Professional Documents
Culture Documents
Gruner D 231 EN
Gruner D 231 EN
Ty p e 2 3 1
Actuator with rotation drive 20 Nm 30 Nm
Page:
2 3 4 16 17 18 - 19 20 9 10 - 15
Content:
General overview Summary 231, 20 Nm + 30 Nm Technical characteristics, Type 231, 20 Nm Technical characteristics, Type 231, 30 Nm Mounting examples Specific characteristics of continuous control Notes Your way to Gruner
GR
UNER he frie t
alte dly n
rnative
Type
Torque
227
2
232
2
231
2
228
2
238
5 Nm (appr.1 m ) 15 Nm (appr.3 m ) 20 Nm (appr.4 m ) 5 Nm (appr.1 m ) 15 Nm (appr.3 m2) 8 Nm (appr.1.6 m2) 30 Nm (appr.6 m2)
Control
Tri-state On / Off Continuous (0) 2...10 VDC or (0) 4...20 mA with 500
Power supply
24 VAC/DC 230 VAC
Options
Potentiometer Auxiliary switch(es) LON Interface VAV Interface Universal locking clamp Form locking
Applications
Motorised control of dampers, ball and butterfly valves. Application in mixed air and shut-offer damper control. For primary HVAC air-handling and zone units. Smoke and air isolation shut-off damper control for ventilation systems Ball valve control for domestic and drinking water, condensation water, air (i.e. zone units). The actuator 231L has digital communication capabilities and can be networked with a LON-Bus system. All actuators correspond to the UL, CSA & DIN-VDE standards, CE guidelines.
= Optional
Type
Torque Control Tri-state On / Off Continuous control (0) 2...10 VDC or (0) 4...20 mA
20 Nm 20 Nm 20 Nm 20 Nm 20 Nm 20 Nm 20 Nm
Power supply
24 VAC/DC 230 VAC 4 4 4 6 6 6 8
Options
Potentiometer Feedback signal Auxiliary switch(es) Page
All actuators dispose of manual override button, a mechanical limitation of the angle of rotation and setting button for the rotation direction (cw/ccw). Actuators according to US-standards available upon demand.
= Optional
Type
Torque Control Tri-state On / Off Continuous control (0) 2...10 VDC or (0) 4...20 mA
30 Nm 30 Nm 30 Nm 30 Nm 30 Nm 30 Nm 30 Nm
Power supply
24 VAC/DC 230 VAC 10 10 10 12 12 12 14
Options
Potentiometer Feedback signal Auxiliary switch(es) Page
All actuators dispose of manual override button, a mechanical limitation of the angle of rotation and setting button for the rotation direction (cw/ccw). Actuators according to US-standards available upon demand.
= Standard
02 430
= Standard
02 420
Technical characteristics
Control Connecting voltage Power consumption Angle of rotation Direction of rotation Running time Torque Auxiliary switches Switching power auxiliary switch Potentiometer Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight On / Off + Tri-state 24 VAC (50/60 Hz) / DC 20% 3.0 W / 5.5 VA 91 changeable from outside 60...80 s @ 90 20 Nm 2, adjustable from inside (0...10/80...90) 24 VAC / 5 (2.5) A, change-over switch 5 k cable 900 mm / 0.75 mm2 III IP54 (cable downwards) 178 x 92.7 x 75 mm -20...+50 C maintenance-free 73/23/EWG, 89/336/EWG 1,500 g
231-024-20
Connection scheme
231-024-20-P5
Connection scheme
231-024-20-S2
Connection scheme
BU BNBK
On / Off
BU BNBK
BU BNBK
BU BNBK
2 1 3 BU BNBK
Tri-state
BU BNBK
Potentiometer
S1
S2
1 2 3 4 5 6
Auxiliary switches
15 0 75 60 45 3 0...90
90
75
3
L R
S1 BU BN BK
S2
1 2 3 4 5 6 24 VAC 5 (2,5) A
Technical drawing
231-024-20
Technical characteristics
Control Connecting voltage Power consumption Angle of rotation Direction of rotation Running time Torque Auxiliary switches Switching power auxiliary switch Potentiometer Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight Tri-state 230 VAC (50/60 Hz) 15% 3.5 W / 3.5 VA 91 can be chosen by connection 150 s @ 90 20 Nm 2, adjustable from inside (0...10/80...90) 250 VAC / 5 (2.5) A, change-over switch 5 k cable 900 mm / 0.75 mm2 I IP54 (cable downwards) 178 x 92.7 x 75 mm -20...+50 C maintenance-free 73/23/EWG, 89/336/EWG 1,500 g
231E3-230-20
Connection scheme (Tri-state)
231E3-230-20-P5
Connection scheme (Tri-state)
231E3-230-20-S2
Connection scheme (Tri-state)
S1
S2
Auxiliary switches
1 2 3 4 5 6 BU BNBK BU BNBK 2 1 3
Potentiometer
BU BNBK
N L
N L
N L
15 0 75 60 45 3 0...90
90
75
Technical drawing
231E3-230-20
231C-024-20
Applications
To regulate dampers, valves or other regulatory functions: sturdy drive blocking resistant maintenance-free torque 20 Nm position indication Adjustment of the regulation range for continuous control from insde electromagnetic compatibility controlled manual operation
Technical characteristics
Control Control signal Y Continuous control 0...10 VDC or 2...10 VDC (Standard) or 0...20 mA or 4...20 mA Feedback signal U 0...10 VDC or 2...10 VDC (Standard) or 10 VDC or 15 VDC Connecting voltage Power consumption Angle of rotation Direction of rotation Running time Torque Connection Safety class Protection Dimensions Ambient temperature 24 VAC (50/60 Hz) / DC 20% 4.0 W / 5.5 VA 91 changeable from outside 60...80 s @ 90 20 Nm cable 900 mm / 0.75 mm2 III IP54 (cable downwards) 178 x 92.7 x 75 mm -20...+50 C maintenance-free 73/23/EWG, 89/336/EWG 1,500 g
231C-024-20
Connection scheme (Continuous control)
Maintenance CE Weight
BUBN BK GY Y U
231C-024-20
1 Indication of the angle of rotation (fig. 1)
The damper position is indicated on the scale 0...90.
60 45 30 15 0...90 90 0
15 0 75 60 45 3 0...90
90
75
ON 1 2 1, 2
1, 2 2 1 -
4, (1) 4 3, 5 3
3 3, (1) 4 4, 5
0...10 VDC 15 VDC / 5 mA 10 VDC / 5 mA Switches actually unused must be at position OFF.
The constant voltage 15 VDC can be used i.e. for the power supply of the positioner FGEB.
Technical drawing
231C-024-20
10
Technical characteristics
Control Connecting voltage Power consumption Angle of rotation Direction of rotation Running time Torque Auxiliary switches Switching power auxiliary switch Potentiometer Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight On / Off + Tri-state 24 VAC (50/60 Hz) / DC 20% 4.5 W / 8.0 VA 91 changeable from outside 60...100 s @ 90 30 Nm 2, adjustable from inside (0...10/80...90) 24 VAC / 5 (2.5) A, change-over switch 5 k cable 900 mm / 0.75 mm2 III IP54 (cable downwards) 178 x 92.7 x 75 mm -20...+50 C maintenance-free 73/23/EWG, 89/336/EWG 1,500 g
231-024-30
Connection scheme
231-024-30-P5
Connection scheme
231-024-30-S2
Connection scheme
BU BNBK
On / Off
BU BNBK
BU BNBK
BU BNBK
2 1 3 BU BNBK
Tri-state
BU BNBK
Potentiometer
S1
S2
1 2 3 4 5 6
Auxiliary switches
11
15 0 75 60 45 3 0...90
90
75
3
L R
S1 BU BN BK
S2
1 2 3 4 5 6 24 VAC 5 (2,5) A
Technische Zeichnung
231-024-30
12
Technical characteristics
Control Connecting voltage Power consumption Angle of rotation Direction of rotation Running time Torque Auxiliary switches Switching power auxiliary switch Potentiometer Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight Tri-state 230 VAC (50/60 Hz) 10% 3.5 W / 3.5 VA 91 can be chosen by connection 230 s @ 90 30 Nm 2, adjustable from inside (0...10/80...90) 250 VAC / 5 (2.5) A, change-over switch 5 k cable 900 mm / 0.75 mm2 I IP54 (cable downwards) 178 x 92.7 x 75 mm -20...+50 C maintenance-free 73/23/EWG, 89/336/EWG 1,500 g
231E3-230-30
Connection scheme (Tri-state)
231E3-230-30-P5
Connection scheme (Tri-state)
231E3-230-30-S2
Connection scheme (Tri-state)
S1
S2
Auxiliary switches
1 2 3 4 5 6 BU BNBK BU BNBK
Potentiometer
2 1 3 BU BNBK
N L
N L N L
13
15 0 75 60 45 3 0...90
90
75
Technical drawing
231E3-230-30
14
231C-024-30
Applications
To regulate dampers, valves or other regulatory functions: sturdy drive blocking resistant maintenance-free torque 30 Nm position indication Adjustment of the regulation range for continuous control from insde electromagnetic compatibility controlled manual operation
Technical characteristics
Control Control signal Y Continuous control 0...10 VDC or 2...10 VDC (Standard) or 0...20 mA or 4...20 mA Feedback signal U 0...10 VDC or 2...10 VDC (Standard) or 10 VDC or 15 VDC Connecting voltage Power consumption Angle of rotation Direction of rotation Running time Torque Connection Safety class Protection Dimensions Ambient temperature 24 VAC (50/60 Hz) / DC 20% 5.0 W / 8.0 VA 91 changeable from outside 60...100 s @ 90 30 Nm cable 900 mm / 0.75 mm2 III IP54 (cable downwards) 178 x 92.7 x 75 mm -20...+50 C maintenance-free 73/23/EWG, 89/336/EWG 1,500 g
231C-024-30
Connection scheme (Continuous control)
Maintenance CE Weight
BUBN BK GY Y U
231C-024-30
1 Indication of the angle of rotation (fig. 1)
The damper position is indicated on the scale 0...90.
60 45 30 15 0...90 90 0
15
15 0 75 60 45 3 0...90
90
75
ON 1 2 1, 2
1, 2 2 1 -
4, (1) 4 3, 5 3
3 3, (1) 4 4, 5
0...10 VDC 15 VDC / 5 mA 10 VDC / 5 mA Switches actually unused must be at position OFF.
The constant voltages 10 VDC and 15 VDC can be used i.e. for the power supply of the positioner FGEB.
Technical drawing
231C-024-30
16
MOUNTING EXAMPLES
Figure 1
Direct mounting to the damper shaft by locking clamp to the damper shaft... ...and fixing by the enclosed anti-torsion bow.
Figure 2
Direct mounting by two hexagon screws M4 x 30, SW 7, if the actuator is not mounted directly on the damper.
Figure 3
Mounting if the damper is too short.
- +
231C
- +
231C
BU BN BK GY
L2 L1 max. cable length
24VAC
BU BN BK GY
(I +I ) R >
A G L max. cable length L2 L1
24VAC
transformer
R < L
transformer
DC 0(2)...10V
DC 0(2)...10V
by the actuator
by the controller
current of set valve selector actuator current cable cross section cable resistance 0,75 mm2 1 cable length cable cross section mm2 1,5 mm2 2,5 mm2 23 m 31 m 46 m 76 m max. cable length
For several actuators switched in parallel the max. cable length must be divided by the number of actuators.
BUBN BK GY
15 VDC
18
NOTES
NOTES
19
Stuttgart
A8
Mnchen
Balingen Karlsruhe
Schmberg
Freudenstadt
A81
Wehingen
B27
Gosheim Frittlingen Denkingen
Tuttlingen
Strasbourg
Rottweil B14
Schramberg Aldingen
Spaichingen
34
B27
Donaueschingen
Singen Zrich
Basel N1 N3