Configuration of Nivelco Controller for Make Up Valve Project UNICONT PMM 328 - 1

1.

Standard Table S Code S.PrG S.A4 S.A4h Description Software revision number (Read Only) Alarm 4 Value Alarm 4 Hysterisis Configuration 4.208 18 0

2. Code P. P P. I P. d P. dZ

Parameters Table P Description First PID set: Proportional Gain (P) of first control loop (%) First PID set: Integral Time (I) of first control loop (sec) First PID set: Derivative Time (D) of first control loop (sec) First PID set: Dead Band for Heating-Cooling control or motor driven valve application. Hysterisis value for ON-OFF control (P.P = 0, P.I = 0, P.d = 0) Configuration 0.1 1 0 0

3.

Definition Table d Definition Access code (4-digits). When set, the Calibration and Definition Tables can not be accessed. Display set continuously (The complete display value is scrolled) Analogue control for cooling/heating with PID loop. Iout1 Iout2 perform the control Process control parameters Internal buzzer (acoustic alarm) Hysterisis type alarm relay Serial data communication Alarms High alarm (Relay: NO) Alarm is triggered if PV2 value exceed upper limit value Hysterisis value of alarm relays Controller address for serial data communication Configuration 0 00001000 00000110 00000000 00000000 00000000 00000000 00000000 10000010 00000000 00000000

Code d.PAS d.nni d.Cnt d.Pid d.HSt d.AHS d.SEr d.AL1d.AL6 d.AL4 d.A h d.Adr
*

d.Yt Cycle time / valve actuating time for relay C1 (sec) d.YS Initial value of analogue valve control signal d.YL Minimum value of Iout1 (%) d.YH Maximum value of Iout1 (%) d.cYL Minimum value of Iout2 (%) d.cYH Maximum value of Iout2 (%) Note: * Serial number of alarm relays (AL1, AL2, AL3, AL4, AL5, and AL6)

0 0 0 100 0 100

4. Code C. in1 C.in2 C.out

Calibration Table C Definition 4 . 20.00 mA 4 . 20.00 mA - Range of Iout1: 4 20 mA 00001000 - Iout1 is the control output cY2 (cooling) 00000101 - Range of Iout2: 4 20 mA 10000000 - Iout2 is the control output Y1 (heating) 01000000 Recommended value* Rounding the last digit to even number PID parameters will slowly be defined in Auto tuning function Setting the offset of the IN1 analogue input Setting the cold junction compensation (OFFSET) Setting the lower limit of measuring range (Min. Range) Setting the Upper limit of measuring range (Max. Range) Setting the minimum value for the IN1 analogue input Setting the maximum value for the IN1 analogue input Setting the minimum value for the IN2 analogue input Setting the maximum value for the IN2 analogue input Setting the minimum value for the Iout1 analogue output (%) Setting the maximum value for the Iout1 analogue output (%) Setting the minimum value for the Iout2 analogue output Configuration 00011010 00011010 11001101

C.FLt C.nAt C.uSr C.OF1 C.Ofc C.SuL C.SuH C.i1L C.i1H C.i2L C.i2H C.o1L C.o1H C.o2L

00110000 00000001 00000010 0 0 0 40 0 6 0 40 0 100.0 0

C.o2H

(%) Setting the maximum value for the Iout2 analogue output

100.0

(%) Note: * If you are uncertain which filtering to use select this option