You are on page 1of 146

Soft Starter

PCS 7 Block Library for SIRIUS


Soft Starter 3RW44 V6.1 / V7.0 + SP1
Programming and Operating Manual

11/2010
Industrial Controls
Answers for industry.
PCS 7 block library for SIRIUS Soft
Starter 3RW44 V6.1/V7.0 + SP1

___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________

Industrial Controls
Soft starter
PCS 7 block library for SIRIUS Soft
Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual


11/2010
A5E02845977020-02
Introduction
1
Information about the library

2
Soft starter blocks

3
Module drivers of the soft
starter

4
3RW44 soft starter in the
Maintenance Station

5
CFC charts for 3RW44 soft
starter

6
Technical data

7
List of abbreviations

A


Legal information

Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.

CAUTION
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.

NOTICE
indicates that an unintended result or situation can occur if the corresponding information is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation for the specific task, in particular its warning notices and
safety instructions. Qualified personnel are those who, based on their training and experience, are capable of
identifying risks and avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be adhered to. The information in the relevant documentation must be observed.
Trademarks
All names identified by are registered trademarks of the Siemens AG. The remaining trademarks in this
publication may be trademarks whose use by third parties for their own purposes could violate the rights of the
owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.

Siemens AG
Industry Sector
Postfach 48 48
90026 NRNBERG
GERMANY
Order number: 3ZX1012-0CS16-1AC1
11/2010
Copyright Siemens AG 2010.
Technical data subject to change

PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 5
Table of contents

1 Introduction...................................................................................................................................9
1.1 General .................................................................................................................................... 9
1.2 Installing the library .................................................................................................................. 9
1.3 Configuration steps ................................................................................................................ 10
1.4 Handling the driver generator ................................................................................................. 10
1.5 Configuring in HW Config....................................................................................................... 12
1.6 Configuring in Soft Starter ES................................................................................................. 13
1.7 Further documentation ........................................................................................................... 14
2 Information about the library ......................................................................................................... 15
2.1 What's new?........................................................................................................................... 15
2.2 Faceplates ............................................................................................................................. 15
2.3 Block icons............................................................................................................................. 22
3 Soft starter blocks........................................................................................................................ 25
3.1 Overview of the blocks ........................................................................................................... 25
3.2 Error numbers........................................................................................................................ 26
3.3 Quality codes ......................................................................................................................... 27
3.4 SS_DIAG: Diagnostic block .................................................................................................... 28
3.4.1 Description............................................................................................................................. 28
3.4.2 Calling OBs............................................................................................................................ 29
3.4.3 Called blocks.......................................................................................................................... 29
3.4.4 Parameterization.................................................................................................................... 29
3.4.5 Diagnostic functions ............................................................................................................... 30
3.4.5.1 Diagnostics of acyclic events.................................................................................................. 30
3.4.5.2 Slave diagnostics of the 3RW44............................................................................................. 32
3.4.5.3 Diagnostics of upstream block................................................................................................ 37
3.4.6 Message features................................................................................................................... 38
3.4.7 Start-up characteristics........................................................................................................... 39
3.4.8 Interconnection of function blocks........................................................................................... 40
3.4.9 Block parameters ................................................................................................................... 41
3.5 SS_DIR: Signal block for direct starter control function............................................................ 43
3.5.1 Description............................................................................................................................. 43
3.5.2 Calling OBs............................................................................................................................ 44
3.5.3 Called blocks.......................................................................................................................... 44
3.5.4 Parameterization.................................................................................................................... 45
3.5.5 Operating modes.................................................................................................................... 47
3.5.6 Functions ............................................................................................................................... 49
3.5.6.1 Description............................................................................................................................. 49
3.5.6.2 Control ................................................................................................................................... 50
3.5.6.3 Monitoring.............................................................................................................................. 51
3.5.6.4 Trip reset................................................................................................................................ 52
Table of contents

PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
6 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.5.6.5 Slow speed .............................................................................................................................52
3.5.6.6 Emergency start ......................................................................................................................53
3.5.6.7 Lock........................................................................................................................................54
3.5.6.8 Diagnostics .............................................................................................................................55
3.5.6.9 QGRPERR: Group error..........................................................................................................58
3.5.6.10 QCURR: Current message......................................................................................................58
3.5.6.11 Process image input and process image output of 3RW44 soft starter .....................................59
3.5.6.12 Operator authorizations...........................................................................................................61
3.5.6.13 Output 1 and output 2..............................................................................................................62
3.5.6.14 Disable Quick Stop..................................................................................................................62
3.5.6.15 Logbook..................................................................................................................................63
3.5.6.16 Substitute value.......................................................................................................................67
3.5.6.17 Active parameter sets..............................................................................................................67
3.5.6.18 Reading and writing of data sets..............................................................................................68
3.5.6.19 Enabling measurement and statistics ......................................................................................69
3.5.7 Message features....................................................................................................................70
3.5.8 Start-up characteristics............................................................................................................71
3.5.9 Block parameters for the inputs ...............................................................................................72
3.5.10 Block parameters for inputs and outputs..................................................................................75
3.5.11 Block parameters for the Outputs ............................................................................................84
3.5.12 Faceplates ..............................................................................................................................88
3.5.12.1 General ...................................................................................................................................88
3.5.12.2 Standard View.........................................................................................................................89
3.5.12.3 Maintenance View...................................................................................................................91
3.5.12.4 Process Image View................................................................................................................92
3.5.12.5 Limits View..............................................................................................................................93
3.5.12.6 Parameters View.....................................................................................................................94
3.5.12.7 Parameters View and views for Parameter set 1 to Parameter set 3........................................95
3.5.12.8 Logbook View .........................................................................................................................99
3.5.12.9 Views: Station Diagnostics, Control Diagnostics, Device Diagnostics, and Parameter
Diagnostics ...........................................................................................................................100
3.5.12.10 Block icon ........................................................................................................................104
3.6 SS_MEAS: Measurement block.............................................................................................105
3.6.1 Description............................................................................................................................105
3.6.2 Calling OBs...........................................................................................................................106
3.6.3 Called blocks.........................................................................................................................106
3.6.4 Parameterization...................................................................................................................107
3.6.5 Operating modes...................................................................................................................107
3.6.6 Functions ..............................................................................................................................108
3.6.7 Message features..................................................................................................................110
3.6.8 Start-up characteristics..........................................................................................................111
3.6.9 Block parameters ..................................................................................................................112
3.6.10 Faceplates ............................................................................................................................114
3.7 SS_STAT: Statistics block.....................................................................................................119
3.7.1 Description............................................................................................................................119
3.7.2 Calling OBs...........................................................................................................................120
3.7.3 Called blocks.........................................................................................................................120
3.7.4 Parameterization...................................................................................................................121
3.7.5 Operating modes...................................................................................................................121
3.7.6 Functions ..............................................................................................................................122
3.7.7 Block parameters ..................................................................................................................123
3.7.8 Faceplates ............................................................................................................................125
Table of contents

PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 7
4 Module drivers of the soft starter ................................................................................................. 129
4.1 Object lists and action lists ....................................................................................................129
4.2 Requirements for generating the module drivers....................................................................129
4.3 Driver blocks .........................................................................................................................130
5 3RW44 soft starter in the Maintenance Station.............................................................................. 135
6 CFC charts for 3RW44 soft starter............................................................................................... 137
7 Technical data .......................................................................................................................... 141
7.1 Technical data.......................................................................................................................141
A List of abbreviations................................................................................................................... 143
A.1 Abbreviations ........................................................................................................................143
Table of contents

PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
8 Programming and Operating Manual, 11/2010, A5E02845977020-02

PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 9
Introduction
1
1.1 General
The PCS 7 library SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1 integrates 3RW44 soft
starter devices into the PCS 7 environment. The requirements of TIA (Totally Integrated
Automation) are thus met.
The software package PCS 7 block library SIRIUS Soft Starter 3RW44 V6.1/V7.0+ SP1
contains the following components:
Block library (function blocks and user interface) with:
Diagnostic block SS_DIAG
Signal blocks SS_DIR, SS_MEAS and SS_STAT
List Manual in German, English, and Portuguese
Online help in German and English
"Getting Started" in German and English
Installation program
Readme file for installation
1.2 Installing the library
Starting the installation
1. Place the CD in the CD-ROM drive of your PG/PC.
2. Launch the "setup.exe" program.
All the other information you need will be provided during the installation process.

Note
Readme file
Note the information in the readme file.

Introduction
1.3 Configuration steps
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
10 Programming and Operating Manual, 11/2010, A5E02845977020-02
1.3 Configuration steps
Procedure
1. Configuring with HW Config
2. Make the necessary interconnections for the inputs and outputs in the CFC Editor
In so doing, all of the inputs and outputs used must be within the process image.
3. Compile the CFC chart using the "Generate Module Driver" function.
1.4 Handling the driver generator
The "Generate Module Driver" function is available for signal processing in PCS 7. Once the
hardware has been configured in HW Config and the technological functions have been
configured in the CFC, this function automatically generates, interconnects, and
parameterizes the required module drivers. These module drivers are responsible for
diagnosing and reporting errors during signal processing.
The Setup program installs XML files for the connection between the 3RW44 soft starter and
the driver generator.
Supported modules and configurations
The driver concept for the 3RW44 soft starter includes operation of the soft starter:
As a DP slave directly on the DP master system
The connection is made by means of the GSD file.
As a DP slave following a Y link
DPV1 or DPV0 is possible depending on the version of the communication module used.
Introduction
1.4 Handling the driver generator
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 11
More information
Additional information regarding GSD files is available in the "SIRIUS 3RW44 Soft Starter"
System Manual > Chapter "Configuration with the GSD File".
1. The GSD files for the 3RW44 soft starter are available for download on the Internet. To
download, go to:
GSD files (http://support.automation.siemens.com)
2. Enter the following search term in the "Product Name or Part Number" field under
"Search Product Support Documents:
3RW44*BC* GSD
3. Under Downloads click the relevant entry, e.g., "PROFIBUS GSD files: Switchgears".
4. This displays another Internet page where you can download the GSD files.
Purpose of the driver generator
A signal-processing block is inserted in the CFC for each soft starter, and the connection to
the hardware is established using symbolic addressing. You assign this address in
HW Config of SIMATIC Manager. For detailed information on this, refer to the online help in
"Getting Started".
The "Generate Module Driver" option inserts the additionally required OB_DIAG1 and
SS_DIAG blocks and then connects and assigns the corresponding parameters.
See also
Object lists and action lists (Page 129)
Requirements for generating the module drivers (Page 129)
Driver blocks (Page 130)
Introduction
1.5 Configuring in HW Config
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
12 Programming and Operating Manual, 11/2010, A5E02845977020-02
1.5 Configuring in HW Config
The 3RW44 soft starter along with its associated components and GSD file are inserted and
configured in HW Config.

Note
The following diagrams show example configurations to illustrate configuring in HW Config.

DP slave directly on the DP master system
3RW44 soft starter
Profibus DP
ES OS
E
m
p
t
y

s
l
o
t
E
m
p
t
y

s
l
o
t
C
P

5
6
1
3
A
2
C
P

1
6
1
3
C
P

4
4
3
-
1
6
E
S
7
4
4
3
-
1
E
X
1
1
-
0
X
E
0
P
S

4
0
7

1
0
A
3
R
W
4
4
3
R
W
4
4
2
2
-
1
B
C
3
4
C
P

3
R
W
4
9
0
0
-
0
K
C
0
0
C
P
U

4
1
6
-
3

D
P
6
E
S
7
4
1
6
-
3
X
L
0
4
-
0
A
B
0
AS-3 AS416-3DP

Figure 1-1 DP slave directly on the DP master system
Introduction
1.6 Configuring in Soft Starter ES
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 13
DP slave following a Y link
3RW44 soft starter
Y link
Profibus DP
Redundant Profibus DP
ES OS
E
m
p
t
y

s
l
o
t
E
m
p
t
y

s
l
o
t
E
m
p
t
y

s
l
o
t
E
m
p
t
y

s
l
o
t
E
m
p
t
y

s
l
o
t
E
m
p
t
y

s
l
o
t
E
m
p
t
y

s
l
o
t
E
m
p
t
y

s
l
o
t
DP DP
G
N
L1
CPU 417-H
C
P

5
6
1
3
A
2
C
P

1
6
1
3
G
N
L1
C
P
U

4
1
7
-
4
H
C
P

4
4
3
-
1
P
S

4
0
7

1
0
A
P
S

4
0
7

1
0
A
C
P
U

4
1
7
-
4
H
C
P

4
4
3
-
1
3
R
W
4
4
3
R
W
4
4
2
2
-
1
B
C
3
4
C
P

3
R
W
4
9
0
0
-
0
K
C
0
0
6
E
S
7
1
5
3
-
2
B
A
8
2
-
0
X
B
0
l
M
1
5
3
-
2
6
E
S
7
1
5
3
-
2
B
A
8
2
-
0
X
B
0
l
M
1
5
3
-
2
6
E
S
7
1
9
7
-
1
L
B
0
0
-
0
X
A
0

Figure 1-2 DP slave following a Y link
1.6 Configuring in Soft Starter ES
You can connect Soft Starter ES via the COM interface with 3UF 7940-0AA00-0 PC CABLE,
FOR PC/PG COMMUNICATION.
Soft Starter ES - automation system AS
Soft Starter ES takes precedence over the automation system (AS) in order to switch control
over to Manual operation LOCAL mode. If you use this application, you must switch the
control of the PLC back to Auto mode.
Introduction
1.7 Further documentation
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
14 Programming and Operating Manual, 11/2010, A5E02845977020-02
1.7 Further documentation
Overview
For additional information, refer to:
"SIRIUS 3RW44 Soft Starter" System Manual
"Getting Started" in the online help for this block library
Online help for SIMATIC Process Control System PCS 7
Manuals for SIMATIC Process Control System PCS 7

PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 15
Information about the library
2
2.1 What's new?
Function extensions / function changes with the SP1
The following innovations are included in the SP1:
The software has also been released for the PCS 7 V7.1
Extension of the "Generate module driver" CFC function,so that fewer manual
interconnections in the CFC are necessary. Only the inputs and outputs of the device
have to be interconnected.
In the standard view, the motor current is now displayed as a percentage of the setting
current (% of Ie)
The group display to the block can now be arranged in user-defined mode. There are four
options to choose from.
The alarm view can be called up directly to the group display of the relevant block by
right-clicking.
A new view can be opened up in a separate window.
By right-clicking on a view in the view list of an image block, you can open the view in
parallel in a separate window.
The "Back to Process Picture" button is offered in the faceplates to be able to jump back
to the original process image.
2.2 Faceplates
A faceplate displays all elements of a block graphically. The faceplate is displayed in a
separate window on the Operator Station (OS). You can call the faceplate:
Using picture selection keys
From the process tag list
By clicking the specific block symbol
Information about the library
2.2 Faceplates
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
16 Programming and Operating Manual, 11/2010, A5E02845977020-02
Tools
The following software and templates are available for configuring the faceplates:
In WinCCExplorer: the Graphics Designer
Templates available from the Faceplate Designer
PCS 7-specific standard views
Trend
Batch
Alarms
Additionally required views, user objects, and functions
Additional information:
You are recommended not to open the PCS 7 Soft Starter SP1 faceplate graphics files
(*.pdl) in PCS 7 V7.1. Additional information
Information about the library
2.2 Faceplates
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 17
Typical structure of a faceplate
The file name of the faceplate is structured as follows:
"@<PG>_<XXX>_<YYY>.pdl"
Table 2- 1 Meaning of tags
Tag Replaced with
<PG> PG for block-specific elements
PCS7 for elements provided by PCS 7
<XXX> Name of block, e.g., SS_DIR
<YYY> A specific element, e.g., STANDARD for the Standard View.
4
1
5
7 6
2
3

Title + Name of starter
Pinning the faceplate:
You can use this button to secure the faceplate when switching the range.
"Back to Process Picture" button:
This can be used to jump back to the original process picture
Name of block
"Open Loop" button:
Object for selecting the loop picture. The Faceplate Designer automatically hides this object, if
generation or update of the Loop View was not selected there.
Overview window
Dropdown menu for selecting the view
Right clicking on an entry in the view list opens the selected view in a separate window
Figure 2-1 Example of the header structure of a faceplate
Information about the library
2.2 Faceplates
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
18 Programming and Operating Manual, 11/2010, A5E02845977020-02
The overview window
The overview window is a constituent part of the root screen, such as a faceplate. It indicates
the overall status of the block, e.g.:
Unacknowledged alarms
Status of warnings
LOCK status of messages
Status of acknowledgement of messages

The overview window is contained in the following file:
"@PG_<XXX>_OVERVIEW.pdl"
1 2 3 4 5

EventState - Group display:
Indicates whether unacknowledged alarms and warnings are pending.
EventState - Status LOCK of messages:
This function is available to users with authorization level 5 and higher
EventState - Message acknowledgment
This function is available to users with authorization level 5 and higher.
M_SUP_C - Message suppression
OCCUPIED:
This function indicates whether the block instance of SIMATIC BATCH is occupied.
Figure 2-2 Typical toolbar of a faceplate
Information about the library
2.2 Faceplates
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 19
The Trend View
The Trend View is available in all signal blocks in which parameter curves are generated in
online mode, e.g., for the current.

Figure 2-3 Example: Trend View

File name: @PCS7_SS_Trend.pdl
Integrating a curve in a faceplate:
Parameterize the ReturnPath and StandardTrend properties for the block symbol.
Information about the library
2.2 Faceplates
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
20 Programming and Operating Manual, 11/2010, A5E02845977020-02

Property Inputs Example Meaning
ReturnPath .<ZZZ> .OCUR Name of structure element starting with a dot
: : Separator
<VVV> CO_GREEN Color of the curve
StandardTrend 2 Online values with 5-minute time axis
> 2 Archive values with time axis of the entered value in min
Example:
.OCUR:CO_GREEN
Displaying multiple curves:
If multiple curves are to be displayed in the Trend View, parameterize the curves using the
following scheme:
.<Name of structure element 1>:< Color of the curve>,.<Name of structure element 2>:<
Color of the curve>,<Name of structure element 3>:< Color of the curve>
Example:
.QIL1:CO_DKRED,.QIL2:CO_DKBLUE,.QIL3:CO_DKGREEN
The Alarm View
The Alarm View is available in all signal blocks in which a list of all alarms and warnings is
displayed. This view can be selected via the dropdown view list of the relevant block or by
right-clicking on the group representation of the associated block symbol. The list displays
the following for each alarm and warning:
Date
Time of day
Status

Figure 2-4 Example: Alarm View
Information about the library
2.2 Faceplates
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 21
Batch View
The Batch View is available in all signal blocks in which the status of batch parameters is
displayed.
2
1
3
4
5

BA_EN Batch control: indicates the Enabled status
OCCUPIED Batch control: indicates the Occupied status
BA_NA Shows the name of the batch.
STEP_NO Shows the step number of the batch.
BA_ID Shows the identification number of the batch.
Figure 2-5 Example: Batch View of a block
See also
General (Page 88)
Faceplates (Page 114)
Faceplates (Page 125)
Information about the library
2.3 Block icons
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
22 Programming and Operating Manual, 11/2010, A5E02845977020-02
2.3 Block icons
The block symbols are contained in the following file:
"@PCS7Typicals_SS.pdl"
Structure
Each block has four assigned block symbols. The different block symbols of the soft starters
are displayed as follows:

If you click the block symbol, the associated faceplate opens. As long as the faceplate is
open, the block symbol is highlighted in color.
The user can configure the block symbol in CFC within the scope of the available selection
via the block symbol number in the object properties of the block.



Information about the library
2.3 Block icons
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 23
1
2
3
4
5
7
6

Block symbol number
If you click the block symbol, the associated faceplate opens. As long as the faceplate is open,
the block symbol is highlighted in color
Indicates the enable for the lock of the block.
"L" on white background: LOCK or LOCK_ON
Indicates the operating mode of the block:
"M" on white background = Manual
"A" on green background = Auto
Indicates the operating mode:
"L" on white background = Manual operation LOCAL
"R" on white background = Remote
Header: displays the name of the tag
Indicates the status of the motor: VSTATUS.

e.g.: symbol RUN CW

Symbol RUN CCW

Symbol STOP
The symbol flashes when the motor is in the startup or coast-down phase.
Group display
Reads the message configuration of the block and displays alarms and warnings.
Figure 2-6 Structure of a block symbol
Right-clicking on the group representation of the block symbol opens the Alarm View of the
block.
See also
General (Page 88)
Faceplates (Page 114)
Faceplates (Page 125)
Information about the library
2.3 Block icons
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
24 Programming and Operating Manual, 11/2010, A5E02845977020-02

PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 25
Soft starter blocks
3
3.1 Overview of the blocks
The PCS 7 Library for SIRIUS Soft Starter 3RW44 contains the following blocks:
Table 3- 1 List of blocks
Block Name of block Block type and
number
Description
Diagnostic block SS_DIAG FB 561 This block performs the diagnostics of the
3RW44 soft starter. In this processes, it acquires
all diagnostic information regarding controlling,
switching, parameters, and communication.
Signal block for direct starter
control function
SS_DIR FB 562 The block controls, monitors, and switches the
soft starter in the clockwise or counter-clockwise
direction.
This block supports:
Various control functions
Various faceplates with block icon for
operation and control
Measurement block SS_MEAS FB 564 This block provides measurement information,
e.g., regarding phase currents, output power,
phase-to-phase voltages, line frequency
Statistics block SS_STAT FB 563 This block provides statistical information, e.g.,
regarding the operating hours of the device, fault
statistics, maximum pointer
Soft starter blocks
3.2 Error numbers
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
26 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.2 Error numbers
Overview
Table 3- 2 Error numbers per block
Error number Error type Description SS_DIAG SS_DIR SS_MEAS SS_STAT
-1 Default value X X X X
0 No error X X X X
1 System error Rack failure

X X X X
2 System error The module
does not
respond.
X X X
3 System error The module
has been
removed.

4 System error Error in
subnet 1 or in
subnet 2
X
11 Programming
error
LOCK_ON /
LOCK_DIR
command error
X
"X" = Error occurs in this block. "" = Error does not occur in this block.
Soft starter blocks
3.3 Quality codes
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 27
3.3 Quality codes
The quality code is used to check the status and quality of a rack.
Overview
Table 3- 3 Quality codes per block
Quality code Priority
1)
Occurs in Description SS_DIAG SS_DIR SS_MEAS SS_STAT
QRACKF Rack failure
QMODF Module failure
16#00 3
QBUSFLT Failure of a
PROFIBUS DP
station
X X
16#24 2 QRACK1ERR
or
QRACK2ERR
OB is not
loaded
Incorrect quality
code
2)


16#60 1 QSIM Simulation
16#80 0 No error Correct quality code X X X X
"X" = Quality code occurs in this block. "" = Quality code does not occur in this block.
1) "0" = low; "> 0" = high
2) Device-specific
Soft starter blocks
3.4 SS_DIAG: Diagnostic block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
28 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.4 SS_DIAG: Diagnostic block
3.4.1 Description

Block type and number: FB 561
Product group: 3RW44
Purpose of block
The SS_DIAG block performs the diagnostics of the 3RW44 soft starter:
It evaluates the acyclic events that are relevant for the 3RW44 soft starter:
Startup
DP station failure
Module error
Diagnostic interrupt
It evaluates the diagnostics of the upstream block, e.g.:
RACKF: Failure of the master system rack
SUBN1ERR, SUBN2ERR: Subnet error
It generates the associated quality codes.
It reads all diagnostic information of the soft starter
It transfers the diagnostic information to the SS_DIR and SS_MEAS blocks for display in
these blocks.
See also
Technical data (Page 141)
Error numbers (Page 26)
Quality codes (Page 27)
Module drivers of the soft starter (Page 129)
3RW44 soft starter in the Maintenance Station (Page 135)
Soft starter blocks
3.4 SS_DIAG: Diagnostic block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 29
3.4.2 Calling OBs
The "Generate Module Driver" function automatically inserts the block into the following
organization blocks within the run sequence of the CFC:
Table 3- 4 Organization blocks that call the SS_DIAG block
Organization block Description
OB 1 Cyclic program
OB 82 Diagnostic interrupt
OB 85 Priority class error
OB 86 Rack failure
OB 100 Warm restart
3.4.3 Called blocks
The block calls the following blocks:
Table 3- 5 Blocks called by the SS_DIAG block
Block Description
SFB 35 ALARM_8P Generates block-specific messages with values for eight
signals
SFB 52 RDREC Reads a process data set
SFB 54 RALRM Receives the alarm data
SFC 13 DPNRM_DG Reads the diagnostic data of the DP slave
SFC 51 RDSYSST Reads the system status list or the sublist
SFC 6 RD_SINFO Reads the start information of the OB
SFC 64 TIME_TCK Reads the system time
3.4.4 Parameterization
Addressing
The "Generate Module Driver" function assigns all addresses to the SS_DIAG block, for
example:
LADDR
DADDR
RACK_NO
SLOT_NO
SUBN1ID
SUBN_TYP
Soft starter blocks
3.4 SS_DIAG: Diagnostic block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
30 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.4.5 Diagnostic functions
General
This block executes the following diagnostic functions:
Acyclic events:
Rack failure
QMODF: Module error
QERR: Priority class error - Malfunction when loading the organization blocks (OB)
Slave diagnostics:
QBUSFLT: Failure of a PROFIBUS DP station
OB_DIAG1: Diagnostics of upstream block
3.4.5.1 Diagnostics of acyclic events
QRACK: Rack failure
The upstream OB_DIAG1 block detects the failure of the DP master or DP slave and
evaluates it by means of the following outputs:
RACKF
SUB1ERR
SUB2ERR
Interrupt OB 86 detects the failure of the rack.
Table 3- 6 Conditions under which QRACK = 1 is set
Error Status at inputs and outputs
Failure of expansion rack OB86_EV_CLASS = B#16#39 AND
OB86_FLT_ID = B#16#C1
Supported I/O devices:
Failure of a DP master
OB86_EV_CLASS = B#16#39 AND
OB86_FLT_ID = B#16#C3
Failure of a PROFIBUS DP station OB86_EV_CLASS = B#16#39 AND
OB86_FLT_ID = B#16#C4
Fault on a PROFIBUS DP station OB86_EV_CLASS = B#16#39 AND
OB86_FLT_ID = B#16#C5

Soft starter blocks
3.4 SS_DIAG: Diagnostic block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 31
Table 3- 7 Conditions under which QRACK is reset
Error Status at inputs and outputs
Failure of expansion rack OB86_EV_CLASS = B#16#38 AND
(OB86_FLT_ID = B#16#C1 OR OB86_FLT_ID = B#16#C2)
Failure of a PROFIBUS DP station OB86_EV_CLASS = B#16#38 AND
OB86_FLT_ID = B#16#C4
Fault on a PROFIBUS DP station OB86_EV_CLASS = B#16#38 AND
OB86_FLT_ID = B#16#C5
Return of a PROFIBUS DP station, but error in assigning the
module parameters
OB86_EV_CLASS = B#16#38 AND
OB86_FLT_ID = B#16#C7
Return of a PROFIBUS DP station, but discrepancy
between the parameterized and current configuration
OB86_EV_CLASS = B#16#38 AND
OB86_FLT_ID = B#16#C8
When an error occurs, OMODE=16#40xxxxxx is assigned for the value of the OMODE
output.
If the "Rack failure" error QRACKF=1 occurs, the connection between the PROFIBUS and
the device is canceled. This is indicated as follows: QBUSFLT=1.
QMODF: Module error
LADDR addresses a module. Following a restart of the CPU and when ACC_ID=TRUE, this
module is checked. The system status list (SSL) ID xC91 is read out for this purpose.
Temporary errors are detected by reading the system status. These are listed in the
following table. The RDSYSST (SFC51) system function indicates this error as module error
QMODF.
Table 3- 8 Temporary module errors
Error number Description
8085 No information currently available due to a problem in the system, e.g.,
lack of operating resources.
80A2 Temporary error in PROFIBUS DP protocol, layer 2
80A3 Temporary error in PROFIBUS DP protocol with user interface or user.
80A4 Communication problem on the communication bus:
The error occurs between the CPU and the external PROFIBUS DP
interface.
80A5 Temporary error: The distributed I/O is not available.
When an error occurs, OMODE=16#40xxxxxx is assigned for the value of the OMODE
output.
Soft starter blocks
3.4 SS_DIAG: Diagnostic block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
32 Programming and Operating Manual, 11/2010, A5E02845977020-02
QERR: Priority class error - Malfunction when loading the OB
Interrupt OB 85 sets or resets the priority class error QERR - Malfunction when loading OBs
for the following events:
Table 3- 9 Events during which OB 85 QERR is reset
Description Status at inputs and outputs
Error when creating a start event for an OB.
This is not loaded to the CPU.
OB86_EV_CLASS = B#16#35AND
(OB86_FLT_ID = B#16#A1 OR A2)
Error when the operating system accesses a module. OB86_EV_CLASS = B#16#35 AND
(OB86_FLT_ID = B#16#A1 OR A3)
QERR is only triggered once for one execution cycle of the block.
3.4.5.2 Slave diagnostics of the 3RW44
The following system function and diagnostic interrupt calls read the diagnostic information
of the 3RW44 slave.

Block Description
SFC 13 DPNRM_DG Reads the diagnostic data of the PROFIBUS DP slave
SFB 52 RDREC If diagnostic interrupt 82 occurs, this block reads a process
data set.
SFC 64 TIME_TCK Reads the system time
Diagnostic messages that relate to communication and operation are read:
Cyclically every 5 seconds
If interrupt OB 82 occurs.
This diagnostic information is mapped onto the QDIAG_DIR and QDIAG_MEAS output
parameters. These parameters are interconnected with the SS_DIR and SS_MEAS blocks.
The information from the station diagnostics of the PROFIBUS DP slave is read out using
SFC 13 DPNRM_DG.
Table 3- 10 Status of the station
Number of the bus node Byte containing the diagnostic information
1 Byte 0
2 Byte 1
3 Byte 2
Soft starter blocks
3.4 SS_DIAG: Diagnostic block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 33
DIAG_DIR
DIAG_DIR is a structured characteristic map that provides the following information.
Table 3- 11 Diagnostic information in DIAG_DIR.DIAG for each bit
DIAG_DIR.DIAG bit Diagnostic message
0 DP slave cannot be accessed by DP master.
1)

1 DP slave is not yet ready for data exchange.
2 Config data to DP slave from DP master does not match.
3 External diagnostics pending (Group diagnostics display)
4 Function not supported by DP slavee.g., node address change by the
software
5 DP master cannot interpret DP slave response.
6 DP slave type does not match software config.
7 DP slave parameterized by a different DP master
8 DP slave parameters must be reassigned.
9 Static diagnostic message:
A diagnostics message is pending. DP slave will not function until the
error is corrected.
10 Bit is set to "1" as long as DP slave address exists.
11 Watchdog function activated for DP slave
12 DP slave has received "FREEZE" command.
13 DP slave has received "SYNC" command.
14 DP slave has been deactivated, e.g., it is not included in the current
processing.
15 More diagnostic messages than DP slave can store.
The DP master cannot write all diagnostic messages to its diagnostic
buffer that were sent by the DP slave.
16 31 Not used
1) The lost connection is signaled with QBUSFLT and as an alarm in WinCC. See also:
QBUSFLT: Failure of a PROFIBUS DP station (Page 37)
Various other diagnostic information are mapped onto DIAG_DIR, e.g., information on:
Communication
Parameters
Switching
Control
Soft starter blocks
3.4 SS_DIAG: Diagnostic block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
34 Programming and Operating Manual, 11/2010, A5E02845977020-02
Table 3- 12 DIAG_DIR parameters
Parameter Data format Message Diagnostic type
DIAG
1)
DWORD 3RW44 PROFIBUS DP slave diagnostics Station diagnostics
BUSERR BOOL Bus error
CPUMSTRSTOP BOOL CPU/master Stop
AUTOPLCCNTRL BOOL Automatic mode (CPU controls)
MANBUSCNTRL BOOL Manual operation bus, OCM controls
MANLOCCNTRL BOOL Manual operation LOCAL
CONNBRK BOOL Connection break in local mode
PIERROR BOOL Process image error
MANBUSPCCNT BOOL Manual operation bus, PC controls
MANLOCINCNT BOOL Manual operation LOCAL - input controls
MANLOCOMCNT BOOL Manual operation LOCAL - OCM controls
MANLOCPCNT BOOL Manual operation LOCAL - PC controls






Communication
CNTOVLD BOOL Contact block overload
CNTDMAG BOOL Contact block defective
NOMAINPWR BOOL No supply voltage
STRTMODACT BOOL Starting active
STPMODACT BOOL Coast-down active
ELEBRKACT BOOL Electrical braking active
SLWSPDACT BOOL Slow speed active
CTRLINPUT BOOL Input control
QCKSTPACT BOOL Quick stop active
ELEVLTHI BOOL Electronics supply voltage too high
ELEVLTLO BOOL Electronics supply voltage too low
RDYMOTON BOOL Ready for motor ON
CNTSHRT BOOL Contact block short-circuited
BYPPRTFLT BOOL Bypass element defective
SWELE1FAIL BOOL Contact block 1 failed
SWELE2FAIL BOOL Contact block 2 failed
SWELE3FAIL BOOL Contact block 3 failed













Switching and controlling
Soft starter blocks
3.4 SS_DIAG: Diagnostic block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 35
Parameter Data format Message Diagnostic type
FACTSETRSTR BOOL Factory settings restored
FLTPARLB BYTE Incorrect parameter number
(least significant byte)
FLTPARHB BYTE Incorrect parameter number
(most significant byte)
IMPERCLASS BOOL Impermissible Ie / CLASS settings
PSACTIVE BOOL Parameter assignment active
PS1ACTIVE BOOL Parameter set 1 active
PS2ACTIVE BOOL Parameter set 2 active
PS3ACTIVE BOOL Parameter set 3 active
IMPCHNGPS BOOL Parameter set change impermissible
INCORPSVAL BOOL Invalid parameter value
PSPERMIT BOOL Parameter changes not permissible when
ON
PSDISCPUACT BOOL Parameters disabled CPU/master active
MOTHEATACT BOOL Motor heating active
DCBRKACT BOOL DC braking active
DYNDCBRK BOOL Dynamic braking active
CONSTDELT BOOL Motor connection type start/delta
CONINSDDELT BOOL Motor connection type inside delta
CONUNKWN BOOL Motor connection type unknown
NOLOAD BOOL No load
PHS1LOSS BOOL Phase failure L1
PHS2LOSS BOOL Phase failure L2
PHS3LOSS BOOL Phase failure L3
LIPHDIR BOOL Line phase direction right
LIPHREV BOOL Line phase direction left
OUT1ACT BOOL Output 1 active
OUT2ACT BOOL Output 2 active
OUT3ACT BOOL Output 3 active
TRPRSTCARID Trip reset successful
TRPRSTNOTPOS BOOL Trip reset unsuccessful
MAXPNTRDEL BOOL Maximum pointer reset
















Parameter
1) This station diagnostics information is mapped onto the QDIAG.DIAG parameter as shown above.
Soft starter blocks
3.4 SS_DIAG: Diagnostic block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
36 Programming and Operating Manual, 11/2010, A5E02845977020-02
DIAG_MEAS
DIAG_MEAS is a structured characteristic map that provides the following information.
Table 3- 13 DIAG_MEAS parameters
Parameter Data format Meaning Diagnostic type
TMPSNSOVLD BOOL Temperature sensor overload
TMPSNSOPEN BOOL Temperature sensor wire break
TMPSNSSHORT BOOL Temperature sensor short-circuit
TMMOVLD BOOL Thermal motor model overload
OVLDSWOFF BOOL Overload switch off
IDLETMACT BOOL Idle time active
COOLDNTMACT BOOL Cooling time active
ASYMREC BOOL Asymmetry detected
ASYMSWOFF BOOL Asymmetry tripping
CURHI BOOL Current limit overshot
CURLO BOOL Current limit undershot
CURLMSWOFF BOOL Ie limit value tripping
MOTSTLSWOFF BOOL Motor block tripping
INPUT1 BOOL Input 1 active
INPUT2 BOOL Input 2 active
INPUT3 BOOL Input 3 active
INPUT4 BOOL Input 4 active
GNDFLT BOOL Ground fault
GNDFLTSWOFF BOOL Ground fault tripping
TMMDEACT BOOL Thermal motor model deactivated
PHANGCTRFLT BOOL Generalized phase error
COOLCNTACT BOOL Contact block cooling time active
CTNHOTSTART BOOL Contact block too hot for start
CUROVERFLOW BOOL Current measuring range exceeded
PREWRNUNDSHT BOOL Prewarning limit - prewarning time undershot
PREWRNHTEXED BOOL Prewarning limit - motor heating overshot












Protective function
motor/cable/short-circuited
Soft starter blocks
3.4 SS_DIAG: Diagnostic block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 37
QBUSFLT: Failure of a PROFIBUS DP station
QBUSFLT
DIAG_DIR.DIAG Bit 0 indicates QBUSFLT.
Table 3- 14 Possible reasons for the connection error
Byte 0 Meaning Reason or remedy
Bit 0 1: DP slave cannot be accessed by DP master. Is the station address of the DP slave set
correctly?
Is the bus connector connected?
Is voltage applied to the DP slave?
Is the RS 485 Repeater secured correctly?
Has a reset been performed on the DP
slave?
See also
Slave diagnostics of the 3RW44 (Page 32)
3.4.5.3 Diagnostics of upstream block
OB_DIAG1
The upstream OB_DIAG1 block detects the module failure. The module failure calls the
RACKF parameter and outputs QRACKF parameter sets.
See also
Handling the driver generator (Page 10)
Soft starter blocks
3.4 SS_DIAG: Diagnostic block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
38 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.4.6 Message features
Messages
The diagnostic block outputs the messages via WinCC.
Table 3- 15 Output messages
Input
parameter
Message
no.
Parameter Message Message
class
1 QRACK1ERR $$BlockComment$$Subnet1@1%d@:fault S
2 QRACK2ERR $$BlockComment$$Subnet2@2%d@:fault S
3 QRACKF $$BlockComment$$DP Slave @3%d@: failure S
4 QMODF $$BlockComment$$DP Slave
Rack@3%d@/Module@4%d@: Module error
S
5 QBUSFLT $$BlockComment$$DP Slave Rack@3%d@:not
reachable
S
6 MSG_6
1)
$$BlockComment$$ Message Input 6 A
7 MSG_7
1)
$$BlockComment$$ Message Input 7 A
MSG_EVID
2)

8 MSG_8
1)
$$BlockComment$$ Message Input 8 A
1) The MSG_6, MSG_7 and MSG_8 parameters represent messages that can be user-configured.
2) Parameters with message number for ALARM_8P.

Soft starter blocks
3.4 SS_DIAG: Diagnostic block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 39
Table 3- 16 Structure of the related values in ALARM_8P
Message
no.
Related value Parameter Meaning
1 1 SUBN1_ID Number of the DP master system (primary)
2 2 SUBN2_ID Number of the DP master system (redundant)
3 3 RACK_NO Rack/station number
4 4 SLOT_NO Slot number
5 5 AUX_PR05
1)
Auxiliary value 5
6 6 AUX_PR06
1)
Auxiliary value 6
7 7 AUX_PR07
1)
Auxiliary value 7
8 8 AUX_PR08
1)
Auxiliary value 8
9 9 AUX_PR09
1)
Auxiliary value 9
10 10 AUX_PR010
1)
Auxiliary value 10
1) The AUX_PR05 bis AUX_PR010 parameters represent auxiliary values for messages that can be user-configured.
The QMS_STAT, QMSG_ACK and QMSG_ERR parameters transfer the information found
in ALARM_8P:
Status of messages
Status of an alarm acknowledgement
Status of errors during data transfer
See also
Block parameters (Page 41)
3.4.7 Start-up characteristics
Description
The identifier for startup is OMODE=16#xx01xxxx. It is entered in OB 100 in the OMODE
output.
All alarm messages are suppressed in OB 100:
The user defines a value for RUNUPCY. This is assigned to OB 100 in order to suppress the
messages for the configured cycle count.
OB 100 resets the following errors:
QERR
QRACKF
QMODE
QRACK1ERR
QRACK2ERR
Soft starter blocks
3.4 SS_DIAG: Diagnostic block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
40 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.4.8 Interconnection of function blocks
SS_DIR
Function block for
3RW44 soft starter
SS_MEAS
Function block for
3RW44 soft starter
SS_DIAG
Diagnostic
function
block
SS_STAT
Function block for
3RW44 soft starter
User configuration System configuration
RAC_DIAG
MODE
MODE
OMODE
MOD_PAX0
RACKF
OMODE
QUALITY
PA_DIAG
QMODF
EN_DIAG
SUBN2ERR
SUBN1ERR
QRACKF
OB_DIAG1
RAC_DIAG
EN_F
LADDR
DADDR
DIAG_MEAS
DIAG_DIR
DIAG_MEAS
DIAG_DIR
SUBSLOT_NO
SUBN_TYP
SUBN1_ID
SUBN2_ID
RACK_NO
SLOT_NO
SUBN1ERR
SUBN2ERR
QRACKF
MODE
IN_01 OUT_01

Figure 3-1 Interconnection of function blocks
See also
CFC charts for 3RW44 soft starter (Page 137)
Soft starter blocks
3.4 SS_DIAG: Diagnostic block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 41
3.4.9 Block parameters
Table 3- 17 Parameters of the SS_DIAG block
Name of
parameter
Data format Type Default value Meaning
AUX_PR05 ANY Input Auxiliary value 5
AUX_PR06 ANY Input Auxiliary value 6
AUX_PR07 ANY Input Auxiliary value 7
AUX_PR08 ANY Input Auxiliary value 8
AUX_PR09 ANY Input Auxiliary value 9
DADDR INT Input 0 Diagnostic address of module
DPA_LINK BOOL Input FALSE Device connection:
1 = DP master
2 = Y link
EN_DIAG BOOL Input TRUE 1 = Enable: Reading of diagnostic data
MODE WORD Input 16#00 SS_DIAG OMODE
MSG_6 BOOL Input FALSE Message input 6
MSG_7 BOOL Input FALSE Message input 7
MSG_8 BOOL Input FALSE Message input 8
MSG_EVID DWORD Input 16#FF Number of the message event
RACK_NO INT Input 0 Address of DP slave
RACKF BOOL Input FALSE 1 = Rack failure
RUNUPCYC INT Input 3 Number of the cycle for which all messages are
suppressed.
SLOT_NO INT Input 0 Slot number
SUBADDR INT Input 0 Subaddress
SUBN_TYP BOOL Input FALSE 1 = External DP interface
SUBN1_ID BYTE Input 16#FF Number of the primary DP master system
SUBN1ERR BOOL Input FALSE 1 = Slave
2 = Failure
SUBN2_ID BYTE Input 16#FF Number of the redundant DP master system
SUBN2ERR BOOL Input FALSE 1 = Slave
2 = Failure
SUBSLOT_NO INT Input 0 Signal module:
Address of channel
ACC_ID BOOL ON/OFF TRUE 1 = Accept new operating mode settings
LADDR WORD ON/OFF 16#0000 Logical address of soft starter
DIAG_DIR SSDIAGDIR* Outputs Diagnostic information to SS_DIR block
DIAG_MEAS SSDIAGMEAS* Outputs Diagnostic information to SS_MEAS block
ERRORNUM INT Outputs - 1 Error number
OMODE DWORD Outputs 16#00 Status
QBUSFLT BOOL Outputs FALSE 1 = The PROFIBUS connection to the DP slave
has failed
QEN_RD BOOL Outputs FALSE 1 = Enable: Reading of data sets
Soft starter blocks
3.4 SS_DIAG: Diagnostic block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
42 Programming and Operating Manual, 11/2010, A5E02845977020-02
Name of
parameter
Data format Type Default value Meaning
QERR BOOL Outputs FALSE 1 = Group error
QERR_RD BOOL Outputs FALSE 1 = Error while reading the data set
QMODF BOOL Outputs FALSE 1 = Module failure
QMSG_ACK WORD Outputs 16#00 ALARM_8P:
ACK_STATE output
QMSG_ERR BOOL Outputs FALSE 1 = Error during data transfer
QMSG_STAT WORD Outputs 16#00 ALARM_8P:
Status of outputs
QRACK1ERR BOOL Outputs FALSE 1 = Failure of DP slave system
(primary master)
QRACK2ERR BOOL Outputs FALSE 1 = Failure of DP slave system (redundant
master)
QRACKF BOOL Outputs FALSE 1 = Rack failure
QUALITY BYTE Outputs 16#80 Quality code
* = These parameters are structured labels that obtain information from data set 92.

Table 3- 18 Structure of OMODE
Byte Value Meaning
16#80 Valid data
16#40 Invalid data
3
16#20 Redundancy failure
Primary error
2 16#01 Startup OB 100
1; 0 16#0000
See also
Message features (Page 38)
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 43
3.5 SS_DIR: Signal block for direct starter control function
3.5.1 Description

Block type and number: FB 562
Product group: 3RW44
Purpose of block
The SS_DIR block controls, monitors, and switches the soft starter in the clockwise or
counter-clockwise direction.
This block supports different control functions, such as:
RUN / STOP
Monitoring
Slow speed
Emergency start
Lock
Diagnostics
Logbook
Output function
Trip reset
The SS_DIR block supports various faceplates with block icon for operation and control.
See also
Error numbers (Page 26)
Quality codes (Page 27)
Module drivers of the soft starter (Page 129)
Interconnection of function blocks (Page 40)
CFC charts for 3RW44 soft starter (Page 137)
Technical data (Page 141)
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
44 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.5.2 Calling OBs
The "Generate Module Driver" function automatically inserts the block into the following
organization blocks within the run sequence of the CFC:
Table 3- 19 Organization blocks that call the SS_DIR block
Organization block Description
OB 30 OB 38 Cyclic interrupts
OB 100 Warm restart
Recommendation
You are recommended to insert the block SS_DIR into OB 32 for cyclic operation.
See also the CFC manual.
3.5.3 Called blocks
The block calls the following blocks:
Table 3- 20 Blocks called by the SS_DIR block
Block Description
SFB 35 ALARM_8P Generates block-specific messages with values for eight
signals
SFB 52 RDREC Reads a data set
SFB 53 WRREC Writes a data set
SFC 20 BLKMOV Copies variables
SFC 6 RD_SINFO Reads the start information of the OB
SFC 64 TIME_TCK Reads the system time
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 45
3.5.4 Parameterization
IN_01, OUT_01: Assigning the input address and output address of the module
I-address:
2 bytes of input address of the module must be assigned to input parameter IN_01.
Q address:
2 bytes of output address of the module must be assigned to output parameter OUT_01.
LADDR: Assigning the logical address
The module driver parameterizes the logical address LADDR of the soft starter
automatically.
The logical address is used to interconnect the IN_01 parameter of the function block.
DADDR: Diagnostic address
The module driver parameterizes the diagnostics address DADDR of the soft starter
automatically.
Assigning rated operational current
Parameterize the rated operational current of the soft starter in HW Konfig and in the block
parameters.
Call the following in HW Config:
1. Double-click to open the "Properties DP slave" dialog
2. Click "Parameterize". Set the parameters **), e.g., rated operational current
3. Click "OK". This completes the configuration.
Set input parameter PSx_IRATE as the rated operational current of the device.
"X" stands for 1, 2, or 3 based on the active parameter set.

Note
DPV0 in DP alarm mode
If the device is configured as DPV0 in DP alarm mode in HW Config, these parameters will
not be written to the soft starter.

Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
46 Programming and Operating Manual, 11/2010, A5E02845977020-02
Parameter sets
The three parameter sets PS1, PS2, and PS3 have been parameterized to specify the basic
parameters, such as:
Rated operational current
Velocity
Torque
Control functions:
Startup mode
Coast-down mode
Current limits
...
See also
CFC charts for 3RW44 soft starter (Page 137)
Parameters View and views for Parameter set 1 to Parameter set 3 (Page 95)
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 47
3.5.5 Operating modes
Operating mode Manual operation LOCAL/REMOTE
Soft Starter ES uses the introductory commands Automatic mode (remote control by the
CPU) and Manual mode (Manual operation LOCAL mode) to enable switching between
Manual operation LOCAL and Remote control operations. The process image input 0.0
indicates whether the starter is running in REMOTE or Manual operation LOCAL mode.
The specified operating mode is displayed at the QREMOTE output.
1 = Remote
0 = Manual operation LOCAL/Soft Starter ES
The device is controlled either locally or via Soft Starter ES. When Soft Starter ES is used,
operations are available, such as:
Motor CW
Motor CCW



Note
Slow speed must be enabled in order for the Motor CCW operation to be active.

Trip reset
Emergency start
Slow speed
Output 1
Output 2
Disable Quick Stop
The same information is monitored in the faceplate views.
In Manual operation LOCAL mode, the OUT_01 output of the function block monitors the
process image output (PIQ; byte 1 and byte 2). This ensures that the status of the control
output does not change while the CPU switches back to Remote mode.
In Manual operation LOCAL mode, parameterize the parameter sets with Soft Starter ES or
directly in the hardware of the soft starter. These parameters are synchronized with the
parameters of the function block. This ensures that the status of the parameterized values
does not change while the CPU switches back to Remote mode.
The monitoring function does not monitor in Manual operation LOCAL mode.
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
48 Programming and Operating Manual, 11/2010, A5E02845977020-02
Operating mode Auto/Manual
Requirement:
Use the Automatic mode command (remote control by the CPU) in Soft Starter ES. This
defines: Process image input 0.0 = 1.

Switch function block to Auto mode: Set LIOP_SEL = 1 and AUT_L =1 Interlinked parameters
Switch faceplate (OS) to Auto mode: Set LIOP_SEL = 0 and
AUT_ON_OP = 1
Operating parameters


Switch function block to Manual mode: Set LIOP_SEL = 1 and AUT_L =0 Interlinked parameters
Switch faceplate (OS) to Auto mode: Set LIOP_SEL = 0 and set
AUT_ON_OP = 0
Operating parameters
The specified operating mode is displayed at the QMAN_AUT output.
1 = Auto
0 = Manual
Table 3- 21 Parameters that are active in Auto and Manual modes
Operating mode Auto
(interlinked parameters)
Operating mode Manual
(operating parameters)
Description
MOTCW_LI MOTCW_OP Motor CW
MOTCCW_LI MOTCCW_OP Motor CCW
MOTOF_LI MOTOF_OP Motor OFF
TRPRST_LI TRPRST_OP Trip reset
EMRGST_LI EMRGST_OP Emergency start
SLSPD_LI SLSPD_OP Slow speed
OUT1_LI OUT1_OP Output 1 function
OUT2_LI OUT2_OP Output 2 function
DSQSTP_LI DSQSTP_OP Disable Quick Stop
Operating parameters are provided, operating permission is specified, and LINK_MAN = 0
A signal with rising edge is pending at the XXX_LI parameters.
See also
Standard View (Page 89)
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 49
3.5.6 Functions
3.5.6.1 Description
General
The SS_DIR block has the following functions:
Control
Monitoring
Trip reset
Slow speed
Emergency start
Interlock
Diagnostics
QGRPERR: Group error
QCURR: Current message
Process image input and process image output
Operator authorizations
Output 1 and Output 2
Disable Quick Stop
Logbook
Substitute value
Active parameter sets
Reading and writing of data sets
Enabling measurement and statistics
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
50 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.5.6.2 Control
Functions for the motor start
The motor can be started in the clockwise or counter-clockwise direction in the following
operating modes:
Manual operation LOCAL
Auto
Manual
Table 3- 22 Effectiveness of parameters for each operating mode
Operating mode Manual
operation LOCAL
1)

Operating mode Auto Operating mode Manual Description
PIQ 0.0 = 1 MOTCW_LI = 1 MOTCW_OP = 1 Motor CW
PIQ 0.1 = 1 MOTCCW_LI = 1 MOTCCW_OP = 1 Motor CCW
2)

PIQ 0.0 = 0 and PII 0.1 = 0 MOTOF_LI = 1 MOTOF_OP = 1 Motor OFF
1) Soft Starter ES
2) The following must be enabled for Motor CCW:
Slow speed SLSPD_LI = 1 in Auto mode, SLSPD_OP = 1 in Manual mode, and PIQ 0.6 = 1
A signal with rising edge is pending at the XXX_LI parameters.
Operation in Manual operation LOCAL mode has priority. The function block and the
faceplate cannot perform any operations. However, the operation in Manual operation
LOCAL mode is monitored in the faceplate and in the block icon.
Table 3- 23 General information for Auto and Manual modes: Parameters that indicate the ON/OFF status
Output parameter Related PIQ bits Description
QMOT_CW = 1 PIQ 0.0 Introductory command for starting the motor in
the clockwise direction
QMOT_CW = 0 PIQ 0.0 Introductory command for stopping the motor in
the clockwise direction
QMOT_CCW = 1
1)
PIQ 0.1 Introductory command for starting the motor in
the counter-clockwise direction
QMOT_CCW = 0 PIQ 0.1 Introductory command for stopping the motor in
the counter-clockwise direction
1) The following must be enabled for Motor CCW:
Slow speed SLSPD_LI = 1 in Auto mode, SLSPD_OP = 1 in Manual mode, and PIQ 0.6 = 1
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 51
3.5.6.3 Monitoring
QMON_ERR, TIME_MON
This function monitors the consistency between the control command and the feedback
signal of the parameter within the specified TIME_MON monitoring time. Each discrepancy is
indicated with monitoring error QMON_ERR.
Table 3- 24 Parameters of control commands with the assigned PIQ and PII bits
Parameter of control
commands
Assigned PIQ bits
1)
Assigned PII bits
2)
Description
QMOT_CW = 1 PIQ 0.0 PII 0.1 Each discrepancy is indicated with
monitoring error QMON_ERR.
QMOT_CCW = 1
3)
PIQ 0.1 PII 0.1 Each discrepancy is indicated with
monitoring error QMON_ERR.
1) PIQ = Process image output
2) PII = Process image input, feedback parameters
3) For Motor CCW, the slow speed function must be enabled:
SLSPD_LI = 1 in Auto mode and PIQ 0.6 = 1
The MONITOR parameter indicates whether the monitoring function is enabled or disabled:
MONITOR = 1 enables the monitoring function.
MONITOR = 0 disables the monitoring function.
If the feedback signal of the process image input changes, the monitoring function performs
another check to determine whether a discrepancy exists between the feedback signal and
the process image output. Once the specified monitoring time elapses, any discrepancy is
indicated with monitoring error QMON_ERR.
If the block is in Manual operation LOCAL mode, monitoring errors are not checked. The
process image outputs 0.0 and 0.1 monitor the feedback signal of the process image
input 0.1. This prevents a bump from occurring when the operating mode is changed from
Manual operation LOCAL to Auto or Manual mode.
The monitoring time is specified in seconds. If the monitoring time is less than the sampling
time, the monitoring time will be calibrated to the sampling time.
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
52 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.5.6.4 Trip reset
Purpose and trigger of trip reset
Trip reset acknowledges all errors currently pending in the starter that require
acknowledgement. An error can be acknowledged once it has been resolved or if it no longer
exists.
Trip reset can be triggered as follows:
Locally on the device
By actuating TRPRST_OP in the Standard View (command reset), if this view has been
enabled for the Trip reset function:
TRPRSTOP_EN = 1
By the TRPRST_LI link parameter. This is a signal with rising edge.
This sets the process image output DP bit 0.3.
Output parameter QTRPRSTOP indicates whether the Trip reset function is enabled for the
operator.
3.5.6.5 Slow speed
Purpose
This function allows you to temporarily operate an asynchronous motor in both directions of
rotation at a speed that is less than the rated speed.
The slow speed factor and the slow torque can be entered individually for both directions of
rotation in the Parameters View.
Various parameters are used in the different operating modes to set the slow speed.
Table 3- 25 Parameters for activation of slow speed for each operating mode
Operating mode Input parameter Assigned PIQ bits
Manual operation LOCAL PIQ 0.6 Soft Starter ES
Auto SLSPD_LI = 1
1)
PIQ 0.6
Manual SLSPD_OP = 1 PIQ 0.6
1) Precondition for Start Motor CCW is start command Slow speed on the starter.
QMOT_SLSPD = 1 indicates that slow speed is activated.
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 53
3.5.6.6 Emergency start
Purpose and trigger of emergency start
The emergency stop enables a restart in spite of an internal shutdown command.
The emergency start function can be triggered as follows:
By enabling emergency startEMRGST_OP in the Maintenance View, if this view is
enabled on the operator side for the emergency start function:
EMSTOP_EN = 1
By the EMRGST_LI link parameter, which is a signal with a rising edge
This sets the process image output DP bit 0.4.
Output parameter QEMSTOP indicates whether the emergency start function is enabled for
the operator.
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
54 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.5.6.7 Lock
LOCK, LOCK_ON
The LOCK and LOCK_ON functions are only available in Remote operating mode. An active
lock input prevents switching and disables control commands. LOCK always overwrites
LOCK_ON.
LOCK = 1: LOCK is set to OFF
The control commands are set in order to stop the motor.
QMOT_CW = 0
QMOT_CCW = 0
LOCK_ON = 1: LOCK is set to ON
LOCK_DIR = 0: Motor CW
LOCK_DIR = 1: Motor CCW
The control commands are set in order to start the motor based on the values set in
LOCK_ON and LOCK_DIR:
QMOT_CW = 1
QMOT_CCW = 1
For the LOCK and LOCK_ON functions, the following operating commands and linkable
control commands are disabled:
MOTCW_OP
MOTCW_LI
MOTCCW_LI
The Standard View displays the "padlock" symbol to indicate whether the LOCK and
LOCK_ON functions are set.

Note
If slow speed has not been selected and LOCK_ON, LOCK_DIR command has been
initiated with CCW direction, an error number is generated as ERRORNUM. This status is
displayed in the Standard view in the faceplate as LOCK blinking in the status field.

Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 55
3.5.6.8 Diagnostics
The SS_DIR block receives diagnostic information from the SS_DIAG block. The SS_DIR
block displays this diagnostic information in various Diagnostics Views.

Note
The SS_DIAG block detects a rack failure and a module failure. These are interconnected
with the SS_DIR block and are indicated at the following outputs:
QRACKF
QMODF

QDIAG: PROFIBUS DP slave diagnostics
Table 3- 26 DIAG_DIR.DIAG: Bit assignment
Related structured characteristic
map
QDIAG bit no. Description
DIAG_DIR.DIAG 0 DP slave cannot be accessed by DP master.
DIAG_DIR.DIAG 1 DP slave is not yet ready for data exchange.
DIAG_DIR.DIAG 2 Config data to DP slave from DP master does not match.
DIAG_DIR.DIAG 3 External diagnostics pending (Group diagnostics display)
DIAG_DIR.DIAG 4 Function is not supported by DP slavee.g., station address change
by the software
DIAG_DIR.DIAG 5 DP master cannot interpret DP slave response.
DIAG_DIR.DIAG 6 DP slave type does not match software config.
DIAG_DIR.DIAG 7 DP slave parameterized by a different DP master
DIAG_DIR.DIAG 8 DP slave parameters must be reassigned.
DIAG_DIR.DIAG 9 Static diagnostic message:
A diagnostics message is pending. DP slave will not function until the
error is corrected. (Static diagnostic message)
DIAG_DIR.DIAG 10 Bit is set to "1" as long as DP slave address exists.
DIAG_DIR.DIAG 11 Watchdog function activated for DP slave
DIAG_DIR.DIAG 12 DP slave has received "FREEZE" command.
DIAG_DIR.DIAG 13 DP slave has received "SYNC" command.
DIAG_DIR.DIAG 14 DP slave has been deactivated, e.g., it is not included in the current
processing.
DIAG_DIR.DIAG 15 More diagnostic messages than DP slave can store.The DP master
cannot write all diagnostic messages to its diagnostic buffer that were
sent by the DP slave. (Channel diagnostics)
16 31 Not used
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
56 Programming and Operating Manual, 11/2010, A5E02845977020-02
QDIAGCOM: Diagnostics for communication, switching, and control
Table 3- 27 QDIAGCOM Bit assignment of structured characteristic map DIAG_DIR
Related structured characteristic map
DIAG_DIR
QDIAGCOM bit no. Description
BUSERR 0 Bus error
CPUMSTRSTOP 1 CPU/master Stop
AUTOPLCCNTRL 2 Automatic mode (CPU controls)
MANBUSCNTRL 3 Manual operation bus, OCM controls
MANLOCCNTRL 4 Manual operation LOCAL
CONNBRK 5 Connection break in local mode
PIERROR 6 Process image error
MANBUSPCCNT 7 Manual operation bus, PC controls
MANLOCINCNT 8 Manual operation LOCAL - input controls
MANLOCOMCNT 9 Manual operation LOCAL - OCM controls
MANLOCPCNT 10 Manual operation LOCAL - PC controls
CNTOVLD 11 Contact block overload
CNTDMAG 12 Contact block defective
NOMAINPWR 13 No supply voltage
STRTMODACT 14 Starting active
STPMODACT 15 Coast-down active
ELEBRKACT 16 Electrical braking active
SLWSPDACT 17 Slow speed active
CTRLINPUT 18 Input control
QCKSTPACT 19 Quick Stop active
ELEVLTHI 20 Electronics supply voltage too high
ELEVLTLO 21 Electronics supply voltage too low
RDYMOTON 22 Ready for motor ON
CNTSHRT 23 Contact block short-circuited
BYPPRTFLT 24 Bypass element defective
SWELE1FAIL 25 Contact block 1 failed
SWELE2FAIL 26 Contact block 2 failed
SWELE3FAIL 27 Contact block 3 failed
28 31 Reserved
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 57
QDIAGPAR: Diagnostics for parameters and device function
Table 3- 28 QDIAGPAR Bit assignment of structured characteristic map DIAG_DIR
Related structured characteristic map
DIAG_DIR
QDIAGPAR bit no. Description
FACTSETRSTR 0 Factory settings restored
IMPERCLASS 1 Impermissible Ie / CLASS settings
PSACTIVE 2 Parameter assignment active
PS1ACTIVE 3 Parameter set 1 active
PS2ACTIVE 4 Parameter set 2 active
PS3ACTIVE 5 Parameter set 3 active
IMPCHNGPS 6 Parameter set change impermissible
INCORPSVAL 7 Invalid parameter value
PSPERMIT 8 Parameter changes not permissible when ON
PSDISCPUACT 9 Parameters disabled CPU/master active
MOTHEATACT 10 Motor heating active
DCBRKACT 11 DC braking active
DYNDCBRK 12 Dynamic braking active
CONSTDELT 13 Motor connection type start/delta
CONINSDDELT 14 Motor connection type inside delta
CONUNKWN 15 Motor connection type unknown
NOLOAD 16 No load
PHS1LOSS 17 Phase failure 1
PHS2LOSS 18 Phase failure 2
PHS3LOSS 19 Phase failure 3
LIPHDIR 20 Line phase direction right
OUT1ACT 21 Output 1 active
OUT2ACT 22 Output 2 active
OUT3ACT 13 Output 3 active
TRPRSTCARID 24 Trip reset successful
TRPRSTNOTPOS 25 Trip reset unsuccessful
MAXPNTRDEL 26 Maximum pointer reset
LIPHREV 27 Line phase direction left
28 31 Reserved
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
58 Programming and Operating Manual, 11/2010, A5E02845977020-02
QFLTPAR: Diagnostics for incorrect parameter numbers
Table 3- 29 QFLTPAR Byte assignment of structured characteristic map DIAG_DIR
Related structured characteristic map
DIAG_DIR
QFLTPAR byte no. Description
FLTPARLB 0 Incorrect parameter number (least significant byte)
FLTPARHB 1 Incorrect parameter number (most significant byte)
See also
Slave diagnostics of the 3RW44 (Page 32)
3.5.6.9 QGRPERR: Group error
QGRPERR
The Group error parameter is set when one of the failures or errors listed below is detected.
The Standard View displays these errors as a group error.
Group error: Process image bit 0.2:
Module failure
Rack failure
Monitoring error
3.5.6.10 QCURR: Current message
QCURR
Bits 1.0 to 1.5 of the process image input write the current consumption when the motor is
connected. The QCURR output parameter indicates this information in amperes.
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 59
3.5.6.11 Process image input and process image output of 3RW44 soft starter
Bit assignment
Table 3- 30 Process image input: Bit assignment of byte 0 and byte 1
Byte.Bit Meaning
DP 0.0 Ready to start (automatic)
DP 0.1 Motor ON
DP 0.2 Group error
DP 0.3 Group warning
DP 0.4 Input 1
DP 0.5 Input 2
DP 0.6 Input 3
DP 0.7 Input 4
Motor current
DP 1.0
DP 1.1
DP 1.2
DP 1.3
DP 1.4
DP 1.5
DP 1.6 Manual operation LOCAL mode
DP 1.7 Ramp operation

Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
60 Programming and Operating Manual, 11/2010, A5E02845977020-02
Table 3- 31 Process image output: Bit assignment of byte 0 and byte 1
Byte.Bit Meaning
DP 0.0 Motor CW
DP 0.1 Motor CCW
DP 0.2 Brake
DP 0.3 Trip reset
DP 0.4 Emergency start
DP 0.5 Self-test
DP 0.6 Slow speed
DP 0.7 Reserved
DP 1.0 Output 1
DP 1.1 Output 2
DP 1.2
DP 1.3
Active parameter sets 1, 2, 3
DP 1.4
DP 1.5
DP 1.6
Reduction factor
DP 1.7 Disable Quick Stop
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 61
3.5.6.12 Operator authorizations
Operator authorizations
The enable parameters allow the operator to issue the desired commands. These
commands are interconnected to the corresponding outputs. This permits operation to be
enabled from the Standard View of the faceplate.
Example:
If the block is in Manual mode and AUTOP_EN = 0, the operator must not change the
operating mode of the block to Auto. He must not change the operating mode from the
Standard View of the faceplate or in the CFC. QAUTOP = FALSE is set in this process.
In a similar manner, every _EN parameter enables the corresponding operation.

Authorization ON
Name of parameter
Authorization OFF
Name of parameter
Description of _EN parameter Name of related
operating parameter
MANOP_EN QMANOP Enable:
1 = Operator may enter Manual.
AUTOP_EN QAUTOP Enable:
1 = Operator may enter Auto.
AUT_ON_OP
MOTCWOP_EN QMOTCWOP Enable:
1 = Operator may enter Motor CW.
MOTCW_OP
MOTCCWOP_EN QMOTCCWOP Enable:
1 = Operator may enter Motor CCW.
MOTCCW_OP
MOTOFOP_EN QMOTOFOP Enable:
1 = Operator may enter Motor OFF.
MOTOF_OP
TRPRSTOP_EN QTRPRSTOP Enable:
1 = Operator may enter Trip reset.
TRPRST_OP
EMSTOP_EN QEMSTOP Enable:
1 = Operator may enter Emergency
start.
EMRGST_OP
SLSPD_EN SLSPDOP Enable:
1 = Operator may enter Slow speed.
SLSPD_OP
OUT1_EN OUT1OP Enable:
1 = Operator may enter OUT1.
OUT1_OP
OUT2_EN OUT2OP Enable:
1 = Operator may enter OUT2.
OUT2_OP
DSQSTP_EN DSQSTPOP Enable:
1 = Operator may enter Disable
Quick Stop.
DSQSTP_OP
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
62 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.5.6.13 Output 1 and output 2
PS_OUT1, PS_OUT2
If the outputs device function is applied, the motor starter can carry out various
parameterizable actions. The integer values of PS_OUT1 and PS_OUT2 indicate the various
actions that can be parameterized.
Table 3- 32 Actions that can be parameterized for the outputs
Action Description PS_OUT1 / PS_OUT2 value
No action The output is deactivated. 0
Control source (output 1) The output contact closes when bit 1.0
is set in the process image output.
12
Control source (output 2) The output contact closes when bit 1.1
is set in the process image output.
2
The following parameters are active when setting device functions for Output 1 and Output 2
in Auto or Manual mode.
Table 3- 33 Input parameters for each operating mode, output parameters and bit assignment of the process image for
OUT1 and OUT2
Operating mode Manual
Input parameter
Operating mode Auto
Input parameter
Output parameter Process image output
bits
OUT1_OP OUT1_LI QOUTPUT1 PIQ 1.0
OUT2_OP OUT2_LI QOUTPUT2 PIQ 1.1
A signal with rising edge is pending at the XXX_LI parameters.
3.5.6.14 Disable Quick Stop
Function Quick Stop
The Quick Stop function enables the motor and switches off the brake output without a group
error. This function can be disabled.
The following parameters are active in the various operating modes of the block.
Table 3- 34 Input parameters for each operating mode, output parameters and bit assignment of the process image
Operating mode Manual
Input parameter
Operating mode Auto
Input parameter
Output parameter Process image output
bit
DSQSTP_OP DSQSTP_LI PIQ 1.7
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 63
3.5.6.15 Logbook
Content of the logbook
The logbook contains a reverse chronological list of tripping errors, device errors, and
events, which are provided with a time stamp. Each entry in the logbook has the following
attributes:
LOGTIME1 to LOGTIME21: Time stamp
LOGID1 to LOGID22: Number of message
Text of message
This information is called from:
Data set 72
Data set 73
Data set 75
A maximum of 63 messages can be logged with a time delay of 1 second. The LOGDS
parameter contains the values 1, 2, or 3. These indicate reading of data set 72, data set 73,
and data set 75.
The faceplate of the logbook function shows all entries to the log book.
The DEL_LOGTRP and DEL_LOGEVNT parameters can be used to delete the following
logged messages:
Tripping errors
Events
Table 3- 35 Messages regarding device errors received from the soft starter, including the related number
No. Message no. Device error message
1 452 Heat sink thermistor defective
2 1466 Contact block 1 failed
3 1467 Contact block 2 failed
4 1468 Contact block 3 failed
5 1417 Bypass element defective

Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
64 Programming and Operating Manual, 11/2010, A5E02845977020-02
Table 3- 36 Messages regarding tripping errors received from the soft starter, including the related number
No. Message ID Tripping error message
1 309 Contact block overload
2 317 Electronics supply voltage too low
3 319 No supply voltage
4 324 Temperature sensor overload
5 325 Temperature sensor wire break
6 326 Temperature sensor short-circuit
7 327 Thermal motor model overload
8 334 Current limit overshot
9 335 Current limit undershot
10 339 Motor block tripping
11 341 Asymmetry tripping
12 343 Ground fault tripping
13 355 Process image error
14 365 Invalid parameter value:
Number of the invalid parameter
15 1407 Electronics supply voltage too high
16 1408 No load
17 1409 Phase failure L1
18 1410 Phase failure L2
19 1411 Phase failure L3
20 1421 Impermissible Ie / CLASS settings
21 1479 Generalized phase error
22 1481 Supply voltage too high
23 1482 Current measuring range exceeded

Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 65
Table 3- 37 Messages regarding events received from the soft starter, including the related number
No. Message ID Event error message
1 324 Overload
2 325 Temperature sensor wire break
3 326 Temperature sensor short-circuit
4 327 Thermal motor model overload
5 334 Current limit overshot
6 335 Current limit undershot
7 340 Asymmetry detected
8 342 Ground fault
9 310 Emergency start active
10 357 Automatic operating mode
11 358 Manual operation bus
12 359 Manual operation LOCAL mode
13 360 Manual operation connection abort
14 363 Maximum pointer reset
15 365 Invalid parameter value:
Number of the invalid parameter
16 366 Parameters cannot be changed in ON state:
Number of the invalid parameter
17 368 Parameters disabled CPU/master active
18 369 Factory settings restored
19 1302 Logbook - Triggering operations deleted
20 1303 Logbook - Events deleted
21 120 Device function_1
22 1 Device function_2
23 130 Rated operational current
24 3 Load type
25 4 Protection against voltage failure
26 5 Response to overload - thermal motor model
27 6 Tripping class
28 7 Recovery time
29 8 Idle time
30 137 Prewarning limit - remaining time for tripping
31 10 Response to overload - temperature sensor
32 9 Temperature sensor
33 12 Temperature sensor monitoring
34 15 Lower current limit
35 16 Upper current limit
36 14 Response to current limit value violation
37 140 Response to switching element overload
38 21 Asymmetry limit
39 20 Response to asymmetry
40 22 Response to ground fault
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
66 Programming and Operating Manual, 11/2010, A5E02845977020-02
No. Message ID Event error message
41 47 Braking torque
42 40 Starting voltage
43 42 Current limiting value
44 167 Startup mode
45 168 Coasting method
46 35 Substitute value
47 36 Group diagnostics
48 34 Response to CPU/master stop
49 26 Input 1 - action
50 28 Input 2 - action
51 30 Input 3 - action
52 32 Input 4 - action
53 163 Output 1 - action
54 164 Output 2 - action
55 165 Output 3 - action
56 166 Output 4 - action
57 116 Breakaway time
58 117 Breakaway voltage
59 169 Max. starting time
60 170 Starting time
61 171 Coast-down time
62 172 Starting torque
63 118 Limiting torque
64 173 Stopping torque
65 119 Motor thermal capacity
66 178 Dynamic braking torque
67 43 Slow speed factor - CW rotation
68 198 Slow speed factor - CCW rotation
69 44 Slow torque - CW rotation
70 199 Slow torque - CCW rotation
71 104 Rated speed
72 113 Rated torque
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 67
3.5.6.16 Substitute value
SUB_VALUE
The operator parameterizes the substitute value. The SUB_VALUE parameter is 2 bytes
long. The data contained are written to the soft starter via data set 131. If the Response to
CPU/master stop event occurs, the soft starter is switched to the substitute value
parameterized in SUB_VALUE or it retains the last value.
This activation is parameterized at the START_OFF parameter:

START_OFF = 1: Switch substitute value
START_OFF = 0: Retain the last value
The SUB_VALUE parameter can only be written to the OUT_01 output of the block, if
START_OFF = 0:
While a warm restart is performed on the CPU
A rack error is detected
A module error is detected
3.5.6.17 Active parameter sets
PS_SETACT
The process images of output bit PIQ 1.2 and PIQ 1.3 correspond to the settings that the
operator makes for the active parameter sets. These are based on the parameterization of
parameter PS_SETACT = 1, 2, or 3. The digits 1, 2, and 3 refer to the corresponding
parameter sets 1, 2, and 3.

PS_SETACT = 1 (Standard)
PIQ DP 1.2 = FALSE
PIQ DP 1.3 = FALSE


PS_SETACT = 2 (Standard)
PIQ DP 1.2 = TRUE
PIQ DP 1.3 = FALSE


PS_SETACT = 3 (Standard)
PIQ DP 1.2 = FALSE
PIQ DP 1.3 = TRUE
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
68 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.5.6.18 Reading and writing of data sets
RDREC, WRREC
For detailed information on data sets, refer to the "SIRIUS 3RW44 Soft Starter" System
Manual > Chapter "Communication Module PROFIBUS DP" > "Data Sets"
Table 3- 38 Data set table: Read access and/or write access for each data set
No. Data set no. Read
access/write
access
Number of
bytes
Description of data set
1 68 R/W 8 Reading/Writing the Process Image of the Outputs
2 72 R 126 Log List - Reading device errors
3 73 R 126 Log List - Reading the trippings
4 75 R 126 Log List - Reading events
5 92 R 30 Reading the device diagnosis
6 93 W 10 Writing a command
7 131 R/W 138 Technology parameter 2: Set 1
8 132 R/W 64 Technology parameter 3: Set 1
9 141 R/W 138 Technology parameter 2: Set 2
10 142 R/W 64 Technology parameter 3: Set 2
11 151 R/W 138 Technology parameter 2: Set 3
12 152 R/W 64 Technology parameter 3: Set 3
"R" = Read access; "W" = Write access
These data sets are based on the read authorization and/or write authorization. The
RDREC function is used to read the values and the WRREC function is used to write the
setting in the soft starter.
The Q_ENRDWR parameter indicates: The read function or write function is being executed.
Read function
Data sets are read with the following parameters:

RD_DATA = 1 : Operating parameters for reading values
L_RD_DATA = 1 : Linkable parameters for reading values.
EN_RDWR = 1
QERR_RD = 1 : Error when reading data sets.
The WRREC write function is supported in this case.
Write function
The WRREC function writes all values changed by the user to the device.
QERR_WR = 1 indicates errors when writing a data set.
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 69
3.5.6.19 Enabling measurement and statistics
EN_MEAS, EN_STAT
A logical value "1" in the EN_MEAS and EN_STAT parameters activates the link for opening
the faceplates for the measurement block and the statistics block.
Faceplate for the EN_MEAS parameter
The user configures the faceplate that is opened with the EN_MEAS parameter in:
S7_string_1:='MEAS123'
MEAS123 stands for the name of a function block of type SS_MEAS.
Faceplate for the EN_STAT parameter
The user configures the faceplate that is opened with the EN_STAT parameter in:
S7_string_1:='STAT123'
STAT123 stands for the name of a function block of type SS_STAT.

Note
Configure the SS_MEAS function block for measurement and the SS_STAT function block
for statistics in the same CFC as the SS_DIR block.

Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
70 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.5.7 Message features
Messages
The following messages are generated:
Table 3- 39 Output messages
Input parameter Message
no.
Parameter Message Message
class
1 QMON_ERR $$BlockComment$$Monitoring Error or
Starter tripped
S
2 CSF $$BlockComment$$Control System Fault S
3 MSG_3
1)
$$BlockComment$$ Message Input 3 A
4 MSG_4
1)
$$BlockComment$$ Message Input 4 A
5 MSG_5
1)
$$BlockComment$$ Message Input 5 A
6 MSG_6
1)
$$BlockComment$$ Message Input 6 A
7 MSG_7
2)
$$BlockComment$$ Message Input 7 A
MSG_EVID
3)

8 MSG_8
2)
$$BlockComment$$ Message Input 8 A
1) The MSG_3 to MSG_6 parameters represent messages that can be user-configured.
2) The MSG_7 and MSG_8 messages as well as the associated values AUX_PR08 to AUX_PR010 are reserved.
3) Parameters with message number for ALARM_8P.

Table 3- 40 Structure of the related values in ALARM_8P
Message
no.
Related value Parameter Meaning
1 1 BA_NA Name of batch
2 2 STEP_NO Step number
3 3 BA_ID Name of batch
4 4 AUX_PR04
1)
Auxiliary value 4
5 5 AUX_PR05
1)
Auxiliary value 5
6 6 AUX_PR06
1)
Auxiliary value 6
7 7 AUX_PR07
1)
Auxiliary value 7
8 8 AUX_PR08
1)
Auxiliary value 8
9 9 AUX_PR09
1)
Auxiliary value 9
10 10 AUX_PR010
1)
Auxiliary value 10
1) The AUX_PR04 bis AUX_PR07 parameters represent auxiliary values for messages that can be user-configured.
The M_SUP_C input can enable and disable the messages. The QMSG_STAT, QMSG_ACK
and QMSG_ERR parameters transfer the information found in ALARM_8P:
Status of messages
Status of an alarm acknowledgement
Status of errors during data transfer
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 71
3.5.8 Start-up characteristics
Description
All alarm messages are suppressed in OB 100:
The user defines a value for RUNUPCY. This is assigned to OB 100 in order to suppress the
messages for the configured cycle count.
Depending on the value set for the START_OFF characteristic, the outputs contain either the
last valid value or the reset substitute value.
Table 3- 41 Outputs that are reset when START_OFF = 0
Output parameter Value of output
QREMOTE = TRUE
QMAN_AUT = FALSE
OUT_01 = SUB_VALUE
QMOT_CW =
1)

QMOT_CCW =
1)

QMOT_SLSPD =
1)

QOUTPUT1 =
1)

QOUTPUT2 =
1)

1) These parameters follow the value in OUT_01 PIQ 0.0 to PIQ 1.7.
If START_OFF = 1, all the outputs indicated above contain the last valid value.
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
72 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.5.9 Block parameters for the inputs
Table 3- 42 Parameters of the SS_DIR block
Name of
parameter
Data format Type Default
value
Value
range
Factor Meaning
IN_01* WORD Input 16#00 Value of process image
input DP 0.0 1.7
AUT_L BOOL Input FALSE Linkable input for
Auto/Manual mode
AUTOP_EN BOOL Input TRUE Enable:
1 = Operator may enter
Auto.
AUX_PR04 ANY Input Auxiliary value 4
AUX_PR05 ANY Input Auxiliary value 5
AUX_PR06 ANY Input Auxiliary value 6
AUX_PR07 ANY Input Auxiliary value 7
AUX_PR08 ANY Input Auxiliary value 8
AUX_PR09 ANY Input Auxiliary value 9
AUX_PR010 ANY Input Auxiliary value 10
BA_EN BOOL Input FALSE Enable batch
BA_ID DWORD Input 16#00 Name of batch
BA_NA STRING[32] Input Name of batch
CSF BOOL Input FALSE Control system error
DADDR INT Input 0 Diagnostic address of
module
DIAG_DIR SSDIAGDIR Input Diagnostic information
from the SS_DIAG block
DSQSTP_EN BOOL Input TRUE Enable:
1 = Operator may enter
Disable Quick Stop.
DSQSTP_LI BOOL Input FALSE Command in Auto mode:
1 = Disable Quick Stop
command active
EMRGST_LI BOOL Input FALSE Command in Auto mode:
1 = Emergency start
command active.
EMSTOP_EN BOOL Input TRUE Enable:
1 = Operator may enter
Emergency start.
EN_MEAS BOOL Input TRUE 1 = Measurement block
available
EN_RDWR BOOL Input TRUE Enable:1 =
Read and write data sets.
EN_STAT BOOL Input TRUE 1 = The statistics block is
available.
L_RD_DATA BOOL Input FALSE Linkable input 0 > 1:
Read data set
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 73
Name of
parameter
Data format Type Default
value
Value
range
Factor Meaning
LADDR INT Input 0 Logical address of soft
starter
LINK_MAN BOOL Input FALSE Selection:
1 = Link
0 = Operator active
LIOP_SEL BOOL Input FALSE Selection:
1 = Link
0 = Operator active
LOCK BOOL Input FALSE 1 = Lock OFF
LOCK_DIR BOOL Input FALSE 1 = Counter-clockwise
2 = Clockwise
LOCK_ON BOOL Input FALSE According to the setting in
LOCK_DIR:
1 = Clockwise
rotation/counter-clockwise
rotation locked
M_SUP_C BOOL Input TRUE 1 = Suppress alarms
MANOP_EN BOOL Input TRUE Enable:
1 = Operator may enter
Manual.
MODF BOOL Input FALSE 1 = Module failure
MONITOR BOOL Input TRUE 1 = MONITOR ON
0 = MONITOR OFF:
"MONITOR" feedback
MOTCCW_LI BOOL Input FALSE Command in Auto mode:
1 = Motor start CCW
MOTCCWOP_EN BOOL Input TRUE Enable:
1 = Operator may enter
Motor CCW.
MOTCW_LI BOOL Input FALSE Command in Auto mode
1 = Motor start CW
MOTCWOP_EN BOOL Input TRUE Enable:
1 = Operator may enter
Motor CW.
MOTOF_LI BOOL Input FALSE Command in Auto mode:
1 = MOTOR OFF
MOTOFOP_EN BOOL Input TRUE Enable:
1 = Operator may enter
Motor OFF.
MSG_3 BOOL Input FALSE Message input 3
MSG_4 BOOL Input FALSE Message input 4
MSG_5 BOOL Input FALSE Message input 5
MSG_6 BOOL Input FALSE Message input 6
MSG_7 BOOL Input FALSE Message input 7
MSG_8 BOOL Input FALSE Message input 8
MSG_EVID DWORD Input 16#FF Number of the message
event
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
74 Programming and Operating Manual, 11/2010, A5E02845977020-02
Name of
parameter
Data format Type Default
value
Value
range
Factor Meaning
OCCUPIED BOOL Input FALSE Batch: Occupied
OUT1_EN BOOL Input TRUE Enable:
1 = Operator may enter
OUT1.
OUT1_LI BOOL Input FALSE Command in Automode:
:1 = OUT1 active
OUT2_EN BOOL Input TRUE Enable:
1 = Operator may enter
OUT2.
OUT2_LI BOOL Input FALSE Command in Auto mode:
1 = OUT2 active
RACKF BOOL Input FALSE 1 = Rack failure
RUNUPCYC INT Input 3 Number of the cycle for
which all messages are
suppressed.
SAMPLE_T REAL Input 0.1 Sampling time in s
SLSPD_EN BOOL Input TRUE Enable:
1 = Operator may enter
Slow speed.
SLSPD_LI BOOL Input FALSE Command in Auto mode:
1 = Slow speed active
STEP_NO DWORD Input 16#00 Step number of batch
TIME_MON REAL Input 3 Monitoring time in s
TRPRST_LI BOOL Input FALSE Command in Auto mode:
1 = Trip reset active
TRPRSTOP_EN BOOL Input TRUE Enable:
1 = Operator may enter
Trip reset.
PS2_IRATE** REAL Input 29 0 2000 0.01 A Parameter set 2:
Rated
operational current Ie
PS3_IRATE** REAL Input 29 0 200 0.01 A Parameter set 3:
Rated
operational current Ie
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 75
3.5.10 Block parameters for inputs and outputs
Table 3- 43 Parameters of the SS_DIR block
Name of
parameter
Data format Type Default
value
Value
range
Factor Meaning
AUT_ON_OP BOOL Input/
output
FALSE Operator intervention in
mode:
1 = Auto
0 = Manual
DSQSTP_OP BOOL Input/
output
FALSE Command in Manual
mode:
1 = Disable Quick Stop
command active.
EMRGST_OP BOOL Input/
output
FALSE Command in Manual
mode:
1 = Emergency start
command active.
MOTCCW_OP BOOL Input/
output
FALSE Command in
Manual mode:
1 = Motor start CCW
MOTCW_OP BOOL Input/
output
FALSE Command in Manual
mode:
1 = Motor start CW
MOTOF_OP BOOL Input/
output
FALSE Command in Manual
mode:
1 = Motor OFF
OUT1_OP BOOL Input/
output
FALSE Command in Manual
mode:
1 = OUT1 active
OUT2_OP BOOL Input/
output
FALSE Command in Manual
mode:
1 = OUT2 active
PS_IDLTM INT Input/
output
0 0 255 1 s Parameter set:
Thermal motor model idle
time
PS_MTRHT INT Input/
output
80 0 95 5 % Parameter set:
Prewarning limit-motor
heating
PS_OVLRES INT Input/
output
0 Parameter set:
Response to overload
0 =Trip without restart
1 = Trip with restart
2 = Warning
PS_OVLSEN INT Input/
output
0 Parameter set:
Response to overload -
temperature sensor
0 =Trip without restart
1 = Trip with restart
2 = Warning
PS_SETACT INT Input/
output
1 Activates the parameter
sets.
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
76 Programming and Operating Manual, 11/2010, A5E02845977020-02
Name of
parameter
Data format Type Default
value
Value
range
Factor Meaning
RD_DATA BOOL Input/
output
FALSE 1 = Read data from the
data sets
SLSPD_OP BOOL Input/
output
FALSE Command in Manual
mode:
1 = Slow speed active
START_OFF BOOL Input/
output
FALSE 0 = Switch substitute value
1 = Retain last value
SUB_VALUE*** WORD Input/
output
16#00 Substitute value as
Response to CPU/master
stop
PS_RCRYTM REAL Input/
output
1 60 30 s Parameter set:
Recovery time
PS_TRPCLS INT Input/
output
0 Parameter set:
Thermal motor model
0 = CLASS 10
1 = CLASS 20
2 = CLASS 30
3 = CLASS 5(10a)
4 = CLASS 15
15 = CLASS OFF
PS_TRPTM INT Input/
output
0 0 500 1 s Parameter set:
Remaining time for tripping
PS_TMPSNSR INT Input/
output
0 Parameter set:
Temperature sensor
PS_ASYLIM INT Input/
output
30 30 60 10 % Parameter set:
Asymmetry limit
PS_COMMON DWORD Input/
output
16#13 Parameter set:
General parameters
Bit 0: Protection against
voltage failure
Bit 1: Response to current
limit value violation
0 = Warning
1 = Trip
Bit 2: Response to
switching element overload
0 =Trip without restart
1 = Trip with restart
Bit 3: Response to
asymmetry
0 = Warning
1 = Trip
Bit 4: Response to ground
fault
0 = Warning
1 = Trip
Bit 5: Group diagnostics
0 = Disabled
1 = Enabled
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 77
Name of
parameter
Data format Type Default
value
Value
range
Factor Meaning
PS_IN1 INT Input/
output
0 Parameter set: Input 1
0 = No action
5 = Group warning
6 = Manual operation
LOCAL mode
7 = Emergency start
10 = Slow speed
11 = Quick Stop
12 = Trip reset
16 = Motor CW with PS1
17 = Motor CCW with PS1
18 = Motor CW with PS2
19 = Motor CCW with PS2
20 = Motor CW with PS3
PS1_IRATE** REAL Input/
output
29 0 2000 0.001 A Parameter set 1:
Rated operational
current Ie
PS_IN2 INT Input/
output
0 Parameter set: Input 2
0 = No action
5 = Group warning
6 = Manual LOCAL mode
7 = Emergency start
10 = Slow speed
11 = Quick Stop
12 = Trip reset
16 = Motor CW with PS1
17 = Motor CCW with PS1
18 = Motor CW with PS2
19 = Motor CCW with PS2
20 = Motor CW with PS3
PS_IN3 INT Input/
output
0 Parameter set: Input 3
0 = No action
5 = Group warning
6 = Manual LOCAL mode
7 = Emergency start
10 = Slow speed
11 = Quick Stop
12 = Trip reset
16 = Motor CW with PS1
17 = Motor CCW with PS1
18 = Motor CW with PS2
19 = Motor CCW with PS2
20 = Motor CW with PS3
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
78 Programming and Operating Manual, 11/2010, A5E02845977020-02
Name of
parameter
Data format Type Default
value
Value
range
Factor Meaning
PS_IN4 INT Input/
output
0 Parameter set: Input 4
0 = No action
5 = Group warning
6 = Manual LOCAL mode
7 = Emergency start
10 = Slow speed
11 = Quick Stop
12 = Trip reset
16 = Motor CW with PS1
17 = Motor CCW with PS1
18 = Motor CW with PS2
19 = Motor CCW with PS2
20 = Motor CW with PS3
PS_OUT1 INT Input/
output
0 Parameter set:
Output 1 - action
0 = No action
1 = Control source
(Output 1)
2 = Control source
(Output 2)
6 = Control source input 1
7 = Control source input 2
8 = Control source input 3
9 = Control source input 4
10 = Ramp-up
11 = Operation / Bypass
12 = Coast-down
13 = On time motor (RUN)
14 = Control command
motor ON
16 = Brake contactor
18 = Device ON
31 = Group warning
32 = Group error
33 = Bus error
34 = Device error
38 = Ready for motor ON
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 79
Name of
parameter
Data format Type Default
value
Value
range
Factor Meaning
PS_OUT2 INT Input/
output
0 Parameter set:
Output 2 - action
0 = No action
1 = Control source
(Output 1)
2 = Control source
(Output 2)
6 = Control source input 1
7 = Control source input 2
8 = Control source input 3
9 = Control source input 4
10 = Ramp-up
11 = Operation / Bypass
12 = Coast-down
13 = On time motor (RUN)
14 = Control command
motor ON
16 = Brake contactor
18 = Device ON
31 = Group warning
32 = Group error
33 = Bus error
34 = Device error
38 = Ready for motor ON
PS_OUT3 INT Input/
output
0 Parameter set:
Output 3 - action
0 = No action
1 = Control source
(Output 1)
2 = Control source
(Output 2)
6 = Control source input 1
7 = Control source input 2
8 = Control source input 3
9 = Control source input 4
10 = Ramp-up
11 = Operation / Bypass
12 = Coast-down
13 = On time motor (RUN)
14 = Control command
motor ON
16 = Brake contactor
18 = Device ON
31 = Group warning
32 = Group error
33 = Bus error
34 = Device error
38 = Ready for motor ON
PS1_BR_U INT Input/
output
80 40 100 5 % Parameter set 1:
Breakaway voltage
PS1_BRKTQ INT Input/
output
50 20 100 5 % Parameter set 1:
Braking torque
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
80 Programming and Operating Manual, 11/2010, A5E02845977020-02
Name of
parameter
Data format Type Default
value
Value
range
Factor Meaning
PS1_CURLM REAL Input/
output
450 125 550 3,13 % Parameter set 1:
Current limiting value
PS1_DYNTQ INT Input/
output
50 20 100 5 % Parameter set 1:
Dynamic braking torque
PS1_LMTQ INT Input/
output
150 20 200 5 % Parameter set 1:
Limiting torque
PS1_SPDRATE INT Input/
output
1500 500 3600 1 rpm Parameter set 1:
Rated speed
PS1_SPTQ INT Input/
output
10 10 100 5 % Parameter set 1:
Stopping torque
PS1_ST_U INT Input/
output
30 20 100 5 % Parameter set 1:
Starting voltage
PS1_BRTM REAL Input/
output
0 0 2 Parameter set 1:
Breakaway time
PS1_STOP INT Input/
output
0 Parameter set 1:
Coasting method
0 = Coast-down without
load
2 = Torque control
3 = Pump Stop
4 = DC braking
5 = Combined braking
PS1_STMD INT Input/
output
5 Parameter set 1:
Startup mode
0 = Direct
1 = Voltage ramp
2 = Torque control
3 = Motor heating
5 = Voltage ramp + curr
limiting
6 = Trq ctrl + curr limiting
PS1_STPTM REAL Input/
output
10 0 360 0.1 s Parameter set 1:
Coast-down time
PS1_STTM REAL Input/
output
20 0 360 0.1 s Parameter set 1:
Starting time
PS1_STTQ INT Input/
output
50 10 100 5 % Parameter set 1:
Starting torque
PS1_THMCAP INT Input/
output
20 1 100 1 % Parameter set 1:
Motor thermal capacity
PS1_CCWSSPD INT Input/
output
7 3 21 1 Parameter set 1:
Slow speed factor CCW
PS1_CCWSTQ INT Input/
output
50 20 100 5 % Parameter set 1:
Slow torque CCW
PS1_CURH REAL Input/
output
112.5 50 150 3,13 % Parameter set 1:
Upper current limit
(warn/trip)
PS1_CURL REAL Input/
output
18.75 18,75 100 3,13 % Parameter set 1:
Lower current limit
(warn/trip)
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 81
Name of
parameter
Data format Type Default
value
Value
range
Factor Meaning
PS1_CWSSPD INT Input/
output
7 3 21 1 Parameter set 1:
Slow speed factor CW
PS1_CWSTQ INT Input/
output
50 20 100 5 % Parameter set 1:
Slow torque CW
PS1_TM_MAX REAL Input/
output
0 0 1000 0.1 s Parameter set 1:
Max. starting time
PS1_TQRATE INT Input/
output
0 0 65535 1 nm Parameter set 1:
Rated torque
PS2_SPDRATE INT Input/
output
1500 500 3600 1 rpm Parameter set 2:
Rated speed
PS2_STMD INT Input/
output
5 1 nm Parameter set 2:
Startup mode
0 = Direct
1 = Voltage ramp
2 = Torque control
3 = Motor heating
5 = Voltage ramp + curr
limiting
6 = Trq ctrl + curr limiting
PS2_BRKTQ INT Input/
output
50 20 100 5 % Parameter set 2:
Braking torque
PS2_DYNTQ INT Input/
output
50 20 100 5 % Parameter set 2:
Dynamic braking torque
PS2_BR_U INT Input/
output
80 40 100 5 % Parameter set 2:
Breakaway voltage
PS2_BRTM REAL Input/
output
0 0 2 0.01 s Parameter set 2:
Breakaway time
PS2_CURLM REAL Input/
output
450 12 550 3,13 % Parameter set 2:
Current limiting value
PS2_LMTQ INT Input/
output
150 20 200 5 % Parameter set 2:
Limiting torque
PS2_SPTQ INT Input/
output
10 10 100 5 % Parameter set 2:
Stopping torque
PS2_ST_U INT Input/
output
30 20 100 5 % Parameter set 2:
Starting voltage
PS2_STTM REAL Input/
output
20 0 360 0.1 s Parameter set 2:
Starting time
PS2_STTQ INT Input/
output
50 10 100 5 % Parameter set 2:
Starting torque
PS2_TM_MAX REAL Input/
output
0 0 1000 01 s Parameter set 2:
Max. starting time
PS2_TQRATE INT Input/
output
0 0 65535 Parameter set 2:
Rated torque
PS2_CCWSSPD INT Input/
output
7 3 21 1 Parameter set 2:
Slow speed factor CCW
PS2_CCWSTQ INT Input/
output
50 20 100 5 % Parameter set 2:
Slow torque CCW
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
82 Programming and Operating Manual, 11/2010, A5E02845977020-02
Name of
parameter
Data format Type Default
value
Value
range
Factor Meaning
PS2_CURH REAL Input/
output
112.5 50 150 3,10 % Parameter set 2:
Upper current limit
(warn/trip)
PS2_CURL REAL Input/
output
18.75 18.75 100 3,13 % Parameter set 2:
Lower current limit
(warn/trip)
PS2_CWSSPD INT Input/
output
7 3 21 1 Parameter set 2:
Slow speed factor CW
PS2_CWSTQ INT Input/
output
50 20 100 5 % Parameter set 2:
Slow torque CW
PS2_STOP INT Input/
output
0 Parameter set 2:
Coasting method
0 = Coast-down without
load
2 = Torque control
3 = Pump Stop
4 = DC braking
5 = Combined braking
PS2_STPTM REAL Input/
output
10 0 360 0.1 s Parameter set 2:
Coast-down time
PS2_THMCAP INT Input/
output
20 1 100 1 % Parameter set 2:
Motor thermal capacity
PS3_BR_U INT Input/
output
80 40 100 5 % Parameter set 3:
Breakaway voltage
PS3_BRKTQ INT Input/
output
50 20 100 5 % Parameter set 3:
Braking torque
PS3_CURLM REAL Input/
output
450 125 550 3,13 % Parameter set 3:
Current limiting value
PS3_DYNTQ INT Input/
output
50 20 100 5 % Parameter set 3:
Dynamic braking torque
PS3_LMTQ INT Input/
output
150 20 200 5 % Parameter set 3:
Limiting torque
PS3_SPDRATE INT Input/
output
1500 500 3600 1 rpm Parameter set 3:
Rated speed
PS3_SPTQ INT Input/
output
10 10 100 5 % Parameter set 3:
Stopping torque
PS3_ST_U INT Input/
output
30 20 100 5 % Parameter set 3:
Starting voltage
PS3_STMD INT Input/
output
5 Parameter set 3
Startup mode
0 = Direct
1 = Voltage ramp
2 = Torque control
3 = Motor heating
5 = Voltage ramp + curr
limiting
6 = Trq ctrl + curr limiting
PS3_STTM REAL Input/
output
20 0 360 0.1 s Parameter set 3:
Starting time
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 83
Name of
parameter
Data format Type Default
value
Value
range
Factor Meaning
DEL_LOGEVNT BOOL Input/
output
FALSE Delete Logbook - Events
DEL_LOGTRP BOOL Input/
output
FALSE Delete Logbook -
Triggering operations
PS3_BRTM REAL Input/
output
0 0 2 0.01 s Parameter set 3:
Breakaway time
PS3_CCWSSPD INT Input/
output
7 3 21 1 Parameter set 3:
Slow speed factor CCW
PS3_CCWSTQ INT Input/
output
50 20 100 5 % Parameter set 3:
Slow torque CCW
PS3_CURH REAL Input/
output
112.5 50 150 3,13 % Parameter set 3:
Upper current limit
(warn/trip)
PS3_CURL REAL Input/
output
18.75 18,75 100 3,13 % Parameter set 3:
Lower current limit
(warn/trip)
PS3_CWSSPD INT Input/
output
7 3 21 1 Parameter set 3:
Slow speed factorCW
PS3_STTQ INT Input/
output
50 10 100 5 % Parameter set 3:
Starting torque
PS3_TM_MAX REAL Input/
output
0 0 1000 0.1 s Parameter set 3:
Max. starting time
PS3_TQRATE INT Input/
output
0 0 65535 1 nm Parameter set 3:
Rated torque
PS3_CWSTQ INT Input/
output
50 20 100 5 % Parameter set 3:
Slow torque CW
PS3_STOP INT Input/
output
0 Parameter set 3:
Coasting method
0 = Coast-down without
load
2 = Torque control
3 = Pump Stop
4 = DC braking
5 = Combined braking
PS3_STPTM REAL Input/
output
10 0 360 0.1 s Parameter set 3:
Coast-down time
PS3_THMCAP INT Input/
output
20 1 100 1 % Parameter set 3:
Motor thermal capacity
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
84 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.5.11 Block parameters for the Outputs
Table 3- 44 Parameters of the SS_DIR block
Name of
parameter
Data format Type Default
value
Value
range
Factor Meaning
OUT_01* WORD Output 16#00 Value of process image
output DP 0.0 1.7
ERRORNUM INT Output - 1 Error number
LOGDS INT Output 0 Logbook:
Record
LOGID1 INT Output 0 Logbook:
Message no. 1
LOGID10 INT Output 0 Logbook:
Message no. 10
LOGID11 INT Output 0 Logbook:
Message no. 11
LOGID12 INT Output 0 Logbook:
Message no. 12
LOGID13 INT Output 0 Logbook:
Message no. 13
LOGID14 INT Output 0 Logbook:
Message no. 14
LOGID15 INT Output 0 Logbook:
Message no. 15
LOGID16 INT Output 0 Logbook:
Message no. 16
LOGID17 INT Output 0 Logbook:
Message no. 17
LOGID18 INT Output 0 Logbook:
Message no. 18
LOGID19 INT Output 0 Logbook:
Message no. 19
LOGID2 INT Output 0 Logbook:
Message no. 2
LOGID20 INT Output 0 Logbook:
Message no. 20
LOGID21 INT Output 0 Logbook:
Message no. 21
LOGID3 INT Output 0 Logbook:
Message no. 3
LOGID4 INT Output 0 Logbook:
Message no. 4
LOGID5 INT Output 0 Logbook:
Message no. 5
LOGID6 INT Output 0 Logbook:
Message no. 6
LOGID7 INT Output 0 Logbook:
Message no. 7
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 85
Name of
parameter
Data format Type Default
value
Value
range
Factor Meaning
LOGID8 INT Output 0 Logbook:
Message no. 8
LOGID9 INT Output 0 Logbook:
Message no. 9
LOGTIME1 DWORD Output 16#00 Logbook:
Time 1
LOGTIME10 DWORD Output 16#00 Logbook:
Time 10
LOGTIME11 DWORD Output 16#00 Logbook:
Time 11
LOGTIME12 DWORD Output 16#00 Logbook:
Time 12
LOGTIME13 DWORD Output 16#00 Logbook:
Time 13
LOGTIME14 DWORD Output 16#00 Logbook:
Time 14
LOGTIME15 DWORD Output 16#00 Logbook:
Time 15
LOGTIME16 DWORD Output 16#00 Logbook:
Time 16
LOGTIME17 DWORD Output 16#00 Logbook:
Time 17
LOGTIME18 DWORD Output 16#00 Logbook:
Time 18
LOGTIME19 DWORD Output 16#00 Logbook:
Time 19
LOGTIME2 DWORD Output 16#00 Logbook:
Time 2
LOGTIME20 DWORD Output 16#00 Logbook:
Time 20
LOGTIME21 DWORD Output 16#00 Logbook:
Time 21
LOGTIME3 DWORD Output 16#00 Logbook:
Time 3
LOGTIME4 DWORD Output 16#00 Logbook:
Time 4
LOGTIME5 DWORD Output 16#00 Logbook:
Time 5
LOGTIME6 DWORD Output 16#00 Logbook:
Time 6
LOGTIME7 DWORD Output 16#00 Logbook:
Time 7
LOGTIME8 DWORD Output 16#00 Logbook:
Time 8
LOGTIME9 DWORD Output 16#00 Logbook:
Time 9
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
86 Programming and Operating Manual, 11/2010, A5E02845977020-02
Name of
parameter
Data format Type Default
value
Value
range
Factor Meaning
QAUTOP BOOL Output FALSE Status:
1 = Operator may enter
Auto.
QCURR REAL Output 0 Actual motor current
QDIAG DWORD Output 16#00 3RW44 PROFIBUS DP
slave diagnostics
QDIAGCOM DWORD Output 16#00 Diagnostics:
Communication, switching,
and controlling
QDIAGPAR DWORD Output 16#00 Diagnostics:
Parameters and device
function
QDSQSTPOP BOOL Output TRUE Status:
1 = Operator may enter
Disable Quick Stop.
QEMSTOP BOOL Output TRUE Status:
1 = Operator may enter
Emergency start.
QEN_RDWR BOOL Output FALSE 1 = Enable read and write
data sets
QERR_RD BOOL Output FALSE 1 = Error while reading a
data set
QERR_WR BOOL Output FALSE 1 = Error while writing a
data set
QFLTPAR WORD Output 16#00 Diagnostics for invalid
parameter numbers
QGRPERR BOOL Output FALSE 1 = Group error
QMAN_AUT BOOL Output FALSE 1 = Auto mode
2 = Manual mode
QMANOP BOOL Output FALSE Status 1:
Operator may enter
Manual.
QMODF BOOL Output FALSE 1 = Module failure
QMON_ERR BOOL Output FALSE 1 = Monitoring error
QMOT_CCW BOOL Output FALSE Motor CCW active
QMOT_CW BOOL Output FALSE Motor CW active
QMOT_SLSPD BOOL Output FALSE Motor in slow speed active
QMOTCCWOP BOOL Output TRUE Status 1:
Operator may enter Motor
CCW.
QMOTCWOP BOOL Output TRUE Status 1:
Operator may enter Motor
CW.
QMOTOFOP BOOL Output TRUE Status 1:
Operator may enter Motor
OFF.
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 87
Name of
parameter
Data format Type Default
value
Value
range
Factor Meaning
QMSG_ACK WORD Output 16#00 ALARM_8P:
ACK_STATE output
QMSG_ERR BOOL Output FALSE 1 = Error during data
transfer
QMSG_STAT WORD Output 16#00 ALARM_8P:
Status output
QOUT1OP BOOL Output TRUE Status 1:
Operator may enter OUT1.
QOUT2OP BOOL Output TRUE Status 1:
Operator may enter OUT2.
QOUTPUT1 BOOL Output FALSE Value of process image
output 1 DP 1.0
QOUTPUT2 BOOL Output FALSE Value of process image
output 2 DP 1.1
QRACKF BOOL Output FALSE 1 = Rack failure
QRAMP_ON BOOL Output FALSE Ramp operation active
QREMOTE BOOL Output FALSE 1 = Remote
0 = Manual LOCAL
QSLSPDOP BOOL Output TRUE Status 1:
Operator may enter Slow
speed.
QTRPRSTOP BOOL Output TRUE Status 1:
Operator may enter Trip
reset.
QUALITY BYTE Output 16#80 Quality code
VSTATUS DWORD Output 16#00000000 Status information
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
88 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.5.12 Faceplates
3.5.12.1 General
Table 3- 45 Signal block for direct starter control function SS_DIR: Faceplates with their associated
PDL file names
Faceplate PDL file name
Standard @PG_SS_DIR_STANDARD.pdl
Maintenance @PG_SS_DIR_MAINTENANCE.pdl
Process image @PG_SS_DIR_PROCESSIMAGE.pdl
Limits @PG_SS_DIR_LIMITS.pdl
Parameter @PG_SS_DIR_PARAMETER.pdl
Parameter set 1 @PG_SS_DIR_PARAMETERSET1.pdl
Parameter set 2 @PG_SS_DIR_PARAMETERSET2.pdl
Parameter set 3 @PG_SS_DIR_PARAMETERSET3.pdl
Logbook @PG_SS_DIR_LOGBOOK.pdl
Station diagnostics @PG_SS_DIR_STATION_DIAG.pdl
Control diagnostics:
Controlling, switching, and
communication
@PG_SS_DIR_CONTROL_DIAG.pdl
Device diagnostics @PG_SS_DIR_DEVICE_DIAG.pdl
Parameter diagnostics @PG_SS_DIR_PARAMETER_DIAG.pdl
Alarms @PCS7_SS_ALARM.pdl
Trend @PCS7_SS_TREND.pdl
Batch @PCS7_SS_BATCH.pdl
Block icon @PCS7Typicals_SS.pdl.
See also
Faceplates (Page 15)
Block icons (Page 22)
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 89
3.5.12.2 Standard View
2
1
5
8
3
4
6
7

AUT_ON_OP , QMAN_AUT,
QMANOP, QAUTOP
Changes the operating mode of the block.
This control function is available to users with authorization
level 5 and higher. The user can define the text on the button:
String_0 and String_1 attribute of AUT_ON_OP.
MOTCW_OP, QMOTCWOP,
MOTCCW_OP, QMOTCCWOP,
MOTOF_OP, QMOTOFOP
Buttons used to start the motor in the clockwise or counter-
clockwise direction.
Slow speed must be activated in order to start the motor in the
counter-clockwise direction.
This control function is available to users with authorization
level 5 and higher. The user can define the text on the button:
String_1 attributes of MOTCCW_OP, MOTOF_OP,
MOTCW_OP.
LOCK, LOCK_ON, LOCK_DIR The symbols indicate the enable for the lock of the block
according to the direction of rotation.
SLSPD_OP, QSLSPDOP Activates or deactivates the slow speed function.
This control function is available to users with authorization
level 5 and higher. The user can define the text on the button:
String_1 attributes of SLSPD_OP.
TRPRST_OP, QTRPRSTOP Executes a Trip reset.
This control function is available to users with authorization
level 5 and higher. The user can define the text on the button:
String_1 attributes of TRPRST_OP.
VSTATUS Indicates the status of the block.
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
90 Programming and Operating Manual, 11/2010, A5E02845977020-02
QCURR Motor current
VSTATUS Indicates the status of the motor:

Symbol RUN CW

Symbol RUN CCW

Symbol STOP
Figure 3-2 SS_DIR: Standard View
See also
Operating modes (Page 47)
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 91
3.5.12.3 Maintenance View
2
4
5
8
6
9
7
1
3

EN_STAT This button opens the faceplate for the statistics block.
This control function is available to users with authorization level 5 and higher.
SUB_VALUE Activates or deactivates substitute values and sets the active parameter set.
This control function is available to users with authorization level 6 and higher.
START_OFF Sets the Response to CPU/master stop.
This control function is available to users with authorization level 6 and higher.
OUT1_O2 Activates or deactivates the Output2 function.
This control function is available to users with authorization level 6 and higher.
OUT1_OP Activates or deactivates the Output1 function.
This control function is available to users with authorization level 6 and higher.
DSQSTP_OP Activates or deactivates the Disable Quick Stop function.
This control function is available to users with authorization level 6 and higher.
EMRGST_OP Activates or deactivates the Emergency start function.
This control function is available to users with authorization level 6 and higher.
TIME_MON Entry for Monitoring time.
MONITOR Activates or deactivates the Monitoring function.
Figure 3-3 SS_DIR: Maintenance View
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
92 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.5.12.4 Process Image View
1 2

VSTATUS Process image input
VSTATUS Process image output
Figure 3-4 SS_DIR: Process Image View
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 93
3.5.12.5 Limits View
2
1
3
4
6
5

QCURR, PS_COMMON,
PS1_IRATE, PS1_CURH,
PS1_CURL, PS2_IRATE,
PS2_CURH, PS2_CURL,
PS3_IRATE, PS3_CURH,
PS3_CURL
Displays the current as a bar diagram for parameter sets 1, 2,
and 3.
Based on the setting in the "Response to current limit value
violation" field of the Parameters View, the colors of the limits in
the columns change from yellow (= warning) to red (= trip).
QCURR Indicates the motor current for the selected parameter set. The
selected parameter set is highlighted in a different color.
PS1_CURH, PS1_CURL Parameter set 1 current limits
This control function is available to users with authorization
level 6 and higher.
PS2_CURH, PS2_CURL Parameter set 2 current limits
This control function is available to users with authorization
level 6 and higher.
PS3_CURH, PS3_CURL Parameter set 3 current limits
This control function is available to users with authorization
level 6 and higher.
ReadData Button for enabling reading of data.
This control function is available to users with authorization
level 5 and higher. The user can define the text on the button:
String_1 attribute of RD_DATA
Figure 3-5 SS_DIR: Limits View
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
94 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.5.12.6 Parameters View
2
1
4
5
7
6
14
15
13
11
12
8 9
10
3

PS_COMMON Activates or deactivates the Group diagnostics.
This control function is available to users with authorization level 6
and higher.
PS_COMMON Activates or deactivates the Protection against voltage failure.
This control function is available to users with authorization level 6
and higher.
PS_COMMON Sets the Response to ground fault
This control function is available to users with authorization level 6
and higher.
PS_TMPSNSR,
PS_OVLSEN
Parameters for Motor temperature sensor
This control function is available to users with authorization level 6
and higher.
PS_COMMON,
PS_ASYLIM
Parameters for Asymmetry
This control function is available to users with authorization level 6
and higher.
PS_COMMON Parameters for Current limiting
This control function is available to users with authorization level 6
and higher.
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 95
PS_OUT1, PS_OUT2,
PS_OUT3
Specifies actions for the various outputs.
This control function is available to users with authorization level 6
and higher.
EN_MEAS This button opens the faceplate for the SS_MEAS block.
This control function is available to users with authorization level 5
and higher.
ReadData Button for enabling reading of data.
This control function is available to users with authorization level 5
and higher.
The user can define the text on the button: String_1 attribute of
RD_DATA
PS_IN1, PS_IN2,
PS_IN3, PS_IN4
Specifies actions for the various inputs.
This control function is available to users with authorization level 6
and higher.
PS_COMMON Parameters for Contact block
This control function is available to users with authorization level 6
and higher.
PS_OVLRES,
PS_RCRYTM
Parameters for Motor overload
This control function is available to users with authorization level 6
and higher.
PS_MTRHT, PS_TRPTM Parameters for Prewarning limit
This control function is available to users with authorization level 6
and higher.
PS_TRPCLS, PS_IDLTM Parameters for Thermal motor model
This control function is available to users with authorization level 6
and higher.
PS_SETACT Selection of active parameter set
This control function is available to users with authorization level 5
and higher.
Figure 3-6 SS_DIR: Parameters View
3.5.12.7 Parameters View and views for Parameter set 1 to Parameter set 3

Note
Parameter set 1, Parameter set 2, Parameter set 3
The settings in the "Startup mode" and "Coasting method" fields determine whether or not
the field for assigning settings for the soft starter is enabled.

Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
96 Programming and Operating Manual, 11/2010, A5E02845977020-02
Parameter Set 1 View
2
1
3

PS1_IRATE, PS1_SPDRATE,
PS1_TQRATE
Basic parameters of Parameter set 1
This control function is available to users with
authorization level 6 and higher.
PS1_STMD, PS1_ST_U, PS1_STTQ,
PS1_LMTQ, PS1_CURLM, PS1_STTM,
PS1_TM_MAX, PS1_BR_U,
PS1_BRTM, PS1_THMCAP,
PS1_STOP, PS1_STPTM, PS1_SPTQ,
PS1_CWSSPD, PS1_CCWSSPD,
PS1_CWSTQ, PS1_CCWSTQ,
PS1_BRKTQ, PS1_DYNTQ
Control functions of Parameter set 1
This control function is available to users with
authorization level 6 and higher.
RD_DATA Button for enabling reading of data.
This control function is available to users with
authorization level 5 and higher.
The user can define the text on the button: String_1
attribute of RD_DATA
Figure 3-7 SS_DIR: Parameter Set 1 View
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 97
Parameter Set 2 View
2
1
3

PS2_IRATE, PS2_SPDRATE,
PS2_TQRATE
Basic parameters of Parameter set 2
This control function is available to users with
authorization level 6 and higher.
PS2_STMD, PS2_ST_U, PS2_STTQ,
PS2_LMTQ, PS2_CURLM, PS2_STTM,
PS2_TM_MAX, PS2_BR_U,
PS2_BRTM, PS2_THMCAP,
PS2_STOP, PS2_STPTM, PS2_SPTQ,
PS2_CWSSPD, PS2_CCWSSPD,
PS2_CWSTQ, PS2_CCWSTQ,
PS2_BRKTQ, PS2_DYNTQ
Control functions of Parameter set 2
This control function is available to users with
authorization level 6 and higher.
RD_DATA Button for enabling reading of data.
This control function is available to users with
authorization level 5 and higher.
The user can define the text on the button: String_1
attribute of RD_DATA
Figure 3-8 SS_DIR: Parameter Set 2 View
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
98 Programming and Operating Manual, 11/2010, A5E02845977020-02
Parameter Set 3 View
2
1
3

PS3_IRATE, PS3_SPDRATE,
PS3_TQRATE
Basic parameters of Parameter set 3
This control function is available to users with
authorization level 6 and higher.
PS3_STMD, PS3_ST_U, PS3_STTQ,
PS3_LMTQ, PS3_CURLM, PS3_STTM,
PS3_TM_MAX, PS3_BR_U,
PS3_BRTM, PS3_THMCAP,
PS3_STOP, PS3_STPTM, PS3_SPTQ,
PS3_CWSSPD, PS3_CCWSSPD,
PS3_CWSTQ, PS3_CCWSTQ,
PS3_BRKTQ, PS3_DYNTQ)
PS3_STMD, PS3_ST_U, PS3_STTQ,
PS3_LMTQ, PS3_CURLM, PS3_STTM,
PS3_TM_MAX, PS3_BR_U,
PS3_BRTM, PS3_THMCAP,
PS3_STOP, PS3_STPTM, PS3_SPTQ,
PS3_CWSSPD, PS3_CCWSSPD,
PS3_CWSTQ, PS3_CCWSTQ,
PS3_BRKTQ, PS3_DYNTQ
Control functions of Parameter set 3
This control function is available to users with
authorization level 6 and higher.
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 99
RD_DATA Button for enabling reading of data.
This control function is available to users with
authorization level 5 and higher.
The user can define the text on the button: String_1
attribute of RD_DATA
Figure 3-9 SS_DIR: Parameter Set 3 View
3.5.12.8 Logbook View
2 1 3

DEL_LOGEVNT This control function is available to users with authorization level 5 and higher.
The user can define the text on the button:
String_1 attribute of DEL_LOGEVNT
DEL_LOGTRP This control function is available to users with authorization level 5 and higher.
The user can define the text on the button:
String_1 attribute of DEL_LOGTRP
Refresh logbook
This control function is available to users with authorization level 5 and higher.
Figure 3-10 SS_DIR: Logbook View
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
100 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.5.12.9 Views: Station Diagnostics, Control Diagnostics, Device Diagnostics, and Parameter
Diagnostics
Station Diagnostics View

Figure 3-11 SS_DIR: View: Station diagnostics
QDIAG - For a list of parameters, refer to Chapter:
Diagnostics (Page 55)
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 101
Control Diagnostics View - Switching, controlling, and communication

Figure 3-12 SS_DIR: Control Diagnostics View - Switching, controlling, and communication
QDIAGCOM - For a list of parameters, refer to Chapter:
Diagnostics (Page 55)
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
102 Programming and Operating Manual, 11/2010, A5E02845977020-02
Device Diagnostics View

Figure 3-13 SS_DIR: Device Diagnostics View
QDIAGPAR - For a list of parameters, refer to Chapter:
Diagnostics (Page 55)
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 103
Parameter Diagnostics View

Figure 3-14 SS_DIR: Parameter Diagnostics View
QDIAGPAR, QFLTPAR - For a list of parameters, refer to Chapter:
Diagnostics (Page 55)
See also
Slave diagnostics of the 3RW44 (Page 32)
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
104 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.5.12.10 Block icon
Structure of block symbol
2
1
3
4
5
6
7

"G" on white background = Group error
Indicates the operating mode:
"L" on white background = Manual operation LOCAL
"R" on white background = Remote
Indicates the operating mode of the block:
"M" on white background = Manual
"A" on green background = Auto
Indicates the enable for the lock of the block.
"L" on white background: LOCK or LOCK_ON
Header: displays the name of the tag
Indicates the status of the motor: VSTATUS.
e.g.:

Symbol RUN CW

Symbol RUN CCW

Symbol STOP
The symbol flashes when the motor is in the startup or coast-down phase.
Group display
Reads the message configuration of the block and displays alarms and warnings.
Figure 3-15 SS_DIR: Block symbol
Right-clicking on the group representation of the block symbol opens the Alarm View of the
block.
Soft starter blocks
3.6 SS_MEAS: Measurement block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 105
3.6 SS_MEAS: Measurement block
3.6.1 Description

Block type and number: FB 564
Product group: 3RW44
Purpose of block
The SS_MEAS block provides:
Measurement information regarding:
Phase currents
Thermal motor model
Output power
Phase-to-phase voltages
Line frequency
Asymmetry
...
Information regarding diagnostics of measurement parameters
The block receives information from the SS_DIAG and SS_DIR blocks.
See also
Error numbers (Page 26)
Quality codes (Page 27)
Module drivers of the soft starter (Page 129)
Interconnection of function blocks (Page 40)
CFC charts for 3RW44 soft starter (Page 137)
Technical data (Page 141)
Soft starter blocks
3.6 SS_MEAS: Measurement block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
106 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.6.2 Calling OBs
The "Generate Module Driver" function automatically inserts the block into the following
organization blocks within the run sequence of the CFC:
Table 3- 46 Organization blocks that call the SS_MEAS block
Organization block Description
OB 30 OB 38 Cyclic interrupts
OB 100 Warm restart
Recommendation:
You are recommended to insert the block SS_DIR into OB 32 for cyclic operation.
See also the CFC manual.
3.6.3 Called blocks
The block calls the following blocks:
Table 3- 47 Blocks called by the SS_MEAS block
Block Description
SFB 35 ALARM_8P Generates block-specific messages with values for eight
signals
SFB 52 RDREC Reads a data set
SFC 6 RD_SINFO Reads the OB start information
Soft starter blocks
3.6 SS_MEAS: Measurement block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 107
3.6.4 Parameterization
LADDR, DADDR: Assigning the logical address
The module driver parameterizes the logical address LADDR and the diagnostics address
DADDR of the soft starter automatically.
Interconnection
In addition, set: IN_01 = PII address (logical address).
See also
CFC charts for 3RW44 soft starter (Page 137)
3.6.5 Operating modes
Manual operation LOCAL/REMOTE
The specified operating mode is displayed at the QREMOTE output.
1 = Remote
2 = Manual operation LOCAL/Soft Starter ES
Soft starter blocks
3.6 SS_MEAS: Measurement block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
108 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.6.6 Functions
Reading measured values
All measured values are read from:
Data set 94:
The "call RDREC()" function reads data set 94.
Data set 92:
The SS_DIAG block reads data set 92. The related measurement information is passed
to the SS_MEAS block.

EN_RD = TRUE : Read data set
RD_DATA = 1 : Operating parameter for reading measured values
L_RD_DATA = 1 : Linkable parameter for reading measured values. This is a signal
with rising edge.
QERR_RD = 1 : Error when reading data sets.
Measurement functions
For detailed information on measured values, refer to the "SIRIUS Soft Starter 3RW44"
System Manual > Chapter "Communication Module PROFIBUS DP" > "Data Sets" > "Data
Set 94 - Reading the Measured Values".
These values are displayed in the faceplate in the Standard View and Standard 2 View.
Table 3- 48 Data set 94: Access
No. Data set no. Read/write Number of
bytes
Data set description
1 94 R 64 Read measured values
"R" = Read access
Soft starter blocks
3.6 SS_MEAS: Measurement block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 109
Measurement functions of device diagnostics
The SS_DIAG block reads data set 92 "Read device diagnostics". The measured values of
the device diagnostics are passed to the SS_MEAS block. They are displayed there in the
Protection Diagnostics View.
Table 3- 49 List of measured values of device diagnostics
Name of output parameter Structured characteristic
map
DIAG_MEAS
QDIAGMEAS bit
no.
Description
TMPSNSOVLD 0 Temperature sensor overload
TMPSNSOPEN 1 Temperature sensor wire break
TMPSNSSHORT 2 Temperature sensor short-circuit
TMMOVLD 3 Thermal motor model overload
OVLDSWOFF 4 Overload switch off
IDLETMACT 5 Idle time active
COOLDNTMACT 6 Cooling time active
ASYMREC 7 Asymmetry detected
ASYMSWOFF 8 Asymmetry tripping
CURHI 9 Current limit overshot
CURLO 10 Current limit undershot
CURLMSWOFF 11 Ie limit value tripping
MOTSTLSWOFF 12 Motor block tripping
INPUT1 13 Input 1 active
INPUT2 14 Input 2 active
INPUT3 15 Input 3 active
INPUT4 16 Input 4 active
GNDFLT 17 Ground fault
GNDFLTSWOFF 18 Ground fault tripping
TMMDEACT 19 Thermal motor model deactivated
PHANGCTRFLT 20 Generalized phase error
COOLCNTACT 21 Contact block cooling time active
CTNHOTSTART 22 Contact block too hot for start
CUROVERFLOW 23 Current measuring range exceeded
PREWRNUNDSHT 24 Prewarning limit - prewarning time
undershot
PREWRNHTEXED 25 Prewarning limit - motor heating overshot
QDIAGMEAS:
Measurement parameter
diagnostics
26 31 Reserved
Soft starter blocks
3.6 SS_MEAS: Measurement block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
110 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.6.7 Message features
Messages
The following messages are generated:
Table 3- 50 Output messages
Input parameter Message
no.
Parameter Message Message
class
1 DIAG_MEAS.TMPSNSOVLD $$BlockComment$$Temperature Sensor
Overload
S
2 DIAG_MEAS.TMMOVLD $$BlockComment$$ Thermal motor model
overload
S
3 DIAG_MEAS.CURHI $$BlockComment$$ Current limit
exceeded
S
4 DIAG_MEAS.CURLO $$BlockComment$$ Current limit
undershot
S
5 MSG_5
1)
$$BlockComment$$ Message Input 5 A
6 MSG_6
1)
$$BlockComment$$ Message Input 6 A
7 MSG_7
1)
$$BlockComment$$ Message Input 7 A
MSG_EVID
3)

8 MSG_8
2)
$$BlockComment$$ Message Input 8 A
1) The MSG_5 and MSG_7 can be user-configured.
2) The MSG_8 message is reserved.
3) Parameters with message number for ALARM_8P.

Soft starter blocks
3.6 SS_MEAS: Measurement block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 111
Table 3- 51 Structure of the related values in ALARM_8P
Message
no.
Related value Parameter Meaning
1 1 AUX_PR01
1)
Auxiliary value 1
2 2 AUX_PR02
1)
Auxiliary value 2
3 3 AUX_PR03
1)
Auxiliary value 3
4 4 AUX_PR04
1)
Auxiliary value 4
5 5 AUX_PR05
1)
Auxiliary value 5
6 6 AUX_PR06
1)
Auxiliary value 6
7 7 AUX_PR07
1)
Auxiliary value 7
8 8 AUX_PR08
1)
Auxiliary value 8
9 9 AUX_PR09
1)
Auxiliary value 9
10 10 AUX_PR010
1)
Auxiliary value 10
1) The AUX_PR01 bis AUX_PR010 parameters represent auxiliary values for messages that can be user-configured.
The M_SUP_C input can enable and disable the messages. The QMS_STAT, QMSG_ACK
and QMSG_ERR parameters transfer the information found in ALARM_8P:
Status of messages
Status of an alarm acknowledgement
Status of errors during data transfer
3.6.8 Start-up characteristics
OB 100: Suppress all alarm messages
All alarm messages are suppressed in OB 100:
The user defines a value for RUNUPCY. This is assigned to OB 100 in order to suppress the
messages for the configured cycle count.
Soft starter blocks
3.6 SS_MEAS: Measurement block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
112 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.6.9 Block parameters
Table 3- 52 Parameters of the SS_MEAS block
Name of
parameter
Data format Type Default value Meaning
AUX_PR01 ANY Input Auxiliary value 1
AUX_PR02 ANY Input Auxiliary value 2
AUX_PR03 ANY Input Auxiliary value 3
AUX_PR04 ANY Input Auxiliary value 4
AUX_PR05 ANY Input Auxiliary value 5
AUX_PR06 ANY Input Auxiliary value 6
AUX_PR07 ANY Input Auxiliary value 7
AUX_PR08 ANY Input Auxiliary value 8
AUX_PR09 ANY Input Auxiliary value 9
AUX_PR010 ANY Input Auxiliary value 10
DADDR INT Input 0 Diagnostic address of module
DIAG_MEAS SSDIAGMEAS* Input Diagnostic information of SS_DIAG block
EN_RD BOOL Input FALSE 1 = Enable reading of data set
IN_01 WORD Input 16#00 Value of process image input DP 0.0 1.7
L_RD_DATA BOOL Input FALSE Linkable input 0 1:
Read data set
LADDR INT Input 0 Logical address of soft starter
M_SUP_C BOOL Input TRUE 1 = Suppress alarm
MODF BOOL Input FALSE 1 = Module failure
MSG_5 BOOL Input FALSE Message input 5
MSG_6 BOOL Input FALSE Message input 6
MSG_7 BOOL Input FALSE Message input 7
MSG_8 BOOL Input FALSE Message input 8
MSG_EVID DWORD Input 16#FF Number of the message event
RACKF BOOL Input FALSE 1 = Rack failure
RUNUPCYC INT Input 3 Number of cycles for which all messages are
suppressed.
SAMPLE_T REAL Input 0.1 Sampling time in s
RD_DATA BOOL Input/ output FALSE 1 = Read data from data set
ERRORNUM INT Output - 1 Error number
QASYMTRY INT Output 0 Asymmetry
QASYMTYEN BOOL Output FALSE 0 = No asymmetry
1 = Asymmetry 40%
QCNTCOLTM REAL Output 0 Remaining contact block cooling time
QCNTCT_HT INT Output 0 Contact block heating
QCURHI BOOL Output FALSE Current limit overshot
QCURLO BOOL Output FALSE Current limit undershot
QDIAGMEAS DWORD Output 16#00 Current diagnostics and thermal diagnostics
QEN_RD BOOL Output FALSE 1 = Enable reading of data set
Soft starter blocks
3.6 SS_MEAS: Measurement block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 113
Name of
parameter
Data format Type Default value Meaning
QERR_RD BOOL Output FALSE 1 = Error while reading a data set
QGRPERR BOOL Output FALSE 1 = Group error
QHTSNK_TMP INT Output 0 Contact block heating
QIL1 REAL Output 0 Phase current IL1 in %
QIL1E REAL Output 0 Effective phase current IL1 in amperes
QIL2 REAL Output 0 Phase current IL2 in %
QIL2E REAL Output 0 Effective phase current IL2 in amperes
QIL3 REAL Output 0 Phase current IL3 in %
QIL3E REAL Output 0 Effective phase current IL3 in amperes
QKW_OUT REAL Output 0 Output power in KW
QL_FREQ REAL Output 0 Line frequency
QMODF BOOL Output FALSE 1 = Module failure
QMOTCOLTM REAL Output 0 Remaining motor cooling time
QMOTHTBLD INT Output 0 Motor heating
QMSG_ACK WORD Output 16#00 ALARM_8P:
ACK_STATE output
QMSG_ERR BOOL Output FALSE 1 = Error during data transfer
QMSG_STAT WORD Output 16#00 ALARM_8P:
Status output
QOUT_FREQ REAL Output 0 Output frequency
QRACKF BOOL Output FALSE 1 = Rack failure
QREMOTE BOOL Output FALSE 1 = Remote
0 = Manual LOCAL
QTRPTM INT Output 0 Remaining time for tripping the thermal motor
model
QU_ELESUP REAL Output 0 Electronics supply voltage
QU_L1L2 REAL Output 0 Effective phase-to-phase voltage UL1-L2 in
volts
QU_L2L3 REAL Output 0 Effective phase-to-phase voltage UL2-L3 in
volts
QU_L3L1 REAL Output 0 Effective phase-to-phase voltage UL3-L1 in
volts
QUALITY BYTE Output 16#80 Quality code
VSTATUS DWORD Output 16#00 Status information
Soft starter blocks
3.6 SS_MEAS: Measurement block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
114 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.6.10 Faceplates
Table 3- 53 Measurement block SS_MEAS Faceplates with their associated PDL file names
Faceplate PDL file name
Standard @PG_SS_MEAS_STANDARD.pdl
Standard 2 @PG_SS_MEAS_STANDARD2.pdl
Protection diagnostics @PG_SS_MEAS_PROTECTION_DIAG.pdl
Alarms @PCS7_SS_ALARM.pdl
Trend @PCS7_SS_TREND.pdl
Soft starter blocks
3.6 SS_MEAS: Measurement block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 115
Standard View
2
1
3
4
5
6

QIL1, QIL1E, QIL2,
QIL2E, QIL3, QIL3E
Phase current in % and A
QMOTHTBLD Motor heating
QTRPTM: Remaining time for tripping thermal motor model
QMOTCOLTM Remaining motor cooling time
QKW_OUT Output power
ReadData Button for enabling reading of data.
This control function is available to users with authorization level 5
and higher.
The user can define the text on the button: String_1 attribute of
RD_DATA
Figure 3-16 SS_MEAS: Standard View
Soft starter blocks
3.6 SS_MEAS: Measurement block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
116 Programming and Operating Manual, 11/2010, A5E02845977020-02
Standard 2 View
2
1
8
3
4
6
7
5

QU_ELESUP Electronic supply voltage of 3RW44
QU_L1L2, QU_L2L3,
QU_L3L1
Phase-to-phase voltage
QL_FREQ Line frequency
QASYMTYEN Asymmetry 40%
QASYMTRY Asymmetry
QHTSNK_TMP Heat sink temperature
QCNTCT_HT Contact block heating
QCNTCOLTM Remaining contact block cooling time
ReadData Button for enabling reading of data.
This control function is available to users with authorization level 5
and higher.
The user can define the text on the button: String_1 attribute of
RD_DATA
Figure 3-17 SS_MEAS: Standard 2 View
Soft starter blocks
3.6 SS_MEAS: Measurement block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 117
Protection Diagnostics View
QDIAGMEAS - This view displays a maximum of 10 diagnostic messages.

Figure 3-18 SS_MEAS: Protection Diagnostics View
For a list of parameters, refer to Chapter:
Functions (Page 108)
Soft starter blocks
3.6 SS_MEAS: Measurement block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
118 Programming and Operating Manual, 11/2010, A5E02845977020-02
Block symbol of the SS_MEAS measurement block
2
1
3
4
5

Title with name of block
Phase current 1
Phase current 2
Phase current 3
Group display:
Indicates the status of alarms and warnings.
Reads the message configuration of the block for this view.
Figure 3-19 SS_MEAS: Block symbol
Right-clicking on the group representation of the block symbol opens the Alarm View of the
block.
See also
Faceplates (Page 15)
Block icons (Page 22)
Soft starter blocks
3.7 SS_STAT: Statistics block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 119
3.7 SS_STAT: Statistics block
3.7.1 Description

Block type and number: FB 563
Product group: 3RW44
Purpose of block
The SS_STAT block provides statistical information related to:
Operating hours
Operating cycles
Error statistics
Current measurement
Maximum pointer
...
The block receives information from the SS_DIAG and SS_DIR blocks.
See also
Error numbers (Page 26)
Quality codes (Page 27)
Module drivers of the soft starter (Page 129)
Interconnection of function blocks (Page 40)
CFC charts for 3RW44 soft starter (Page 137)
Technical data (Page 141)
Soft starter blocks
3.7 SS_STAT: Statistics block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
120 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.7.2 Calling OBs
The "Generate Module Driver" function automatically inserts the block into the following
organization blocks within the run sequence of the CFC:
Table 3- 54 Organization blocks that call the SS_MEAS block
Organization block Description
OB 30 OB 38 Cyclic interrupts
OB 100 Warm restart
Recommendation:
You are recommended to insert the block SS_DIR into OB 32 for cyclic operation.
See also the CFC manual.
3.7.3 Called blocks
The block calls the following blocks:
Table 3- 55 Blocks called by the SS_STAT block
Block Description
SFB 52 RDREC Reads a data set
SFB 53 WRREC Writes a data set
SFC 6 RD_SINFO Reads the start information of the OB
Soft starter blocks
3.7 SS_STAT: Statistics block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 121
3.7.4 Parameterization
IN_01: Assigning the input address of the module
I-address:
2 bytes of input address of the module must be assigned to input parameter IN_01.
LADDR: Assigning the logical address
The module driver parameterizes the logical address LADDR of the soft starter
automatically.
L DADDR: Diagnostic address
The module driver parameterizes the diagnostics address DADDR of the soft starter
automatically
See also
CFC charts for 3RW44 soft starter (Page 137)
3.7.5 Operating modes
Operating mode Manual operation LOCAL/REMOTE
The specified operating mode is displayed at the QREMOTE output.
1 = Remote
2 = Manual operation LOCAL/Soft Starter ES
Soft starter blocks
3.7 SS_STAT: Statistics block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
122 Programming and Operating Manual, 11/2010, A5E02845977020-02
3.7.6 Functions
Statistical values
For detailed information on statistical values, refer to the "SIRIUS Soft Starter 3RW44"
System Manual > Chapter "Communication Module PROFIBUS DP" > "Data Sets":
> Data Set 93 - "Writing a Command"
> Data Set 95 - "Reading the Statistics Data"
> Data Set 96 - "Reading the Maximum Pointer"
Table 3- 56 Data set 93, Data set 95, and Data set 96: Read access and/or write access
SI No. Data set no. Read/write Number of
bytes
Data set description
1 93 RW 10 Writing a command
2 95 R 90 Read statistics data
3 96 R 86 Read maximum pointer
"R" = Read access; "W" = Write access
The following parameters are active:

EN_RD = TRUE : Read data set
RD_DATA = 1 : Operating parameter for reading measured values
L_RD_DATA = 1 : Linkable parameter for reading measured values. This is a signal
with rising edge.
DEL_MXPTR = 1 : Delete maximum pointer values
QERR_RDWR = 1 : The reading/writing of the data set is finished.
QERR_RD = 1 : Error when reading data sets.
QERR_WR = 1 : Error when writing data sets.
Statistics function
Data set 95 reads the statistics data. These are displayed in the faceplate in Standard View.
Maximum pointer function
Data set 96 reads the maximum pointer information. These are displayed in the faceplate in
Maximum Pointer View.
Soft starter blocks
3.7 SS_STAT: Statistics block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 123
3.7.7 Block parameters
Table 3- 57 Parameters of the SS_STAT block
Name of
parameter
Data format Type Default value Meaning
DADDR INT Input 0 Diagnostic address of module
EN_RDWR BOOL Input TRUE 1 = Enable reading/writing of data set
IN_01 WORD Input 16#00 Value of process image input DP 0.0 1.7
L_RD_DATA BOOL Input FALSE Linkable input 0 1:
Read data set
LADDR INT Input 0 Logical address of soft starter
MODF BOOL Input FALSE 1 = Module failure
RACKF BOOL Input FALSE 1 = Rack failure
SAMPLE_T REAL Input 0.1 Sampling time in s
DEL_MXPTR BOOL Input/ output FALSE Maximum pointer reset
RD_DATA BOOL Input/ output FALSE 1 = Read data from data set
ERRORNUM INT Output - 1 Error number
QCNTCTMP INT Output 0 Maximum contact block heating
QEN_RDWR BOOL Output FALSE 1 = Enable read and write data sets
QERR_RD BOOL Output FALSE 1 = Error while reading a data set
QERR_WR BOOL Output FALSE 1 = Error while writing a data set
QGRPERR BOOL Output FALSE 1 = Group error
QHTSKMP INT Output 0 Maximum heat sink temperature
QIL1MAX REAL Output 0 Phase current IL1max in %
QIL1MAXE REAL Output 0 Effective phase current IL1max
QIL1MIN REAL Output 0 Phase current IL1min in %
QIL1MINE REAL Output 0 RMS phase current IL1min
QIL2MAX REAL Output 0 Phase current IL2max in %
QIL2MAXE REAL Output 0 RMS phase current IL2max
QIL3MAX REAL Output 0 Phase current IL3max in %
QIL3MAXE REAL Output 0 RMS phase current IL3max
QIL3MIN REAL Output 0 Phase current IL3min in %
QIL3MINE REAL Output 0 RMS phase current IL3min
QILTRPEMX REAL Output 0 RMS maximum tripping current
QILTRPMX REAL Output 0 Maximum tripping current in %
QL2MIN REAL Output 0 Phase current IL2min in %
QL2MINE REAL Output 0 RMS phase current IL2min
QLFREQMAX REAL Output 0 Maximum line frequency
QLFREQMIN REAL Output 0 Minimum line frequency
QM_IMAX REAL Output 0 Motor current Imax in %
QM_IMAXE REAL Output 0 RMS motor current Imax
QM_OPH DWORD Output 16#00000000 Motor operating hours
QMODF BOOL Output FALSE 1 = Module failure
Soft starter blocks
3.7 SS_STAT: Statistics block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
124 Programming and Operating Manual, 11/2010, A5E02845977020-02
Name of
parameter
Data format Type Default value Meaning
QN_BRKSTP DINT Output 0 Number of stops with electrical braking
QN_CNTTRP DINT Output 0 Number of contact block overload trips
QN_OVLTRP INT Output 0 Number of overload trips
QN_ST_CCW DINT Output 0 Number of motor starts CCW
QN_ST_CW DINT Output 0 Number of motor starts CW
QOHIL120MP DWORD Output 16#00000000 Maximum pointer:
Operating hours - motor current
= 120 1000% x Ie(max)
QOHIL18MP DWORD Output 16#00000000 Maximum pointer:
Operating hours - motor current
= 18 49.9% x Ie(max)
QOHIL50MP DWORD Output 16#00000000 Maximum pointer:
Operating hours - motor current
= 50 89.9% x Ie(max)
QOHIL90MP DWORD Output 16#00000000 Maximum pointer:
Operating hours - motor current
= 90 1199.9% x Ie(max)
QOPHIL120 DWORD Output 16#00000000 Operating hours - motor current
= 120 1000% x Ie(max)
QOPHIL18 DWORD Output 16#00000000 Operating hours - motor
current= 18 49.9% x Ie(max)
QOPHIL50 DWORD Output 16#00000000 Operating hours - motor
current= 50 89.9% x Ie(max)
QOPHIL90 DWORD Output 16#00000000 Operating hours - motor current= 90 1199.9
% x Ie(max)
QOUTPUT1 DINT Output 0 Number of starts - output 1
QOUTPUT2 DINT Output 0 Number of starts - output 2
QOUTPUT3 DINT Output 0 Number of starts - output 3
QOUTPUT4 DINT Output 0 Number of starts - output 4
QOVLTRPMP INT Output 0 Number of motor overload trips, e.g., motor
protection, temperature sensor, blocking
QRACKF BOOL Output FALSE 1 = Rack failure
QREMOTE BOOL Output FALSE 1 = Remote
0 = Manual LOCAL
QS_OPH DWORD Output 16#00000000 Starter operating hours
QS_OPHMP DWORD Output 16#00000000 Operating hours - Device:
Maximum pointer
QTRG_I REAL Output 0 Last tripping current IA in %
QTRG_IE REAL Output 0 Last tripping current IA RMS
QUALITY BYTE Output 16#80 Quality code
QUEL_MAX REAL Output 0 Max. electronics power supply
QUEL_MIN REAL Output 0 Min. electronics power supply
QUL1L2MAX REAL Output 0 RMS phase-to-phase voltage UL1-L2max
QUL1L2MIN REAL Output 0 RMS phase-to-phase voltage UL1-L2min
QUL2L3MAX REAL Output 0 RMS phase-to-phase voltage UL2-L3max
Soft starter blocks
3.7 SS_STAT: Statistics block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 125
Name of
parameter
Data format Type Default value Meaning
QUL2L3MIN REAL Output 0 RMS phase-to-phase voltage UL2-L3min
QUL3L1MAX REAL Output 0 RMS phase-to-phase voltage UL3-L1max
QUL3L1MIN REAL Output 0 RMS phase-to-phase voltage UL3-L1min
VSTATUS DWORD Output 16#00000000 Status information
3.7.8 Faceplates
Table 3- 58 Statistics block SS_STAT: Faceplates with their associated PDL file names
Name of view PDL file name
Standard @PG_SS_STAT_STANDARD.pdl
Maximum pointer @PG_SS_STAT_MAX_POINTER.pdl
Soft starter blocks
3.7 SS_STAT: Statistics block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
126 Programming and Operating Manual, 11/2010, A5E02845977020-02
Standard View
2
1
3
4
5

QS_OPH, QM_OPH Operating hours
QOPHIL18, QOPHIL50,
QOPHIL90, QOPHIL120
Operating hours motor current
QN_CNTTRP, QN_OVLTRP Fault statistics
QM_IMAX, QM_IMAXE,
QTRG_I, QTRG_IE
Current measuring
QN_ST_CW, QN_ST_CCW,
QN_BRKSTP, QOUTPUT1,
QOUTPUT2, QOUTPUT3,
QOUTPUT4
Operating cycles
ReadData: Button for enabling reading of data.
This control function is available to users with authorization
level 5 and higher.
The user can define the text on the button: String_1 attribute of
RD_DATA
Figure 3-20 SS_STAT: Standard View
Soft starter blocks
3.7 SS_STAT: Statistics block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 127
Maximum Pointer View
2
1
3
4
5
7 6
8
9
10
11

QS_OPHMP Operating hours - device
QOHIL18MP, QOHIL50MP,
QOHIL90MP, QOHIL120MP
Motor operating hours
QUEL_MIN, QUEL_MAX Electronics supply voltage
QLFREQMIN, QLFREQMAX Main energy monitoring
QUL1L2MIN, QUL1L2MAX,
QUL2L3MIN, QUL2L3MAX
Voltage measurement
QIL1MIN, QIL1MAX, QIL1MINE,
QIL1MAXE,QIL2MIN, QIL2MAX,
QIL2MINE, QIL2MAXE,QIL3MIN,
QIL3MAX, QIL3MINE, QIL3MAXE
Current measuring
DeleteMaxPntr Delete maximum pointer button
This button is only available in Fern mode.
This control function is available to users with
authorization level 5 and higher.
The user can define the text on the button: String_1
attribute of DEL_MXPTR
Soft starter blocks
3.7 SS_STAT: Statistics block
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
128 Programming and Operating Manual, 11/2010, A5E02845977020-02
ReadData Button for enabling reading of data.
This control function is available to users with
authorization level 5 and higher.
The user can define the text on the button: String_1
attribute of RD_DATA
QILTRPMX, QILTRPEMX Current measuring - maximum tripping current
QOVLTRPMP Fault statistics
QCNTCTMP Thermal contact block model
QHTSKMP Solid-state switching
Figure 3-21 SS_STAT: Maximum Pointer View
Block icon of the SS_STAT statistics block
2
1
3
4

Title with name of block
Operating hours of soft starter
Number of motor starts
Manual operation LOCAL or REMOTE:
"L" = Manual operation LOCAL
"R" = Remote
Figure 3-22 SS_STAT: Block icon
See also
Faceplates (Page 15)
Block icons (Page 22)

PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 129
Module drivers of the soft starter
4
4.1 Object lists and action lists
Hardware modules, among other things, are configured in HW Config.
Description
The object lists and the action lists are used to generate the module drivers for these
hardware modules.
The object list contains a unique object identification number for each of these hardware
modules. Each object list is assigned to a particular hardware configuration.
The action list contains a list of actions. These actions must be executed for the object
identification numbers that appear in the object list Examples of such actions include:
Assigning the device address
Interconnecting the input and output parameters of the driver block
The "Generate Module Driver" function generates the module drivers when the CFC is
compiled.
See also
Handling the driver generator (Page 10)
4.2 Requirements for generating the module drivers
Requirements
After generating an instance for a signal block, ensure that the following requirements are
met:
IN_01 and IN_02 are parameterized.
The driver blocks have been generated in the CFC with the "Generate module driver"
function when compiling the CFC chart.
Module drivers of the soft starter
4.3 Driver blocks
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
130 Programming and Operating Manual, 11/2010, A5E02845977020-02
4.3 Driver blocks
Following successful compilation of the signal blocks, specific driver blocks are generated
depending on the configuration.
Circuit diagrams

Figure 4-1 Circuit diagram: 3RW44 soft starter directly on the DP master system
Module drivers of the soft starter
4.3 Driver blocks
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 131

Figure 4-2 Circuit diagram: 3RW44 soft starter following a Y link

Note
The blocks highlighted in yellow generate the module drivers.

Module drivers of the soft starter
4.3 Driver blocks
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
132 Programming and Operating Manual, 11/2010, A5E02845977020-02
3RW44 soft starter directly on the DP master system - Configuration using the hardware catalog or a
GSD file
The following driver blocks and interconnections are generated when the CFC is compiled:
1. SS_DIAG - Diagnostics for the SIRIUS 3RW44 soft starter
2. OB_DIAG1 - OB diagnostic function
3. OB_BEGIN - CPU function block
4. MOD_PAX0 - Message diagnostics for PA slave DP V0 connected to the DP master
system
Table 4- 1 Interconnections generated when CFC is compiled
OB_DIAG1 OB_BEGIN MOD_PAX0 SS_DIAG SS_DIR SS_STAT SS_MEAS
QRACKF RACKF
EN_F EN EN
EN_DIAG EN_DIAG
SUBN1ERR SUBN1ERR
SUBN2ERR SUBN2ERR
RAC_DIAG RAC_DIAG
CPU_DIAG CPU_DIAG
MODF QMODF
MODE_00 OMODE
QC_00 QUALITY
PA_DIAG PA_DIAG
QEN_RD EN_RDWR EN_RDWR EN_RD
DIAG_DIR DIAG_DIR
DIAG_MEAS DIAG_MEAS
OMODE_00 MODE MODE MODE
QRACKF RACKF RACKF RACKF
1) 3RW44 soft starter directly on the DP master system: DP alarm mode is set to DPV1.
2) The driver blocks for PCS 7 V6.1 do not support interconnection of the CPU_DIAG parameter with MOD_PAX0.
3RW44 soft starter following a Y link - Configuration using the hardware catalog
This configuration cannot be applied.
Module drivers of the soft starter
4.3 Driver blocks
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 133
3RW44 soft starter following a Y link - Configuration using GSD file
The following driver blocks and interconnections are generated when the CFC is compiled:
1. SS_DIAG - Diagnostics for the SIRIUS 3RW44 soft starter
2. OB_DIAG1 - OB diagnostic function
3. OB_BEGIN - CPU function block
4. MOD_PAL0 - Message diagnostics for PA slave DP V0 connected to the DP master
system
Table 4- 2 Interconnections generated when CFC is compiled
OB_DIAG1 OB_BEGIN MOD_PAL0 SS_DIAG SS_DIR SS_STAT SS_MEAS
QRACKF RACKF
EN_F EN EN
EN_DIAG EN_DIAG
SUBN1ERR SUBN1ERR
SUBN2ERR SUBN2ERR
RAC_DIAG RAC_DIAG
CPU_DIAG CPU_DIAG
MODF QMODF
MODE_00 OMODE
QC_00 QUALITY
PA_DIAG PA_DIAG
QEN_RD EN_RDWR EN_RDWR EN_RD
DIAG_DIR DIAG_DIR
DIAG_MEAS DIAG_MEAS
OMODE_00 MODE MODE MODE
QRACKF RACKF RACKF RACKF
The driver blocks for PCS 7 V6.1 do not support interconnection of the CPU_DIAG parameter with MOD_PAL0.


Note
3RW44 soft starter following a Y link - Configuration using GSD file
If you are using the communication module with firmware version < E*04, a DPV1 following
the Y link is not possible.

Module drivers of the soft starter
4.3 Driver blocks
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
134 Programming and Operating Manual, 11/2010, A5E02845977020-02
More information
Additional information regarding GSD files is available in the "SIRIUS 3RW44 Soft Starter"
System Manual > Chapter "Configuration with the GSD File".
Additional information on:
DPV1 functionality for SIRIUS 3RW44 soft starter following a Y link
(http://support.automation.siemens.com)
1. Enter the following search term in the "Product Name or Part Number" field: y link 3rw44
2. Select the entry.
See also
Handling the driver generator (Page 10)

PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 135
3RW44 soft starter in the Maintenance Station
5
Description
The Maintenance Station is a node in the network control. It displays the status of all devices
that are configured in the network. The Maintenance Station is primarily connected to the
Plant Asset Management System.
The Maintenance Station supports the following basic functions:
Collecting online information:
For evaluation of the system
For evaluation of the status of components
For evaluation of system errors
Decisions regarding service activities, such as
Customer service for system
Inspection
Maintenance
Eliminating faults
Maintenance request and status management
The "Generate Module Driver" function generates the module drivers when the CFC is
compiled.
Modules of the starter and power modules are added to the ET 200S rack. They are
equipped with the following driver blocks, for example:
RACK
OB_DIAG1
MOD_PAL0
MOD_PAX0
SS_DIAG
The type of driver block depends on the configuration.
These blocks function as an interface for writing the status of service activities to the
Maintenance Station.
3RW44 soft starter in the Maintenance Station

PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
136 Programming and Operating Manual, 11/2010, A5E02845977020-02

Figure 5-1 Message diagnostics for PA slave DP V0 linked to the DP master system

Figure 5-2 Maintenance Station

PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 137
CFC charts for 3RW44 soft starter
6
Description
The CFC charts are a ready-made reference for using blocks from the block library. They
reduce the engineering effort required to configure the various blocks that support the proper
functioning of the signal blocks.
The charts are available in the block library under:
"PCS7 SS Library V7.0 > Blocks+Templates\Templates > SoftStarter"
Generate instances of the charts stored in the block library for incorporation in the CFC
charts. These are stored in the "Templates" directory of the SIMATIC project S7_program.

Figure 6-1 Path of directory where the CFC charts are stored
CFC charts for 3RW44 soft starter

PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
138 Programming and Operating Manual, 11/2010, A5E02845977020-02
Soft Starter CFC chart
The "Soft Starter" CFC chart contains one instance each of the following blocks:
SS_DIR
SS_MEAS
SS_STAT
Use this CFC chart for the following:
For operating
For measuring
For providing statistical information on the 3RW44 soft starter
The parameters have a textual interconnection that mentions the parameters to be
interconnected.
The following parameters must be assigned:
PS1_IRATE = Rated operational current of the starter block
PS2_IRATE = Rated operational current of the starter block
PS3_IRATE = Rated operational current of the starter block
OUT_01 = Logical address of the starter block

Figure 6-2 "Soft Starter" CFC chart
CFC charts for 3RW44 soft starter

PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 139
Note:
To facilitate the symbolic interconnection of the block inputs and outputs IN_01 and OUT_01
with the inputs and outputs of the device, symbols can be created in the symbol table.
You can find the symbol table in the HW Config Options > Symbol Table.
The inputs and outputs for the device are created here. Since the addresses are available in
BOOL, and the blocks are interconnected with WORD, the data type must be stored
accordingly in the symbol table.

In this example, the symbols In01 and Out01 are assigned for the addresses IW 3 and QW 3
in data type WORD.
The suitable symbol can now be selected when interconnecting.
CFC charts for 3RW44 soft starter

PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
140 Programming and Operating Manual, 11/2010, A5E02845977020-02

Alternatively, editing can be carried out without the symbol table. Then a direct
interconnection is made with, for example, IW 3.
See also
Parameterization (Page 45)
Parameterization (Page 107)
Parameterization (Page 121)
Interconnection of function blocks (Page 40)

PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 141
Technical data
7
7.1 Technical data
Table 7- 1 Memory requirement, FB number, and called blocks, per block type
Name of
block
1)

FB no.
2)
Length of
block in the
load
memory, in
bytes
3)

Length of block
in the work
memory, in
bytes
3)

Length of
instance
data in the
load
memory, in
bytes
4)

Length of
instance data
in the work
memory, in
bytes
4)

Temporary
memory, in
bytes
5)

Blocks
called
6)

SS_DIAG FB 561 5158
7)
4294
7)
1096 382 214 SFB 35
SFB 52
SFB 54
SFC 13
SFC 51
SFC 6
SFC 64
SS_DIAG FB 561 5156
8)
4292
8)
1096 382 214 SFB 35
SFB 52
SFB 54
SFC 13
SFC 51
SFC 6
SFC 64
SS_DIR FB 562 67794 61970 3612 2076 106 SFB 35
SFB 52
SFB 53
SFC 20
SFC 6
SFC 64
Technical data
7.1 Technical data
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
142 Programming and Operating Manual, 11/2010, A5E02845977020-02
Name of
block
1)

FB no.
2)
Length of
block in the
load
memory, in
bytes
3)

Length of block
in the work
memory, in
bytes
3)

Length of
instance
data in the
load
memory, in
bytes
4)

Length of
instance data
in the work
memory, in
bytes
4)

Temporary
memory, in
bytes
5)

Blocks
called
6)

SS_MEAS FB 564 3862 3290 818 420 52 SFB 35
SFB 52
SFC 6
SS_STAT FB 563 6844 6202 874 510 56 SFB 52
SFB 53
SFC 6
1)
The symbolic designator in the symbol table of the library for the respective function block (FB). It must be unique within
the project.
2)
Composed of the block type, e.g., FB for function block and the number.
3)
Memory requirement of program code, once per block type
4)
Memory requirement for an instance data block.
5)
The memory required for the local data when the block is called in an execution level. This is limited according to the
specific CPU. If this amount is exceeded, you must check the setting in the CPU configuration and redistribute it among
the organization blocks based on the actual requirement.
6)
The relevant driver block uses these blocks. They are now located in the user program They are stored in the same
library.
7) Applies for V6.1 + SP1
8) Applies for V7.0 + SP1

PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
Programming and Operating Manual, 11/2010, A5E02845977020-02 143
List of abbreviations
A
A.1 Abbreviations
Overview
Table A- 1 Meaning of abbreviations
Abbreviation Meaning
AS Automation station
HMI Operator control and monitoring
CFC Continuous Function Chart
CCW Counter-clockwise
CW Clockwise
DC Direct-current voltage
DP Distributed I/O
ES Engineering system
FB Function block
GSD Device master data
HW Config "Hardware configuration" module in SIMATIC Manager
ID Identification number
OB Organization block
OS Operator station
PCS 7 Process Control System 7
PIQ Process image output
PII Process image input
PG Programming device
PS Parameter set
RS Formerly: Radio Selector; now usually: Recommended Standard
SFB System function block
SFC Sequential function chart
PLC Programmable logic controller
SS Soft starter
SSL System status list
TIA Totally Integrated Automation


List of abbreviations
A.1 Abbreviations
PCS 7 block library for SIRIUS Soft Starter 3RW44 V6.1/V7.0 + SP1
144 Programming and Operating Manual, 11/2010, A5E02845977020-02

www.siemens.com/automation
Subject to change without prior notice
Order No.: 3ZX1012-0CS16-1AC1

Siemens AG 2009
Siemens AG
Industry Sector
Postfach 23 55
90713 FRTH
GERMANY
Service & Support
Download catalogs and information material:
www.siemens.com/industrial-controls/catalogs
Newsletter always up to date:
www.siemens.com/industrial-controls/newsletter
E-business in the Industry Mall:
www.siemens.com/industrial-controls/mall
Online Support:
www.siemens.com/industrial-controls/support
Contact for all technical information:
Technical Assistance
Tel.: +49 (911) 895-5900
e-mail: technical-assistance@siemens.com
www.siemens.com/industrial-controls/technical-assistance