PFEER Standard Tones NORSOK Standard Tones IMO Standard Tones DNV Standard Tones

The mandatory tones that make up these alarm sets are as follows: 1) PFEER PAPA (Prepare to Abandon Platform Alarm) Alarm Tone Warble tone; frequency 1200Hz ramping down to 500Hz within 1 second.

GA (General Alarm) Alarm Tone Intermittent tone 1 second on, 1 second off at 1 KHz.

Toxic Gas Alarm Tone

2) NORSOK Muster/Prepare to Abandon Platform Alarm Tone Warble tone: frequency 1200Hz ramping down to 500Hz within 1 second.

GA (General Alarm) Alarm Tone Intermittent tone 1 second on, 1 second off at 1 kHz.

Toxic Gas Alarm Tone Intermittent tone 1kHz, 0.1 second on, 0.1 second off, in bursts of duration 1 second alternating with 1 second silence.

3) IMO Muster Alarm Tone

Fire Alarm Tone 7x short blasts of 1kHz followed by 1 x continuous 1kHz for 7 seconds then the cycle repeats.

Toxic Gas Alarm Tone Interrupted 1KHZ tone

4) DNV GA (General Alarm) Alarm Tone 7x short blasts of 1kHz followed by 1 x continuous 1kHz for 7 seconds then the cycle repeats.

Muster and Toxic gas alarm tones are equipped as above Muster Alarm Tone

Toxic Gas Alarm Tone Interrupted 1KHZ tone