You are on page 1of 30

Reactive Power Issues

What is Reactive Power?


While active power is the energy supplied to run a motor, heat a home, or illuminate an electric light bulb, reactive power provides the important function of regulating voltage. If voltage on the system is not high enough, active power cannot be supplied. Reactive power is used to provide the voltage levels necessary for active power to do useful work. Reactive power is essential to move active power through the transmission and distribution system to the customer.

Reactive power analogies


The loft in a baseball throw.

The lift in an airplane.

The loft analogy

The AIRCRAFT lift analogy

Reactive Power is a Byproduct of Alternating Current (AC) Systems Transformers, transmission lines, and motors require reactive power Transformers and transmission lines introduce inductance as well as resistance Both oppose the flow of current Must raise the voltage higher to push the power through the inductance of the lines Unless capacitance is introduced to offset inductance The farther the transmission of power, the higher the voltage needs to be raised Electric motors need reactive power to produce magnetic fields for their operation

What is Reactive Power?


While active power is the energy supplied to run a motor, heat a home, or illuminate an electric light bulb, reactive power provides the important function of regulating voltage. Reactive power is used to provide the voltage levels necessary for active power to do useful work. Reactive power is essential to move active power through the transmission and distribution system to the customer.

How Are Voltages Controlled?

Voltages are controlled by providing sufficient reactive power control margin to modulate and supply needs through:
1. Shunt capacitor and reactor compensations 2. Dynamic compensation 3. Proper voltage schedule of generation.

Voltages are controlled by predicting and correcting reactive power demand from loads.

Reactive Power Management and Control is Critical for Overall System Stability

Voltage Must be Maintained Within Acceptable Levels


Under normal system conditions, both peak or off peak load conditions, the voltages need to be maintained between 95% and 105% of the nominal. Low voltage conditions could result in equipment malfunctions: 1. Motor will stall, overheat or damage 2. Reactive power output of capacitors will be reduced exponentially 3. Generating units may trip. High voltage conditions may: 1. Damage major equipment insulation failure 2. Automatically trip major transmission equipment.

Reactive Power System Sources & Sinks


Sources Transmission System Sinks

Line Charging (Source) Synchronous Condensers & Generators Reactive Losses (Sink) Synchronous Condensers & Generators

Reactors Capacitors
Reactive flow across interconnections

Reactive Load

Reactive flow across interconnections

Voltage and Reactive Power

Voltage and reactive power must be properly managed and controlled to: 1. Provide adequate service quality 2. Maintain proper stability of the power system.

Maintain Proper Stability of the Power System

Voltage Collapse Phenomenon


Inadequate reactive support

Which results in:


Voltage drops

Which results in:


Reduced reactive power from capacitors and line charging

Which results in:


Less reactive power support Which results in: Greater voltage drops
Which results in:

Tripping of generating units due to low auxiliary voltage level or TCUL actions or generator field current limiters

VOLTAGE COLLAPSE

August 14, 2003 Blackout


Several Causes: Sufficient voltage studies were not conducted. Operational voltage criteria that did not reflect actual voltage stability conditions and needs were used in voltage analyses. Inadequate practices without correction were used.

August 14, 2003 Blackout


Conclusion: The August 2003 Blackout study team concluded that inadequate voltage and reactive power planning were contributing factors to the incident.

Recommendation: National Electric Reliability Council specifically recommended stricter voltage and reactive planning and assessment practices to be implemented by electric utilities.

Voltage & Reactive Power Planning And Assessment Practices


Key Principles: Reactive power cannot be transmitted over a long distance or through power transformers due to excessive reactive power losses. Reactive power supply should be located in close proximity to its consumption. Sufficient static and dynamic voltage support is needed to maintain voltage levels within an acceptable range. Sufficient reactive power reserves must be available to regulate voltage at all times.

Voltage & Reactive Power Planning And Assessment Practices


Key Implications: Metering must be in place and maintained to capture actual reactive consumption at various points. Transmission and Distribution planners must determine in advance the required type and location of reactive correction. Reactive power devices must be maintained and functioning properly to ensure the correct amount of reactive compensation. Distribution reactive loads must be fully compensated before transmission reactive compensation is considered.

Transmitting Reactive Power

Reactive power cannot be effectively transmitted across long distances or through power transformers due to high I2X losses.

Reactive Power Location

Reactive power should be located in close proximity to its consumption.

Static vs. Dynamic Voltage Support


The type of reactive compensation required is based on the time needed for voltage recovery. Static Compensation is ideal for second and minute responses. (capacitors, reactors, tap changes). Dynamic Compensation is ideal for instantaneous responses. (condensers, generators) A proper balance of static and dynamic voltage support is needed to maintain voltage levels within an acceptable range.

Reactive Reserves During Varying Operating Conditions


Ideally, the system capacitors, reactors, and condensers should be operated to supply the normal reactive load. As the load increases or following a contingency, additional capacitors should be switched on or reactors removed to maintain acceptable system voltages. The reactive capability of the generators should be largely reserved for contingencies on the EHV system or to support voltages during extreme system operating conditions. Load shedding schemes must be implemented if a desired voltage is unattainable thru reactive power reserves.

Voltage Coordination
The reactive sources must be coordinated to ensure that adequate voltages are maintained everywhere on the interconnected system during all possible system conditions. Maintaining acceptable system voltages involves the coordination of sources and sinks which include: 1. Plant voltage schedules 2. Transformer tap settings 3. Reactive device settings 4. Load shedding schemes.

Voltage Coordination

The consequences of uncoordinated operations would include: 1. Increased reactive power losses 2. A reduction in reactive margin available for contingencies and extreme light load conditions 3. Excessive switching of shunt capacitors or reactors 4. Increased probability of voltage collapse conditions.

Voltage Schedule
Each power plant is requested to maintain a particular voltage on the system bus to which the plant is connected. The assigned schedule will permit the generating unit to typically operate: 1. In the middle of its reactive capability range during normal conditions 2. At the high end of its reactive capability range during contingencies 3. Under excited or absorb reactive power under extreme light load conditions.

Transformer Tap Settings

Transformer taps must be coordinated with each other and with nearby generating station voltage schedules. The transformer taps should be selected so that secondary voltages remain below equipment limits during light load conditions.

Reactive Device Settings

Capacitors on the low voltage networks should be set to switch on to maintain voltages during peak and contingency conditions.

And Off when no longer required to support voltage levels.

Load Shedding Schemes

Load shedding schemes must be implemented as a last resort to maintain acceptable voltages.

Voltage and Reactive Power Control


Requires the coordination work of all Transmission and Distribution disciplines. 1. Transmission needs to: Forecast the reactive demand and required reserve margin Plan, engineer, and install the required type and location of reactive correction Maintain reactive devices for proper compensation Maintain meters to ensure accurate data Recommend the proper load shedding scheme if necessary.

Voltage and Reactive Power Control

2. Distribution needs to: Fully compensate distribution loads before Transmission reactive compensation is considered Maintain reactive devices for proper compensation Maintain meters to ensure accurate data Install and test automatic under voltage load shedding schemes.

You might also like