Professional Documents
Culture Documents
ASHARAE62
ASHARAE62
An Outline
General comments General requirements Ventilation requirements Construction and O/M requirements Questions
ASHRAE Standard 62
1970
1980
1990
2000
2010
62.1-2004 Commercial and High Rise Res. Enforceable code language ETS vent. rates not covered Vent. Rate. Proc. Modified Occupant and area vent. rates
Std 62.1-2007 is the most current version IMC adopted methodology and rates in 2007 Supplement Several educational courses are available from ASHRAE
62.1-2007 Purpose
1.1 Specify minimum ventilation rates and other measures intended to provide IAQ that is acceptable to human occupants and that minimizes adverse health effects. 1.2 Intended for regulatory application to new buildings, and additions 1.3 Guide the improvement of IAQ in existing buildings.
62.1-2007 Scope
2.1 All spaces intended for human occupancy. 2.2 Defines requirements for ventilation, aircleaning design, commissioning, installation and O&M 2.3 Additional requirements and other standards may apply (labs, healthcare, industrial, etc.) 2.4 May be applied to both new and existing buildings, not intended to be used retroactively 2.5 Does not prescribe specific ventilation rates for smoking spaces
2.6 Ventilation requirements based on chemical, physical, & biological contaminants 2.7 Consideration or control of thermal comfort is not included 2.8 Contains requirements, in addition to ventilation related to certain sources
2.9 Acceptable IAQ may not be reached in all buildings meeting these requirements because of special conditions noted Definition Acceptable Indoor Air Quality: air in which there are no known contaminants at harmful concentrations as determined by cognizant authorities and with which a substantial majority (80% or more) of the people exposed do not express dissatisfaction
Must determine NAAQS attainment status www.EPA.gov If nonattainment, air cleaning is required in some cases Conduct observational site survey to identify local sources of air contaminants
4.3 Documentation
Regional air quality compliance status Local survey information Conclusions regarding acceptability of outdoor air quality
5.1 Natural Ventilation. Must meet minimum requirements for location and size of openings 5.2 Ventilation Air Distribution.
Must provide means to adjust (balance) Must be sure that mixing occurs in RA/OA mixing plenums
5.3 Exhaust Duct Location. Operate exhaust ducts (with harmful contaminants) at negative pressure 5.4 Ventilation System Controls. Control to assure proper ventilation under any operating condition 5.5 Airstream Surfaces. Use materials that have documented resistance to microbial growth and erosion
5.6 Outdoor Air Intakes. Separate OA intake from outdoor contaminant sources
Must comply with default minimum separation distances in Table 5-1. Examples:
25 ft 15 ft 1 ft 25 ft
Must limit rain water penetration (using hood, proper velocity, etc.) or manage water that penetrates Must use bird screens and prevent bird nesting
Discharge air from non-combustion equipment with exhaust vents must be exhausted to outdoors
5.8 Combustion Air. Provide combustion air and exhaust air for indoor fuel-fired appliances
5.9 Particulate Matter Removal. Use a filter with a MERV 6 (or greater) upstream of dehumidifying coils and other wet-surface devices in supply stream
Intake airflow must be greater than relief/exhaust during cooling (to minimize moist air infiltration)
62F DP
Slope: 1/8 per foot toward outlet Drain: At lowest point, large enough to prevent overflow Drain seal: P-trap or other seal for negatively pressurized drain pans to prevent ingestion of air while allowing complete drainage (fan on or off) Pan size: length at least 1/2 coil height or as necessary to limit carryover
Use drain pan Select to limit coil pressure drop to 0.75 in.wc.@ 500 fpm face velocity If higher pressure drop, provide access on both sides for maintenance
Use potable water (or better) No downstream devices within absorption distance
Weather barrier to prevent water penetration into envelope Vapor retarder or other means to prevent condensation on cold surfaces within envelope Seal all seams, joints, penetrations to limit infiltration Insulate pipes, ducts expected to have surface temperature below surrounding dew point
5.16 Buildings with Attached Parking Garages. Limit infiltration of vehicular exhaust
Maintain garage pressure at or below adjacent occupied space Or, use a vestibule Or, otherwise design to minimize air migration from garage to occupied space
5.17 Air Classification and Recirculation. Limit recirculation or transfer of dirty air to cleaner spaces 5.17.1 Classification - Designate air leaving each space using Table 6.1
Class 1: Low contaminant concentration (office) Class 2: Moderate concentration (dining room) Class 3: Significant concentration (sick room) Class 4: Highly objectionable or potentially harmful concentration
Air Cleaning. May reclassify air cleaned by passing it through an appropriate aircleaning system Transfer. Mixed classes are re-designated. Energy Recovery. Energy recovery from class 2 (exhaust) airstreams must have no more than 10% leakage into a class 1 airstream.
5.18 Requirements when building has both ETS and ETS-Free areas. Does not purport to achieve acceptable IAQ in ETS areas. Spaces must be classified as ETS or ETS-Free Air must be kept separate by means of walls, automatic door closers and pressurization
5.18 (continued) Recirculation or transfer from ETS to ETS-Free is prohibited ETS areas must be exhausted to the outdoors
6.1 General. Ventilation Rate Procedure or IAQ Procedure for outdoor airflow values for mechanical ventilation systems 6.1.1 Ventilation Rate Procedure. Prescribes rates & procedures based on typical space contaminant sources & source strengths
6.1.2 IAQ Procedure. Requires calculation of rates based on analysis of contaminant sources, concentration targets and perceived air quality targets.
Don t operate air handlers without filters Protect building materials Protect occupied areas Limit migration of construction contamination into occupied space
7.1.5 Air Duct Construction shall be in accordance with the SMACNA duct construction standards and NFPA standards governing installation of HVAC systems 7.2 System Start-Up. Balance airflow values, test drain pans, clean up before starting, test damper controls
7.2.6 Documents including balance report, construction drawings and design criteria with assumptions shall be provided to Owner
Develop and maintain a building operations and maintenance manual which shall include a maintenance schedule with frequencies of tasks.
8.3 Ventilation System Operation. Operate in accordance with Building Operations Manual 8.4 Ventilation System Maintenance. Maintain in accordance with Building Operations Manual.
8.4.1.4 Coil drains. Drain pans shall be inspected at least once a year and cleaned if required 8.4.1.8 Outside Air Flow Verification. For units >2,000 cfm the outside air flow shall be tested a minimum of every 5 years and adjustments shall be made to have the design flow provided to system
ASHRAE 62.1
Standard is under continuous maintenance process You can propose a change to the standard Notice of proposed changes appears in ASHRAE Standards Action You can comment on proposed changes You can request an interpretation
ASHRAE 62.1
User s manual for 62.1-2007 IMC & UMC Code adoption ALI Short Course and Professional Development Course eLearning course IAQ Design Guideline is in the works Next publication of ASHRAE 62.1, 2010
Questions?
ASHRAE 62.1 update: Overview - Where are we now?