Code No.

LIT-1922410 Issued February 1, 2009

S351

Humidity Stage Module


Description
The S351 Stage Module is used in conjunction with the W351 Humidity Control to add multiple staging capability. Using a Y350R, up to five S351s can be added to the W351 via the 5-pin, plug-together connector. Using a 24 VAC or greater external transformer, up to nine S351s can be added. The S351 has an SPDT output relay and three adjustments including offset (de-energize stage action from setpoint), humidification or dehumidification mode, and differential. .
Offset Potentiometer Module Connector Relay Energized LED Indicator Differential Potentiometer Module Connector
Jumper Block Position Humidification Relay Dehumidification

Features
humidification or dehumidification mode, field selectable adjustable differential and offset 5-pin connectors eliminate wiring between modules

Applications
Use for multiple staging for humidification/ dehumidification of clean rooms, computer rooms, or space humidity control.

S351

Selection Chart
Code Number
S351AA-1C

Output
SPDT Relay

Differential
2 to 10% RH

Offset
2 to 30% RH

N.C. Relay

COM N.O. Output Terminals

s3511.eps

Interior of S351

0.145 Mounting Slot 3.68 For #6 Screws 0 .5 13 2.94 75

Technical Specifications
S351 Humidity Stage Module with Percent RH Scale
Case and Cover Material Supply Voltage Power Consumption Ambient Temperature Ambient Humidity Relay Mounting Operating Shipping Operating Shipping NEMA 1, high-impact thermoplastic 24 volt power supply provided by Y350R or external 24 VAC transformer 1 VA max. -30 to 150F (-34 to 66C) -40 to 185F (-40 to 85C) 10 to 90% RH non-condensing 0 to 95% RH non-condensing SPDT enclosed relays, contacts rated at 10 amp non-inductive, 1/2 hp, 120/240 VAC Surface or DIN rail

DIN Rail

5.00 127

S351
ON

1.56 40

0.42 11

2.40 61 1.20 31

Relay Contact Ratings Voltage, AC


Full Load Amp Locked Rotor Amp Pilot Duty 125 VA at 24/240 VAC

2.40 61

120
9.8 58.8

208/240
4.9 29.4

Non-Inductive Amp 10 at 24/240 VAC

0 .8 7 5 Conduit 22 Hole

S351 Dimensions, in. (mm)

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. www.johnsoncontrols.com Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. 2009 Johnson Controls, Inc.

1 of 1

s3512.eps