kV
12 24 12 24
A
375 430 395 480
B
880 880 940 940
C
820 1030 860 1060
D
210 300 210 300
Weight
(mm) (mm)
(mm) (mm)
(kg.) 60 75 65 80
1P - 3P
B
(*)
2P - 4P
Type 1 - Switch disconnector Type 3 - Disconnector (off-load) Type 2 - Transformer protection fuse-switch disconnector Type 4 - Disconnector with fuse-holders (off-load)
ELECTRICAL FEATURES
Rated voltage Power frequency withstand voltage (50/60 Hz 1 min) to earth and between phases Impulse withstand voltage to earth and between phases Rated current Breaking capacity of active circuits (cos 0.7) and ring circuits at 0.3 Vn Breaking capacity of no-load transformers Breaking capacity of no-load lines / cables Short time current - 1 sec Short time current - 3 sec Making capacity Ur [kV] [kV] Up [kV]
12 28 75 17,5 38 95 24 50 125 36 70 170
In [A] 400-630 400-630 400-630 400-630 Isc [kA] 400-630 400-630 400-630 Isc [kA] Isc [kA]
25 25 25 25 25 25 400 16 25 12,5 31,5
Ik [kA] 12,5...25 12,5...25 12,5...25 Ik [kA] 12,5...20 12,5...20 12,5...20 [kA] 31,5...62,5 31,5...62,5 31,5...62,5
VEI S.p.A. reserves the right of bringing any modification due to technical and commercial reasons at any time.Therefore the information and pictures reported in the present issue are updated until the approval of printing.