Professional Documents
Culture Documents
Reliability Based Design of Transmission Line
Reliability Based Design of Transmission Line
Design philosophy
Types of towers
Suspension towers Tangent towers (0o) with suspension string for straight runs only. Intermediate towers ( 0o to 2o) with suspension string for straight runs and upto 2o line deviation. Light angle towers (0o to 5o) with suspension string on straight runs and upto 5o line deviation
Tension towers 1. Small angle towers (0o to 15o ) with tension string for line deviation from 0o to 15o. 2. Medium angle towers (0o to 30o) for line deviation 0o to 30o. 3. Large angle towers (30o to 60o) for line deviation from 30o to 60o.
4. Dead end towers with tension string for use as dead end ( terminal) tower or anchor tower. 5. Large angle and dead end towers with tension string for line deviation from 30o to 60o or for dead ends.
Reliability levels
Reliability
1 2 3
Reliability level 1 - for EHV lines upto 400kV class Reliability level 2 for EHV lines above 400kV class and for triple and quadruple circuit towers upto 400kV lines Reliability level 3 for tall river crossing towers and special towers.
Wind effects
Basic Wind Speed Meteorological Reference Wind Speed Design Wind Speed Risk Coefficient K1 Terrain Roughness coefficient K2
Terrain categories
1. Exposed open terrain seacoasts, open stretch of water, deserts and flat treeless plains 2. Open terrain - normal country lines with very few obstacles. 3. Terrain with numerous obstructions built up areas and forest areas
Wind loads
Wind load on tower Wind load on conductor and ground wire Wind load on insulator strings
Temperature variations
Maximum and minimum temperatures as per isopleths Average everyday temperature shall be 32o C Maximum conductor temperature for design 75o for ACSR 85o for AAAC
As per IS 5613( Part 2 / Sec 1) : 1985 100% Design Wind Pressure at Everyday Temperature 36% Design Wind Pressure at minimum temperature
Loads on tower
Computation of loads
Loading combinations
Loading combinations
Loading combinations
All angle towers shall be checked for the following anti cascading conditions with all conductors and ground wire intact only on one side of the tower Transverse loads Vertical loads Longitudinal loads
Tension limits
Conductor / Ground wire tension at everyday temperature and without external load should not exceed the following percentages of Ultimate Tensile Strength Initial unloaded tension Final unloaded tension 35% 25%
The ultimate tension under everyday temperature and 100% design wind pressure Or Minimum temperature and 36% design wind pressure Shall not exceed 70% of Ultimate Tensile Strength of the Conductor / Ground wire
Single circuit towers Any one phase or ground wire broken whichever is more stringent for a particular member
Suspension towers Any one phase or ground wire broken whichever is more stringent for a particular member
Small and medium angle towers Any two phases broken on the same side and same span or any one phase and one ground wire broken on the same side and same span whichever is more stringent for a particular member
Large angle tension towers / Dead end towers Any three phases broken on the same side and same span or any two of the phases and one ground wire broken on the same side and same span, whichever is more stringent for a particular member