Operating Environment - p570 p6

O Temperature:
4 5 to 45 degrees C (41 to 113 F) nonoperating
4 5 to 35 degrees C (41 to 95 F) operating
O Relative humidity: (noncondensing)
4 8% to 80% operating
4 5% to 100% nonoperating
O Maximum wet bulb:
4 27 degrees C (80 F) nonoperating
4 23 degrees C (73 F) operating
O Operating voltage:
4 200 to 240 V ac
O Operating frequency:
4 50/60 Hz
O Power consumption:
4 1400 watts maximum (per enclosure with all (four or eight) cores active)
O Power source loading:
4 1.428 kVA maximum (per enclosure with all (four or eight) cores active)
O Thermal output:
4 4778 BTU/hr maximum (per enclosure with all (four or eight) cores active)
O Noise level: (one CEC enclosure with two processor features and all cores active,
operating and idle)

Operating Environment - 7042-CR5 HMC
O Temperature:
4 System on: 10 to 35 degrees C (50 to 95 degrees F)
4 System off: 0 to 50 degrees C (32 to 140 degrees F)
O Relative humidity: 8% to 80%
O Acoustical noise emissions:
4 Sound power, idling: 6.1 bels
4 Sound power, operating: 6.1 bels (maximum)
O Maximum altitude: 2,133 m (7,000 ft)

Power requirements
O Operating voltage: Sine-wave input (50 or 60 Hz) required; input voltage and frequency
ranges automatically selected
4 Low range: 100 to 127 V ac
4 High range: 200 to 240 V ac
O Power source loading: 0.49 kVA (maximum)
Thermal output: 307 Btu/hr (90 watts) (minimum)
1620 Btu/hr (475 watts) (maximum)