WORKS TEST REPORT

Sr.No. Date :
Customer Name :

Customer P.O. No. : Date :
Sr.
No.
Cat. Ref Description Batch
Qty.
Test
Qty.
Short
Circ.
Current Wattage Power
fact.
Start Run
(BaIIast)
Line TotaI B.Ioss
These reading are from one of the representing sample tested. The sample tested were found to comply generally with the I.S.
specifications.
No. TEST PARAMETERS OBSERVATIONS
I. Visual/Dimension Examinations a) Wiring and Assembly b) Construction and
Workmanship
SATISFACTORY
II. Protection against mechanical and
Electrical Failure
a) Cables and Conductors
b) Terminals and Connections
c)Creepage Distance
SATISFACTORY
III. Protection against Electrical Shock
(CI. 21 of 10322 (Part 2) -1982)
a) Guarding Live Parts
b) Separation of live parts from non_current carrying
conductive parts
SATISFACTORY
IV. Method of making earth continuity
connections.
(CI 20 of 10322 (Part 2) -1982)
a) Earthing
b) Design, Construction of earthing terminal
SATISFACTORY
V. Electrical Test : a) Insulation resistance test (Dry) as per
cl. 3.2 of IS 10322 (Part 4) 1984
b) High voltage test as per CI. 3.3 of 10322 (Part 4)
1984
Above 5 Mega Ohms
SATISFACTORY
SATISFACTORY
The sample drawn were subjected to the tests/examination as per the following I.S. Specifications and the result are noted as above.
I.S. Specifications. IS 10322 - (Part 5) - 1987.

For Crompton Greaves Ltd.
Manager (Q. A.)
CGL/L1/QA/LUM-10117 10/17/2011
SHALIMAR ENGINEERING PVT.LTD
FOR GRID STATION,PISHNAH --
1 FHD1524 FLOODLIGHT LUM. 24 8 0 0 0 0 0 0 0
2 CG1340S C.G. BOXE 48 8 7 2.57 4.4 2.15 440 40 0.8527