Flag Relay RXSF1 Testing and Commissioning Site Report Site Test Report Customer : ROYAL COMMISSION Consultant Substation : MARAFIQ : 380 kV S/S 10J Contract No Bay/Feeder Date : PIC B-1191A : Mechanical Protection Panel : 23/7/2011

1. GENERAL DATA AND INFORMATION: Bay No. Bay Name : : ABB-SWEDEN Hand Reset Aux. Voltage : 110 125V DC Device Ref Order No. : : 271 018-AN : 3 N/O Per Coil

Manufacturer : Type of Flag :

No. of contacts

2. MECHANICAL CHECKS AND VISUAL INSPECTION :


ITEM 1 2 3 4 5 DESCRIPTION Inspect for physical damage / defects. Verify connections as per approved drawings. Check tightness of all connections. Check Ferrules. Check apparatus lists. CHECKED OK OK OK OK OK

3. ELECTRICAL TESTS : a) FUNCTION TEST :


ITEM 1 2 3 4 5 6 7 DESCRIPTION Test switch / plug checked for correct function. Indications checked. Alarm contacts checked. Trip contacts checked. Self test checked. All output contacts resistance measured. Flag operation checked. CHECKED

SIEMENS
Name: Date: Signature:

Client: RC
Name: Date: Signature:

Consultant:
Name: Date: Signature:

SIEMENS
Flag Relay RXSF1 Testing and Commissioning Site Report Site Test Report Customer : ROYAL COMMISSION Consultant Substation : MARAFIQ : 380 kV S/S 10J Contract No Bay/Feeder Date : PIC B-1191A : Mechanical Protection Panel : 23/7/2011

b) PICK-UP AND DROP OFF TEST : Coil No. 11-12 21-22 Limits: Pick-up voltage : < 0.8 Ur Drop-off voltage: > 0.05 Ur c) OPERATING AND RESET TIME TEST (at rated voltage) : Coil No. 11-12 21-22 Pickup (ms) Contact No. 13-14 23-24 Drop Off (ms) Contact No. 13-14 23-24 Pick up Value Volts (V) Current (mA) Drop off Value Volts (V) Current (mA)

Limits: Pick-up Time: 30/20 ms d) RELAY BURDEN TEST : Coil No. 11-12 21-22 Voltage (V) 125 125 Current(mA) Power (watt.) Drop-off Time: 5/10 ms

Limits: VA: 1.1 1.3 W

SIEMENS
Name: Date: Signature:

Client: RC
Name: Date: Signature:

Consultant:
Name: Date: Signature: