TOTAL 3 PHASE POWER


S =3 V X I

(PHASE PARAMETERS)

FOR STAR: LINE CURRENT = 1.732 XPHASE CURRENT


LINE VOLTAGE = PHASE VOLTAGE
FOR DELTA : LINE VOLTAGE

= 1.732 XPHASSE VOLTAGE

LINE CURRENT =

PHASE CURRENT

POWER PER PHASE(FOR STAR ,DELTA BOTH)


S= 1.732 X V X I

(LINE PARAMETERS)

P= 1.732 X V X I COS(0)

(LINE PARAMETERS)

Q= 1.732 X V X I SIN(0)

(LINE PARAMETERS)

--------------------HORSE POWER KW RELATION------------------------1 hp = 0.746 kw


>>
1 kw = 1.34 hp
---------------------------------------------------------------------------------------------GIVEN
I=

P = 100 KW
100 X 1000
----------------1.732 X 400 X 0.8

(1.80)

180.4 A

---------------------------------------------------------------------------------------------GIVEN

s = 100 KVA

(1.44)

I=

100 X 1000
----------------=
144 A
1.732 X 400
------------------------------ Capacitor bank current finding -----------------------------------GIVEN

Q = 100 KVAR
( 1.44 at

400v )

kvar X 1000
I = --------------------

[COS()=0.8 -----> SIN()=0

.6]
1.732 X 400 x sin(90)
sin(90)=1
since angle between voltage and current inside pure capacitor bank is 90 so
100 X 1000
--------------------

I=

= 144 A

[COS()=0.8 -----> SIN()=0.

6]
1.732 X 400 X 1
----------------------------------------------------------------------------------------------POWER FACTOR = 0.8
1-

KVA X 0.8 = KW

2-

KW
----- =
0.8

3N()=0.6]

KVA

KVA X 0.6 = KVAR

[COS()=0.8 -----> SI

----------------------------------------------------------------------------------------------INDUCTION MOTORS

POWER FACTOR GIVEN

= 0.8
1-

KVA = 1.732 X V X I x

2-

KW

3SIN()=0.6]

EFFICIENCY

= 1.732 X V X I x 0.8 x EFFICIENCY

KVAR = 1.732 X V X I x 0.6 x EFFICIENCY

[COS()=0.8 ----->

YOU CAN FIND ACTUAL LOAD CURRENT FROM ABOVE FORMULAE


--------------------------------------------------------------------------------------------------