actual
space demand is an improvement
‘ver the traditional method of re-
setting them from outside air tem-
peratures. This former approach
Virtually alway’ results in excessive
energy waste because the hot and
cold deck temperatures have to be
set for worst case conditions and
the eontrols can’t sense changes in
space conditions.
‘Another control strategy that is
acknowledged to save energy is the
“deadband” thermostat. In lieu of @
single room temperature set point
such as 74 F, a deadband thermo-
stathas two set points such a8 78/70
F. Essentially no heating nor cool-
ing is added between the set points;
heating will beused tomaintain the
loner set point, while cooling will be
‘Multizone air handlers, for a
long time, were considered the Cad
illacs of air conditioning systems
because of their ability to maintain,
precise zone temperatures. Howey.
cr, with the rapid increase in energy
prices, the inefficiency of mixing
hot air with eold air has virtually
eliminated the multizone from to
day’s energy designs. One problem
isthat during the economizer cycle,
for every degree the cold deck tem.
perature is lowered below the re-
turn air temperature, a degree of
reheating is added to the hot deck
as shown in Fig. 1, Also, when me-
chanical cooling is required in liew
of the economizer cycle, extra ener-
gyis consumed when zone mixing is
required to mechanically cool the
used to maintain the upper set
point (see Fig. 5). This control has
the added advantage of automat.
ically switching the space tempera-
ture settings from heating to cool-
ing.
Other considerations
‘The deadband thermostat has
not been recommended in the past
for use with simultaneous heating
and cooling systems such as multi-
zones. What happens is the zone
mixing dampers are at their ap-
proximate midpoint, which is their
last controlling position as the
room temperature enters the dead-
band temperature range. ‘There-
fore, if one zone calls for heating,
some heat is added to all zones de-
pending on the last controlling pos-
ition of all of the multizone damp-
ers. As a result, on multizones, in-
stead of the space temperature
is usually forced to the
jt, and then the econo-
air and then reheat it (see Fig. 2)
Advancements fa
One established advancement in
the area of multizone energy con-
servation is the use of high-low
pressure selectors to reset the hot
and cold deck temperatures from
the actual space temperature. For i.
example, the hot deck temperature | {04 )} | Siro G
is reset to the selected temperature 4 ;
necessary to meet the coldest zone Sue
(sceFig. 9) Similarly the mixed air ioja CU
femperature is reset up during pe- aLUTER hile
riods of economizer operation to ee
provide only enough outside air to
1% 200 etm > (88:3 — 60) = 6226 Btun
11 x 200 cfm > (883 ~ 70) = 4026 Btn
2 savings = 2200 Blu
meet the greatest cooling demand 1 Economizer jee ofact on hot deck of raising cold dock (mixed a)
20 Hestng!Piping/Ar Conditioning « Novernber 1961mizer cycle is activated to maintain “forcing” the space temperature to these deadband conditions; it
the upper limit. the opposite limit, but also the oe- makes little sense not to make use
The opposite effect will ocenr cupants ean become uncom. of this free economizer cooling until
during the cvoling season because —fortable. the upper limit of the deadband
‘mechanical cooling will gradually Another problem to overcome is temperature is reached (e.g, 78 F)
foree the space temperatiie to the that of lost temperature control A possible solution is to utilize a
lower limit. Asa result, not only is during the deadband range. Usu- return air thermostat to modulate
excessive energy wasted by ally free cooling is available during the mixed air dampers during econ-
‘omizer periods to maintain an aver-
a ‘age space temperature of, for ex-
e ample, 72 to 74 F. This will provide
a substantial improvement in the
ability to control space tempera-
tures during a period when outdoor
air is available for free cooling. In
ase one of the temperatures ex-
ceeds the limits of the deadband
temperatures, then either the
deadband thermostat will increase
the hot deck temperature to main-
tain the lower deadband tempera-
heat = 1.1 x 100 efmx (80 — 70) = 1100 Btu ture setting, or in the ease of econo-
2 cool = 1.1 x 100 crx (80 — 60) 3415 Buh per ei12,000 Buh ger em= _62661u» | mizer cooling, the deadband ther-
otal mostat will override the return air
2 Mechanical cooing efoct of mang ot and cola deck alr streams, ‘wonroller thea ye nasal loro ene
sure selector and will inerease the
amount of outdoor air to lower the
mixed air temperature to maintain
the upper limit temperature in the
‘worst zone,
‘The primary advantage of the
deadband thermostat with a multi-
zone system is that simultaneous
heating and cooling will largely be
avoided because there isa tempera-
ture range between the space heat.
ing and cooling temperature set
points. When one zone is calling for
Tinie x 0st = Resting with ase poineof (0 Fite
deg 21x 0 x Woah oo unlikely that second zone wl be
ees Callingforcolingat TF Thts, the
Leaecre ree eee wisn a imore cxtone hot and
2 Te esting ol ho dock fo ao dona cold deck Temperatures is tin
2
A & “Deatband
€ fat ~ 11 200 cm x (83 — 652) = S060 un 2 ae
deed = 11% 0x 653-653) = 0
i ‘awa 5060 Btun ‘Space temperature
{The esting of th eomonar col deck am space dan oasaaieT anode
HeatngPiping/Ar Concttioning » November 1981 aAdvanced multizone
control concepts
imized or eliminated. As a result,
during heating periods, the mixed
air temperature can he automat.
ically reset to substantially higher
temperatures, thereby greatly re-
ducing the amount of required
heating.
Energy consumption
‘Tables 1, 2, and 8 show the energy
consumption for a multizone that
hhas three 200 sq ft zones (see Fig. 6)
under three different temperature
control schemes. Table 1 shows the
energy consumption for a multi-
zone that has a constant 60 F cold
deck temperature. ‘Table 2 shows
the energy consumption for a mul
tizone that has an economizer
mixed air temperature automat-
ically reset to meet maximum space
demand using a high-low pressure
selector. Table 3 shows the energy
consumption for a multizone unit
that incorporates both a deadband
thermostat system and a hot deck
and economizer cold deck reset
from space demand.
Since Space 2 in Table 2 has a 4.7
F air temperature rise from the in-
ternal heat gain, Space 2's tempera.
ture will be maintained 4.7 F above
the supply air temperature. With
the deadband thermostat, the min:
imum supply temperature will usu.
ally be set by the minimum outside
air damper setting (see Column 2in
‘Table 2). Therefore, with a dead-
band thermostat, in our example,
the temperature will float from 70.5
F (65.8 + 4.7) at zero F outdoor air
temperature to 74.7 F (70-+4.7) at
70 F outdoor air temperature. Ob-
viously a temperature of 70 F is less
comfortable in winter than 74 F.
Note that above 50 F outdoor air
temperature, virtually no heating
‘or cooling energy is required. Fur-
thermore, additional energy sav-
ings could be obtained if the min-
imum percent of outside air could
be reduced,
Since the bulk of the heating
“hours of occurence” for most cli
mates is in the intermediate tem-
perature ranges, the deadband
thermostat can substantially re-
2
“Tgble 1 Space thermostats are set a 70 F and economizer cod Seeks set at 60 F
(See Fig
Saeet Soe? Sees
| sear ary reir
Cuca ar} ol ening cosine corsunp-|oot ev] consuro- | col enn] osu
‘rere | sama [eters un renee] en (erp en
fet | meet [ume | wu tum | wus [uel | vee
0 ry Tse] s:) it] we az
0 & sa | ss | 1 m2 | 334
a 6 7 | ea | an | as | ae
2 & | #5 | aa | tt | ne | 2a
a je) ei | ue | ae | ee
a 60 oo | @a | iit | ae | te
a o jim | Si | ir | go) ie
n 0 iss | ea | ts | ea | 3s
‘Gonatart 0 cld ock mpeg.
"Cal mpacue neces to aan 7DF ft nt nat oss
mun = 1-1» 200 cm» feaveg a emperare ~ etn 2 anger),
"Table 2—_Space thermosiats are set at 70 F and economizer cold deck ls sat fom
space demand (soe Fi. 6)
‘wae Space 2 spaces
| far Tey tear
Cutcr ai] ot ering | ean] consump |ct iain] const | Collen] cons
Tamora: | ar tempus jr eget ton [taper] ton (se terpary on
fuer | cuwese [were | wwure [turer | wane [west | were
a | ss | ms | sm] e2 | ¢ 78 | 258
w | @3 | so | a | a | o me | oa
a | 83 ae | ea | a ns | ia
a | 8 be | ea | a we | iat
a | ea ou | ei | a m2
| ws ta | 3 | 0 Be
a | 3 m | 3 | 0 oo
n no as | @2 | ts | Bo
TTorwerarocesay tv Space 2070 Fn wie 125 Buk = 200G)= 47 F
‘Gon wenpertute mersay to ara 70F oot me et ss,
Sunt 20 cn
ten a oroetre eng a teu),
Table $7870 F deadband thermostats and economizer cold deck se rom space
demand (see Fig.)
‘Spas?
Ere
ato a | ol ning coi evn) consumo-
tum | ar tmper jar temuray ten,
wwe | “we ‘ue | bah?
> | 8 ss | 0
o | ge fe | 0
a | me fe | 0
o | oa | we | 0
o | o. fe] 0
so | ms me | 0
| mo mo | 0
m | no mo |
‘Getening ata —(eaceterpaue «alg <8 ousoora emp) 105
°Galtempere neces to arian TOF ett hast oss
‘Mur 20 n= eng ar eget" oer engerati)
- tk
=| soe | span
4 3
: + 102511495
=| space
= 2 Qe = WT = 026 x vall ama x (10 ~ OF)
‘b °3-w pot og ft x 3415 Btuh per w x 200 sqft
& x O50 = 1025,
6 Three zones under diferent temperature control schemes.
Heating/Piping/Alr Condtioning « November 1981duce the multizone’s annual energy
consumption,
Normally, the problem of the
deadband thermostat “forcing” the
temperature would occur in Spaces
2 and 3, and the space tempera-
tures would be forced to 78 F; then
the multizone damper would move
from the midpoint at the deadband
temperatures to eventual full cold
deck as the space temperature
moves above 78 F. Some ineffi-
ciencies would result if the econo-
rizer cold deck temperature was
then activated
‘The “forcing” problem can be
solved by the incorporation of two
additional temperature control fea-
tures. First, the multizone damper
‘operator springs should be selected
so that the zone dampers are open
to full heating at 5 psi and open to
full cooling at 10 psi. Therefore,
when the space temperature now
enters the deadband zone (9¥: to 10
pai), the zone damper will be open
to full bypass, which is normally
return ait, instead of at. the zone
damper’s midpoint (see Table 4).
fone of the zones requires heat~
ing, the deadband thermostat will
send a zero to 9¥% psi signal to the
high-low pressure selector. For
‘moming warmup, a zer0 psi signal
willset the hot deck temperature to
maximum. If the various zones be-
come heated to the deadband limit,
all of the zone deadband tempera:
signals
proach 9% psi, and the high-low
pressure selector will gradually re-
set the hot deck to cold deck tem-
perature so that no heating is ener-
gized. When all ofthe temperatures
enter the deadband range, neither
heating nor cooling is required.
During the economizer operation
(below 75 F outside air temper
ture), a return air thermostat oper-
ates to modulate the mixed air
dampers to produce a mixed air
temperature between 58 and 74 F
to maintain a return air tempera:
ture between 72 and 74 F. The re-
turn air temperature should, of
course, be adjusted to represent an
average space temperature of 72 to
4,
AAs the outdoor air temperature
increases beyond 65 F, outdoor air
ray not be able to cool the space
temperatures. At a predetermined
outdoor air temperature, such as 65
F, the chiller system will be ener-
sized and the heating system will
be de-energized. Furthermore, to
provide full zone damper control
during mechanical cooling, «three
Way air solenoid valve will switeh
the multizone’s damper operator
air pressure through a sequencing
cumulator, which will reduce the
zone damper's input air signal by
44% psiso that the zone damper will,
be at 5 psi and calling for full by-
pass around the cooling coil. As fur-
ther zone cooling is required, each
deadband thermostat will increase
its signal from 9¥% psi to 20 psi, and
the zone dampers will increase
from 5 to 10 psi and call for full
cooling. This will modulate the
‘multizone dampers to provide the
proper cool air temperature.
A three-way chilled water valve
shail modulate to maintain a con-
stant 60 F cold deck temperature
which will always ensure debu-
fication. A schematic showing
the complete advanced multizone
control concepts shown in Fig. 7.
‘A deadband thermostat was
chosen in lieu of a two-temperature
thermostat because a two-
temperature thermostat cannot
provide the same economies as a
deadband thermostat. A two-
temperature unit has changeover
accomplished by a change in the
supply pressure. The difficulty of
changing individual zone thermo-
stats based upon varying solar and
internal loads is virtually impos-
sible. For example, if an internal
zone was set at 78 F and the lights
were switched off, then the two-
temperature thermostat would re-
quire additional heating to mai
tain 78 F as opposed to the dead-
band unit allowing the temperature
tofloat between 70 and 78 F
Essentially, this deadband/mul-
tizone system will require no waste-
ful mixing of hot and cold air
streams. ‘The resulting energy sav-
ings offer excellent benefits for the
Hosting/Piping/Ale Conditioning « November 1981,
"Table 4 Position ot mulizone min