100 Percent Stator Earth Fault Protection
100 Percent Stator Earth Fault Protection
Content Basics of stator earth fault protection Fault locations Disturbances from the high voltage side 100%-stator-earth-fault protection with 20-Hz-injection method Basic idea Practical design Numerical measuring technique Frequency operating range Design of the protection schemes Examples of real practical failures
Copyright Siemens
Basics of Stator Earth Fault Protection Fault Location Region of earth faults Earth fault locations in the stator
U0
Low displacement voltage at earth faults close to the star point
Copyright Siemens
Basics of Stator Earth Fault Protection Disturbances from the High Voltage Side
An additional load resistor limits the disturbance influence The design of the load resistor determines the protective range (80% or 90 % or 95%)
Copyright Siemens
100%-Stator-Earth-Fault Protection with 20-HzInjection Method Goal and Basic Idea Goal Basic idea
max. 200 V
20 Hz RE I
Protection principle should cover 100 % protection range Different measuring principles
Copyright Siemens
With injection of a 20-Hzvoltage into the star point a e.m.f. is available in case of an earth fault
Siemens. Innovation for generations.
Copyright Siemens
RB
Fourierfilter
(20Hz)
I 20 Re = V 20
Vr . Ir + Vi . Ii V2r + V2i
Yers
CE
RE
Yers =
1 + j CE RE
RE =
V2r + V2i Vr . Ir + Vi . Ii
Copyright Siemens
0Hz
10Hz
40Hz
50Hz
70Hz
Copyright Siemens
Design of the Protection Schemes Redundancy of 100%-Stator Earth Fault Protection Group1
90% U0 calculated
UL
Group2
90% U0 calculated
UL
7UM62 UE
7UM62
100% SEF-1
IEE1 UE IEE1
Neutral transformer
100% SEF-2
Copyright Siemens
Displacement voltage
Ground current
Copyright Siemens
Copyright Siemens
150
REm R in Ohm
k k 100 86
SES100Aus GAnr k
60 50
0 100 100
200
300
400 k .ta t in ms
500
600
700 687.5
Copyright Siemens
Real Practical Failures Earth Fault in the Cable of Static Frequency Converter
SFC
G
Permanently pickup by 100%-stator earth fault protection
Copyright Siemens
Real Practical Failures Earth Fault in the Cable of Static Frequency Converter Fault Record
frequency appr. 1,7 Hz
Copyright Siemens
Real Practical Failures Earth Fault in the Cable of Static Frequency Converter Calculated Secondary Fault Resistance
100 100
80
R in Ohm
60
57
Drop off
48
Pickup
40
20
0 99.92
100
200
300 k ta t in ms
400
500
600
700 686.95
Copyright Siemens