PFEER Standard Tones NORSOK Standard Tones IMO Standard Tones DNV Standard Tones
The mandatory tones that make up these alarm sets are as follows: 1) PFEER PAPA (Prepare to Abandon Platform Alarm) Alarm Tone Warble tone; frequency 1200Hz ramping down to 500Hz within 1 second.
GA (General Alarm) Alarm Tone Intermittent tone 1 second on, 1 second off at 1 KHz.
2) NORSOK Muster/Prepare to Abandon Platform Alarm Tone Warble tone: frequency 1200Hz ramping down to 500Hz within 1 second.
GA (General Alarm) Alarm Tone Intermittent tone 1 second on, 1 second off at 1 kHz.
Toxic Gas Alarm Tone Intermittent tone 1kHz, 0.1 second on, 0.1 second off, in bursts of duration 1 second alternating with 1 second silence.
Fire Alarm Tone 7x short blasts of 1kHz followed by 1 x continuous 1kHz for 7 seconds then the cycle repeats.
4) DNV GA (General Alarm) Alarm Tone 7x short blasts of 1kHz followed by 1 x continuous 1kHz for 7 seconds then the cycle repeats.
Muster and Toxic gas alarm tones are equipped as above Muster Alarm Tone