BTS Terminal Maintenance

You might also like

You are on page 1of 41

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 1 Introduction

Table of Contents
1 Introduction..................................................................................................................................................................1-1 1.1 BTS Terminal Maintenance .............................................................................................................................1-1 1.2 Operations of Site Maintenance Terminal System ..........................................................................................1-1 1.2.1 User Login...........................................................................................................................................1-1 1.2.2 Interface Operations ...........................................................................................................................1-2 2 Installation ...................................................................................................................................................................2-1 3 "SITE" Functions .........................................................................................................................................................3-1 3.1 Site Administrationship....................................................................................................................................3-1 3.2 Opstart Site .....................................................................................................................................................3-1 3.3 View Resource ................................................................................................................................................3-2 3.4 Force Load SW ...............................................................................................................................................3-3 3.5 SW Activation..................................................................................................................................................3-4 3.6 Reset Site Hierarchically.................................................................................................................................3-4 4 "Cell" Functions ...........................................................................................................................................................4-1 4.1 Cell Attributes Management............................................................................................................................4-1 4.2 Cell Extended Attributes Management............................................................................................................4-2 4.3 Opstart Cell .....................................................................................................................................................4-3 4.4 Change Administrative State...........................................................................................................................4-4 4.5 Cell Performance Test.....................................................................................................................................4-4 4.6 Cell Reinitialization..........................................................................................................................................4-5 5 "BT" Functions.............................................................................................................................................................5-1 5.1 Opstart BT.......................................................................................................................................................5-1 5.2 Change BT Administrative State .....................................................................................................................5-2 5.3 BT Reinitialization ...........................................................................................................................................5-3 6 "RC" Functions ............................................................................................................................................................6-1 6.1 RC Attributes Management.............................................................................................................................6-1 6.2 RC Extended Attributes Management.............................................................................................................6-2 6.3 Opstart RC ......................................................................................................................................................6-3 6.4 Change RC Administrative State.....................................................................................................................6-3 6.5 RC Reinitialization...........................................................................................................................................6-4 7 "Channel" Functions....................................................................................................................................................7-1 7.1 Channel Attributes Management.....................................................................................................................7-1 7.2 Opstart Channel..............................................................................................................................................7-2 7.3 Change Channel Administrative State ............................................................................................................7-2 8 "Board" Functions........................................................................................................................................................8-1 8.1 Rack Configuration and Board Configuration..................................................................................................8-1 8.2 Board Management.........................................................................................................................................8-2

Huawei Technologies Proprietary i

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 1 Introduction

Introduction

1.1 BTS Terminal Maintenance


In GSM system, BTS (Base Transceiver Station) is generally located far away from BSC (Base Station Controller), so it is usually unattended. Maintenance and supervision operations on BTS are carried out remotely at BSC side. But when field maintenance are necessary, local BTS terminal maintenance becomes indispensable. Usually, BTS terminal maintenance is carried out through installing BTS terminal maintenance software on a PC (either a desktop or laptop, the latter is usually preferred) and is connected to MMU board through serial communication cable (MMU board is equipped with a 9-pin serial communication cable socket). As in the case of BTS maintenance, BTS terminal maintenance operations are also carried out in terms of BTS logic objects. As for the logic objects and their various status, they have already been described in detail in BTS Maintenance Part One, it would be unnecessary to repeat it here.

1.2

Operations of Site Maintenance Terminal System


As the operations in site maintenance terminal system are performed locally over a single PC, they are somewhat different from those in BTS maintenance. Detailed description on these operations is to be given in this section.

1.2.1 User Login


I. Function
A user must first log in site maintenance terminal system before being authorized to perform any maintenance operations over the console.

II.

Login
Click on the fifth button on the toolbar, or choose [User Management/User Login] menu to pop up a "User Login" window. Enter user name and password, then click <OK> button. See Figure 1-1.

Huawei Technologies Proprietary 1

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 1 Introduction

Figure 1-1 User login After the user is successfully logged in, the above-mentioned window would be automatically closed and the user can proceed to perform desired operations. If the login fails, the reason would be displayed in the window.

1.2.2

Interface Operations
As shown in Figure 1-2, the interface of site maintenance terminal system is divided into the following parts: menu, toolbar, BTS logic object, object function, alarm window, status bar and etc. All the menu commands in the menu are easy to understand and the buttons on the toolbar are shortcuts for these commands. Move the cursor on a button to display its functions.

Huawei Technologies Proprietary 2

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 1 Introduction

Figure 1-2 Site maintenance terminal system BTS logic objects and their functions will be described later. This part focuses on alarm functions. As shown in Figure 1-3, the part in light blue on the interface of site maintenance terminal system is BTS alarm display part, that means, when an alarm occurs to BS, it would be displayed in this part of the interface. Double click any alarm message in, it would display an "Alarm Detailed Explanation" window for this alarm, as shown in Figure 1-5. Right click a certain alarm message would pop up a menu as shown in Figure 1-4. Choose commands on the menu, and the functions of message setting, saving, clearing and scrolling can be performed over the message in the alarm window.

Huawei Technologies Proprietary 3

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 1 Introduction

Figure 1-3 Alarm display in the site maintenance terminal system

Figure 1-4 Operations on an alarm message

Huawei Technologies Proprietary 4

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 1 Introduction

Figure 1-5 Detailed explanations on an alarm message

Huawei Technologies Proprietary 5

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS terminal Maintenance 2 Installation

2
I.

Installation

Connect the terminal O&M cable


Both ends of a BTS terminal operations & maintenance cable are DB9 connectors. One end is connected to the terminal O&M interface on the MOP board at the side of BS, and the other is connected to a serial port of an operation terminal (usually, a laptop computer). The pin-to-pin correspondence between the two DB9 connectors at the two ends of the cable is described in Table 2-1. Table 2-1 Pin-to-pin correspondence between the two DB9 connectors at the two ends of an O&M cable
BTS side connector Operation terminal side connector 2 3 3 2 5 5

II.

Start the terminal O&M system


On an operation terminal (usually, a laptop computer), run BTS terminal application program MMI. If MMI gets connected to BS, a main man-machine interface for BTS O&M system would be displayed as shown in Figure 2-1.

Figure 2-1 BTS O&M man-machine interface

Huawei Technologies Proprietary 1

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS terminal Maintenance 2 Installation

If MMI fails to connect to BS, a failure dialogue box would pop up. Click <OK> button in this box to open a dialogue box as shown in Figure 2-2 and set the communication port parameters in it. Select a communication port as COM1, COM2 or COM3 according to which port is actually connected to the cable, and select "38400" as the communication rate, then click <OK> button.

Figure 2-2 Set communication port parameters dialogue box If MMI still cannot get connected to BTS after all these settings, check whether the hardware connection of maintenance cables and the serial port hardware of the operation terminal is normal.

III. User login


After MMI gets connected to BS, choose [User Management/User Login] menu to open a dialogue box as shown in Figure 2-3. Enter "User Name" and "User Password", then click <OK> button. If the entered "User Name" and "User Password" are both correct, this dialogue box would disappear, which indicates that the user successfully logs in. Otherwise, a "Wrong Username or Password" prompt would be displayed.

Figure 2-3 User login dialogue box

Huawei Technologies Proprietary 2

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 3 SITE Functions

"SITE" Functions

As shown in Figure 2-1 BTS O&M Man-Machine Interface, left click [Site0] in the tree structure, and all the function commands corresponding to [Site0] would be displayed in the right part of this site window. Detailed description of the function commands under [Site0], including operation procedures as well as the explanation of function commands, is given in the following.

3.1 Site Administrationship


I. Operation procedure
Double click [Site0/Site administrationship] in the interface window as shown in Figure 2-1, and a dialogue box would pop up. In this dialogue box, click [Obtain] and a "Site Administrationship Successfully Obtained" prompt would be displayed under normal circumstances. Click [Release] button in the dialogue box mentioned above, a "Site Administrationship Successfully Released" prompt would be displayed under normal circumstances.

II.

Description
This function command is used for MMI to obtain or release site administrationship. Once MMI obtains site administrationship, it can take the place of BSC to perform such operation and maintenance functions over BTS as various configurations, attribute settings, operations on boards, and etc. In this sense, MMI plays the role of background maintenance. Normally, all O&M commands can be executed by this MMI. When MMI releases site administrationship, the O&M commands related to modification can no longer be executed, while the O&M commands related to reading can still be executed as usual.

3.2

Opstart Site
I. Operation procedure
Double click [Site0/Opstart Site] as shown in Figure 2-1. Then, click <OK> button in the popped-up dialogue box, and a "Site Successfully Opstart" prompt would be displayed normally.

II.

Description
This command is used for MMI to command "site0" into operation.

Huawei Technologies Proprietary 1

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 3 SITE Functions

3.3 View Resource


I. Operation procedure
Double click [Site0/View resource] as shown in Figure 2-1, and normally a "System Responds" prompt as well as the configured CPU occupation rate of MFU and MMU would be displayed as shown in Figure 3-1. Select [Select Resource Type/Temperature Trace] to display the configured temperatures of MMU and MTR as shown in Figure 3-2.

Figure 3-1 View CPU occupation rate

Figure 3-2 View temperatures

Huawei Technologies Proprietary 2

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 3 SITE Functions

II.

Description
This command is used for the MMI to instruct the BTS to report in real time the CPU usage rates concerning the MMU and MFU boards as well as the temperatures of the MMU and MTR boards, so that the maintenance staff can be at any time informed of the CPU loads and internal temperatures and take necessary measures thereby in an event of an over-high CPU usage rate or temperature.

3.4 Force Load SW


I. Operation procedure
Double click [Site0/Force load SW] as shown in Figure 2-1 to open a dialogue box as shown in Figure 3-3. In this box, select the "File Name" of the file to be loaded, "Send Window Size" (40 as recommended value, and no larger than 49 under any circumstances), "Version", "File ID", and etc.. Then click <Begin>. Normally a SW download progress (0~100%) will be displayed and a "SW successfully downloaded" prompt would be shown after several minutes.

Figure 3-3 Force load SW and its progress

II.

Description
BTS software upgrade can be performed in two steps: "Force load SW" and "SW activation". "Force load SW" is to load the upgraded software onto MMU board. Generally speaking, files to be downloaded onto various boards are: mmuxxxx.hex (MMU board download SW), mfuxxxx.omu (MFU board download SW) and mcidown.bin (MTR board download SW). In these file names, "xxxx" stands for version number.

Huawei Technologies Proprietary 3

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 3 SITE Functions

3.5 SW Activation
I. Operation procedure
Double click [SITE0/ SW activation] as shown in Figure 2-1 to open a dialogue box as Figure 3-4. In this box, select "Version", "Board No.", "File ID", etc.. Then click <OK>. Normally if it is MMU board SW activated, a "Software Successfully Activated" prompt would be directly displayed. If it is other boards SW activated, the activating progress (0~100%) would be displayed. Then, a "Software Activation Complete" prompt would be displayed after a few minutes.

Figure 3-4 Software activation

II.

Description
BTS software upgrade is performed in two steps: "Force load SW" and "SW activation". "SW activation" is to load the software which is forcibly loaded onto MMU to different boards.

3.6 Reset Site Hierarchically


I. Operation procedure
Double click [Site0/ Reset site hierarchically] in Figure 2-1 to open a dialogue box as shown in Figure 3-5. Select a level in <Reset Level>, then click <OK>. Normally a "Site Hierarchical Reset successful" prompt would be displayed.

Huawei Technologies Proprietary 4

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 3 SITE Functions

Figure 3-5 Site hierarchical reset

II.

Description
There are three levels of reset, the functions of which are described as follows: First level reset: forcibly put an out-of-service BTS into service, abort the downloading progress from MMU to the board. Third level reset: reinitialize BS, load data but not program. Fourth level reset: BTS re-initializes, loads data, and loads program from FLASH MEMORY.

Huawei Technologies Proprietary 5

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 4 Cell Functions

"Cell" Functions

As shown in Figure 2-1, double click [Site0/Celln] in the tree structure, and all the function commands corresponding to this cell would be displayed in the right part of this window. Detailed explanation including operation procedures as well as description of the function commands corresponding to all the function commands under [Celln] is given in the following. The operation interface under [Celln] is shown in Figure 4-1. Note: The "n" in the "Celln" stands for the No. of this cell.

Figure 4-1 CELL O&M interface

4.1 Cell Attributes Management


I. Operation procedure
Double click [Celln/ Cell attributes management] in Figure 4-1 to open a dialogue box as shown in Figure 4-2. Click <Set> button in this box and under normal circumstances a "Set Cell Attributes Successfully" prompt would be shown. Click
Huawei Technologies Proprietary 1

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 4 Cell Functions

<Refresh> button in this box and under normal circumstances the current attributes of the cell as well as a "Get Attributes Successfully" prompt would be displayed.

Figure 4-2 Cell attributes management

II.

Description
This command is used to set or get the current attributes of [CELLn] under [Site0], which include "Interference Level Limit", "Interference Average Parameter", "Connection Failure Threshold", "T200", "Max. Timing Advance", "Overload Period", "CCCH Load Threshold", "CCCH Load Indication Period", "RACH Busy Threshold", "RACH Load Averaging Slots", "Cell Air Timer", "NY1", "BCCH ARFCN", "BSIC" and "Starting Time".

4.2 Cell Extended Attributes Management


I. Operation procedure
Double click [Celln/Cell extended attributes management] in Figure 4-1 to open a dialogue box as shown in Figure 4-3. Click <Set> and under normal circumstances a "Set Cell Extended Attributes Successfully" prompt would be shown. Click [Refresh] and under normal circumstances the current extended attributes of the cell in question as well as a "Get Attributes Successfully" prompt would be displayed.

Huawei Technologies Proprietary 2

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 4 Cell Functions

Figure 4-3 Cell extended attributes management

II.

Description
This command is used to set or get the current extended attributes of the [CELLn] under [Site0], which includes "RF Source Indication Period", "Paging Times" and "Access Lapse Threshold".

4.3

Opstart Cell
I. Operation procedure
Double click [Celln/ Opstart cell] in Figure 4-1 open a dialogue box as shown in Figure 4-4. Click <OK> and under normal circumstances an "Opstart Cell Successfully" prompt would be displayed.

Figure 4-4 Start cell operation

Huawei Technologies Proprietary 3

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 4 Cell Functions

II.

Description
This command is used for MMI to put the "celln" into operation.

4.4 Change Administrative State


I. Operation procedure
Double click [Celln/ Change administrative state] in Figure 4-1 to open a dialogue box as shown in Figure 4-5. In this box, select an administrative state LOCKED or UNLOCKED. Then, click <OK> and under normal circumstances a "Cell Administrative State Successfully Changed" prompt would be displayed.

Figure 4-5 Change cell administrative state

II.

Description
This command is used to change the state of BTs and RCs under CELLn into "LOCKED" and switch off the amplifier, or to return them into "IDLE" and switch on amplifier by changing the state to "UNLOCKED" under CELLn.

4.5 Cell Performance Test


I. Operation procedure
Double click [Celln/ Cell performance test] in Figure 4-1 to open a dialogue box as shown in Figure 4-6. Click <Begin> button in this box and under normal circumstances the self-test results of the BTs and RCs under the cell would be displayed.

Huawei Technologies Proprietary 4

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 4 Cell Functions

Figure 4-6 Cell performance test

II.

Description
This command is used to command the BTs and RCs under CELLn to conduct self-tests and report the results of these tests.

4.6 Cell Reinitialization


I. Operation procedure
Double click [Celln/ Cell Reinitialization] in Figure 4-1 to open a dialogue box as shown in Figure 4-7. Click <OK> and under normal circumstances a "Reinitialize Cell Successfully" prompt would be displayed.

Figure 4-7 Cell reinitialization

II.

Description
This command is used to reinitialize the BTs and RCs in the cell so that its data can be reset. Note that cell reinitialization should be performed with care, for it will bring the network covering the cell out of service for several minutes.
Huawei Technologies Proprietary 5

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 5 BT Functions

"BT" Functions

As shown in Figure 2-1, left click [Site0/Celln/BTi] in the tree structure and all the function commands corresponding to BTi would be displayed in the right part of the window. Detailed explanation of these function commands including operation procedures as well as the description of these commands is given in the following. The BT Function Test Interface is shown as in Figure 5-1. Note: The "i" in "BTi" stands for the No. of BT.

Figure 5-1 BT function test interface

5.1

Opstart BT
I. Operation procedure
Double click [Celln/BTi/Opstart BT] in Figure 5-1 to open a dialogue box as shown in Figure 5-2. Click <OK> and under normal circumstances an "Opstart BT successfully" prompt would be displayed.
Huawei Technologies Proprietary 1

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 5 BT Functions

Figure 5-2 Start BT operation

II.

Description
This command is used for MMI to put "BTi" into operation.

5.2 Change BT Administrative State


I. Operation procedure
Double click the [Celln/BTi/Change BT administrative state] to open a dialogue box as shown in Figure 5-3. Select the BT(s) whose state is to be changed and change it into LOCKED or UNLOCKED. Then click <OK> and under normal circumstances a "BT Administrative State Successfully Changed" prompt would be displayed.

Figure 5-3 Change BT administrative state

II.

Description
This command is used to change the state of the BT(s) in question to LOCKED, or to return it into "IDLE" by changing it to "UNLOCKED".
Huawei Technologies Proprietary 2

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 5 BT Functions

5.3 BT Reinitialization
I. Operation procedure
Double click [Celln/BTi/BT Reinitialization] to open a dialogue box as shown in Figure 5-4. Click <OK> and under normal circumstances a "Reinitialize BT Successfully" prompt would be displayed.

Figure 5-4 BT reinitialization

II.

Description
This command is used to reinitialize the BT in question so that its data can be reset.

Huawei Technologies Proprietary 3

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 6 RC Functions

"RC" Functions

As shown in Figure 2-1, left click [Site0/Celln/RCj] in the tree structure and all the function commands corresponding to this RC will be displayed in the right part of the window. Detailed explanation of these function commands including operation procedures as well as description is given in the following. RC Function Test Interface is shown as in Figure 6-1. Note: The "j" in "RCj" stands for the No. of this RC.

Figure 6-1 RC function test interface

6.1 RC Attributes Management


I. Operation procedure
Double click [Celln/RCj/RC attributes management] to open a dialogue box as shown in Figure 6-2. Click <Set> and under normal circumstances a "RC Attributes Successfully Set" prompt would be displayed. Click <Refresh> and under normal

Huawei Technologies Proprietary 1

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 6 RC Functions

circumstances the current attributes of the RC in question? as well as a "Getting RC Attributes Succeeded" prompt would be shown.

Figure 6-2 RC attributes management

II.

Description
This command is used to set or get the current RC attribute parameters of [CELLn/RCj] under [Sitem], which include "RF Max. Power Reduction" and "ARFCN" (Absolute RF Channel Number).

6.2 RC Extended Attributes Management


I. Operation procedure
Double click [Celln/RCj/RC extended attributes management] to open a dialogue box as shown in Figure 6-3. Click <Set> and under normal circumstances a "RC Extended Attributes Successfully Set" prompt would be displayed. Click <Refresh> and under normal circumstances the current extended attributes of the RC in question as well as a "Get RC Extended Attributes Successfully" prompt would be shown.

Figure 6-3 RC extended attributes management

Huawei Technologies Proprietary 2

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 6 RC Functions

II.

Description
This command is used to set or get the current extended attributes parameters of the [CELLn/RCj] under Sitem, which include "Static Power Class", "Saturation Threshold" and "Saturation Voltage Threshold".

6.3

Opstart RC
I. Operation procedure
Double click [Celln/RCj/Opstart RC] in Figure 6-1 to open a dialogue box as shown in Figure 6-4. Click <OK> and under normal circumstances an "Opstart RC Successfully" prompt would be displayed.

Figure 6-4 Start TRX operation

II.

Description
This command is used for MMI to put "RCj" into operation.

6.4 Change RC Administrative State


I. Operation procedure
Double click [Celln/RCj/Change RC administrative state] to open a dialogue box as shown in Figure 6-5. Select the RC(s) whose state is to be changed and change it into LOCKED or UNLOCKED. Then click <OK> under normal circumstances a "RC Administrative State Successfully Changed" prompt would be displayed.

Huawei Technologies Proprietary 3

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 6 RC Functions

Figure 6-5 Change RC administrative state

II.

Description
This command is used to change the state of the RC(s) in question to LOCKED and switch of amplifier, or to return it into "IDLE" and switch on the amplifier by changing it to "UNLOCKED".

6.5 RC Reinitialization
I. Operation procedure
Double click [Celln/RCj/RC Reinitialization] to open a dialogue box as shown in Figure 6-6. Then click <OK> and under normal circumstances a "Reinitialize RC Successfully" prompt would be displayed.

Figure 6-6 RC reinitialization

II.

Description
This command is used to reinitialize the RC in question so that its data can be reset.

Huawei Technologies Proprietary 4

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 7 Channel Functions

"Channel" Functions

As shown in Figure 2-1, left click [Site0/Celln/BTi/Channelx] in the tree structure and all the function commands corresponding to this channel would be displayed in the right part of the window. Detailed explanation of these function commands including operation procedures as well as description is given in the following. The Channel Function Interface is shown as in Figure 7-1. Note: The "x" in the "Channelx" stands for the No. of this channel.

Figure 7-1 Channel Function Interface

7.1 Channel Attributes Management


I. Operation procedure
Double click [Celln/BTi/Channelx/Channel Attributes Management] in Figure 7-1 to open a dialogue box as shown in Figure 7-2. Click <Set> and under normal circumstances a "Channel Attributes Successfully Set" prompt would be displayed.

Huawei Technologies Proprietary 1

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 7 Channel Functions

Click <Refresh> and under normal circumstances the current attributes of the channel in question as well as a "Get Attributes Successfully" prompt would be displayed.

Figure 7-2 Channel attributes management

II.

Description
This command is used to set or get the current channel attributes parameters of [CELLn/BTi/Channelx] under [Sitem], which include "Channel Combination", "TSC Selection" and "Starting Time".

7.2

Opstart Channel
I. Operation procedure
Double click [Celln/BTi/Channelx/Opstart channel] in Figure 7-1 to open a dialogue box. Click <OK> button and under normal circumstances an "Opstart Channel Successfully" prompt would be displayed.

II.

Description
This command is used for MMI to put [BTi/Channelx] into operation.

7.3 Change Channel Administrative State


I. Operation procedure
Double click [Celln/BTi/Channelx/Change channel administrative state] in Figure 7-1 to open a dialogue box as shown in Figure 7-3. Select the number(s) of the channel (s) whose states are to be changed and change them into LOCKED or UNLOCKED. Then click <OK> and under normal circumstances a "Channel Administrative State Successfully Changed" prompt would be displayed.

Huawei Technologies Proprietary 2

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 7 Channel Functions

Figure 7-3 Change channel administrative state

II.

Description
This command is used to change the state of the channel(s) in question to LOCKED, or to return it (them) into IDLE by changing it (them) to UNLOCKED.

Huawei Technologies Proprietary 3

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 8 Board Functions

"Board" Functions

As shown in Figure 2-1, left click [Board] in the tree structure and all the function commands corresponding to it would be displayed on the right part of the window. Detailed explanation of on these function commands including operation procedures as well as descriptions is given in the following. The Board function Interface is as shown in Figure 8-1.

Figure 8-1 Board function interface

8.1 Rack Configuration and Board Configuration


I. Operation procedure
Double click [Board/Rack Configuration or Board Configuration] in Figure 8-1 to open a dialogue box as shown in Figure 8-2. Under normal circumstances, "Board Report Message" would be displayed at the bottom left corner of this box. Right-clicking on a certain slot would help to perform ADD or DELETE operations over the board.

Huawei Technologies Proprietary 1

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 8 Board Functions

Figure 8-2 Rack Configuration

II.

Description
This command is used to perform ADD or DELETE operations over boards of BS. "Rack configuration" is for the entire rack, while "board configuration" is for boards.

8.2 Board Management


Double click [Board/Board Management] in Figure 8-1 to open a dialogue box as shown in Figure 8-3. Under normal circumstances, a "Board Report Message" prompt would be displayed at the bottom left corner of this box. Right-clicking on a certain board would help to perform corresponding operations on this board. Detailed explanation of on these function commands including operation procedures as well as descriptions is given in the following.

Huawei Technologies Proprietary 2

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 8 Board Functions

Figure 8-3 Board operation

I.

MTR board

i. Reset MTR Operation procedure In "Board Operation" dialogue box as shown in Figure 8-3, right click MTR board to display a pull-down menu. Then click [Reset...] option in this menu and under normal circumstances a "Board Successfully Reinitialized" prompt would be displayed. Description This command is used for MMI to reinitialize MTR board in question so that its data can be reset. ii. Opstart MTR Operation procedure In "Board Operation" dialogue box as shown in Figure 8-3, right click MTR board to display a pull-down menu. Then, [Opstart...] option in this menu and under normal circumstances a "Opstart Board Successfully" prompt would be displayed. Description This command is used for MMI to put MTR in question into operation. iii. MTR self-test Operation procedure In "Board Operation" dialogue box as shown in Figure 8-3, right click MTR board to display a pull-down menu. Then click [Test...] option in this menu and under normal circumstances a "Board Test Succeeded" prompt would be displayed.

Huawei Technologies Proprietary 3

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 8 Board Functions

Description This command is used for MMI to command MTR in question to conduct a self-test and report the test result. iv. MTR administrative state Operation procedure In "Board Operation" dialogue box as shown in Figure 8-3, right click MTR board to display a pull-down menu. Then choose [Administrative State/ Lock or Unlock] and under normal circumstances an "Administrative State Successfully Changed" prompt would be displayed. Description This command is used to change the state of MTR in question to LOCKED, or to return it into IDLE by changing it to UNLOCKED. v. MTR board information Operation procedure In "Board Operation" dialogue box as shown in Figure 8-3, right click MTR board to display a pull-down menu. Then click [Board Information] to open a dialogue box as shown in Figure 8-4. Normally a "System Responds" prompt would be displayed.

Figure 8-4 MTR Board Information Description This command is used to command MTR board to report board type, board number, board state, software version and the number of alarms. vi. MTR loop test Operation procedure In "Board Operation" dialogue box as shown in Figure 8-3, right click MTR board to display a pull-down menu. Then click [Loop Test...] to open a dialogue box as shown in Figure 8-5. Click <Begin> and under normal circumstances a "Loop Test Success" prompt would be displayed.

Huawei Technologies Proprietary 4

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 8 Board Functions

Figure 8-5 MTR loop test Description This command is used for layer-3 message loop from MMI to MTR and can be used to check DCL link between MMU and MTR. vii. MTR Board Alarm Information Operation procedure In "Board Operation" dialogue box as shown in Figure 8-3, right click MTR board to display a pull-down menu. Then click [Board Alarm...] to open a dialogue box as shown in Figure 8-6. A "System Responds" prompt would be displayed under normal circumstances.

Figure 8-6 MTR board alarm information Description

Huawei Technologies Proprietary 5

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 8 Board Functions

This command is used for MMI to command MTR to report its detailed alarm information. Each cell in the above Figure represents an alarm type assigned with an alarm code, which is a two-digit hex number AB. "A" stands for the row number of the cell and "B" the column number of the cell. If no alarm occurs to the alarm module corresponding to a certain cell, the cell would be in green, otherwise, it would be in red. Detailed alarm explanation is listed in Table 8-1. Table 8-1 Alarm indication on MTR board
Alarm type Code Level Possible causes 1. There is a breakpoint in the connection cable between MTR and MPA modules. 2. MTR module loses lock. 3. MTR or MPA module is faulty. A-level temperature alarm 02 Minor The temperature of MPA module is too high. Handling suggestion 1. Check if there is a power supply alarm. 2. Reset MTR board. 3. Reset BS. Check BTS internal temperature. 1. Check BTS internal temperature. 2. Power off the power amplifier by unlocking RC. 3. Reset MTR. Transmitting phase-lock loop alarm_0 Transmitting phase-lock loop alarm_1 Transmitting phase-lock loop alarm _2 (intermediate frequency) Receiving phase-lock loop alarm_0 Receiving phase-lock loop alarm_1 Receiving phase-lock loop alarm_2 (intermediate frequency) 1. MMU clock module is ineffective. 05 Major 2. Connection cable between MTR and MMU modules is faulty. 3. MTR module is faulty. 06 Major Same as the above 1. Check if there is a clock alarm. 2. Reset MTR board. 3. Reset BS.

"Forward Power Too Low" alarm

01

Minor

B-level temperature alarm

03

Critical

1. The temperature of MPA module is too high. 2. MPA module is faulty.

Same as the above

07

Major

Same as the above

Same as the above

08 09

Major Major

Same as the above Same as the above

Same as the above Same as the above

0A

Major

Same as the above

Same as the above

Huawei Technologies Proprietary 6

User Manual M900/M1800 Base Transceiver Station (BTS22C) Alarm type Code Level

BTS Maintenance BTS Terminal Maintenance 8 Board Functions Possible causes 1. MMU clock module is faulty. Handling suggestion

Clock alarm

0B

Major

2. Connection cable between MMU and MTR module is faulty. 3. MTR module is faulty. 1. Power supply distribution cable between the backplane and MTR module is faulty. 2. MTR module is faulty.

1. Reset MTR board. 2. Reset BS.

Power supply alarm

0C

Critical

1. Reset MTR board. 2. Reset BS.

Frame number alarm

0D

Minor if it is set as non-hopping frequency. Major if hopping frequency

1. MMU clock module is faulty. 2. The distribution cable between the backplane and MTR module is faulty. 3. MTR module is faulty. 1. There is a B-level temperature alarm. 1. Turn off power amplifier by unlocking RC. 2. Reset MTR board. 3. Reset BS. 1. Wait 1 minute to see if the alarm would be cleared. 2. Reset MTR board. 3. Reset MFU board. 4. Reset BS. 1. Reset MTR board. 2. Reset MMU board. 3. Reset BS.

Power amplifier alarm

0E

Critical

2. There is a phase-lock loop lose-lock alarm. 3. Power amplifier is turned down manually in the background.

1. Data settings are incorrect. Downlink Bus alarm 12 Major 2. MMU clock module is faulty. 3. MTR module is faulty.

MCI link alarm

1D

Critical

DCL link between MMU and MCI is faulty.

Reset BS.

II.

MFU Board

i. Reset MFU Operation procedure In "Board Operation" dialogue box as shown in Figure 8-3, right click MFU board to display a pull-down menu. Then click [Reset...] and under normal circumstances a "Reinitialize Board Successfully" prompt would be displayed. Description This command is used for MMI to reinitialize MFU board so that its data can be reset. ii. Opstart MFU Operation procedure

Huawei Technologies Proprietary 7

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 8 Board Functions

In "Board Operation" dialogue box as shown in Figure 8-3, right click MFU board to display a pull-down menu. Then click [Opstart...] and under normal circumstances an "Opstart Board Successfully" prompt would be displayed. Description This command is used for MMI to put MFU into operation. iii. MFU self-test Operation procedure In "Board Operation" dialogue box as shown in Figure 8-3, right click MFU board to display a pull-down menu. Then click [Test...] and under normal circumstances a "Board Test Succeeded" prompt would be displayed. Description This command is used for MMI to command MFU to conduct a self-test and report the test result. iv. MFU administrative state Operation procedure In "Board Operation" dialogue box as shown in Figure 8-3, right click MFU board to display a pull-down menu. Then choose [Administrative State/Lock or Unlock] and under normal circumstances an "Administrative State Successfully Changed" prompt would be displayed. Description This command is used to change the state of MFU or the channel following to LOCKED, or to return it or the channel following into IDLE by changing it or the channel following to UNLOCKED. v. MFU board information Operation procedure In "Board Operation" dialogue box as shown in Figure 8-3, right click MFU board to display a pull-down menu. Then click [Board Information] to open a dialogue box similar to Figure 8-4. A "System Responds" prompt would be displayed under normal circumstances. Description This command is used to command MFU to report board type, board number, board state, software version and the number of alarms. vi. MFU loop test Operation procedure In "Board Operation" dialogue box as shown in Figure 8-3, right click MFU board to display a pull-down menu. Then click [Loop Test...] to open a dialogue box similar to Figure 8-5. click <Begin> and under normal circumstances a "Loop Test Success" prompt would be displayed. Description This command is used for layer-3 message loop from MMI to MFU and can be used to check HDLC link between MMU and MFU.

Huawei Technologies Proprietary 8

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 8 Board Functions

vii. MFU board alarm information Operation procedure In "Board Operation" dialogue box as shown in Figure 8-3, right click MFU board to display a pull-down menu. Then click [Board Alarm...] to open a dialogue box similar to Figure 8-6. A "System Responds" prompt would be displayed under normal circumstances. Description This command is used for MMI to command MTR to report its detailed alarm information. Detailed alarm explanation is listed in Table 8-2. Table 8-2 MFU board alarm indication
Alarm type Code Level Possible causes 1. The connection between MFU and MMU clock module may be faulty. 2. E1 module of MMU is faulty. 3.MFU module is faulty. 1. The connection between MFU and MMU clock module is faulty. 2. MMU clock module is faulty. 3. MFU module is faulty. 1. Reset MFU board. 2. Reset MMU board. 3. Reset BS. 1. Wait 1 minute to see if the alarm would be cleared. 2. Check BSC data setting. 3. Reset MFU board. 4. Reset BS. Internal mailbox fault MFU SW loading failure 0A Critical 1. Wait 1 minute to see if the MFU internal mailbox link is faulty. alarm would be cleared. 2. Reset MFU board. 0E Minor Loading communication fails. Reset MFU board and reactivate MFU software. 1. Wait 1 minute to see if the alarm would be cleared. CUI link fault 40 Critical /Minor Uplink between MFU and MTR modules is faulty. 2. Reset MFU board. 3. Reset MTR board. 4. Reset BS. Frame number abnormal MFU link alarm 41 1D Critical /Minor Critical The connection between MFU and MMU clock module is faulty. HDLC link between MFU and MMU is faulty. Reset BS. Handling suggestions 1. Reset MFU board. 2. Reset MMU board. 3. Reset BS.

PCM clock fault

01

Major

TDMA clock fault

03

Major

LAPD link fault

09

Minor

1. MFU data is not set. 2. BSC data setting is incorrect.

Huawei Technologies Proprietary 9

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 8 Board Functions

III.

MMU board

i. Reset MMU Operation procedure In "Board Operation" dialogue box as shown in Figure 8-3, right click MMU board to display a pull-down menu. Then click [Reset...] and under normal circumstances a "Reinitialize Board Successfully" prompt would be displayed. Description This command is used for MMI to reset MMU board. ii. MMU self-test Operation procedure In "Board Operation" dialogue box as shown in Figure 8-3, right click MMU board to display a pull-down menu. Then click [Test...] and under normal circumstances a "Board Test Succeeded" prompt would be displayed. Description This command is used for MMI to command MMU to conduct a self-test and report the test result. iii. MMU board information Operation procedure In "Board operation" dialogue box as shown in Figure 8-3, right click MMU board to display a pull-down menu. Then click [Board Information] to open a dialogue box as shown in Figure 8-7. A "System Responds" prompt would be displayed under normal circumstances. Description This command is used to command MMU board to report board type, board No., board state, delay parameter, crystal DA oscillation value, board alarm No., SW version, difference of discriminator and setting working mode.

Figure 8-7 MMU Board Information


Huawei Technologies Proprietary 10

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 8 Board Functions

iv. Set MMU clock mode Operation procedure In "Board operation" dialogue box as shown in Figure 8-3, right click MMU board to display a pull-down menu. Then click [Set Clock Mode] to display a dialogue box as shown Figure 8-8. Select an option respectively for [Select Clock] and [Rack Delay] fields. Then click <OK> and under normal circumstances a "Clock Mode Successfully Set" prompt would be displayed.

Figure 8-8 Set MMU clock mode Description This command is used for MMI to specify the working mode of 13M crystal oscillator on MMU board. v. MMU loop test Operation procedure In "Board operation" dialogue box as shown in Figure 8-3, right click MMU board to display a pull-down menu. Then click [Loop Test...] to open a dialogue box similar to Figure 8-5. Click <Begin> and under normal circumstances a "Loop Test Succeeded" prompt would be displayed. Description This command is used for layer-3 message loop from MMI to MMU and can be used to test MMU software. vi. MMU Board Alarm Information Operation procedure In "Board operation" dialogue box as shown in Figure 8-3, right click MMU board to display a pull-down menu. Then click [Board Alarm...] to open a dialogue box similar to Figure 8-6. A "System Responds" prompt would be displayed under normal circumstances. Description This command is used for MMI to command MMU to report its detailed alarm information. Detailed alarm explanation is listed in Table 8-3.

Huawei Technologies Proprietary 11

User Manual M900/M1800 Base Transceiver Station (BTS22C)

BTS Maintenance BTS Terminal Maintenance 8 Board Functions

Table 8-3 MMU board alarm indication


Alarm type Temperature alarm Code 22 Level Major Possible causes The internal temperature is too high. The 220V power supply is off. The board hardware or the backplane is faulty. Handling suggestions 1. Check the ambient temperature. 2. Check if there is a power amplifier alarm. 1. Wait several minutes to see whether the alarm would be cleared. 2. Reset BS. Reset MMU board.

Power-off alarm Clock-module 13M clock alarm

2A

Major

41

Critical

"Clock-module crystal oscillation DA 42 value 3/4 transgresses the threshold" alarm 8K reference clock alarm

Minor

Crystal oscillation is aged 1. Check the accuracy of BSC clock. and most likely goes 2. Keep a record and deliver the faulty beyond the adjusting board for repair. range. E1 module of MMU does 1. Check the accuracy of BSC clock and the not send reference clock transmission link quality. or the reference clock is 2. Wait for recovery. unstable. 1. Check the transmitting-end connection cable of No. 0 E1 at BS. The transmitting-end connection cable of No. 0 2. Check the receiving-end connection E1 is faulty. cable of the corresponding E1 at BSC or the superior BS. 1. Ignore this alarm if no inferior BTS is attached to this BS.

43

Minor

E1 link remote end out-of-sync

51

Minor

E1 link remote end out-of-sync

52

Minor

2. Check the transmitting-end connection The transmitting-end connection cable of No. 1 cable of No. 1 E1 at BS. E1 is faulty. 3. Check the receiving-end connection cable of the corresponding E1 at the inferior BS. 1. Check if the E1 module at BSC or the 1. E1 module at BSC or superior BTS is in service. the superior BTS is out of 2. Check the receiving-end connection service. cable of No. 0 E1. 2. The receiving-end 3. Check the transmitting-end connection connection cable of No. 0 cable of the corresponding E1 at BSC or E1 is faulty. superior BS. 1. E1 module at the inferior BTS is out of service. 2. The receiving-end connection of the No. 1 E1 is faulty. 1. Ignore this alarm if no inferior BTS is attached to this BS. 2. Check if the E1 module at the inferior BTS is in service. 3. Check the receiving-end connection cable of No. 1 E1. 4. Check the transmitting-end connection cable of the corresponding E1 at inferior BS.

E1 link local end out-of-sync

53

Minor

E1 link local end out-of-sync

54

Minor

Huawei Technologies Proprietary 12

User Manual M900/M1800 Base Transceiver Station (BTS22C) Alarm type E1 tributary_0 out-of-service E1 tributary_1 out-of-service Code 55 56 Level Minor Minor

BTS Maintenance BTS Terminal Maintenance 8 Board Functions Possible causes The board hardware is faulty. The board hardware is faulty Handling suggestions Reset MMU board. Reset MMU board.

Huawei Technologies Proprietary 13

You might also like