TITUS

Diffusers

Linear Slot

Performance Data

1946

1996

Model: ML-37 12" Slot Supply


Airflow, cfm/ft.

10

16

21

26

31

36

42

47

Static Pressure
NC ( Noise Criteria)

0.006
-

0.023
-

0.051
20

0.090
27

0.141
32

0.203
37

0.277
40

0.361
44

0.458
46

Horizontal
Vertical

1-1-6
2

3 - 6 - 12
6

6 - 11 - 15
9

10 - 12 - 17
11

11 - 14 - 19
12

12 - 15 - 21
14

13 - 16 - 23
15

14 - 17 - 25
16

15 - 18 - 26
17

Airflow, cfm/ft.
Static Pressure

10
0.006

21
0.023

31
0.051

42
0.090

52
0.141

62
0.203

73
0.277

83
0.361

94
0.458

Slot

NC ( Noise Criteria)

13

23

30

35

40

43

47

49

Horizontal
Vertical

1 - 3 - 10
4

5 - 10 - 17
8

10 - 15 - 21
13

14 - 17 - 25
16

16 - 19 - 28
17

17 - 21 - 30
19

19 - 23 - 33
20

20 - 25 - 35
22

21 - 26 - 37
24

Airflow, cfm/ft.
Static Pressure
NC ( Noise Criteria)
Horizontal
Vertical

16
0.006
2 - 4 - 13
5

31
0.023
15
7 - 13 - 21
10

47
0.051
25
13 - 18 - 26
15

62
0.090
32
17 - 21 - 30
19

78
0.141
37
19 - 24 - 34
21

94
0.203
41
21 - 26 - 37
23

109
0.277
45
23 - 28 - 40
25

125
0.361
48
25 - 30 - 43
27

140
0.458
51
26 - 32 - 45
28

1
Slot

3
Slot

Airflow, cfm/ft.

21

42

62

83

104

125

146

166

187

Static Pressure

0.006

0.023

0.051

0.090

0.141

0.203

0.277

0.361

0.458

Slot

NC ( Noise Criteria)
Horizontal
Vertical

3 - 6 - 14
7

16
10 - 14 - 25
12

26
14 - 21 - 30
18

33
19 - 25 - 35
22

38
22 - 28 - 39
25

43
25 - 30 - 43
27

46
27 - 33 - 46
29

50
28 - 35 - 49
31

52
30 - 37 - 52
33

Airflow, cfm/ft.
Static Pressure
NC ( Noise Criteria)
Horizontal
Vertical

26
0.006
3 - 7 - 16
7

52
0.023
17
11 - 16 - 28
14

78
0.051
27
16 - 24 - 34
20

104
0.090
34
22 - 28 - 39
25

130
0.141
39
25 - 31 - 44
28

156
0.203
44
28 - 34 - 48
30

182
0.277
47
30 - 36 - 52
32

208
0.361
51
32 - 39 - 55
35

234
0.458
53
34 - 41 - 58
37

Airflow, cfm/ft.
Static Pressure
NC ( Noise Criteria)

31
0.006
-

62
0.023
18

94
0.051
28

125
0.090
35

156
0.141
40

187
0.203
44

218
0.277
48

250
0.361
51

281
0.458
54

Horizontal
Vertical

4 - 9 - 18
7

12 - 18 - 30
16

18 - 26 - 37
22

24 - 30 - 43
27

28 - 34 - 48
30

30 - 37 - 52
33

33 - 40 - 56
35

35 - 43 - 60
38

37 - 45 - 64
40

Airflow, cfm/ft.
Static Pressure
NC ( Noise Criteria)
Horizontal
Vertical

36
0.006
6 - 10 - 19
8

73
0.023
19
13 - 19 - 33
16

109
0.051
29
19 - 28 - 40
24

146
0.090
35
25 - 33 - 46
29

182
0.141
41
30 - 36 - 52
32

218
0.203
45
33 - 40 - 56
35

255
0.277
49
35 - 43 - 61
38

291
0.361
52
38 - 46 - 65
41

328
0.458
55
40 - 49 - 69
43

Airflow, cfm/ft.
Static Pressure
NC ( Noise Criteria)
Horizontal
Vertical

42
0.006
7 - 10 - 20
8

83
0.023
19
14 - 20 - 35
17

125
0.051
29
20 - 30 - 43
26

166
0.090
36
27 - 35 - 49
31

208
0.141
41
32 - 39 - 55
35

250
0.203
46
35 - 43 - 60
38

291
0.277
49
38 - 46 - 65
41

333
0.361
53
40 - 49 - 70
43

374
0.458
55
43 - 52 - 74
45

5
Slot

6
Slot

7
Slot

8
Slot

For performance notes, see page G16.

NC corrections for various diffuser lengths.


Length

10

Supply
Return

-3
0

0
+3

+2
+5

+3
+6

+5
+8

TITUS

Diffusers

Linear Slot

Performance Data

1946

1996

G15

12

19

25

31

37

43

50

56

Static Pressure
NC ( Noise Criteria)

0.004
-

0.016
-

0.037
14

0.065
20

0.102
26

0.146
30

0.199
34

0.260
37

0.330
40

Horizontal
Vertical

1-2-6
2

3 - 6 - 16
6

6 - 12 - 20
10

11 - 16 - 23
12

13 - 18 - 26
14

16 - 20 - 28
15

18 - 22 - 31
16

19 - 23 - 33
17

20 - 25 - 35
18

Airflow, cfm/ft.
Static Pressure

12
0.004

25
0.016

37
0.037

50
0.065

62
0.102

74
0.146

87
0.199

99
0.260

112
0.330

Slot

NC ( Noise Criteria)

17

23

29

33

37

40

43

Horizontal
Vertical

1 - 3 - 11
4

5 - 11 - 22
9

11 - 17 - 28
14

15 - 22 - 33
17

19 - 26 - 37
19

22 - 28 - 40
21

25 - 31 - 43
23

27 - 33 - 46
24

28 - 35 - 49
25

Airflow, cfm/ft.
Static Pressure
NC ( Noise Criteria)
Horizontal
Vertical

19
0.004
2 - 5 - 14
6

37
0.016
8 - 14 - 27
11

56
0.037
18
14 - 20 - 35
17

74
0.065
25
18 - 27 - 40
21

93
0.102
31
23 - 32 - 45
23

112
0.146
35
27 - 35 - 49
26

130
0.199
39
31 - 38 - 53
28

149
0.260
42
33 - 40 - 57
30

167
0.330
45
35 - 43 - 60
32

3
Slot

Airflow, cfm/ft.

25

50

74

99

124

149

174

198

223

Static Pressure

0.004

0.016

0.037

0.065

0.102

0.146

0.199

0.260

0.330

Slot

NC ( Noise Criteria)
Horizontal
Vertical

3 - 6 - 16
6

11 - 16 - 32
13

20
16 - 24 - 40
19

26
21 - 32 - 46
24

32
26 - 37 - 52
27

36
32 - 40 - 57
30

40
36 - 43 - 61
32

43
38 - 46 - 66
34

46
40 - 49 - 70
36

Airflow, cfm/ft.
Static Pressure
NC ( Noise Criteria)
Horizontal
Vertical

31
0.004
4 - 8 - 18
7

62
0.016
12 - 18 - 35
14

93
0.037
21
18 - 26 - 45
21

124
0.065
27
24 - 35 - 52
27

155
0.102
33
29 - 41 - 58
30

186
0.146
37
35 - 45 - 64
33

217
0.199
41
40 - 49 - 69
36

248
0.260
44
42 - 52 - 73
38

279
0.330
47
45 - 55 - 78
40

Airflow, cfm/ft.
Static Pressure
NC ( Noise Criteria)

37
0.004
-

74
0.016
12

112
0.037
21

149
0.065
28

186
0.102
34

223
0.146
38

260
0.199
42

298
0.260
45

335
0.330
48

Horizontal
Vertical

5 - 10 - 19
8

13 - 19 - 39
15

19 - 29 - 49
24

26 - 39 - 57
30

32 - 45 - 64
33

39 - 49 - 70
36

43 - 53 - 75
39

46 - 57 - 81
42

49 - 60 - 85
45

Airflow, cfm/ft.
Static Pressure
NC ( Noise Criteria)
Horizontal
Vertical

43
0.004
6 - 10 - 21
8

87
0.016
12
14 - 21 - 42
16

130
0.037
22
21 - 31 - 53
24

174
0.065
29
28 - 42 - 61
32

217
0.102
34
35 - 49 - 69
36

260
0.146
39
42 - 53 - 75
39

304
0.199
42
47 - 58 - 81
42

347
0.260
45
50 - 61 - 87
45

391
0.330
48
53 - 65 - 92
48

Airflow, cfm/ft.
Static Pressure
NC ( Noise Criteria)
Horizontal
Vertical

50
0.004
7 - 11 - 22
8

99
0.016
13
15 - 22 - 45
16

149
0.037
23
22 - 33 - 57
24

198
0.065
29
30 - 45 - 66
33

248
0.102
35
37 - 52 - 73
38

298
0.146
39
45 - 57 - 81
42

347
0.199
43
50 - 61 - 87
45

397
0.260
46
54 - 66 - 93
48

446
0.330
49
57 - 70 - 99
51

5
Slot

6
Slot

7
Slot

8
Slot

For performance notes, see page G16.

NC corrections for various diffuser lengths.


Length

10

Supply
Return

-3
0

0
+3

+2
+5

+3
+6

+5
+8

Diffusers

Airflow, cfm/ft.
1
Slot

Model: ML-38 34" Slot Supply

G16

TITUS

Diffusers

Linear Slot

Performance Data

1946

1996

Model: ML-39 1" Slot Supply


Airflow, cfm/ft.

13

20

26

33

40

46

53

59

Static Pressure
NC ( Noise Criteria)

0.004
-

0.014
-

0.032
13

0.057
20

0.089
26

0.128
30

0.174
34

0.228
37

0.288
40

Horizontal
Vertical

1-2-6
2

3 - 6 - 16
8

6 - 12 - 21
12

11 - 16 - 24
14

14 - 19 - 27
15

16 - 21 - 29
17

18 - 22 - 32
18

20 - 24 - 34
19

21 - 25 - 36
20

Airflow, cfm/ft.
Static Pressure

13
0.004

26
0.014

40
0.032

53
0.057

66
0.089

79
0.128

92
0.174

106
0.228

119
0.288

Slot

NC ( Noise Criteria)

16

23

29

33

37

40

43

Horizontal
Vertical

1 - 3 - 12
5

5 - 12 - 23
11

12 - 17 - 29
16

15 - 23 - 34
19

19 - 27 - 38
22

23 - 29 - 42
24

26 - 32 - 45
26

28 - 34 - 48
28

29 - 36 - 51
30

Airflow, cfm/ft.
Static Pressure
NC ( Noise Criteria)
Horizontal
Vertical

20
0.004
2 - 5 - 14
7

40
0.014
8 - 14 - 28
13

59
0.032
18
14 - 21 - 36
20

79
0.057
25
19 - 28 - 42
24

99
0.089
30
23 - 33 - 46
27

119
0.128
35
28 - 36 - 51
29

139
0.174
39
32 - 39 - 55
32

158
0.228
42
34 - 42 - 59
34

178
0.288
45
36 - 44 - 62
36

1
Slot

3
Slot

Airflow, cfm/ft.

26

53

79

106

132

158

185

211

238

Static Pressure

0.004

0.014

0.032

0.057

0.089

0.128

0.174

0.228

0.288

Slot

NC ( Noise Criteria)
Horizontal
Vertical

3 - 6 - 16
8

11 - 16 - 33
15

19
16 - 24 - 42
23

26
22 - 33 - 48
28

32
27 - 38 - 54
31

36
33 - 42 - 59
34

40
37 - 45 - 63
36

43
39 - 48 - 68
39

46
42 - 51 - 72
42

Airflow, cfm/ft.
Static Pressure
NC ( Noise Criteria)
Horizontal
Vertical

33
0.004
4 - 8 - 18
9

66
0.014
12 - 18 - 36
17

99
0.032
20
18 - 27 - 46
25

132
0.057
27
24 - 36 - 54
31

165
0.089
33
30 - 42 - 60
34

198
0.128
37
36 - 46 - 66
38

231
0.174
41
41 - 50 - 71
41

264
0.228
44
44 - 54 - 76
43

297
0.288
47
46 - 57 - 80
45

Airflow, cfm/ft.
Static Pressure
NC ( Noise Criteria)

40
0.004
-

79
0.014
12

119
0.032
21

158
0.057
28

198
0.089
33

238
0.128
38

277
0.174
42

317
0.228
45

356
0.288
48

Horizontal
Vertical

5 - 10 - 20
9

13 - 20 - 40
19

20 - 30 - 51
28

27 - 40 - 59
34

33 - 46 - 66
38

40 - 51 - 72
41

45 - 55 - 78
45

48 - 59 - 83
48

51 - 62 - 88
51

Airflow, cfm/ft.
Static Pressure
NC ( Noise Criteria)
Horizontal
Vertical

46
0.004
6 - 11 - 22
10

92
0.014
12
14 - 22 - 43
20

139
0.032
22
22 - 32 - 55
30

185
0.057
29
29 - 43 - 63
36

231
0.089
34
36 - 50 - 71
41

277
0.128
38
43 - 55 - 78
45

323
0.174
42
48 - 59 - 84
48

370
0.228
45
52 - 63 - 90
52

416
0.288
48
55 - 67 - 95
55

Airflow, cfm/ft.
Static Pressure
NC ( Noise Criteria)
Horizontal
Vertical

53
0.004
8 - 12 - 23
11

106
0.014
13
15 - 23 - 46
22

158
0.032
23
23 - 35 - 59
32

211
0.057
29
31 - 46 - 68
39

264
0.089
35
38 - 54 - 76
43

317
0.128
39
46 - 59 - 83
48

370
0.174
43
52 - 63 - 90
52

422
475
0.228
0.288
46
49
55 - 68 - 96 59 - 72 - 102
55
58

5
Slot

6
Slot

7
Slot

8
Slot

NC corrections for various diffuser lengths.

Throw Correction Multiplier for length

Length
Supply

2
-3

4
0

6
+2

8
+3

10
+5

Return

+3

+5

+6

+8

Length
Throw Corr.

2
0.72

4
1.0

8
1.5

10
1.7

12
1.8

Data were obtained from tests conducted in accordance with ANSI/ASHRAE Standard 70-1991. Actual performance, with flexible duct inlet, may vary in the field
See the engineering section of this catalog, pages C37-C38, for additional information.
Horizontal throw values are given for terminal velocities of 150, 100, and 50 fpm.
Throw values are given for isothermal conditions, and are based on 4 ft. active section. For other lengths, see the Throw Correction Table.
Pressure is given in inches of WG for ML only.
Vertical throw values are given for terminal velocities of 50 fpm.
For divided throw, use the cfm-per-foot value for the number of slots in each direction. For sound, use the NC values for cfm-per-foot for the total number of slots.
Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any
of the octave bands, 2nd through 7th, with a room absorption of 10 dB, re 10-12 watts.
For vertical throw, deduct 11 NC.
Dash (-) in space denotes an NC value of less than 10.
Data were obtained from tests conducted in accordance with ANSI / ASHRAE Standard 70-91.
NC is based on 4 ft. lengths; for other lengths use the NC correction table.
Throws listed are for the 1-way air pattern. For divided airflow, select the airflow in each direction according to the number of slots aimed in that direction,
with the total airflow apportioned between slots. For an explanation of catalog throw data, see page C13.

Diffusers

All pressures are in inches of water.


NC values are based on a room

NC Correction for
Various MLR Lengths
Length (ft.)

10

15

20

-7

-4

+2

+3

Performance Data

1946

1996

G17

Model: MLR-37
No. of
Slots

absorption of 10 dB, re 10-12 watts,


with a 10 ft. active diffuser section
(see the table below).
Dash () in space denotes NC
value less than 10.
Data were obtained from tests
conducted in accordance with
ANSI/ASHRAE Standard 70-1991.

MLR

Linear Slot

Negative SP

.011

.025

.045

.072

.103

.180

.275

.415

cfm per ft.


NC

10

15

20
14

25
20

30
25

40
33

50
39

60
44

cfm per ft.


NC

20

30

40
17

50
23

60
28

80
36

100
42

120
47

cfm per ft.


NC

30

45
11

60
19

75
25

90
30

120
38

150
44

180
49

cfm per ft.


NC

40

60
12

80
20

100
26

120
31

160
39

200
45

240
50

cfm per ft.


NC

50

75
13

100
21

125
27

150
32

200
40

250
46

300
51

cfm per ft.


NC

60

90
14

120
22

150
28

180
33

240
41

300
47

360
52

cfm per ft.


NC

70

105
15

140
23

175
29

210
34

280
42

350
48

420
53

cfm per ft.


NC

80

120
15

160
23

200
29

240
34

320
42

400
48

480
53

.007

.028

.063

.108

.170

.250

.345

.450

No. of
Slots

Negative SP

cfm per ft.


NC

10

20

30
18

40
26

50
32

60
37

70
41

80
45

cfm per ft.


NC

20

40
10

60
21

80
29

100
35

120
40

140
44

160
48

cfm per ft.


NC

30

60
12

90
23

120
31

150
37

180
42

210
46

240
50

cfm per ft.


NC

40

80
13

120
24

160
32

200
38

240
43

280
47

320
51

cfm per ft.


NC

50

100
14

150
25

200
33

250
39

300
44

350
48

400
52

cfm per ft.


NC

60

120
15

180
26

240
34

300
40

360
45

420
49

480
53

cfm per ft.


NC

70

140
16

210
27

280
35

350
41

420
46

490
50

560
54

cfm per ft.


NC

80

160
16

240
27

320
35

400
41

480
46

560
50

640
54

.018

.040

.070

.108

.160

.215

.280

.450

Model: MLR-39
No. of
Slots

Negative SP

cfm per ft.


NC

20

30
11

40
19

50
25

60
30

70
34

80
38

100
44

cfm per ft.


NC

40

60
14

80
22

100
28

120
33

140
37

160
41

200
47

cfm per ft.


NC

60

90
16

120
24

150
30

180
35

210
39

240
43

300
49

cfm per ft.


NC

80

120
17

160
25

200
31

240
36

280
40

320
44

400
50

cfm per ft.


NC

100

150
18

200
26

250
32

300
37

350
41

400
45

500
51

cfm per ft.


NC

120

180
19

240
27

300
33

360
38

420
42

480
46

600
52

cfm per ft.


NC

140

210
20

280
28

350
34

420
39

490
43

560
47

700
53

cfm per ft.


NC

160

240
20

320
28

400
34

480
39

560
43

640
47

800
53