ESTUDIO DE VERIFICACIN Y COORDINACIN DE PROTECCIONES

Preparado Para :

Servicios Especializados de Ingeniera DIgSILENT Limitada Av. Bicentenario 4063, Depto. 112-D, Vitacura, Santiago Tel.: +56 9 97797093 Fax: +56 2 9536385

Contacto: Celso A. Gonzlez G. e-mail: celso.digsilent@manquehue.net

Rev 0

CHI-DT-NT-10-2011

Informe Tc nic o

Pgina 2

0 nd ice

ndice
ndice ............................................................................................................................................................... 3 1 2 2.1 3 3.1 4 4.1 4.2 4.2.1 4.2.2 4.2.3 4.2.4 4.3 5 5.1 5.2 5.3 6 6.1 6.1.1 6.1.2 6.1.3 6.2 6.2.1 6.2.2 6.2.3 6.3 6.3.1 6.3.2 6.3.3 Resumen Ejecutivo .................................................................................................................................. 5 Introduccin ........................................................................................................................................... 7 Generalidades ........................................................................................................................................................... 9 Objetivo y Alcance de los Estudios ..........................................................................................................10 Acerca de los Tipos de Esquemas de Protecciones .................................................................................................... 10 Antecedentes y Consideraciones del Estudio ...........................................................................................12 Horizonte de Anlisis ............................................................................................................................................... 12 Topologa y Expansin de Cada SM .......................................................................................................................... 12 Sistema Elctrico de Punta Arenas ....................................................................................................................... 12 Sistema Elctrico de Puerto Natales ..................................................................................................................... 14 Sistema Elctrico de Porvenir ............................................................................................................................... 15 Sistema Elctrico de Puerto Williams .................................................................................................................... 17 Herramienta de Simulacin ...................................................................................................................................... 18 Aspectos Normativos Relacionados con el Estudio de Verificacin y Coordinacin de Protecciones ..........19 Instalaciones de Generacin .................................................................................................................................... 19 Instalaciones de Transmisin ................................................................................................................................... 19 Responsabilidad de la Empresa Edelmag .................................................................................................................. 19 Protecciones Consideradas en el Estudio ................................................................................................20 Esquemas de Protecciones Punta Arenas .................................................................................................................. 21 Instalaciones de Generacin ................................................................................................................................ 21 Instalaciones de Transmisin ............................................................................................................................... 21 Instalaciones de Clientes ..................................................................................................................................... 22 Esquema de Protecciones Sistema Puerto Natales ..................................................................................................... 23 Instalaciones de Generacin ................................................................................................................................ 23 Instalaciones de Transmisin ............................................................................................................................... 23 Instalaciones de Clientes ..................................................................................................................................... 24 Esquema de Protecciones Sistema Porvenir .............................................................................................................. 25 Instalaciones de Generacin ................................................................................................................................ 25 Instalaciones de Transmisin ............................................................................................................................... 25 Instalaciones de Clientes ..................................................................................................................................... 26

Informe Tc nic o

Pgina 3

0 nd ice

6.4 6.4.1 6.4.2 6.4.3 7 7.1 7.2 7.2.1 7.2.2 7.2.3 7.2.4

Esquema de Protecciones Sistema Puerto Williams .................................................................................................... 26 Instalaciones de Generacin ................................................................................................................................ 26 Instalaciones de Transmisin ............................................................................................................................... 27 Instalaciones de Clientes ..................................................................................................................................... 27 Desarrollo de los Estudios ......................................................................................................................28 Determinacin del tiempo mximo de despeje de fallas en instalaciones de Edelmag .................................................. 28 Estudios de Cortocircuitos ........................................................................................................................................ 30 Resultados para SM Punta Arenas ........................................................................................................................ 30 Resultados para SM Puerto Natales ...................................................................................................................... 31 Resultados para SM Porvenir .............................................................................................................................. 31 Resultados para SM Puerto Williams.................................................................................................................... 31 Comentarios: ................................................................................................................................................. 32

7.2.4.1 7.3 7.3.1 7.4 7.4.1 7.4.2

Corrientes de Carga por Alimentador ........................................................................................................................ 32 Comentarios ....................................................................................................................................................... 33 Verificacin de la Coordinacin................................................................................................................................. 34 Coordinacin de Protecciones en Alimentadores .................................................................................................... 34 Coordinacin de Protecciones en Lnea de 66 kV ................................................................................................... 35 Verificacin Coordinacin de Protecciones en Lnea 66 kV ................................................................................ 36 Caso sin generacin en central Punta Arenas (Caso de Mayor Probabilidad) ................................................. 36 Caso con generacin en central en Punta Arenas (Caso de menor Probabilidad) ........................................... 36

7.4.2.1

7.4.2.1.1 7.4.2.1.2 7.4.3 7.4.4 8 9 1 2 3 4

Coordinacin de Protecciones en Generadores ...................................................................................................... 37 Comentarios y Conclusiones Estudios de Verificacin de Protecciones .................................................................... 39 Conclusiones ..........................................................................................................................................41 Referencias ............................................................................................................................................42 Anexo 1 Grficos Determinacin Tiempo Mximo de Despeje ..................................................................43 Anexo 2 Curvas de Coordinacin Alimentadores ......................................................................................50 Anexo 3 Curvas de Coordinacin de Lnea de Transmisin .......................................................................99 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores .........................................................103

Informe Tc nic o

Pgina 4

1 Resumen Ejecutivo

1 Resumen Ejecutivo
En el presente informe se describen los resultados de la verificacin de la coordinacin efectuada en los esquemas de protecciones de cada Sistema Mediano de propiedad de la Empresa Elctrica de Magallanes S.A., Edelmag, esto es: Punta Arenas, Puerto Natales, Porvenir y Puerto Williams. El estudio en cuestin resulta en una obligacin normativa, impuesta por la NT. La ejecucin y desarrollo de los estudios le corresponde a las empresas propietarias u operadoras de sistemas elctricos medianos, a quienes stas designen y debern estar a disposicin de la Comisin Nacional de Energa y la Superintendencia, en una fecha que tambin est determinado por la misma norma. Para los efectos de la ejecucin del mencionado estudio, la Empresa Elctrica de Magallanes S.A., en adelante Edelmag, ha encargado a Digsilent Limitada, en adelante Digsilent, el desarrollo del estudio referido. En este informe tcnico se aportan los criterios de diseo, anlisis y resultados asociados con el Estudio de Verificacin y Coordinacin de Protecciones, efectuado en cada Sistema Mediano. Se entiende por verificacin de coordinacin de protecciones en un sistema, a un sistema de protecciones que se encuentre bien concebido y ajustado de manera de asegurar un comportamiento adecuado, de alta selectividad, rpido y confiable ante perturbaciones, procurando dentro de lo posible, otorgar los respaldos necesarios y suficientes a otras instalaciones del sistema. Por adecuado se entiende un esquema de alta sensibilidad que permita detectar cualquier tipo de fallas que ocurran en la zona protegida, de alta selectividad que permita discriminar cual es el equipo o componente fallado, rpido para proceder en forma automtica al retiro del equipo fallado y confiable, es decir, que slo opere cuando efectivamente ha ocurrido una falla. El estudio deba efectuar los siguientes anlisis: Determinar el tiempo mximo para despeje de falla, cuyo valor no podr ser superado por las protecciones que operan como esquema primario. Verificar el cumplimiento de los estndares impuesto en el Captulo N 3 y 5 de la NT. La verificacin de la coordinacin de los equipos de protecciones exigida en la NT se efectu mediante simulaciones estticas (Flujos y cortocircuitos), sobre escenarios que representan adecuadamente la operacin esperada de cada SM.

El estudio consider analizar tanto las protecciones de los transformadores, unidades generadoras, lneas de transmisin, as como tambin las instalaciones de clientes (Protecciones de alimentadores). La simulacin del esquema de protecciones se efectu mediante la modelacin digital de cada proteccin en el programa de simulacin y anlisis Power Factory. Toda la informacin proporcionada de tipo de proteccin, modelo, fabricante y ajustes de protecciones fue provista por la empresa Edelmag. El estudio en cuestin determin lo siguiente:

Informe Tcnico

Pgina 5

1 Resumen Ejecutivo

En general los ajustes actuales definidos en cada tipo de instalacin, esto es, Alimentadores, Transmisin y Generacin, no requieren ser modificados, salvo ajustes menores en algunos generadores, para evitar poner en riesgo la estabilidad del sistema. En cada uno de los anlisis se ha verificado que se cumple la debida coordinacin de protecciones. En efecto, para fallas que ocurren aguas debajo de cada alimentador se aprecia que la falla es despejada por los propios alimentadores, los cuales responden de manera ms rpida que los generadores y sistemas de transmisin. Para este tipo de fallas, las protecciones de transmisin y generacin slo actan como respaldo ante fallas en el correcto despeje de la falla. Para fallas que ocurren aguas arriba de los alimentadores, las protecciones de los alimentadores no participan, dado que las protecciones no registran aportes de corrientes de falla desde los alimentadores hacia el punto de falla, lo cual se debe a que los alimentadores no poseen generadores aguas abajo que contribuyan con corrientes de falla. Para las lneas de transmisin se ha determinado que el esquema de protecciones opera adecuadamente, por cuanto despeja en forma rpida las fallas que se origina en la lnea, y acta como respaldo para fallas que ocurran fuera de la propia instalacin. Esta verificacin se efectu para diferentes configuraciones de generacin en los extremos de la lnea. En el caso de las unidades generadoras se ha verificado la correcta operacin de su esquema de protecciones, actuando selectivamente y con tiempos acordes a cada falla que se presente en el sistema, salvo los cambios que se plantean en algunos generadores del SM Punta Arenas. En efecto, para fallas que ocurren en las proximidades de la barra donde la unidad se conecta, la proteccin acta en forma rpida. En cambio para fallas ms alejadas acta con tiempos que permiten el despeje de las instalaciones que se encuentran en fallas, actuando estas protecciones como respaldo sino ocurre el despeje exitoso. En todos los casos se verific que los esquemas de protecciones no actan para las mximas corrientes de carga esperadas en el periodo 2010-2014. En resumen, se ha verificado el correcto desempeo del esquema de protecciones en las instalaciones de los Sistemas Medianos operados por la empresa Edelmag. De los anlisis efectuados y de los resultados obtenidos se concluye que el sistema de protecciones ya implementado ms los ajustes que han definido en los estudios que ha encargado recientemente Edelmag, se ajusta a los requerimientos que impone la Norma tcnica, por cuanto cumple a cabalidad con la debida coordinacin de protecciones. En todas las instalaciones se aprecia que el esquema de protecciones acta en forma rpida para fallas que ocurren en la propia instalacin, adems de prestar respaldo remoto para fallas que ocurren en otras instalaciones del sistema. En el caso de los alimentadores para la operacin de los reconectadores. Aunque no se visualiza modificar el esquema de protecciones en el periodo 2011-2014, se plantea revisar el esquema una vez que los estudios que ha encargado la empresa Edelmag se encuentren finalizados.

Informe Tcnico

Pgina 6

2 Introduccin

2 Introduccin
La Norma Tcnica de Seguridad y Calidad de Servicio para Sistemas Medianos[1], dictada por la Autoridad en el mes de febrero del ao 2006, en adelante, NTSyCS SM, establece a la empresas propietarias/Operadoras de Sistemas Medianos, la ejecucin de Estudios para realizar la programacin del Control de Tensin, el Control de Frecuencia y el PRS, para el conjunto de instalaciones de los Sistemas Medianos, los cuales debern estar a disposicin de la Comisin Nacional de Energa y la Superintendencia. Se entiende por Sistemas Medianos, en adelante SM, a los sistemas elctricos cuya capacidad instalada de generacin es menor de 200 MW y mayor a 1,5 MW. Con esta parcializacin de los sistemas, los estudios se efectuarn para los Sistemas Elctricos de propiedad de Edelmag para los siguientes SM: Punta Arenas, Puerto Natales, Porvenir y Puerto Williams. En trminos especficos las exigencias de la NTSyCS SM establece la ejecucin de los siguientes estudios:

Figura 1. Estudios exigidos por la NTSyCS de SM Para cada estudio se solicita en concreto lo siguiente: EDAC: Deber determinar el nivel ptimo y localizacin de desconexin de carga. El objetivo es evitar colapso por frecuencia y tensin con la activacin de esquemas de desconexin para estados de operacin distinto del Estado Normal. Control de Frecuencia y Determinacin de Reservas: Tiene por objeto efectuar una verificacin del cumplimiento de los estndares SyCS establecidos en el Captulo N 5. En particular debe determinarse un porcentaje de reserva ptimo que se utilizar para efectuar la asignacin de la reserva entre las unidades generadoras participantes del CPF y del CSF.

Informe Tcnico

Pgina 7

2 Introduccin

Control de Tensin y Requerimientos de Potencia Reactiva: Tiene por objeto efectuar una verificacin del cumplimiento de los estndares de SyCS establecidos en el Captulo N 5, adems de determinar el perfil ptimo de tensiones y los requerimientos de potencia reactiva para las Instalaciones Transmisin, con resolucin semestral para un horizonte de operacin de 48 meses. Restricciones en Instalaciones de Transmisin: Se debe identificar las potencias mximas que se pueden transmitir por las lneas de transmisin que la Empresa identifique como crticas para garantizar frente a la ocurrencia de las contingencias indicadas que se establecen en el Artculo 5-36 de la presente NT. Estudio de PSR: El objetivo del PRS es que con posterioridad a un Apagn Total o Apagn Parcial, sea posible establecer los mecanismos que permitan de una manera segura y organizada, restablecer el suministro elctrico en todas las Islas Elctricas afectadas en el menor tiempo posible, considerando las Cargas Crticas. Los Estudios se realizarn con una periodicidad de cada cuatro aos, salvo que se estime necesario un tiempo para su actualizacin parcial o completa. Estudio de Continuidad: Determinar los ndices de continuidad FMIK y TTIK del SM, para un horizonte de operacin de 12 meses. Verificacin de Coordinacin de Protecciones: Tiene por objeto confirmar que el desempeo de los rels de proteccin de las lneas de transmisin, transformadores de potencia y unidades generadoras cumple con las exigencias de SyCS establecidas en la presente NT.

Estos estudios se deben realizar con una periodicidad de cada cuatro aos, salvo que se estime necesario un tiempo para su actualizacin parcial o completa. De acuerdo con esta exigencia los estudios consideran un horizonte de anlisis tambin de cuatro aos, aos 2011-2014, para as ser consistente con la exigencia normativa. Cabe mencionar que desde la vigencia de la NTSCS SM, esta es la segunda oportunidad en que se llevan a cabo los anlisis, correspondiendo en esta oportunidad una revisin de los estudios que ya realizaron las empresas propietarias de Sistemas Medianos en el ao 2007. Algunos de estos estudios estn directamente relacionados entre s, as como otros resultan complementa independientes. Respecto del primer grupo de estudios, se debe definir un estudio que inicie los anlisis cuyos resultados sean la entrada para los otros. En este sentido existe una directa relacin entre los estudios de EDAC (por subfrecuencia y subtensin) con los estudios de Control de Frecuencia, Control de Tensin y de Restricciones en el Sistema de Transmisin. En cambio los estudios de Continuidad, PRS y de Protecciones se pueden abordar en forma completamente independiente, por cuanto resultan de distinta naturaleza tcnica que los anteriores. El estudio que se aborda en este informe corresponde al Estudio de Verificacin de Coordinacin de Protecciones.

Informe Tcnico

Pgina 8

2 Introduccin

2.1 Generalidades
En la operacin de los sistemas se debe procurar que toda instalacin de suministro de energa elctrica provea la calidad de suministro en condiciones ptimas de seguridad, continuidad y economa. La operacin de los sistemas elctricos frente a la aparicin de contingencias debe ser capaz de proteger tanto las instalaciones como la vida de las personas que se pueden encontrarse expuestas. Un sistema de protecciones bien concebido debe estar ajustado de manera de asegurar un comportamiento adecuado, de alta selectividad, rpido y confiable ante perturbaciones y procurar, dentro de lo posible, otorgar los respaldos necesarios y suficientes a otras instalaciones del sistema. Por adecuado se entiende un esquema de alta sensibilidad que permita detectar cualquier tipo de fallas que ocurran en la zona protegida, de alta selectividad que permita discriminar cual es el equipo o componente fallado, rpido para proceder en forma automtica al retiro del equipo fallado y confiable, es decir, que slo opere cuando efectivamente ha ocurrido una falla.

En el caso del presente estudio se verificar la correcta coordinacin de las protecciones en los distintos Sistemas Medianos que opera la Empresa Edelmag y el nivel de cumplimiento con los estndares impuesto en la Norma Tcnica de Seguridad y Calidad de Servicio para Sistemas Medianos[1], en adelante, NT. En este documento se describen los criterios de diseo, anlisis y resultados asociados con el Estudio de Verificacin y Coordinacin de Protecciones, efectuado en cada Sistema Mediano. Se entiende por sistemas medianos, en adelante SM, a los sistemas elctricos cuya capacidad instalada de generacin es menor de 200 MW y mayor a 1,5 MW. Con esta parcializacin de los sistemas, los estudios se efectuarn para los Sistemas Elctricos de: Punta Arenas, Puerto Natales, Porvenir y Puerto Williams. La verificacin de coordinacin de cada proteccin y su respaldo hacia otras instalaciones se realiza en base a los criterios establecidos en la NT y de acuerdo con la informacin y experiencia adquirida por la empresa Edelmag en la operacin de sus sistemas elctricos. Para los efectos de la ejecucin del mencionado estudio, la Empresa Elctrica de Magallanes S.A., en adelante Edelmag, ha encargado a Digsilent Limitada, en adelante Digsilent, el desarrollo de los estudios referidos, empresa que asume la ejecucin de los mismos.

Informe Tcnico

Pgina 9

3 Objetivo y Alcance de los Estudios

3 Objetivo y Alcance de los Estudios


El objetivo del presente estudio, impuesto por la NT1, es: Confirmar que el desempeo de los rels

de protecciones de las lneas de transmisin, transformadores de potencia y unidades generadoras cumple con las exigencias de SyCS establecidas en la presente NT.
El estudio deber verificar el cumplimiento de los estndares impuesto en el Captulo N 3 y 5 de la NT, dicho cuerpo normativo en el Captulo N 3 impone caractersticas de diseo mnimo para las instalaciones que operan en sincronismo, entre estas las caractersticas de los elementos de proteccin de las instalaciones. En cambio, en el Captulo N 5 se definen los estndares de operacin para las distintas condiciones operativas que puede presentar un sistema elctrico, esto es Normal, de Alerta y Emergencia, condiciones que el estudio deber verificar. La verificacin de la coordinacin de los equipos de protecciones exigida en la NT se efectuar mediante simulaciones estticas (Flujos y cortocircuitos), sobre escenarios que representen adecuadamente la operacin esperada de cada SM. El estudio considera estudiar las siguientes instalaciones: Protecciones de los transformadores Unidades generadoras Lneas de transmisin Instalaciones de clientes (Protecciones de alimentadores).

3.1 Acerca de los Tipos de Esquemas de Protecciones


Los tipos de protecciones en los sistemas elctricos se dividen en protecciones del tipo Unitario y No Unitario. Los primeros basan su operacin en la medida de magnitudes elctricas en los terminales del equipo protegido, no requieren coordinacin con otros equipos del sistema y no prestan respaldo remoto (respaldo de otras instalaciones del sistema elctrico), son intrnsecamente selectivos y por lo tanto su operacin puede ser instantnea, un ejemplo de estas protecciones son las protecciones diferenciales. Los sistemas de protecciones No Unitarios basan su operacin en la medida de las magnitudes elctricas en slo uno de los terminales del equipo protegido. Como ests magnitudes pueden variar para una misma falla segn su configuracin del sistema, su zona de proteccin no est claramente delimitada a priori. Esto impide que por razones de selectividad (coordinacin) con otras protecciones, que operen en forma instantnea, al menos para algunas ubicaciones de la falla. Este tipo de protecciones se presta para dar respaldo a las protecciones de equipos adyacentes, asegurando su operacin selectiva por medio del ajuste de retardos de tiempos intencionales. Un ejemplo de este tipo de protecciones son las protecciones de distancia y de sobrecorriente.

Se refiere a la exigencia impuesta en el artculo 6-3, literal c), que menciona el objetivo del estudio de Verificacin de Coordinacin de Protecciones.
Pgina 10

Informe Tcnico

3 Objetivo y Alcance de los Estudios

El estudio en cuestin estar orientado en verificar la coordinacin de las protecciones del tipo No Unitario y en forma especial las protecciones de distancia, si las hubiere, y las protecciones de sobrecorriente (residual y de fase), sean stas direccionales no direccionales. En consideracin que los Sistemas Medianos operados por Edelmag, ya cuentan con esquemas de protecciones operativos y con ajustes definidos, se proceder en este estudio a revisar si los ajustes ya establecidos permiten una adecuada coordinacin de las distintas instalaciones ante fallas en el sistema elctrico. En forma especfica la NT establece que el estudio de Coordinacin de Protecciones debe establecer tiempos de actuacin de protecciones, los cuales se revisarn una vez determinados los tiempos reales de operacin de protecciones en cada una de las instalaciones. En caso que los tiempos actuales de operacin resulten excesivos o no permitan la coordinacin adecuada con otras instalaciones se propondrn soluciones de mejora. En concreto, la revisin de la coordinacin de las protecciones se efectuar en base a los anlisis de la informacin aportada por Edelmag y teniendo en consideracin los tipos, caractersticas y especificaciones de ajustes de las protecciones actualmente en servicio en las instalaciones de los Sistemas medianos.

Informe Tcnico

Pgina 11

4 Antecedentes y Consideraciones del Estudio

4 Antecedentes y Consideraciones del Estudio


El estudio que a continuacin se presenta se efectuar para cada uno de los sistemas elctricos medianos de propiedad de Edelmag. En consideracin que cada sistema elctrico se encuentra aislados unos de otros se analizarn cada uno por separado y considerando sus propias caractersticas, no obstante, estarn incluidos en un nico informe. A continuacin se mencionan y describen todos los antecedentes y las consideraciones tenidas en cuenta para el desarrollo del estudio. Los antecedentes que se indican en el estudio fueron provistos por Edelmag, en cambio las consideraciones utilizadas en el estudio corresponden a criterios formulados por el Consultor Digsilent y a la experiencia de la empresa Edelmag en la operacin de sus sistemas Elctricos.

4.1 Horizonte de Anlisis


El estudio en cuestin se efectuar para un horizonte de anlisis de 4 aos, considerando el periodo del 2011 al 2014. Para dicho periodo se escoger los escenarios representativos de demanda mxima y mnima que determinen el rango de operacin de las protecciones de cada instalacin.

4.2 Topologa y Expansin de Cada SM


Para los estudios se utiliza la topologa elctrica de cada Sistema Mediano disponible al mes de octubre del ao 2011, ms todas las incorporaciones de instalaciones de generacin y transmisin que se estim necesario en los estudios de planificacin de la expansin de los sistemas medianos. A continuacin se detallan las instalaciones de generacin, transmisin y clientes consideradas en cada sistema elctrico.

4.2.1 Sistema Elctrico de Punta Arenas


El sistema elctrico de Punta Arenas est constituido bsicamente por dos subsistemas, Tres Puentes y central Punta Arenas. Tres Puentes est formado por dos barras principales, una de 11,5 KV que corresponde a una barra de generacin y otra de 13,2 kV que abastece alimentadores de cargas y que tambin cuenta con inyeccin de generacin. Ambas barras se conectan a travs de un transformador 13,2/11,5 kV de 20 MVA. Por su parte central Punta Arenas posee una barra de 13,2 kV, donde se concentran alimentadores de consumos y un centro de generacin, aunque estas ltimas usualmente no son despachadas por criterios econmicos, transformndose dicha barra en una de retiros de energa. Los subsistemas se interconectan mediante una lnea de transmisin, de simple circuito, en 66 kV de unos 8,15 km y se conecta en un extremo mediante un transformador de 66/12 kV de 33 MVA y en el otro uno de 66/13,8 kV tambin de 33 MVA. La capacidad trmica de la lnea de transmisin

Informe Tcnico

Pgina 12

4 Antecedentes y Consideraciones del Estudio

es de 48 MVA (0,42 kAmp), no obstante, queda limitada por la capacidad de los transformadores de los extremos. Este Sistema Mediano cuenta con recursos de potencia reactiva shunt (banco de condensadores y reactores) por un monto de 2,0 MVAr que se ubica en la barra de Punta Arenas. Este sistema no cuenta con esquemas EDAC por subtensin. La topologa del sistema se aprecia en la siguiente figura.

13.2 kV T.P..
Consumo AL-X10B

13.2 kV P.A..

MG CATERPILLAR
Unidad N 5 T.P. Consumo AL-7 Consumo AL-8A Autotransformador N 2 Consumo AL-9 Shunt/Filter Consumo AL-8B

~ G

Consumo AL-1 Consumo AL-X10A

11.5 kV
Trafo N 3 - C.T.P.

Unidad N 2 T.P. Trafo N 4 - C.T.P. Autotransformador N 6 Consumo AL-4

~ G

~ G

Unidad N 3 T.P. Consumo AL-5 Line(1) AWG 3/0 C.. Trafo N 7 C.P.A.

Consumo AL-2

Consumo AL-3

Celdas 11.5 kV
Consumo AL-X11 XConsumo AL-13 52D1 52CS3

23 kV

Celdas 13.2 kV G.E.


Consumo AL-6

HITACHI 24 MW
52DT1 Trafo N 1 C.T.P. YConsumo COCAR - Ingesur

~ G

Unidad N 1 T.P.

XConsumo AL-12 Trafo N 6 C.P.A. Lnea de unin en 23 kV AWG 3/0 Cu (167.8 MCM)

Lnea de respaldo para PRS CENTRAL PUNTA ARENAS

52 DS

Trafo N 5 - C.P.A.

Celdas 11.5 kV Rhona

Unidad N 5 P.A.

SOLAR MARS 10.5 MW


Trafo N 5 C.T.P. Line(2) AWG 3/0 C..

Trafo N 4 - C.P.A.

Unidad N 4 P.A.

Unidad N 4 T.P.

~ G

Breaker

13.2 kV
Trafo N 2 - C.P.A.

G ~

G ~

SOLAR TITAN
13.7 MW

Unidad N 7 T.P.

15 MW

Unidad N 9 T.P.

~ G

Trafo N 3 - C.P.A.

G ~

G ~
Unidad N 2 P.A.

Trafo N 1 - C.P.A.

~ G

G ~
Unidad N 1 P.A.

GE 10.7 MW
~ G

Unidad N 3 P.A.

Unidad N 8 T.P.

Estudios de la Norma de Seguridad y Calidad Periodo de Evaluacin 2011 - 2014 Diagrama Unilineal PowerFactory 14.0.525

Project: EDELMAG SA Graphic: RED Date: 10/29/2011

Annex: P. ARENAS

Figura 2. Unilineal Sistema Elctrico Punta Arenas Las unidades generadoras que componen este sistema son las siguientes:
CENTRALES GENERADORAS SM PUNTA ARENAS N Descripc. Tipo THD MD MD TI-Gas MG TI THD TI-GAS Pmx MW Observacin Existente Existente Existente Existente Existente Existente Existente Existente CENTRAL TRES PUENTES 1 2 3 4 5 7 8 9

Unidad Hitachi a GAS Motor-Generador Caterpillar DIESEL - PA Motor-Generador Caterpillar DIESEL - PA Unidad Solar Mars a GAS Motor-Generador Caterpillar a GAS Unidad Solar Titn a GAS Turbina a GAS GE 12.22 MVA T.G. SOLAR TITAN

24,00 1,46 1,46 10,50 2,726 13,70 10,997 15,02


MW

CENTRAL PUNTA ARENAS

Informe Tcnico

Pgina 13

DIgSILENT

4 Antecedentes y Consideraciones del Estudio

1 2 3 4 5

SULZER SULZER SULZER G. ELECTRIC G. ELECTRIC

MD MD MD THD THD

1,400 1,400 1,400 6,700 6,500

Existente Existente Existente Unidades de respaldo Unidades de respaldo

Cuadro 1 Unidades que componen el SM Punta Arenas

4.2.2 Sistema Elctrico de Puerto Natales


El sistema elctrico de Puerto Natales est constituido bsicamente por una barra principal en 13,2 kV, donde se conectan las unidades generadoras y los alimentadores. En este sistema elctrico no existen lneas de transmisin y transformadores de transmisin, excepto los propios de las unidades generadoras. Este sistema mediano no cuenta con recursos de potencia reactiva shunt (banco de condensadores y reactores), as como tampoco con esquemas EDAC por subtensin. La topologa del sistema es la siguiente:
AL1-6

AL1-4

C1 - Linea 3b

AL1-5

AL2-2 C1 - Linea 2b AL1-2 C1 - Linea 2a AL1-3

AL3-2

AL4-2

C2 - Linea 2

C3 - Linea 2

AL2-1

AL3-1

Linea C4 - 2

AL4-1

C1 - Linea 1a

C1 Linea 1b

AL1-1

SS.AA

Alimentador - 2

Alimentador - 1

S. Auxiliar

89 CT

13.2 kV II
89 CTD F4

13.2 kV
Jenbacher 416

Trafo N 10

Jenbacher

Generador N 6 Trafo N 3

M.D. CATERPILLAR
Trafo N 11 Trafo N 09

Lnea(1)

Generador N 10

Generador N 5

Generador N 4

PALMERO

T.G. SOLAR 5

T.G. SOLAR 4
G ~
Generador N 2

Lnea

G ~

Trafo Waukesha 8

G ~

G ~

AutoTrafo

G ~

Fusible(1)

Trafo N 5

Trafo N 4

Fusible

Alimentador - 4

Alimentador 3

G ~
Generador N 1

G ~
Generador N 11

G ~
Generador N 9

G ~
Generador N 8

G ~
Generador N 3

MD MORSE

JENBACHER 612

JENBACHER

WAUKESHA

WAUKESHA

Estudios de la Norma de Seguridad y Calidad Periodo de Evaluacin 2011 - 2014 Diagrama Unilineal PowerFactory 14.0.525

Project: EDELMAG SA Graphic: RED Date: 10/29/2011 Annex: P.NATALES

Figura 3. Unilineal Sistema Elctrico Puerto Natales

Informe Tcnico

Pgina 14

DIgSILENT

4 Antecedentes y Consideraciones del Estudio

Las unidades generadoras que componen este sistema son:


CENTRALES GENERADORAS SM PUERTO NATALES N Descripc. CENTRAL PUERTO NATALES 1 2 3 4 5 6 8 9 10 11 Tipo Pmx MW MD MD MG TI-Gas TI-Gas MD MG MG MD MG Observacin Unidad de respaldo Unidad de respaldo Existente Existente Existente Existente Existente Existente Existente Disponible 2012

Motor-Generador DIESEL (150 kW) F.Morse Palmero 1.36 MW Motor-Generador DIESEL (300 kW) F.Morse Motor-Generador a GAS - Waukesha Turbina Solar Saturno a GAS Turbina Solar Saturno a GAS Motor-Generador Caterpillar a DIESEL-PN Motor-Generador a GAS - Waukesha Jenbacher 1.42 MW

0,150 1,360 0,300 1,175 0,800 0,800 1,500 1,175 1,420

JM612 1

1,816

Cuadro 2 Unidades que componen el SM Puerto Natales

4.2.3 Sistema Elctrico de Porvenir


El sistema elctrico de Porvenir, al igual que el de Puerto Natales, est constituido bsicamente por una barra principal en 13,8 kV, donde se conectan las unidades generadoras y los alimentadores. En este sistema elctrico no existen lneas de transmisin ni transformadores, excepto los propios de las unidades generadoras. Este sistema mediano no cuenta con recursos de potencia reactiva shunt (banco de condensadores y reactores), as como tampoco con esquemas EDAC por subtensin. La topologa del sistema es la siguiente:

Informe Tcnico

Pgina 15

4 Antecedentes y Consideraciones del Estudio

Alimentador 2 - Carga 2

Alimentador 2 - Carga 1 Alimentador 1 (SACOR)

C2 - Linea 2 Alimentadores..

Alimentador 3 - Carga 1

Alimentador 4 - Carga 1

Alimentador - 1 Alimentadores..

Alimentador - 2 Alimentadores..

Alimentador - 3 Alimentadores..

89 CT

13.8_B
89-CT1-F HV 63A 89-CT2-F HV 63A 89-CT8-F HV 63A 89-CT4-F HV 63A 89-CT3-F HV 63A

13.8_A
89-CT7-F(1) HV 63A 89-CT9-F HV 63A 89-CT7-F HV 63A 89-CT6-F HV 63A 89-CT5-F HV 63A

Trafo N 1

Trafo N 3

Alimentador - 4 Alimentadores..

Trafo N 10

Trafo TG11

Trafo TG1..

Trafo TG1..

Trafo N 6

Trafo N 5

G ~
Unidad N 1

Trafo N 4

G ~
Unidad N 2

Trafo N 2

G ~
Unidad N 3

MD CATERPILLAR MD DEUTZ
G ~
Unidad N 9

G ~
Unidad N 10

G ~
Unidad N 7

G ~
Unidad N 6

G ~
Unidad N 5

G ~
Unidad N 8

G ~
Unidad N 4

CAT - GAS JENBACHER 416

WAUKESHA

WAUKESHA

CAT - DIESEL

PALMERO

WAUKESHA

Estudios de la Norma de Seguridad y Calidad Periodo de Evaluacin 2011 - 2014 Diagrama Unilineal PowerFactory 14.0.525

Project: EDELAMG SA Graphic: RED Date: 10/29/2011 Annex: PORVENIR

Figura 4. Unilineal Sistema Elctrico Porvenir Las unidades generadoras que componen este sistema son:
CENTRALES GENERADORAS SM PORVENIR N Descripc. CENTRAL PORVENIR 1 2 3 4 5 6 7 8 9 10 Tipo Pmx MW MD MD MD MG MD MG MG MD MG MG Observacin Unidades de respaldo Unidades de respaldo Unidades de respaldo Existente Existente Existente Existente Existente Existente Disponible 2012

Motor-Generador Caterpillar DIESEL 1- PO Motor-Generador Deutz DIESEL - PO Motor-Generador Deutz DIESEL - PO Motor-Generador a GAS - Waukesha - PO Motor-Generador Caterpillar DIESEL 2- PO Motor-Generador a GAS - Waukesha -PO Motor-Generador a GAS - Waukesha -PO Palmero 1.36 MW Motor-Generador Caterpillar DIESEL - PA

GE Jenbacher JM416 1

0,500 0,200 0,200 0,875 0,920 1,175 1,175 1,360 0,923 1,131

Cuadro 3 Unidades que componen el SM Porvenir

Informe Tcnico

Pgina 16

DIgSILENT

4 Antecedentes y Consideraciones del Estudio

4.2.4 Sistema Elctrico de Puerto Williams


El sistema elctrico de Puerto Williams, est constituido bsicamente por una barra principal en 13,2 kV, donde se conectan las unidades generadoras y los alimentadores. En este sistema elctrico no existen lneas de transmisin ni transformadores, excepto los propios de las unidades generadoras y alimentadores. Este sistema mediano no cuenta con recursos de potencia reactiva shunt (banco de condensadores y reactores), as como tampoco con esquemas EDAC por subtensin. La topologa del sistema es la siguiente:
DIgSILENT
Carga Alimentador 2 Carga Alimentador 1 Carga Alimentador 3 Alimentador - 2 89 CT

13.2 kV II
89 CTD F4 Trafo N 3 Lnea

13.2 kV

Trafo N 05

Jenbacher

G ~
Generador N 4

G ~
Generador N 5

G ~
Generador N 6

M.D. CUMMINS
G ~
Generador N 7

Trafo N 01

G ~
Generador N 1

Trafo N 2

Fusible(1)

G ~
Generador N 2

Alimentador - 3

Alimentador 1

M.D. Detroit N 3
G ~
Generador N 3

M.D. CATERPILLAR N 1

M.D. CATERPILLAR N 2

M.D. CATERPILLAR N 3

Estudios de la Norma de Seguridad y Calidad Periodo de Evaluacin 2011 - 2014 Diagrama Unilineal PowerFactory 14.0.525

Project: EDELMAG SA Graphic: RED Date: 10/29/2011 Annex: P.WILLIAMS

Figura 5. Unilineal Sistema Elctrico Puerto Williams Las unidades generadoras que componen este sistema son:

Informe Tcnico

Pgina 17

4 Antecedentes y Consideraciones del Estudio

CENTRALES GENERADORAS SM PUERTO WILLIAMS N Descripc. CENTRAL PORVENIR 1 2 3 4 5 6 7 Tipo Pmx Observacin MW MD MD MD MD MD MD MD

MotorGenerador Caterpillar Diesel 3508B MotorGenerador Caterpillar Diesel PW3508 Motor-Generador Diesel Caterpillar (PW) Motor-Generador Cummins Diesel PW Motor-Generador Cummins Diesel PW Motor-Generador Deutz Diesel PW Motor-Generador Deutz Diesel PW

0,590 0,500 0,360 0,282 0,282 0,252 0,252

Existente Existente Existente Existente Existente De Respaldo De Respaldo

Cuadro 4 unidades que componen el SM Puerto Williams

Notas Importantes: En relacin con el tipo de unidades generadoras, las abreviaciones tienen el siguiente significado.
MD MG TI Motor Diesel Motor a Gas Turbina a gas Industrial

THD Turbina a gas Heavy Duty

Las Unidades generadoras que segn el plan ptimo de expansin deban ser retiradas de cada sistema elctrico, dado que ya haban cumplido su fecha de retiro, se han mantenido en las bases de datos, por cuanto dichas unidades se utilizan en la actualidad como unidades de respaldo.

4.3 Herramienta de Simulacin


Los estudios aludidos consideran realizar sendas simulaciones estticas del sistema elctrico de Edelmag. Para tales efectos, tanto en lo referente a estudios de flujos de potencia, cortocircuitos, coordinacin de protecciones, se utilizar el programa Power Factory Versin 14.1.525 de DIgSILENT GmbH (u otra superior), simulador digital de amplio uso en el sector elctrico chileno. Para ello se emplear la ms completa modelacin de los sistemas elctricos de Edelmag existente en la actualidad, cuya topologa para SM se indic en trminos grficos en las figuras N 2, 3, 4 y 5 respectivamente.

Informe Tcnico

Pgina 18

5 Aspectos Normativos Relacionados con el Estudio Coordinacin de Protecciones

de Verificacin y

5 Aspectos Normativos Relacionados con el Estudio de Verificacin y Coordinacin de Protecciones


El estudio debe efectuar lo siguiente: ..Confirmar que el desempeo de los rels de protecciones

de las lneas de transmisin, transformadores de potencia y unidades generadoras cumple con las exigencias de SyCS establecidas en la presente NT. (Artculo 6-3, literal c).

5.1 Instalaciones de Generacin


La proteccin de las unidades generadoras y sus conexiones con el SM debe cumplir con las exigencias mnimas especificadas a continuacin: (Artculo 3-4, literal b) i) El tiempo mximo para despeje de falla en ningn caso podr exceder los valores lmites resultantes del Estudio de Verificacin de Coordinacin de Protecciones sealado en el Ttulo 6-2 de la presente NT, el cual ser determinado por la Empresa. Para el caso de unidades generadoras que se incorporan al SM, el tiempo mximo para despeje de falla deber ser determinado en forma previa a la conexin de la unidad generadora. Cada unidad generadora conectada al SM, deber disponer de la proteccin de respaldo para fallas en Instalaciones de Transmisin, debiendo la Empresa disponer de proteccin para fallas que ocurran en las instalaciones de la unidad generadora. Los tiempos de despeje de fallas de estas protecciones sern coordinados por la Empresa, pero en ningn caso podrn exceder los valores lmites resultantes del Estudio de Verificacin de Coordinacin de Protecciones sealado en el Ttulo 6-2 de la presente NT. El ajuste de los rels y de las protecciones que afecten al rea del Punto de conexin deber estar coordinado en forma previa a la conexin de acuerdo a lo que establezca el Estudio que desarrolle la Empresa para tal efecto.

ii)

iii)

iv)

5.2 Instalaciones de Transmisin


Las Instalaciones de Transmisin debern estar equipadas con protecciones elctricas que sean capaces de aislar selectivamente el componente fallado. Los tiempos de actuacin de estas protecciones debern estar en concordancia con el Estudio de Verificacin de Coordinacin de Protecciones sealado en el Ttulo 6-2 de la presente NT. (Artculo 3-13)

5.3 Responsabilidad de la Empresa Edelmag


La Empresa deber comprobar el estado de conservacin y mantenimiento de las protecciones elctricas del SM y verificar que sus ajustes y parmetros corresponden a los valores resultantes del Estudio de Verificacin de Coordinacin de Protecciones establecido en el Ttulo 6-2 de la presente NT. (Artculo 4-14).

Informe Tcnico

Pgina 19

6 Protecciones Consideradas en el Estudio

6 Protecciones Consideradas en el Estudio


De acuerdo con la informacin proporcionada por Edelmag, a continuacin se indican las protecciones que se analizar su coordinacin en este estudio. Para cada proteccin de cada SM, se indica el tipo de proteccin y los ajustes ya definidos. Las protecciones estn separadas en protecciones de instalaciones de Generacin, Transmisin (en los casos en que existan instalaciones de transformacin y lneas) e instalaciones de Clientes (alimentadores). Al respecto para los ajustes de protecciones de cada uno de los SM y en consideracin que la empresa Edelmag se encontraba, en el momento del desarrollo de este estudio, en proceso de actualizar los estudios de protecciones de cada SM, se intento utilizar dicha informacin para verificar el comportamiento de los esquemas y ajustes de protecciones, especialmente por cuanto este estudio debe abarcar un horizonte de 4 aos, periodo en el cual ya debieran estar incorporados los ajustes de los estudios que se estn desarrollando. En este sentido la situacin es la siguiente: Para los SM de Puerto Natales y Porvenir se utiliz los resultados del estudio de Anlisis del Sistema de Protecciones, documentado en el documento Informe Protecciones Natales VI. doc y Informe Protecciones Porvenir. doc, efectuado por la Empresa Digsilent. Para el SM de Puerto Williams se uso la informacin proporcionado por Edelmag en los documentos Ajustes Protecciones Puerto Williams.doc. Para el SM de Punta Arenas se utiliz la propuesta que est desarrollando la empresa Digsilent, especialmente la propuesta de ajustes para los alimentadores. Para el caso de los ajustes de los generadores se ha utilizado por el momento los ajustes actuales que estn contenidos en las bases de datos de Power Factory.

En general los nuevos estudios de protecciones que se estn realizando en la actualidad contemplan modificaciones en los esquemas de protecciones de los alimentadores de cada SM, con la finalidad de coordinar adecuadamente con las protecciones de los reconectadores, mantenindose pocas modificaciones en los ajustes de los generadores. A continuacin se informa acerca de los ajustes de cada instalacin de los distintos SM.

Informe Tcnico

Pgina 20

6 Protecciones Consideradas en el Estudio

6.1 Esquemas de Protecciones Punta Arenas


6.1.1 Instalaciones de Generacin
Ajuste 50 Punta Arenas Tiempo Definido Generador 1 4 5 7 8 9 Proteccin Unidad Hitachi a GAS Unidad Solar Mars a GAS Unidad Caterpillar a GAS Unidad Solar Titn a GAS Turbina a GAS GE 12.22 MVA T.G. SOLAR TITAN TT/CC 2000/5 800/5 200/5 1200/5 800/5 1200/5 40 5,8 9600 928 0 0 25 1000 1 Trip [A] Trip [A] sec pri TMS [s] Tiempo Definido Trip [A] Trip [A] sec pri TMS [s] Trip [A] Trip [A] Curva de Tiempo sec 3 5,8875 4,25 5,4 5,75 3,6 pri 1200 942 170 1296 920 864 IEC Normal Inversa (255-3) ANSI/IEEE Mode Inversa ANSI/IEEE Inversa IEC Normal Inversa (255-3) IEC Normal Inversa (255-3) IEC Very Inversa 0,54 3 1 0,8 0,07 11 TMS [s] Tiempo Inverso Ajustes 51

Cuadro 5 Resumen Protecciones generadores SM Punta Arenas

6.1.2 Instalaciones de Transmisin


Sobrecorriente Residual Ajuste 50N Linea de transmisin 66 kV Tiempo Definido N 1 2 Subestacin TT/CC 400/5 400/5 Trip [A] Trip [A] sec pri 672 672 TMS [s] 0,04 0,04 Tiempo Definido Trip [A] Trip [A] sec 5,25 5,25 pri 420 420 TMS [s] 1 1 Trip [A] Trip [A] Curva de Tiempo sec 1,58 1,58 pri 126,4 126,4 IEC Normal Inversa (255-3) IEC Normal Inversa (255-3) 0,05 0,05 TMS [s] Tiempo Inverso Ajustes 51N

Tres Puentes Punta Arenas

8,4 8,4

Cuadro 6 Resumen Ajustes de 50/51N Lnea de Transmisin

Informe Tcnico

Pgina 21

6 Protecciones Consideradas en el Estudio

Sobrecorriente Direccional de fase Ajuste 67 Linea de transmisin 66 kV Tiempo Definido N Subestacin TT/CC 400/5 1 Trip [A] Trip [A] sec 7,6 1,48 9,2 7,6 1,48 9,2 pri 608 116 736 608 116 736 TMS [s] 0,5 0,04 0,04 0,5 0,04 0,04 Forward Forward Forward Forward Forward Forward 3,99 0,84 319,2 67,2 IEC Normal Inversa (255-3) IEC Normal Inversa (255-3) 0,07 0,07 Forward Forward Direccin Trip [A] Trip [A] sec 3,99 0,84 pri 319,2 67,2 IEC Normal Inversa (255-3) IEC Normal Inversa (255-3) 0,07 0,07 Forward Forward Tiempo Inverso Curva de Tiempo TMS [s] Direccin

Tres Puentes

400/5 400/5 400/5

Punta Arenas

400/5 400/5

Cuadro 7 Resumen Ajustes de 67 Lnea de Transmisin

6.1.3 Instalaciones de Clientes


En el siguiente cuadro se resume la informacin de protecciones asociada a los alimentadores de Clientes.
Ajustes 51 Punta Arenas Tiempo Definido Trip [A] Trip [A] Alimentador Proteccin 1 2 3 4 5 6 7 8 9 10 11 51/51N 51/51N 51/51N 51/51N 51/51N 51/51N 51/51N 51/51N 51/51N 51/51N 51/51N Tipo TT/CC sec P141 Alstom 500/5 P141 Alstom 500/5 P141 Alstom 500/5 P141 Alstom 500/5 P141 Alstom 500/5 P141 Alstom 500/5 P141 Alstom 500/5 P141 Alstom 500/5 P141 Alstom 500/5 P141 Alstom 500/5 P141 Alstom 500/5 3 4 3 12 22 12 12 3 3 3 12 pri 300 400 300 1200 2200 1200 1200 300 300 300 1200 0,2 0,2 0,2 0,05 0,05 0,2 0,05 0,2 0,2 0,2 0,075 3 300 3 3 3 3 300 300 300 300 TMS [s] sec pri IEC Normal Inversa (255-3) IEC Normal Inversa (255-3) IEC Normal Inversa (255-3) IEC Normal Inversa (255-3) IEC Normal Inversa (255-3) IEC Normal Inversa (255-3) IEC Normal Inversa (255-3) IEC Normal Inversa (255-3) IEC Normal Inversa (255-3) IEC Normal Inversa (255-3) IEC Normal Inversa (255-3) 0,075 0,095 0,010 0,120 0,075 Trip [A] Trip [A] Curva de Tiempo TMS [s] sec 1 1 1 1 1 1 1 1 1 1 1 pri 100 100 100 100 100 100 100 100 100 100 100 0,60 0,60 0,60 0,60 0,60 0,60 0,60 0,60 0,60 0,60 0,60 Tiempo Inverso Tiempo Definido Trip [A] Trip [A] TMS [s] Ajustes 51N

Cuadro 8 Informacin de Proteccin de clientes sistema Punta Arenas

Informe Tcnico

Pgina 22

6 Protecciones Consideradas en el Estudio

6.2 Esquema de Protecciones Sistema Puerto Natales


6.2.1 Instalaciones de Generacin
En el cuadro siguiente se resume la informacin de protecciones de los generadores
Ajuste 50 Puerto Natales Tiempo Definido N 3 4 5 6 8 9 Generador Motor-Generador DIESEL (300 kW) F.Morse Motor-Generador a GAS - Waukesha Turbina Solar Saturno a GAS Turbina Solar Saturno a GAS Motor-Generador Caterpillar a DIESEL-PN Motor-Generador a GAS - Waukesha TT/CC 400/5 200/5 200/5 100/5 400/5 5000/5 3000/5 15 10 16,5 1200 10000 9900 0 0 0 Trip [A] Trip [A] sec 15 20 20 pri 1200 800 800 TMS [s] 0 0 0 17,5 7 4,5 350 560 4500 0,3 0,82 0,82 7 4200 IEC Normal Inversa (255-3) 0,09 Tiempo Definido Trip [A] Trip [A] sec 7 pri 560 TMS [s] 0,82 9 9 9 360 360 180 IEC Normal Inversa (255-3) IEC Normal Inversa (255-3) IEC Normal Inversa (255-3) 0,08 0,08 0,08 Trip [A] Trip [A] Curva de Tiempo sec pri TMS [s] Tiempo Inverso Tiempo Definido Trip [A] Trip [A] sec 1 1 1 1 1 1 pri 80 40 40 20 80 1000 TMS [s] 0,05 0,05 0,05 0,05 0,05 0,05 Ajustes 51 Ajustes 51N

10 Jenbacher 1.42 MW

Cuadro 9 Resumen protecciones generador SM Puerto Natales

6.2.2 Instalaciones de Transmisin


En este sistema no existen instalaciones de transmisin para los cuales evaluar la coordinacin de protecciones.

Informe Tcnico

Pgina 23

6 Protecciones Consideradas en el Estudio

6.2.3 Instalaciones de Clientes


En el siguiente cuadro se resume la informacin de protecciones asociada a los alimentadores de Clientes.
Ajustes 51 Puerto Natales Tiempo Inverso Alimentador Proteccin 1 2 3 4 51/51N 51/51N 51/51N 51/51N Tipo TT/CC Trip [A] Trip [A] sec pri 4 3 4 3 80 60 80 60 Curva de Tiempo IEC Normal Inversa IEC Normal Inversa IEC Normal Inversa IEC Normal Inversa TMS [s] 0,10 0,14 0,10 0,14 Tiempo Definido Tiempo Definido Trip [A] Trip [A] Trip [A] Trip [A] TMS [s] TMS [s] sec pri sec pri 32,5 32,5 32,5 32,5 650 650 650 650 0,06 0,06 0,06 0,06 1 1 1 1 20 20 20 20 0,48 0,45 0,45 0,45 Ajustes 51N

P141 Alstom 100/5 P141 Alstom 100/5 P141 Alstom 100/5 P141 Alstom 100/5

Cuadro 10 Informacin de Proteccin de clientes sistema Puerto Natales

Informe Tcnico

Pgina 24

6 Protecciones Consideradas en el Estudio

6.3 Esquema de Protecciones Sistema Porvenir


6.3.1 Instalaciones de Generacin
En el cuadro siguiente se resume la informacin de protecciones de los generadores

Ajuste 50 Porvenir Tiempo Definido N 1 4 5 6 7 8 9 Generador TT/CC 1000/5 2000/5 500/5 2500/5 2500/5 3000/5 2000/5 2500/5 15 23 17 9000 0,05 9200 0,05 8500 0,05 Trip [A] Trip [A] sec pri 4000 TMS [s] 0,05 Tiempo Definido Trip [A] Trip [A] sec 5 5 2,5 5 5 5 5 5 pri 1000 2000 250 2500 2500 3000 2000 2500 TMS [s] 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85 5 2,5 5 5

Ajustes 51 Tiempo Inverso Trip [A] Trip [A] Curva de Tiempo sec pri TMS [s] Tiempo Definido Trip [A] Trip [A] sec 20 2000 250 2500 2500 IEC Normal Inversa IEC Normal Inversa IEC Normal Inversa IEC Normal Inversa 0,15 0,16 0,16 0,16 16 8000 0,05 pri 4000 TMS [s] 0,05

Ajustes 51N Tiempo Inverso Trip [A] Trip [A] Curva de Tiempo sec pri TMS [s]

Caterpillar DIESEL 1- PO Waukesha - PO Caterpillar DIESEL 2- PO Waukesha -PO Waukesha -PO Palmero 1.36 MW Caterpillar DIESEL - PA

20

1,6

660

IEC Normal Inversa 0,35

1,5

750

IEC Normal Inversa 0,34

3000

IEC Normal Inversa 0,16

10 GE Jenbacher JM416 1

16

8000 0,05

Cuadro 11 Resumen protecciones generador SM Porvenir

6.3.2 Instalaciones de Transmisin


En este sistema no existen instalaciones de transmisin para los cuales evaluar la coordinacin de protecciones.

Informe Tcnico

Pgina 25

6 Protecciones Consideradas en el Estudio

6.3.3 Instalaciones de Clientes


En el siguiente cuadro se resume la informacin de protecciones asociada a los alimentadores de Clientes.
Ajustes 51 Porvenir Tiempo Inverso Trip [A] Trip [A] Alimentador Proteccin 1 2 3 4 51/51N 51/51N 51/51N 51/51N Tipo P141 Alstom P141 Alstom P141 Alstom P141 Alstom TT/CC sec 50/5 50/5 50/5 50/5 5 7 5 5 pri 50 70 50 50 Kyle 112 Kyle 112 Kyle 112 Kyle 112 1 1 1 1 Curva de Tiempo TMS [s] sec 65 65 65 65 pri 650 650 650 650 0,05 0,05 0,05 0,05 Tiempo Definido Trip [A] Trip [A] TMS [s] sec 1 1 1 1 pri 10 10 10 10 0,5 0,5 0,5 0,5 Tiempo Definido Trip [A] Trip [A] TMS [s] Ajustes 51N

Cuadro 12 Informacin de Proteccin de clientes sistema Porvenir

6.4 Esquema de Protecciones Sistema Puerto Williams


6.4.1 Instalaciones de Generacin
Unidad generadora Unidad N 1 Caterpillar 3508B Interruptor 52G1, Cutler Hammer, Digitrip In: 1600 Amp. Long delay setting: 0.8 Long delay time: 2 Short delay setting: 3 Short delay time: 0.5* Instantaneous: OFF Unidad N 2 Caterpillar 3508 Interruptor 52G2, Merlin Gerin, STR28D In: 1600 Amp. Ir: 1 Im: 10 Unidad Generadora Unidad N 3 Caterpillar Interruptor 52G3, Merlin Gerin, STR38S In: 800Amp. Io: 0.8 Ir: 0.85 Im: 8 Tm: 0.4 I: 7 Unidad N 6 Cummins - Petbow Interruptor 52G6, Merlin Gerin, STR38S In: 800Amp. Io: 0.8 Ir: 0.85 Im: 8 Tm: 0.4 I: 7

Cuadro 13 Informacin de protecciones de Unidades generadoras en sistema Puerto Williams

Informe Tcnico

Pgina 26

6 Protecciones Consideradas en el Estudio

6.4.2 Instalaciones de Transmisin


En este sistema no existen instalaciones de transmisin para los cuales evaluar la coordinacin de protecciones.

6.4.3 Instalaciones de Clientes


En el siguiente cuadro se resume la informacin de protecciones asociada a los alimentadores de Clientes.
Ajustes 51 Puerto Williams Tiempo Inverso Trip [A] Trip [A] Alimentador Proteccin 1 2 3 51/51N 51/51N 51/51N Tipo TT/CC sec NOVA Form 5 1000/1 NOVA Form 5 1000/1 NOVA Form 5 1000/1 0,02 0,02 0,02 pri 20 20 20 Kyle 104 Kyle 104 Kyle 104 1,0 1,0 1,0 Curva de Tiempo TMS [s] sec 0,01 0,01 0,01 pri 10 10 10 Kyle 104 Kyle 104 Kyle 104 0,5 0,5 0,5 Tiempo Inverso Trip [A] Trip [A] Curva de Tiempo TMS [s] Ajustes 51N

Cuadro 14 Informacin de Proteccin de clientes sistema Puerto Williams

Informe Tcnico

Pgina 27

7 Desarrollo de los Estudios

7 Desarrollo de los Estudios


En primer trmino el estudio considera efectuar una determinacin del tiempo mximo para despeje de fallas que debern poseer las protecciones de los distintos elementos, generacin, transmisin y consumos, los cuales debern estar determinados en funcin de la prdida de estabilidad de cada sistema. Posteriormente se determinarn los niveles de cortocircuito en cada Sistema Mediano, en condiciones de demanda mnima y mxima, con la finalidad de obtener las mximas corrientes de falla que se espera en cada condicin de demanda. Dichos valores permitirn aportar una idea de si los ajustes de cada proteccin se encuentran suficientemente bien determinados, adems de obtener el crecimiento de estos valores en el periodo 2011-2014. En tercer trmino est contemplado modelar las protecciones en el simulador Power Factory y determinar para diferentes situaciones de fallas la efectiva coordinacin de las protecciones. Esta verificacin se efectuar mediante el aporte de curvas de operacin aportadas por las propias protecciones simuladas en Power Factory.

7.1 Determinacin del tiempo mximo de despeje de fallas en instalaciones de Edelmag


A continuacin y cumpliendo con uno de los puntos bsicos que establece la NT para este estudio, se determinar el tiempo mximo para despeje de falla que se deber cumplir para los distintos tipos de instalaciones, el tiempo mximo deber ser determinado de tal forma que no implique poner en riesgo la operacin de los Sistemas Medianos. Segn la propia NTSyCS de SM, el tiempo de Tiempo mximo para despeje de falla corresponde al

Tiempo transcurrido desde el momento del inicio de la falla hasta la extincin del arco en el interruptor, para fallas que ocurran en los equipamientos de la unidad generadora directamente conectados al SM o en las instalaciones o equipamientos de las Instalaciones de Transmisin.
Para tal efecto la determinacin del tiempo mximo para despeje de fallas se determinar como: Se considerar el comportamiento de los sistemas de control de tensin y frecuencia de cada unidad generadora, por cuanto influyen directamente en el comportamiento dinmico del sistema interconectado ante fallas severas. El tiempo mximo de despeje de falla se determinar para las contingencias de mayor severidad, esto es, fallas del tipo trifsicas en puntos cercanos de las barras de los generadores. Lo anterior con diferentes duraciones de las fallas aplicadas. Se medir en cada caso el ngulo rotrico de las unidades generadoras, adoptando para dicha variable un valor mximo de 120 para la primera excursin angular, medidos respecto de una referencia angular nica representativa de la posicin del eje inercial de cada SM. Dicho valor representar el valor lmite sobre el cual se estima prdida de estabilidad de las unidades generadoras.

Informe Tcnico

Pgina 28

7 Desarrollo de los Estudios

La determinacin anterior se efectuar para los despachos de generacin que se presentan con mayor probabilidad en la operacin de cada sistema. Con la finalidad de obtener un nico valor representativo del periodo se efectuar una revisin con la operacin estimada para al ao 2014. De acuerdo con el tamao de los Sistemas Medianos, se determinarn tiempos mximos de despeje de falla para dos tipos de SM. Uno para el SM de Punta Arenas y otro para los dems SM. En el cuadro siguiente se resume la operacin de los SM para las fallas aplicadas y para los diferentes tiempos de despeje de las mismas. El detalle grfico de estas simulaciones se encuentra incorporadas en el Anexo N1 de este informe.
SM Punta Arenas Tiempo de Despeje de falla Mayor ngulo rotrico seg 2,00 1,50 1,45 1,40 1,35 1,25 [ ] 179 138 126 114 107 90 Inestable Inestable Inestable Estable Estable Estable Estabilidad dinmica

Cuadro 15 Determinacin tiempo de despeje SM Punta Arenas


Otros Sistemas Medianos Tiempo de Despeje de falla Mayor ngulo rotrico seg 1,50 1,30 1,00 0,90 0,80 0,60 [ ] 175 175 111 (*) 97 (*) 70 70 Inestable Inestable Inestable Inestable Estable Estable Estabilidad dinmica

Cuadro 16 Determinacin tiempo de despeje Otros SM

(*): Se observa que pese a que se obtiene un valor mximo del ngulo en la primera oscilacin menor a 120 , el sistema sigue un comportamiento inestable.

Informe Tcnico

Pgina 29

7 Desarrollo de los Estudios

De acuerdo con los resultados obtenidos e indicados en los cuadros anteriores y considerando un grado de seguridad en la determinacin del tiempo mximo de despeje de fallas, se propone utilizar para cada SM un tiempo mximo de despeje de fallas de:
Tiempo mximo de despeje de Falla (TMdF) Sistemas Medianos Punta Arenas Otros Menores TMdF [seg] 1,35 0,8

Cuadro 17 TMdF propuestos

7.2 Estudios de Cortocircuitos


A continuacin se presentan los resultados de las simulaciones de cortocircuitos esperadas para cada uno de los sistemas medianos. Los niveles de cortocircuitos determinados corresponden a fallas en barras principales de cada SM. Los niveles de cortocircuito se determinan para la condicin de demanda mxima y mnima que se presentan anualmente en cada Sistema Mediando en el periodo 2011-2014. La determinacin de los niveles de cortocircuito se efecta bajo la Norma Internacional IEC, con factores de tensiones de prefalla de 1,1 sobre tensiones nominales para el caso de cortocircuitos en demanda mxima y de 1,0 para cortocircuitos en demanda mnima. Los clculos se efectan sin impedancias de falla.

7.2.1 Resultados para SM Punta Arenas


Niveles de Cortocircuitos Sistema Punta Arenas Mnima Ao Barras Monofsico MVA
13.2 kV P.A. 2011 13.2 kV T.P. 11.5 kV T.P. 13.2 kV P.A. 2012 13.2 kV T.P. 11.5 kV T.P. 13.2 kV P.A. 2013 13.2 kV T.P. 11.5 kV T.P. 13.2 kV P.A. 2014 13.2 kV T.P. 11.5 kV T.P. 64,60 78,36 130,00 72,00 88,48 160,30 72,00 88,48 160,30 72,00 88,48 160,30

Mxima Monofsico MVA


86,96 115,85

Trifsico MVA
49,30 85,50 151,11 55,13 102,80

Trifsico MVA
68,71 158,28

kA
2,83 3,43 6,53 3,15 3,87 8,05 3,15 3,87 8,05 3,15 3,87 8,05

kA
2,16 3,74 7,59 2,41 4,50

kA
3,80 5,07

kA
3,01 6,92

215,53 10,82 405,76 20,37 86,96 115,85 3,80 5,07 68,71 158,28 3,01 6,92

214,71 10,78 215,53 10,82 405,76 20,37 55,13 102,80 2,41 4,50 86,96 115,85 3,80 5,07 68,71 158,28 3,01 6,92

214,71 10,78 215,53 10,82 405,76 20,37 55,13 102,80 2,41 4,50 86,96 115,85 3,80 5,07 68,71 158,28 3,01 6,92

214,71 10,78 215,53 10,82 405,76 20,37

Cuadro 18 Niveles de Cortocircuito SM Punta Arenas

Informe Tcnico

Pgina 30

7 Desarrollo de los Estudios

7.2.2 Resultados para SM Puerto Natales


Niveles de Cortocircuitos Sistema Puerto Natales Mnima Ao Barras Monofsico MVA
2011 13.2 kV 2012 13.2 kV 2013 13.2 kV 2014 13.2 kV 16,66 21,65 21,15 21,15

Mxima Monofsico MVA


41,61 43,86 50,30 50,30

Trifsico MVA kA
11,22 14,64 14,28 14,28 0,49 0,64 0,62 0,62

Trifsico MVA kA
28,55 30,11 34,70 34,70 1,25 1,32 1,52 1,52

kA
0,73 0,95 0,92 0,92

kA
1,82 1,92 2,20 2,20

Cuadro 19 Niveles de Cortocircuito SM Puerto Natales

7.2.3 Resultados para SM Porvenir


Niveles de Cortocircuitos Sistema Porvenir Mnima Ao Barras Monofsico Trifsico MVA
2011 2012 2013 2014 13.2 kV 13.2 kV 13.2 kV 13.2 kV 16,11 15,87 15,87 15,87

Mxima Monofsico MVA


32,69 32,44 32,44 32,44

Trifsico MVA kA
22,35 22,17 22,17 22,17 0,94 0,93 0,93 0,93

kA
0,67 0,66 0,66 0,66

MVA kA
10,86 10,70 10,70 10,70 0,45 0,45 0,45 0,45

kA
1,37 1,36 1,36 1,36

Cuadro 20 Niveles de Cortocircuito SM Porvenir

7.2.4 Resultados para SM Puerto Williams


Niveles de Cortocircuitos Sistema Puerto Williams Mnima Ao Barras Monofsico MVA
2011 2012 2013 2014 13.2 kV 13.2 kV 13.2 kV 13.2 kV 4,68 4,68 4,68 4,68

Mxima Monofsico MVA


9,75 9,75 9,75 9,75

Trifsico MVA kA
3,17 3,17 3,17 3,17 0,14 0,14 0,14 0,14

Trifsico MVA kA
6,72 6,72 6,72 6,72 0,29 0,29 0,29 0,29

kA
0,20 0,20 0,20 0,20

kA
0,43 0,43 0,43 0,43

Cuadro 21 Niveles de Cortocircuito SM Puerto Williams

Informe Tcnico

Pgina 31

7 Desarrollo de los Estudios

7.2.4.1

Comentarios:
En muchos casos se presentan idnticos valores de nivel de cortocircuito en el periodo 2011-2014, lo cual indica que las unidades que abastecen la demanda son las mismas, aunque con un nivel distinto de despacho de generacin, sin embargo, para las corrientes de fallas el nivel de generacin no resulta relevante. Slo en sistema de Punta Arenas, se aprecia un crecimiento en el nivel de cortocircuito, tanto trifsico como monofsico. En los dems sistemas se observan valores similares en cada ao.

7.3 Corrientes de Carga por Alimentador


A continuacin se indican las corrientes de carga mxima por alimentador de cada sistema elctrico, lo cual permitir determinar sobre qu valor de corriente deben ajustarse los primeros ajustes de operacin de protecciones. Los valores indicados en tabla corresponden al mayor valor que cada alimentador alcanza en el periodo 2011-2014, y que por el nivel de crecimiento de los consumos estos se presentan en el ao 2014. Corrientes de Carga Mxima por Alimentadores Alimentador SM Punta Arenas
Alimentador-1 Alimentador-2 Alimentador-3 Alimentador-4 Alimentador-5 Alimentador-6 Alimentador-7 Alimentador-8 Alimentador-9 Alimentador-10 Alimentador-X11 Alimentador-12 Alimentador-13 AL-1 AL-2 AL-3 AL-4 AL-5 AL-6 AL-7 AL-8A AL-8B AL-9 AL-X10A AL-X10B AL-X11 AL-12 AL-13

Demanda Mxima MVA


4,579 4,579 5,309 3,848 4,384 2,435 2,776 2,557 2,557 5,017 1,364 1,364 2,776 2,435 2,728

Fp
0,986 0,998 0,96 0,992 0,99 0,983 0,968 0,958 0,958 0,961 0,954 0,954 0,958 0,983 0,954

KAmp
0,219 0,225 0,263 0,187 0,199 0,116 0,133 0,125 0,124 0,243 0,064 0,064 0,133 0,108 0,124

Kamp Total
219 225 263 187 199 116 133 249 243 128 133 108 124

Cuadro 22 Nivel mximo de corriente de carga en Alimentadores SM Punta Arenas

Informe Tcnico

Pgina 32

7 Desarrollo de los Estudios

Corrientes de Carga Mxima por Alimentadores Alimentador SM Puerto Natales


AL1-1 AL1-2

Demanda Mxima MVA


0,242 0,242 0,242 0,242 0,242 0,242 0,486 0,486 0,863 0,863 0,582 0,582

Fp
0,936 0,936 0,936 0,936 0,936 0,936 0,991 0,991 0,96 0,96 0,965 0,965

KAmp
0,012 0,012 0,012 0,012 0,012 0,012 0,022 0,022 0,04 0,04 0,027 0,027

Amp Total

Alimentador 1

AL1-3 AL1-4 AL1-5 AL1-6

72

Alimentador 2 Alimentador 3 Alimentador 4

AL2-1 AL2-2 AL3-1 AL3-2 AL4-1 AL4-2

44

80

54

Cuadro 23 Nivel mximo de corriente de carga en Alimentadores SM Puerto Natales

Corrientes de Carga Mxima por Alimentadores Alimentador SM Porvenir MVA


AL1 AL2-1 AL2-2 0,49 0,223 0,223 1,85 0,842

Demanda Mxima Fp
0,964 0,89 0,89 0,953 0,994

KAmp
0,021 0,011 0,011 0,081 0,036

Amp Total

Alimentador 1 Alimentador 2 Alimentador 3 Alimentador 4

21 22 81 36

AL3 AL4

Cuadro 24 Nivel mximo de corriente de carga en Alimentadores SM Porvenir

Corrientes de Carga Mxima por Alimentadores Alimentador SM Puerto Williams MVA


0,49 0,223 1,85

Demanda Mxima Fp
0,964 0,89 0,953

KAmp
0,021 0,011 0,081

Amp Total

Alimentador 1 Alimentador 2 Alimentador 3

AL1 AL2 AL3

21 11 81

Cuadro 25 Nivel mximo de corriente de carga en Alimentadores SM Puerto Williams

7.3.1 Comentarios
El nivel de carga mximo esperado en el periodo 2011-2014 permite verificar si los ajustes de las protecciones deben modificar sus ajustes para adecuarse al crecimiento de la demanda. Este valor define el punto para el cual la proteccin no debe activarse.

Informe Tcnico

Pgina 33

7 Desarrollo de los Estudios

7.4 Verificacin de la Coordinacin


La verificacin de la coordinacin de protecciones se efectuar mediante el anlisis de curvas de operacin. Para tal efecto se modelar cada proteccin con el simulador Power Factory. En los casos que por obsolescencia tecnologa no se puedan representar mediante un modelo digital, sern modeladas por un modelo aproximado. En primer trmino se evaluar el nivel de coordinacin de las protecciones de los alimentadores y posteriormente las correspondientes a sistemas de transmisin y generadores.

7.4.1 Coordinacin de Protecciones en Alimentadores


Para fallas que ocurran aguas abajo de los alimentadores, estas deben ser despejadas por cada alimentador. Se debe verificar en cada caso que estas protecciones resultan ms rpidas en operar que las correspondientes de los generadores o de otras instalaciones de transmisin. Especialmente para los SM donde no existen sistemas de transmisin y tanto la generacin como los alimentadores se conectan en una barra comn. Como los alimentadores no poseen generacin aguas abajo que contribuyan con aportes de corriente a las fallas que se originen en el sistema elctrico, no se requiere especificar direccionalidad a las protecciones de sobrecorrientes. Adicionalmente, las fallas que suceden en un alimentador, sus efectos, no provocan problemas en otros alimentadores, es decir, sus protecciones no se enteran de la sobrecorriente en otros puntos. El efecto directo, de no ser despejada adecuadamente la falla en el alimentador se produce sobre todas las unidades generadoras, las cuales actuarn de acuerdo con sus tiempos de despeje. A continuacin se informa acerca de los tiempos de actuacin de las protecciones de los alimentadores ante fallas que se registren en sus propias instalaciones. Estos tiempos sern posteriormente contrastados con los tiempos de operacin de protecciones de los generadores y as verificar la correcta coordinacin de protecciones en cada alimentador. La informacin base que respalda el resumen de los cuadros siguientes se encuentra en el Anexo N 02, donde se aportan las curvas de operacin de protecciones de cada alimentador y su punto de operacin (tiempo de actuacin) ante la falla.

Informe Tcnico

Pgina 34

7 Desarrollo de los Estudios

Operacin de Protecciones de Alimentadores


Corriente Carga Alimentador Descripcin Mxima 0 Ohms T Operacin 20 Ohms T Operacin 0 Ohms T Operacin 20 Ohms T Operacin Coordinacin SM Punta Arenas AL-1 AL-2 AL-3 AL-4 AL-5 AL-6 AL-7 AL-8 AL-9 AL-10 AL-11 Alimentador-1 Alimentador-2 Alimentador-3 Alimentador-4 Alimentador-5 Alimentador-6 Alimentador-7 Alimentador-8 Alimentador-9 Alimentador-10 Alimentador-11 Amp 219 225 263 187 199 116 133 249 243 128 133 Amp 72 44 80 54 Amp 21 22 81 36 Amp 21 11 81 KA 1,831 1,276 1,998 3,068 3,599 3,068 3,068 1,998 2,193 1,998 1,988 KA 1,286 1,222 1,286 1,286 KA 0,831 0,831 0,927 0,831 KA 0,288 0,288 0,288 mseg 300 300 300 140 120 290 170 300 300 300 155 mseg 245 190 245 180 mseg 125 105 102 102 mseg 100 100 100 KA 0,381 0,585 0,387 0,391 0,397 0,391 0,391 0,387 0,393 0,387 0,391 KA 0,348 0,339 0,348 0,348 KA 0,33 0,33 0,38 0,33 KA 0,216 0,216 0,216 mseg 300 300 300 2498 248 3155 1972 300 300 300 1972 mseg 470 406 470 394 mseg 104 107 104 104 mseg 100 100 100 KA 2,086 1,389 2,200 2,686 3,071 2,686 2,686 2,310 2,580 2,310 2,686 KA 1,692 1,564 1,692 1,692 KA 1,147 1,147 1,357 1,147 KA 0,418 0,418 0,418 mseg 620 620 620 620 620 620 620 620 620 620 620 mseg 600 570 570 570 mseg 520 520 520 520 mseg 100 100 100 KA 0,383 0,355 0,389 0,391 0,397 0,391 0,391 0,389 0,396 0,391 0,389 KA 0,357 0,348 0,357 0,357 KA 0,352 0,352 0,41 0,352 KA 0,269 0,269 0,269 mseg 620 620 620 620 620 620 620 620 620 620 620 mseg 600 570 570 570 mseg 520 520 520 520 mseg 100 100 100 Protecciones Ok Ok Ok Ok Ok Ok Ok Ok Ok Ok Ok Protecciones Ok Ok Ok Ok Protecciones Ok Ok Ok Ok Protecciones Ok Ok Ok Falla Trifsica Corriente de falla Falla Monofsica Verificacin

SM Puerto Natales AL-1 AL-2 AL-3 AL-4 Alimentador-1 Alimentador-2 Alimentador-3 Alimentador-4

SM Porvenir AL-1 AL-2 AL-3 AL-4 Alimentador-1 Alimentador-2 Alimentador-3 Alimentador-4

SM Puerto Williams AL-1 AL-2 AL-3 Alimentador-1 Alimentador-2 Alimentador-3

Cuadro 26 Resumen Operacin de Protecciones en Alimentadores

7.4.2 Coordinacin de Protecciones en Lnea de 66 kV


Esta medicin se efectuar slo en las instalaciones de transmisin del Sistema Mediano correspondiente a Punta Arenas, por cuanto es el nico sistema que cuenta con este tipo de instalaciones. En este sistema, el de Punta Arenas, cuenta con una lnea de transmisin de 66 kV (compuesta con dos transformadores en sus extremos) que permite la conexin de la barra de Tres Puentes 11,5 kV y la barra de Central Punta Arenas 13,2 kV. Los transformadores de los extremos son de 33 MVA.
Informe Tcnico Pgina 35

7 Desarrollo de los Estudios

7.4.2.1

Verificacin Coordinacin de Protecciones en Lnea 66 kV

Esta lnea de 66 kV que est compuesta en cada extremo por dos transformadores 66/13,2 kV (en central Punta Arenas) y 66/11,5 kV (en Central Puentes) de 33 MVA, cuenta con un esquema de protecciones idnticos en cada extremo y que est compuesto por: Para fallas entre fases protecciones de sobrecorriente direccionales (67), ubicado en los extremos de la lnea. Para fallas residuales por protecciones de sobrecorriente residual (51N) que se encuentran ubicadas en la parte de baja tensin de cada transformador.

Las protecciones de sobrecorriente direccionales cuentan con tres ajustes, uno de tiempo inverso (normalmente inverso) y dos ajustes de tiempo definido. De igual manera la proteccin de sobrecorriente residual. A continuacin se revisar el esquema de protecciones para diferentes tipos de configuracin de generacin entre central Punta Arenas y central Tres Puentes.

7.4.2.1.1

Caso sin generacin en central Punta Arenas (Caso de Mayor Probabilidad)

Para este caso se espera que el esquema de protecciones se comporte de la siguiente manera: Para corrientes de carga la recta de corrientes debe quedar fuera de la zona de operacin de cada proteccin. Uno de los extremos no la debe observar, dada su direccionalidad. De existir una falla en la lnea, el extremo central Punta Arenas no ver la falla, dado que desde su extremo no hay contribucin de corrientes hacia la falla (ausencia de generacin en este extremo). En cambio, el extremo central Tres Puentes debe provocar la apertura en un tiempo mnimo. Para cualquier falla aguas arriba de la barra 66 kV de central Tres Puentes las protecciones de sobrecorriente direccional no vern las fallas. En efecto, la proteccin de 66 kV en central Tres Puentes ve la falla hacia atrs y la del extremo Punta Arenas 66 kV no ve corrientes de falla por ausencia de generacin. Para fallas que ocurran aguas debajo de la barra 66 kV Central Punta Arenas, la proteccin de dicho extremo ver la falla hacia atrs y el del extremo 66 kV Tres Puentes si registrar la falla, pero debe operar en un tiempo de respaldo.

7.4.2.1.2

Caso con generacin en central en Punta Arenas (Caso de menor Probabilidad)

Para esta configuracin de centrales el esquema se debe comportar como sigue: Para la corriente de carga, la recta de corrientes, debe quedar fuera de la zona de operacin de cada proteccin. Uno de los extremos no la debe observar, dada su direccionalidad. La corriente de carga sigue la direccin del rea que es excedentaria en generacin.
Pgina 36

Informe Tcnico

7 Desarrollo de los Estudios

En este caso, de existir una falla en la lnea, la falla se aprecia desde ambos extremos, dado que desde ambos existe contribucin de corriente hacia el punto de falla. Para fallas que ocurran fuera de la lnea, una de las protecciones ver la falla, dado que la otra la observa en reversa.

Mediante simulaciones se determinar si el esquema de protecciones se comporta como el indicado.


Corriente de Carga Caso Estudio Caso 1 Caso 2 Zona Operacin Extremo T. Puentes No No Falla en lnea Caso Estudio Caso 1 Caso 2 Zona Operacin Extremo T. Puentes Si Si Falla en 66 KV PA Caso Estudio Caso 1 Caso 2 Zona operacin Extremo T. Puentes Si Si Falla en 66 KV TP Caso Estudio Caso 1 Caso 2 Zona operacin Extremo T. Puentes No No Extremo P. Arenas Si Si Extremo P. Arenas No No Extremo P. Arenas No Si Extremo P. Arenas No No Verificacin Coordinacin Protecciones Ok Ok Verificacin Coordinacin Protecciones Ok Ok Verificacin Coordinacin Protecciones Ok Ok Verificacin Coordinacin Protecciones Ok Ok

Cuadro 27 Resumen Operacin Esquema de protecciones de lnea 66 kV

La informacin de respaldo se encuentra en el Anexo N 3, a modo de curvas de operacin para cada estudio.

7.4.3 Coordinacin de Protecciones en Generadores


Para verificar la efectividad en la coordinacin de protecciones de las unidades generadoras se procedi a simular digitalmente las diferentes protecciones que cada unidad posee. En algunos casos fue necesario asimilar la proteccin mediante un modelo aproximado, lo cual se debi principalmente a que algunas unidades son de tecnologa electrodinmica y no cuentan con modelos representativos de su operacin. El procedimiento de verificacin de la coordinacin de la proteccin es el siguiente:

Informe Tcnico

Pgina 37

7 Desarrollo de los Estudios

Se determina un flujo de carga con demanda mxima en cada sistema, lo cual permite verificar que con los aumentos de la carga esperada en el periodo 2011-2014 no se activen zonas de operacin de protecciones. Se efectan fallas cercanas y alejadas de la barra donde se conecta cada generador, esto permite determinar el tiempo de operacin de la proteccin y comparacin con los dems tiempos de operacin de otras instalaciones, especialmente con la operacin de protecciones de los alimentadores. En un mismo grfico se han incluido las corrientes de flujos de carga, corrientes de fallas cercanas y alejadas, ms la curva de operacin de las protecciones. Esto permite determinar los tiempos de operacin de cada proteccin. Slo se ha modelado las protecciones de sobrecorrientes entre fases (51) por cuanto la mayora de las unidades generadoras slo posee este tipo de protecciones de sobrecorriente.

A continuacin se aporta en un cuadro resumen la operacin de los generadores de cada sistema, con que se cont con informacin para efectuar la simulacin.
Operacin de Protecciones Unidades Generadoras Unidad Sistema Unidad Hitachi a GAS Unidad Solar Mars a GAS Punta Arenas Unidad Caterpillar a GAS Unidad Solar Titn a GAS Turbina a GAS GE 12.22 MVA T.G. SOLAR TITAN Motor-Generador DIESEL (300 kW) F.Morse Motor-Generador a GAS - Waukesha Turbina Solar Saturno a GAS Puerto Natales Turbina Solar Saturno a GAS Motor-Generador Caterpillar a DIESEL-PN Motor-Generador a GAS - Waukesha Jenbacher 1.42 MW Caterpillar DIESEL 1- PO Waukesha - PO Caterpillar DIESEL 2- PO Porvenir Waukesha -PO Waukesha -PO Palmero 1.36 MW Caterpillar DIESEL - PA GE Jenbacher JM416 1 Puerto Williams Generadora Flujo de Carga Amp 994 516 131 657 253 709 191 83 89 25 191 1869 2464 723 802 161 1574 1574 2252 524 1519 783 seg Falla Alejada kA 2,519 1,161 0,777 2,992 1,065 1,379 0,917 0,660 0,660 0,335 0,916 7,819 12,748 3,014 4,866 0,615 0,655 0,655 0,655 7,280 6,356 2,328 mseg 5059 7440 567 6737 3356 2897 840 917 917 897 840 850 850 970 970 970 970 970 970 870 970 558 Falla Cercana KA 7,623 3,513 0,83 7,851 3,327 4,172 1,436 0.977 0,977 0,440 1,436 10,497 12,302 5,234 9,161 1,045 12,302 5,343 5,343 14,215 11,839 6,176 Coordinacin

mseg Protecciones 2007 1227 512 3053 376 301 120 120 120 320 120 130 120 170 680 772 692 170 170 170 170 153 Ver Nota OK OK Ver Nota OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK

MotorGenerador Caterpillar Diesel 3508B

Informe Tcnico

Pgina 38

7 Desarrollo de los Estudios

MotorGenerador Caterpillar Diesel PW3508 Motor-Generador Diesel Caterpillar (PW) Motor-Generador Deutz Diesel PW

437 469 369

2,162 1,163 1,710

464 559 519

5,234 3,768 2,446

117 133 310

OK OK OK

Cuadro 28 Resumen Operacin de Protecciones Unidades generadoras

Nota: Los Valores de tiempo de operacin destacados indican que para fallas cercanas la proteccin opera con tiempos de operacin por sobre lo indicado en los anlisis de tiempo Mximo de despeje de falla (1135 mseg), lo cual requiere ser ajustado. Sin corresponder a una descoordinacin de protecciones, lo anterior pone en riesgo la estabilidad del sistema. La informacin de respaldo se encuentra incluida en el Anexo N4, a modo de curvas de operacin por cada simulacin efectuada.

7.4.4 Comentarios y Conclusiones Estudios de Verificacin de Protecciones


Los comentarios que se emiten a continuacin resultan vlidos para los cuatro Sistemas Medianos analizados: Se ha efectuado una verificacin de la efectiva coordinacin de las protecciones para cada una de las instalaciones que conforman cada sistema mediano. De los resultados obtenidos se concluye como relevante lo siguiente: En general los ajustes actuales definidos en cada tipo de instalacin, esto es, Alimentadores, Transmisin y Generacin, no requieren ser modificados, salvo ajustes menores en algunos generadores, para evitar poner en riesgo la estabilidad del sistema. En cada uno de los anlisis se ha verificado que se cumple la debida coordinacin de protecciones. En efecto, para fallas que ocurren aguas debajo de cada alimentador se aprecia que la falla es despejada por los propios alimentadores, los cuales responden de manera ms rpida que los generadores y sistemas de transmisin. Para este tipo de fallas, las protecciones de transmisin y generacin slo actan como respaldo ante fallas en el correcto despeje de la falla. Para fallas que ocurren aguas arriba de los alimentadores, las protecciones de los alimentadores no participan, dado que las protecciones no registran aportes de corrientes de falla desde los alimentadores hacia el punto de falla, lo cual se debe a que los alimentadores no poseen generadores aguas abajo que contribuyan con corrientes de falla. Para las lneas de transmisin se ha determinado que el esquema de protecciones opera adecuadamente, por cuanto despeja en forma rpida las fallas que se origina en la lnea, y acta como respaldo para fallas que ocurran fuera de la propia instalacin. Esta verificacin se efectu para diferentes configuraciones de generacin en los extremos de la lnea. En el caso de las unidades generadoras se ha verificado la correcta operacin de su esquema de protecciones, actuando selectivamente y con tiempos acordes a cada falla que se presente en el sistema, salvo los cambios que se plantean en algunos generadores del
Pgina 39

Informe Tcnico

7 Desarrollo de los Estudios

SM Punta Arenas. En efecto, para fallas que ocurren en las proximidades de la barra donde la unidad se conecta, la proteccin acta en forma rpida. En cambio para fallas ms alejadas acta con tiempos que permiten el despeje de las instalaciones que se encuentran en fallas, actuando estas protecciones como respaldo sino ocurre el despeje exitoso. En todos los casos se verific que los esquemas de protecciones no actan para las mximas corrientes de carga esperadas en el periodo 2010-2014.

En resumen, se ha verificado el correcto desempeo del esquema de protecciones en las instalaciones de los Sistemas Medianos operados por la empresa Edelmag.

Informe Tcnico

Pgina 40

8 Conclusiones

8 Conclusiones
Se ha efectuado un completo estudio acerca de la efectiva coordinacin del esquema de protecciones con que cuenta cada instalacin de los sistemas mediando que opera la empresa Edelmag. Para tal efecto se procedi a simular digitalmente en el programa computacional de anlisis Power Factory, el esquema de protecciones que fuera informado por Edelmag. Tal cual lo determina la normativa vigente, se determin los tiempos mximos de despeje de falla para los sistemas medianos. Efectuada la modelacin se procedi a efectuar la verificacin solicitada por la normativa vigente, para lo cual se simul diversas configuraciones de demanda y topologa de transmisin y generacin, estudiando especialmente aquellos escenarios que presentan mayor probabilidad de presentarse en la operacin de los sistemas elctricos. De los anlisis efectuados y de los resultados obtenidos se concluye que el sistema de protecciones ya implementado ms los ajustes que se han definido en los estudios que ha encargado recientemente Edelmag, se ajusta a los requerimientos que impone la Norma tcnica, por cuanto cumple adecuadamente con la debida coordinacin de protecciones. En todas las instalaciones se aprecia que el esquema de protecciones acta en forma rpida para fallas que ocurren en la propia instalacin, adems de prestar respaldo remoto para fallas que ocurren en otras instalaciones del sistema. En el caso de los alimentadores para la operacin de los reconectadores. Aunque no se visualiza modificar el esquema de protecciones en el periodo 2011-2014, se plantea revisar el esquema una vez que los estudios que ha encargado la empresa Edelmag se encuentren finalizados.

Informe Tcnico

Pgina 41

9 Referencias

9 Referencias
[1] Norma Tcnica de Seguridad y Calidad de Servicio para Sistemas Medianos, Comisin Nacional de Energa Enero 2006 [2] Procedimientos, Edelmag-Digsilent, Abril 2007 [3] Estudio de verificacin de Coordinacin de Protecciones, Digsilent Ltda, ao 2001 [4] Informe final Proteccin Punta Arenas II, de Digsilent, 2011 (informe preliminar) [5] Informe final Proteccin Natales (V I), de Digsilent, 2011 [6] Informe final Proteccin Porvenir(V I), de Digsilent, 2011 [7] Ajuste Protecciones Puerto Williams, de Edelmag Agosto 2010

Informe Tcnico

Pgina 42

1 Anexo 1 Grficos Determinacin Tiempo Mximo de Despeje

ANEXOS

1 Anexo 1 Grficos Determinacin Tiempo Mximo de Despeje

Informe Tcnico

Pgina 43

1 Anexo 1 Grficos Determinacin Tiempo Mximo de Despeje

Para Sistema de Punta Arenas


200,00
DIgSILENT

2.713 s 178.626 deg

SISTEMA INESTABLE

100,00

0,00

-100,00

2.713 s -179.552 deg

-200,00 0,0000

3,9865

7,9730

11,960

15,946

[s]

19,933

Unidad N 1 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 4 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 5 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 7 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 9 T.P.: Rotor angle with reference to reference machine angle in deg

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 2014: Tiempo Mximo de Despeje de Falla 200,00 Fall Trifsica: Tdespeje 2.0 seg

Subplot/Diagramm

Date: 12/9/2011 Annex: /22


DIgSILENT

SISTEMA INESTABLE

100,00

0,00

-100,00

2.613 s -138.050 deg

-200,00 0,0000

3,9865

7,9730

11,960

15,946

[s]

19,933

Unidad N 1 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 4 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 5 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 7 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 9 T.P.: Rotor angle with reference to reference machine angle in deg

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 2014: Tiempo Mximo de Despeje de Falla Fall Trifsica: Tdespeje 1.5 seg

Subplot/Diagramm

Date: 12/9/2011 Annex: /22

Informe Tcnico

Pgina 44

1 Anexo 1 Grficos Determinacin Tiempo Mximo de Despeje

200,00

SISTEMA ESTABLE

100,00

0,00

-100,00 2.313 s -90.647 deg

-200,00 0,0000

3,9865

7,9730

11,960

15,946

[s]

19,933

Unidad N 1 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 4 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 5 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 7 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 9 T.P.: Rotor angle with reference to reference machine angle in deg

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 2014: Tiempo Mximo de Despeje de Falla 200,00 Fall Trifsica: Tdespeje 1.25 seg

Subplot/Diagramm

Date: 12/9/2011 Annex: /22


DIgSILENT

SISTEMA ESTABLE

100,00

0,00

-100,00

2.433 s -106.782 deg

-200,00 0,0000

3,9865

7,9730

11,960

15,946

[s]

19,933

Unidad N 1 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 4 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 5 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 7 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 9 T.P.: Rotor angle with reference to reference machine angle in deg

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 2014: Tiempo Mximo de Despeje de Falla Fall Trifsica: Tdespeje 1.35 seg

Subplot/Diagramm

Date: 12/9/2011 Annex: /22

Informe Tcnico

Pgina 45

DIgSILENT

1 Anexo 1 Grficos Determinacin Tiempo Mximo de Despeje

200,00

SISTEMA ESTABLE

100,00

0,00

-100,00

2.443 s -114.784 deg

-200,00 0,0000

3,9865

7,9730

11,960

15,946

[s]

19,933

Unidad N 1 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 4 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 5 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 7 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 9 T.P.: Rotor angle with reference to reference machine angle in deg

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 2014: Tiempo Mximo de Despeje de Falla 200,00 Fall Trifsica: Tdespeje 1.4 seg

Subplot/Diagramm

Date: 12/9/2011 Annex: /22


DIgSILENT

SISTEMA INESTABLE

100,00

0,00

-100,00

2.523 s -126.041 deg

-200,00 0,0000

3,9865

7,9730

11,960

15,946

[s]

19,933

Unidad N 1 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 4 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 5 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 7 T.P.: Rotor angle with reference to reference machine angle in deg Unidad N 9 T.P.: Rotor angle with reference to reference machine angle in deg

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 2014: Tiempo Mximo de Despeje de Falla Fall Trifsica: Tdespeje 1.45 seg

Subplot/Diagramm

Date: 12/9/2011 Annex: /22

Informe Tcnico

Pgina 46

DIgSILENT

1 Anexo 1 Grficos Determinacin Tiempo Mximo de Despeje

Para Otros Sistema Medianos


200,00
SISTEMA ESTABLE
DIgSILENT

100,00

1.605 s 69.503 deg

0,00

-100,00

-200,00 -0,000

0,999 1,999 Generador N 11: Rotor angle with reference to reference machine angle in deg Generador N 3: Rotor angle with reference to reference machine angle in deg Generador N 8: Rotor angle with reference to reference machine angle in deg Generador N 9: Rotor angle with reference to reference machine angle in deg

2,998

3,998

[s]

4,997

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales: Tiempo mximo de despeje de falla
200,00

Angulo

Date: 12/9/2011 Annex: /6


DIgSILENT

Falla Trifsica: Tiempor de despeje 0.6 seg

SISTEMA ESTABLE

1.809 s 70.534 deg

100,00

0,00

-100,00

-200,00 -0,000

0,999 1,999 Generador N 11: Rotor angle with reference to reference machine angle in deg Generador N 3: Rotor angle with reference to reference machine angle in deg Generador N 8: Rotor angle with reference to reference machine angle in deg Generador N 9: Rotor angle with reference to reference machine angle in deg

2,998

3,998

[s]

4,997

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales: Tiempo mximo de despeje de falla Falla Trifsica: Tiempor de despeje 0.8 seg

Angulo

Date: 12/9/2011 Annex: /6

Informe Tcnico

Pgina 47

1 Anexo 1 Grficos Determinacin Tiempo Mximo de Despeje

200,00

SISTEMA INESTABLE

1.991 s 96.681 deg 100,00

0,00

-100,00

-200,00 -0,000

0,999 1,999 Generador N 11: Rotor angle with reference to reference machine angle in deg Generador N 3: Rotor angle with reference to reference machine angle in deg Generador N 8: Rotor angle with reference to reference machine angle in deg Generador N 9: Rotor angle with reference to reference machine angle in deg

2,998

3,998

[s]

4,997

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales: Tiempo mximo de despeje de falla
200,00

Angulo

Date: 12/9/2011 Annex: /6


DIgSILENT

Falla Trifsica: Tiempor de despeje 0.9 seg

2.288 s 175.474 deg


SISTEMA INESTABLE

100,00

0,00

-100,00

-200,00 -0,000

0,999 1,999 Generador N 11: Rotor angle with reference to reference machine angle in deg Generador N 3: Rotor angle with reference to reference machine angle in deg Generador N 8: Rotor angle with reference to reference machine angle in deg Generador N 9: Rotor angle with reference to reference machine angle in deg

2,998

3,998

[s]

4,997

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales: Tiempo mximo de despeje de falla Falla Trifsica: Tiempor de despeje 1.5 seg

Angulo

Date: 12/9/2011 Annex: /6

Informe Tcnico

Pgina 48

DIgSILENT

1 Anexo 1 Grficos Determinacin Tiempo Mximo de Despeje

200,00

SISTEMA INESTABLE

2.053 s 110.732 deg 100,00

0,00

-100,00

-200,00 -0,000

0,999 1,999 Generador N 11: Rotor angle with reference to reference machine angle in deg Generador N 3: Rotor angle with reference to reference machine angle in deg Generador N 8: Rotor angle with reference to reference machine angle in deg Generador N 9: Rotor angle with reference to reference machine angle in deg

2,998

3,998

[s]

4,997

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales: Tiempo mximo de despeje de falla
200,00 2.288 s 175.474 deg

Angulo

Date: 12/9/2011 Annex: /6


DIgSILENT

Falla Trifsica: Tiempor de despeje 1.0 seg

SISTEMA INESTABLE

100,00

0,00

-100,00

-200,00 -0,000

0,999 1,999 Generador N 11: Rotor angle with reference to reference machine angle in deg Generador N 3: Rotor angle with reference to reference machine angle in deg Generador N 8: Rotor angle with reference to reference machine angle in deg Generador N 9: Rotor angle with reference to reference machine angle in deg

2,998

3,998

[s]

4,997

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales: Tiempo mximo de despeje de falla Falla Trifsica: Tiempor de despeje 1.3 seg

Angulo

Date: 12/9/2011 Annex: /6

Informe Tcnico

Pgina 49

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

ANEXOS

2 Anexo 2 Curvas de Coordinacin Alimentadores

Informe Tcnico

Pgina 50

2 Anexo 2 Curvas de Coordinacin Alimentadores

Curvas de Operacin para Fallas entre Fases

Informe Tcnico

Pgina 51

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =218,521 pri.A

I =1831,070 pri.A

10

A01-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s [s]

A01-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s

[s]

1988.579 pri.A 0.300 s

1 968.236 pri.A 0.700 s 0.220 s

0,1

0,01 13,20 kV 100 13.2 kV P.A.\AL 1\A01-51

1000

[pri.A]

10000

0,1 13,20 kV 100 13.2 kV P.A.\AL 1\A01-51N

1000

[pri.A] Alimentador 1

10000 Date: 12/5/2011 Annex:


DIgSILENT

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =224,756 pri.A I =1276,338 pri.A 10 Falla Trifsica sin impedancia de falla

A02-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s A02-51 Ipset: 4,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s [s] [s]

986.684 pri.A 0.700 s

1801.995 pri.A 0.300 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 2\A02-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 2\A02-51N

1000 Alimentador 2

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Trifsica sin impedancia de falla

Date: 12/5/2011 Annex:

Informe Tcnico

Pgina 52

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =263,108 pri.A

I =1997,986 pri.A

10 A03-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s

[s]

A03-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s

[s]

837.751 pri.A 0.700 s 1 1

0.620 s 2621.841 pri.A 0.300 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 3\A03-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 3\A03-51N

1000 Alimentador 3

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =186,807 pri.A I =3068,171 pri.A A04-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,09 Tripping Time: 0,279 s 10 Falla Trifsica sin impedancia de falla

Date: 12/5/2011 Annex:


DIgSILENT

A04-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s

[s]

[s]

740.999 pri.A 0.690 s

3305.817 pri.A 0.140 s

0,1 0.070 s

0,1

A04-51 Ipset: 12,00 sec.A Tset: 0,05 s Tripping Time: 0,070 s

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 4\A04-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 4\A04-51N

1000 Alimentador 4

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Trifsica sin impedancia de falla

Date: 12/5/2011 Annex:

Informe Tcnico

Pgina 53

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =198,779 pri.A

I =3598,988 pri.A

10

A05-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s

[s] A05-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,01 Tripping Time: 0,050 s

[s]

921.655 pri.A 0.690 s

3443.853 pri.A 0.120 s

0,1

0,1

0.050 s

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 5\A05-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 5\A05-51N

1000 Alimentador 5

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =115,702 pri.A I =3068,171 pri.A A06-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,12 Tripping Time: 0,353 s 10 Falla Trifsica sin impedancia de falla

Date: 12/5/2011 Annex:


DIgSILENT

A06-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s

[s]

[s] 809.674 pri.A 0.690 s 1

4800.966 pri.A 0.290 s

0,1

0.220 s

0,1 13,20 kV 100

1000 13.2 kV T.P.\AL 6\A06-51

10000

[pri.A]

100000

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 6\A06-51N

1000 Alimentador 6

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Trifsica sin impedancia de falla

Date: 12/5/2011 Annex:

Informe Tcnico

Pgina 54

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =132,996 pri.A

I =3068,171 pri.A

10 A07-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s

A07-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,08 Tripping Time: 0,221 s

[s]

[s]

716.165 pri.A 0.720 s

5588.206 pri.A 0.170 s

0,1 0.070 s

0,1

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 7\A07-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 7\A07-51N

1000 Alimentador 7

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =248,467 pri.A I =1997,986 pri.A 10 Falla Trifsica sin impedancia de falla

Date: 12/5/2011 Annex:


DIgSILENT

A08-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s A08-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s

[s]

[s]

782.538 pri.A 0.700 s

1801.995 pri.A 0.300 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 08\A08-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 08\A08-51N

1000 Alimentador 8

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Trifsica sin impedancia de falla

Date: 12/5/2011 Annex:

Informe Tcnico

Pgina 55

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =243,290 pri.A

I =2193,308 pri.A

10

A09-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s [s] [s]

A09-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s

766.695 pri.A 0.700 s 1 1

1729.769 pri.A 0.300 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 9\A09-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 9\A09-51N

1000 Alimentador 9

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =128,437 pri.A I =1997,986 pri.A 10 Falla Trifsica sin impedancia de falla

Date: 12/5/2011 Annex:


DIgSILENT

A10-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s A10-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s

[s]

[s]

902.995 pri.A 0.700 s

1 535.431 pri.A 0.300 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 10\A10-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 10\A10-51N

1000 Alimentador 10

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Trifsica sin impedancia de falla

Date: 12/5/2011 Annex:

Informe Tcnico

Pgina 56

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =132,668 pri.A

I =3068,171 pri.A A11-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,08 Tripping Time: 0,221 s

10

A11-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s

[s]

[s]

977.078 pri.A 0.680 s

7751.722 pri.A 0.155 s 1

0,1

0.095 s

A11-51 Ipset: 12,00 sec.A Tset: 0,08 s Tripping Time: 0,095 s

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 11\A11-51

1000

[pri.A]

10000

0,1 13,20 kV 100 13.2 kV T.P.\AL 11\A11-51N

1000

[pri.A] Alimentador 11

10000 Date: 12/5/2011 Annex:

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Trifsica sin impedancia de falla

Informe Tcnico

Pgina 57

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =218,521 pri.A I =380,584 pri.A

10

A01-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s [s]

A01-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s

[s]

1988.579 pri.A 0.300 s

1 968.236 pri.A 0.700 s 0.220 s

0,1

0,01 13,20 kV 100 13.2 kV P.A.\AL 1\A01-51

1000

[pri.A]

10000

0,1 13,20 kV 100 13.2 kV P.A.\AL 1\A01-51N

1000

[pri.A] Alimentador 1

10000 Date: 12/8/2011 Annex:


DIgSILENT

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =224,756 pri.A I =585,140 pri.A 10 Falla Trifsica con impedancia de falla 20 Ohms

A02-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s A02-51 Ipset: 4,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s [s] [s]

986.684 pri.A 0.700 s

1801.995 pri.A 0.300 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 2\A02-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 2\A02-51N

1000 Alimentador 2

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Trifsica con impedancia de falla 20 Ohms

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 58

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =263,108 I =386,753 pri.A pri.A

10 A03-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s

[s]

A03-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s

[s]

837.751 pri.A 0.700 s 1 1

0.620 s 2621.841 pri.A 0.300 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 3\A03-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 3\A03-51N

1000 Alimentador 3

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =186,807 I pri.A =391,226 pri.A A04-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,09 Tripping Time: 2,498 s 10 Falla Trifsica con impedancia de falla 20 Ohms

Date: 12/8/2011 Annex:


DIgSILENT

A04-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s

[s] 2.498 s

[s]

740.999 pri.A 0.690 s

3305.817 pri.A 0.140 s

0,1

0,1

A04-51 Ipset: 12,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 4\A04-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 4\A04-51N

1000 Alimentador 4

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Trifsica con impedancia de falla 20 Ohms

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 59

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =198,779I pri.A =397,348 pri.A

10

A05-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s

[s] A05-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,01 Tripping Time: 0,248 s

[s]

921.655 pri.A 0.690 s

0.248 s

3443.853 pri.A 0.120 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 5\A05-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 5\A05-51N

1000 Alimentador 5

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =115,702 pri.A I =391,226 pri.A A06-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,12 Tripping Time: 3,155 s 10 Falla Trifsica con impedancia de falla 20 Ohms

Date: 12/8/2011 Annex:


DIgSILENT

A06-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s

[s]

[s]

3.155 s

809.674 pri.A 0.690 s 1

4800.966 pri.A 0.290 s

0,1

0,1 13,20 kV 100

1000 13.2 kV T.P.\AL 6\A06-51

10000

[pri.A]

100000

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 6\A06-51N

1000 Alimentador 6

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Trifsica con impedancia de falla 20 Ohms

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 60

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =132,996 pri.A I =391,226 pri.A

10 A07-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s

A07-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,08 Tripping Time: 1,972 s

[s]

[s]

1.972 s 716.165 pri.A 0.720 s

5588.206 pri.A 0.170 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 7\A07-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 7\A07-51N

1000 Alimentador 7

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =248,467 I =386,753 pri.A pri.A 10 Falla Trifsica con impedancia de falla 20 Ohms

Date: 12/8/2011 Annex:


DIgSILENT

A08-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s A08-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s

[s]

[s]

782.538 pri.A 0.700 s

1801.995 pri.A 0.300 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 08\A08-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 08\A08-51N

1000 Alimentador 8

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Trifsica con impedancia de falla 20 Ohms

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 61

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =243,290 I =393,077 pri.A pri.A

10

A09-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s [s] [s]

A09-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s

766.695 pri.A 0.700 s 1 1

1729.769 pri.A 0.300 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 9\A09-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 9\A09-51N

1000 Alimentador 9

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =128,437 pri.A I =386,753 pri.A 10 Falla Trifsica con impedancia de falla 20 Ohms

Date: 12/8/2011 Annex:


DIgSILENT

A10-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s A10-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s

[s]

[s]

902.995 pri.A 0.700 s

1 535.431 pri.A 0.300 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 10\A10-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 10\A10-51N

1000 Alimentador 10

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Trifsica con impedancia de falla 20 Ohms

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 62

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =132,668 pri.A I =391,226 pri.A A11-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,08 Tripping Time: 1,972 s

10

A11-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 9999,999 s

[s]

1.972 s [s]

977.078 pri.A 0.680 s

7751.722 pri.A 0.155 s 1

0,1

A11-51 Ipset: 12,00 sec.A Tset: 0,08 s Tripping Time: 9999,999 s

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 11\A11-51

1000

[pri.A]

10000

0,1 13,20 kV 100 13.2 kV T.P.\AL 11\A11-51N

1000

[pri.A] Alimentador 11

10000 Date: 12/8/2011 Annex:

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Trifsica con impedancia de falla 20 Ohms

Informe Tcnico

Pgina 63

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

I =347,626 pri.A 51 IEC 255-3 inverse Ipset: 4,00 sec.A Tpset: 0,10 Tripping Time: 0,470 s

10 51N Ipset: 1,00 sec.A Tset: 0,48 s Tripping Time: 9999,999 s

[s]

[s]

0.470 s 1

0,1

51 Ipset: 32,50 sec.A Tset: 0,06 s Tripping Time: 9999,999 s 0,01 13,20 kV 10 0,1 10000 13,20 kV 10

100 1000 13.2 kV\AL C1 (Interruptor principal)\51

[pri.A]

100 [pri.A] 13.2 kV\AL C1 (Interruptor principal)\51N

1000

Estudios Norma Tcnica Estudios EVCP SM Puerto Natales


10 I =1286,283 pri.A 51 IEC 255-3 inverse Ipset: 4,00 sec.A Tpset: 0,10 Tripping Time: 0,245 s [s]

Alimentador 1

Date: 12/3/2011 Annex:


DIgSILENT

Falla a Trifsica con impedancia de falla de 20 Ohms


10 51N Ipset: 1,00 sec.A Tset: 0,48 s Tripping Time: 9999,999 s

[s]

51 Ipset: 32,50 sec.A Tset: 0,06 s Tripping Time: 0,080 s

1 0.245 s

0,1 0.080 s

0,01 13,20 kV 10

100 1000 13.2 kV\AL C1 (Interruptor principal)\51

[pri.A]

0,1 10000 13,20 kV 10

100 [pri.A] 13.2 kV\AL C1 (Interruptor principal)\51N

1000

Estudios Norma Tcnica Estudios EVCP SM Puerto Natales Falla a Trifsica

Alimentador 1

Date: 12/3/2011 Annex:

Informe Tcnico

Pgina 64

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

100

I =339,394 pri.A 51 IEC 255-3 very inverse Ipset: 3,00 sec.A Tpset: 0,14 Tripping Time: 0,406 s

100

[s]

[s] 51N Ipset: 1,00 sec.A Tset: 0,45 s Tripping Time: 9999,999 s

10

10

0.406 s

0,1

0,1

51 Ipset: 32,50 sec.A Tset: 0,06 s Tripping Time: 9999,999 s 0,01 13,20 kV 10 0,01 10000 13,20 kV 10

100 13.2 kV\C 4\51

1000

[pri.A]

100 13.2 kV\C 4\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudios EVCP SM Puerto Natales


100 I =1222,417 pri.A 51 IEC 255-3 very inverse Ipset: 3,00 sec.A Tpset: 0,14 Tripping Time: 0,099 s

Alimentador 2

Date: 12/3/2011 Annex:


DIgSILENT

Falla a Trifsica con impedancia de falla de 20 Ohms


100

[s]

[s] 51N Ipset: 1,00 sec.A Tset: 0,45 s Tripping Time: 9999,999 s

10

10

0,1

0.099 s 0.080 s

0,1

0,01 13,20 kV 10

100 13.2 kV\C 4\51

1000

[pri.A]

0,01 10000 13,20 kV 10

100 13.2 kV\C 4\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudios EVCP SM Puerto Natales Falla a Trifsica

Alimentador 2

Date: 12/3/2011 Annex:

Informe Tcnico

Pgina 65

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

I =347,626 pri.A 51 IEC 255-3 inverse Ipset: 4,00 sec.A Tpset: 0,10 Tripping Time: 0,470 s

10 51N Ipset: 1,00 sec.A Tset: 0,45 s Tripping Time: 9999,999 s [s]

[s]

1 51 Ipset: 32,50 sec.A 0.470Tset: s 0,06 s Tripping Time: 9999,999 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV II\AL 03\51

1000

[pri.A]

0,01 10000 13,20 kV 10

100 13.2 kV II\AL 03\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudios EVCP SM Puerto Natales


10 51 IEC 255-3 inverse Ipset: 4,00 sec.A Tpset: 0,10 Tripping Time: 0,245 s I =1286,283 pri.A

Alimentador 3

Date: 12/3/2011 Annex:


DIgSILENT

Falla a Trifsica con impedancia de falla de 20 Ohms


10 51N Ipset: 1,00 sec.A Tset: 0,45 s Tripping Time: 9999,999 s [s]

[s]

1 51 Ipset: 32,50 sec.A Tset: 0,06 s Tripping Time: 0,080 s

0,1 0.080 s

0,1

0,01 13,20 kV 10

100 13.2 kV II\AL 03\51

1000

[pri.A]

0,01 10000 13,20 kV 10

100 13.2 kV II\AL 03\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudios EVCP SM Puerto Natales Falla a Trifsica

Alimentador 3

Date: 12/3/2011 Annex:

Informe Tcnico

Pgina 66

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

100

I =347,626 pri.A

100

[s]

51 IEC 255-3 very inverse Ipset: 3,00 sec.A Tpset: 0,14 Tripping Time: 0,394 s

[s] 51N Ipset: 1,00 sec.A Tset: 0,45 s Tripping Time: 9999,999 s

10

10

51 Ipset: 32,50 sec.A Tset: 0,06 s Tripping Time: 9999,999 s 0.394 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV II\AL01\51

1000

[pri.A]

0,01 10000 13,20 kV 10

100 13.2 kV II\AL01\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudios EVCP SM Puerto Natales


100 I =1286,283 pri.A

Alimentador 4

Date: 12/3/2011 Annex:


DIgSILENT

Falla Trifsica con impedancia de falla de 20 Ohms


100

[s]

51 IEC 255-3 very inverse Ipset: 3,00 sec.A Tpset: 0,14 Tripping Time: 0,099 s

[s] 51N Ipset: 1,00 sec.A Tset: 0,45 s Tripping Time: 9999,999 s

10

10

51 Ipset: 32,50 sec.A Tset: 0,06 s Tripping Time: 0,080 s

0,1

0.080 s

0,1

0,01 13,20 kV 10

100 13.2 kV II\AL01\51

1000

[pri.A]

0,01 10000 13,20 kV 10

100 13.2 kV II\AL01\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudios EVCP SM Puerto Natales Falla a Trifsica

Alimentador 4

Date: 12/3/2011 Annex:

Informe Tcnico

Pgina 67

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X = 21,374 pri.A

I =330,454 pri.A

10 A01_51N Ipset: 1,00 sec.A Tset: 0,50 s Tripping Time: 9999,999 s

A01_51 KYLE 112 (cesar) Ipset: 5,00 sec.A Tpset: 1,00 Tripping Time: 0,042 s

[s]

[s]

0,1

0,1

0.042 s

0,01 13,80 kV 10

100 13.8_A\AL01\A01_51

1000

[pri.A]

10000

0,01 13,80 kV 10

100 13.8_A\AL01\A01_51N

1000 Alimentador 1

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Porvenir 10 X = 21,374 pri.A I =830,663 pri.A 10 A01_51N Ipset: 1,00 sec.A Tset: 0,50 s Tripping Time: 9999,999 s Falla Trifsica con resistenciua de falla de 20 Ohms

Date: 12/3/2011 Annex:


DIgSILENT

A01_51 KYLE 112 (cesar) Ipset: 5,00 sec.A Tpset: 1,00 Tripping Time: 0,025 s

[s]

[s]

0,1

0,1

0.025 s

0,01 13,80 kV 10

100 13.8_A\AL01\A01_51

1000

[pri.A]

10000

0,01 13,80 kV 10

100 13.8_A\AL01\A01_51N

1000 Alimentador 1

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Porvenir Falla Trifsica con resistenciua de falla de 0 Ohms

Date: 12/3/2011 Annex:

Informe Tcnico

Pgina 68

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X = 21,095 pri.A

I =330,454 pri.A

10 A02_51N Ipset: 1,00 sec.A Tset: 0,50 s Tripping Time: 9999,999 s A02_51 KYLE 119 (cesar) Ipset: 7,00 sec.A Tpset: 1,00 Tripping Time: 0,073 s

[s]

[s]

0,1 0.073 s

0,1

0,01 13,80 kV 10

100 13.8_B\AL02\A02_51

1000

[pri.A]

10000

0,01 13,80 kV 10

100 13.8_B\AL02\A02_51N

1000 Alimentador 2

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Porvenir 10 X = 21,095 pri.A I =830,663 pri.A 10 A02_51N Ipset: 1,00 sec.A Tset: 0,50 s Tripping Time: 9999,999 s A02_51 KYLE 119 (cesar) Ipset: 7,00 sec.A Tpset: 1,00 Tripping Time: 0,051 s [s] [s] Falla Trifsica con resistenciua de falla de 20 Ohms

Date: 12/3/2011 Annex:


DIgSILENT

0,1

0,1

0.051 s

0,01 13,80 kV 10

100 13.8_B\AL02\A02_51

1000

[pri.A]

10000

0,01 13,80 kV 10

100 13.8_B\AL02\A02_51N

1000 Alimentador 2

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Porvenir Falla Trifsica con resistenciua de falla de 0 Ohms

Date: 12/3/2011 Annex:

Informe Tcnico

Pgina 69

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X = 81,001 pri.A

I =379,733 pri.A A03_51 KYLE 112 (cesar) Ipset: 5,00 sec.A Tpset: 1,00 Tripping Time: 0,038 s

10 A03_51N Ipset: 1,00 sec.A Tset: 0,50 s Tripping Time: 9999,999 s

[s]

[s]

0,1

0,1

0.038 s

0,01 13,80 kV 10

100 13.8_B\AL03\A03_51

1000

[pri.A]

10000

0,01 13,80 kV 10

100 13.8_B\AL03\A03_51N

1000 Alimentador 3

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Porvenir 10 X = 81,001 pri.A I =927,686 pri.A A03_51 KYLE 112 (cesar) Ipset: 5,00 sec.A Tpset: 1,00 Tripping Time: 0,024 s 10 A03_51N Ipset: 1,00 sec.A Tset: 0,50 s Tripping Time: 9999,999 s Falla Trifsica con resistenciua de falla de 20 Ohms

Date: 12/3/2011 Annex:


DIgSILENT

[s]

[s]

0,1

0,1

0.024 s

0,01 13,80 kV 10

100 13.8_B\AL03\A03_51

1000

[pri.A]

10000

0,01 13,80 kV 10

100 13.8_B\AL03\A03_51N

1000 Alimentador 3

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Porvenir Falla Trifsica con resistenciua de falla de 0 Ohms

Date: 12/3/2011 Annex:

Informe Tcnico

Pgina 70

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X = 35,822 pri.A

I =330,454 pri.A

10

A04_51 KYLE 112 (cesar) Ipset: 5,00 sec.A Tpset: 1,00 Tripping Time: 0,042 s [s] [s]

A03_51N Ipset: 1,00 sec.A Tset: 0,50 s Tripping Time: 9999,999 s

0,1

0,1

0.042 s

0,01 13,80 kV 10

100 13.8_B\AL04\A04_51

1000

[pri.A]

10000

0,01 13,80 kV 10

100 13.8_B\AL03\A03_51N

1000 Alimentador 4

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Porvenir 10 X = 35,822 pri.A I =830,663 pri.A 10 Falla Trifsica con resistenciua de falla de 20 Ohms

Date: 12/3/2011 Annex:


DIgSILENT

A04_51 KYLE 112 (cesar) Ipset: 5,00 sec.A Tpset: 1,00 Tripping Time: 0,025 s [s] [s]

A03_51N Ipset: 1,00 sec.A Tset: 0,50 s Tripping Time: 9999,999 s

0,1

0,1

0.025 s

0,01 13,80 kV 10

100 13.8_B\AL04\A04_51

1000

[pri.A]

10000

0,01 13,80 kV 10

100 13.8_B\AL03\A03_51N

1000 Alimentador 4

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Porvenir Falla Trifsica con resistenciua de falla de 0 Ohms

Date: 12/3/2011 Annex:

Informe Tcnico

Pgina 71

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X = 6,328 pri.A

I =215,563 pri.A

100

51 KYLE 104 Ipset: 0,02 sec.A Tpset: 1,00 Tripping Time: 0,011 s [s]

[s] 51N KYLE 104 Ipset: 0,01 sec.A Tpset: 1,00 Tripping Time: 9999,999 s 10

0,1

0,1

0.011 s 0,01 13,20 kV 1 10 13.2 kV II\AL 03\51 100 [pri.A] 1000 0,01 13,20 kV 10 13.2 kV II\AL 03\51N 100 [pri.A] 1000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams


10 X = 6,328 pri.A I =288,437 pri.A

Alimentador 1

Date: 12/4/2011 Annex:


DIgSILENT

Falla Trifsica con resistencia de falla de 20 Ohms


100

51 KYLE 104 Ipset: 0,02 sec.A Tpset: 1,00 Tripping Time: 0,011 s [s]

[s] 51N KYLE 104 Ipset: 0,01 sec.A Tpset: 1,00 Tripping Time: 9999,999 s 10

0,1

0,1

0.011 s 0,01 13,20 kV 1 10 13.2 kV II\AL 03\51 100 [pri.A] 1000 0,01 13,20 kV 10 13.2 kV II\AL 03\51N 100 [pri.A] 1000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams

Alimentador 1 Falla Trifsica sin resistencia de falla

Date: 12/4/2011 Annex:

Informe Tcnico

Pgina 72

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X = 12,871 pri.A

I =215,563 pri.A

10 51N KYLE 104 Ipset: 0,01 sec.A Tpset: 1,00 Tripping Time: 9999,999 s [s]

51 KYLE 104 Ipset: 0,02 sec.A Tpset: 1,00 Tripping Time: 0,011 s [s]

0,1

0,1

0.011 s 0,01 13,20 kV 10 100 [pri.A] 13.2 kV\AL C1 (Interruptor principal)\51 1000 0,01 13,20 kV 10 100 [pri.A] 13.2 kV\AL C1 (Interruptor principal)\51N 1000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams


10 X = 12,871 pri.A I =288,437 pri.A

Alimentador 2

Date: 12/4/2011 Annex:


DIgSILENT

Falla Trifsica con resistencia de falla de 20 Ohms


10 51N KYLE 104 Ipset: 0,01 sec.A Tpset: 1,00 Tripping Time: 9999,999 s [s]

51 KYLE 104 Ipset: 0,02 sec.A Tpset: 1,00 Tripping Time: 0,011 s [s]

0,1

0,1

0.011 s 0,01 13,20 kV 10 100 [pri.A] 13.2 kV\AL C1 (Interruptor principal)\51 1000 0,01 13,20 kV 10 100 [pri.A] 13.2 kV\AL C1 (Interruptor principal)\51N 1000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams

Alimentador 2 Falla Trifsica sin resistencia de falla

Date: 12/4/2011 Annex:

Informe Tcnico

Pgina 73

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

100

X = 17,680 pri.A

I =215,563 pri.A

100

[s]

[s] 51N KYLE 104 Ipset: 0,01 sec.A Tpset: 1,00 Tripping Time: 9999,999 s

10

51 KYLE 104 Ipset: 0,02 sec.A Tpset: 1,00 Tripping Time: 0,011 s

10

0,1

0,1

0.011 s 0,01 13,20 kV 10 13.2 kV II\AL01\51 100 [pri.A] 1000 0,01 13,20 kV 10 13.2 kV II\AL01\51N 100 [pri.A] 1000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams


100 X = 17,680 pri.A I =288,437 pri.A

Alimentador 3

Date: 12/4/2011 Annex:


DIgSILENT

Falla Trifsica con resistencia de falla de 20 Ohms


100

[s]

[s] 51N KYLE 104 Ipset: 0,01 sec.A Tpset: 1,00 Tripping Time: 9999,999 s

10

51 KYLE 104 Ipset: 0,02 sec.A Tpset: 1,00 Tripping Time: 0,011 s

10

0,1

0,1

0.011 s 0,01 13,20 kV 10 13.2 kV II\AL01\51 100 [pri.A] 1000 0,01 13,20 kV 10 13.2 kV II\AL01\51N 100 [pri.A] 1000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams

Alimentador 3 Falla Trifsica sin resistencia de falla

Date: 12/4/2011 Annex:

Informe Tcnico

Pgina 74

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

Curvas de Operacin para Fallas Residuales

Informe Tcnico

Pgina 75

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =218,521 pri.A

I =2085,851 pri.A

10

3*I0 =2085,851 pri.A

A01-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s [s]

A01-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s

[s]

1988.579 pri.A 0.300 s

1 968.236 pri.A 0.700 s 0.220 s

0.620 s

0,1

0,01 13,20 kV 100 13.2 kV P.A.\AL 1\A01-51

1000

[pri.A]

10000

0,1 13,20 kV 100 13.2 kV P.A.\AL 1\A01-51N

1000

[pri.A] Alimentador 1

10000 Date: 12/4/2011 Annex:

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =224,756 pri.A I =1388,591 pri.A 10 Falla Monofsica sin impedancia de falla

3*I0 =1388,591 pri.A A02-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s

A02-51 Ipset: 4,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s [s] [s]

986.684 pri.A 0.700 s

0.620 s

1801.995 pri.A 0.300 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 2\A02-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 2\A02-51N

1000 Alimentador 2

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Monofsica sin impedancia de falla

Date: 12/4/2011 Annex:

Informe Tcnico

Pgina 76

DIgSILENT

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =263,108 pri.A

I =2309,670 pri.A

10 A03-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s

[s]

A03-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s

[s]

837.751 pri.A 0.700 s 1 1

0.620 s 2621.841 pri.A 0.300 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 3\A03-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 3\A03-51N

1000 Alimentador 3

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =186,807 pri.A I =2685,545 pri.A A04-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,09 Tripping Time: 0,297 s 10 Falla Monofsica sin impedancia de falla

Date: 12/4/2011 Annex:

3*I0 =2685,545 pri.A A04-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s

[s]

[s]

740.999 pri.A 0.690 s

0.620 s

3305.817 pri.A 0.140 s

0,1 0.070 s

0,1

A04-51 Ipset: 12,00 sec.A Tset: 0,05 s Tripping Time: 0,070 s

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 4\A04-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 4\A04-51N

1000 Alimentador 4

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Monofsica sin impedancia de falla

Date: 12/4/2011 Annex:

Informe Tcnico

Pgina 77

DIgSILENT

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =198,779 pri.A

I =3070,839 pri.A

10

3*I0 =3070,839 pri.A

A05-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s

[s] A05-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,01 Tripping Time: 0,050 s

[s]

921.655 pri.A 0.690 s

0.620 s

3443.853 pri.A 0.120 s

0,1

0,1

0.050 s

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 5\A05-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 5\A05-51N

1000 Alimentador 5

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =115,702 pri.A I =2685,545 pri.A A06-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,12 Tripping Time: 0,375 s 10 A06-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s Falla Monofsica sin impedancia de falla

Date: 12/4/2011 Annex:

3*I0 =2685,545 pri.A

[s]

[s] 809.674 pri.A 0.690 s 1

0.620 s

4800.966 pri.A 0.290 s

0,1

0.220 s

0,1 13,20 kV 100

1000 13.2 kV T.P.\AL 6\A06-51

10000

[pri.A]

100000

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 6\A06-51N

1000 Alimentador 6

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Monofsica sin impedancia de falla

Date: 12/4/2011 Annex:

Informe Tcnico

Pgina 78

DIgSILENT

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =132,996 pri.A

I =2685,545 pri.A

10 A07-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s

3*I0 =2685,545 pri.A

A07-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,08 Tripping Time: 0,234 s

[s]

[s]

716.165 pri.A 0.720 s

0.620 s

5588.206 pri.A 0.170 s

0,1 0.070 s

0,1

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 7\A07-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 7\A07-51N

1000 Alimentador 7

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =248,467 pri.A I =2309,670 pri.A 10 Falla Monofsica sin impedancia de falla

Date: 12/4/2011 Annex:

3*I0 =2309,670 pri.A

A08-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s A08-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s

[s]

[s]

782.538 pri.A 0.700 s

1801.995 pri.A 0.300 s

0.620 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 08\A08-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 08\A08-51N

1000 Alimentador 8

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Monofsica sin impedancia de falla

Date: 12/4/2011 Annex:

Informe Tcnico

Pgina 79

DIgSILENT

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =243,290 pri.A

I =2580,345 pri.A

10

3*I0 =2580,345 pri.A

A09-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s [s] [s]

A09-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s

766.695 pri.A 0.700 s 1 1

0.620 s 1729.769 pri.A 0.300 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 9\A09-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 9\A09-51N

1000 Alimentador 9

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =128,437 pri.A I =2309,670 pri.A 10 Falla Monofsica sin impedancia de falla

Date: 12/4/2011 Annex:

3*I0 =2309,670 pri.A

A10-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s A10-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s

[s]

[s]

902.995 pri.A 0.700 s

1 535.431 pri.A 0.300 s

0.620 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 10\A10-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 10\A10-51N

1000 Alimentador 10

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Monofsica sin impedancia de falla

Date: 12/4/2011 Annex:

Informe Tcnico

Pgina 80

DIgSILENT

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =132,668 pri.A

I =2685,545 pri.A A11-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,08 Tripping Time: 0,234 s

10

3*I0 =2685,545 pri.A

A11-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s

[s]

[s]

977.078 pri.A 0.680 s

7751.722 pri.A 0.155 s 1

0.620 s

0,1

0.095 s

A11-51 Ipset: 12,00 sec.A Tset: 0,08 s Tripping Time: 0,095 s

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 11\A11-51

1000

[pri.A]

10000

0,1 13,20 kV 100 13.2 kV T.P.\AL 11\A11-51N

1000

[pri.A] Alimentador 11

10000 Date: 12/4/2011 Annex:

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Monofsica sin impedancia de falla

Informe Tcnico

Pgina 81

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =218,521 pri.A I =383,190 pri.A

10

3*I0 =383,190 pri.A

A01-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s [s]

A01-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s

[s]

1988.579 pri.A 0.300 s

1 968.236 pri.A 0.700 s 0.220 s

0.620 s

0,1

0,01 13,20 kV 100 13.2 kV P.A.\AL 1\A01-51

1000

[pri.A]

10000

0,1 13,20 kV 100 13.2 kV P.A.\AL 1\A01-51N

1000

[pri.A] Alimentador 1

10000 Date: 12/5/2011 Annex:


DIgSILENT

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =224,756 I =354,598 pri.A pri.A 10 Falla Monofsica con impedancia de falla 20 Ohms 3*I0 =354,598 pri.A

A02-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s A02-51 Ipset: 4,00 sec.A Tset: 0,20 s Tripping Time: 9999,999 s [s] [s]

986.684 pri.A 0.700 s

0.620 s

1801.995 pri.A 0.300 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 2\A02-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 2\A02-51N

1000 Alimentador 2

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Monofsica con impedancia de falla 20 Ohms

Date: 12/5/2011 Annex:

Informe Tcnico

Pgina 82

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =263,108 I =389,330 pri.A pri.A

10

3*I0 =389,330 pri.A A03-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s

[s]

A03-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s

[s]

837.751 pri.A 0.700 s 1 1

0.620 s 2621.841 pri.A 0.300 s

0.620 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 3\A03-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 3\A03-51N

1000 Alimentador 3

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =186,807 I pri.A =390,692 pri.A A04-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,09 Tripping Time: 2,511 s 10 Falla Monofsica con impedancia de falla 20 Ohms 3*I0 =390,692 pri.A

Date: 12/5/2011 Annex:


DIgSILENT

A04-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s

[s] 2.511 s

[s]

740.999 pri.A 0.690 s

0.620 s

3305.817 pri.A 0.140 s

0,1

0,1

A04-51 Ipset: 12,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 4\A04-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 4\A04-51N

1000 Alimentador 4

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Monofsica con impedancia de falla 20 Ohms

Date: 12/5/2011 Annex:

Informe Tcnico

Pgina 83

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =198,779I pri.A =396,901 pri.A

10

3*I0 =396,901 pri.A

A05-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s

[s] A05-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,01 Tripping Time: 0,249 s

[s]

921.655 pri.A 0.690 s

0.620 s

0.249 s

3443.853 pri.A 0.120 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 5\A05-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 5\A05-51N

1000 Alimentador 5

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =115,702 pri.A I =390,692 pri.A A06-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,12 Tripping Time: 3,172 s 10 Falla Monofsica con impedancia de falla 20 Ohms 3*I0 =390,692 pri.A A06-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s

Date: 12/5/2011 Annex:


DIgSILENT

[s]

[s]

3.172 s

809.674 pri.A 0.690 s 1

0.620 s

4800.966 pri.A 0.290 s

0,1

0,1 13,20 kV 100

1000 13.2 kV T.P.\AL 6\A06-51

10000

[pri.A]

100000

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 6\A06-51N

1000 Alimentador 6

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Monofsica con impedancia de falla 20 Ohms

Date: 12/5/2011 Annex:

Informe Tcnico

Pgina 84

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =132,996 pri.A I =390,692 pri.A

10

3*I0 =390,692 pri.A A07-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s

A07-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,08 Tripping Time: 1,982 s

[s]

[s]

1.982 s 716.165 pri.A 0.720 s

0.620 s

5588.206 pri.A 0.170 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 7\A07-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 7\A07-51N

1000 Alimentador 7

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =248,467 I =389,330 pri.A pri.A 10 Falla Monofsica con impedancia de falla 20 Ohms 3*I0 =389,330 pri.A

Date: 12/5/2011 Annex:


DIgSILENT

A08-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s A08-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s

[s]

[s]

782.538 pri.A 0.700 s

1801.995 pri.A 0.300 s

0.620 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 08\A08-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 08\A08-51N

1000 Alimentador 8

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Monofsica con impedancia de falla 20 Ohms

Date: 12/5/2011 Annex:

Informe Tcnico

Pgina 85

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =243,290 I =395,618 pri.A pri.A

10

3*I0 =395,618 pri.A

A09-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s [s] [s]

A09-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s

766.695 pri.A 0.700 s 1 1

0.620 s 1729.769 pri.A 0.300 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 9\A09-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 9\A09-51N

1000 Alimentador 9

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =128,437 pri.A I =389,330 pri.A 10 Falla Monofsica con impedancia de falla 20 Ohms 3*I0 =389,330 pri.A

Date: 12/5/2011 Annex:


DIgSILENT

A10-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s A10-51 Ipset: 3,00 sec.A Tset: 0,20 s Tripping Time: 0,220 s

[s]

[s]

902.995 pri.A 0.700 s

1 535.431 pri.A 0.300 s

0.620 s

0.220 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 10\A10-51

1000

[pri.A]

10000

0,01 13,20 kV 10

100 13.2 kV P.A.\AL 10\A10-51N

1000 Alimentador 10

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Monofsica con impedancia de falla 20 Ohms

Date: 12/5/2011 Annex:

Informe Tcnico

Pgina 86

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X =132,668 pri.A I =390,692 pri.A A11-51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,08 Tripping Time: 1,982 s

10

3*I0 =390,692 pri.A

A11-51N Ipset: 1,00 sec.A Tset: 0,60 s Tripping Time: 0,620 s

[s]

1.982 s [s]

977.078 pri.A 0.680 s

7751.722 pri.A 0.155 s 1

0.620 s

0,1

A11-51 Ipset: 12,00 sec.A Tset: 0,08 s Tripping Time: 9999,999 s

0,01 13,20 kV 10

100 13.2 kV T.P.\AL 11\A11-51

1000

[pri.A]

10000

0,1 13,20 kV 100 13.2 kV T.P.\AL 11\A11-51N

1000

[pri.A] Alimentador 11

10000 Date: 12/5/2011 Annex:

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Falla Monofsica con impedancia de falla 20 Ohms

Informe Tcnico

Pgina 87

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

I =357,164 pri.A 51 IEC 255-3 inverse Ipset: 4,00 sec.A Tpset: 0,10 Tripping Time: 0,461 s

10

3*I0 =357,164 pri.A 51N Ipset: 1,00 sec.A Tset: 0,48 s Tripping Time: 0,500 s

[s]

[s]

0.461 s 1

0.500 s 0,1

51 Ipset: 32,50 sec.A Tset: 0,06 s Tripping Time: 9999,999 s 0,01 13,20 kV 10 0,1 10000 13,20 kV 10

100 1000 13.2 kV\AL C1 (Interruptor principal)\51

[pri.A]

100 [pri.A] 13.2 kV\AL C1 (Interruptor principal)\51N

1000

Estudios Norma Tcnica Estudios EVCP SM Puerto Natales


10 I =1692,026 pri.A 51 IEC 255-3 inverse Ipset: 4,00 sec.A Tpset: 0,10 Tripping Time: 0,227 s [s]

Alimentador 1

Date: 12/3/2011 Annex:


DIgSILENT

Falla Monofsica con impedancia de falla de 20 Ohms


10 51N Ipset: 1,00 sec.A Tset: 0,48 s Tripping Time: 0,500 s

3*I0 =1692,026 pri.A

[s]

0.500 s 0,1 0.080 s

51 Ipset: 32,50 sec.A Tset: 0,06 s Tripping Time: 0,080 s 0,01 13,20 kV 10 0,1 10000 13,20 kV 10

100 1000 13.2 kV\AL C1 (Interruptor principal)\51

[pri.A]

100 1000 13.2 kV\AL C1 (Interruptor principal)\51N

[pri.A]

10000

Estudios Norma Tcnica Estudios EVCP SM Puerto Natales

Alimentador 1

Date: 12/3/2011 Annex:

Falla Monofsica con impedancia de falla de 0 Ohms

Informe Tcnico

Pgina 88

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

100

I =348,369 pri.A 51 IEC 255-3 very inverse Ipset: 3,00 sec.A Tpset: 0,14 Tripping Time: 0,393 s

100

3*I0 =348,369 pri.A

[s]

[s] 51N Ipset: 1,00 sec.A Tset: 0,45 s Tripping Time: 0,470 s

10

10

1 0.470 s

0.393 s

0,1

0,1

51 Ipset: 32,50 sec.A Tset: 0,06 s Tripping Time: 9999,999 s 0,01 13,20 kV 10 0,01 10000 13,20 kV 10

100 13.2 kV\C 4\51

1000

[pri.A]

100 13.2 kV\C 4\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudios EVCP SM Puerto Natales


100 I =1564,468 pri.A 51 IEC 255-3 very inverse Ipset: 3,00 sec.A Tpset: 0,14 Tripping Time: 0,099 s

Alimentador 2

Date: 12/3/2011 Annex:


DIgSILENT

Falla Monofsica con impedancia de falla de 20 Ohms


100

3*I0 =1564,468 pri.A

[s]

[s] 51N Ipset: 1,00 sec.A Tset: 0,45 s Tripping Time: 0,470 s

10

10

1 0.470 s

0,1

0.080 s

0,1

51 Ipset: 32,50 sec.A Tset: 0,06 s Tripping Time: 0,080 s 0,01 13,20 kV 10 0,01 10000 13,20 kV 10

100 13.2 kV\C 4\51

1000

[pri.A]

100 13.2 kV\C 4\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudios EVCP SM Puerto Natales

Alimentador 2

Date: 12/3/2011 Annex:

Falla Monofsica con impedancia de falla de 0 Ohms

Informe Tcnico

Pgina 89

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

I =357,164 pri.A 51 IEC 255-3 inverse Ipset: 4,00 sec.A Tpset: 0,10 Tripping Time: 0,461 s

10

3*I0 =357,164 pri.A 51N Ipset: 1,00 sec.A Tset: 0,45 s Tripping Time: 0,470 s

[s]

[s]

1 51 Ipset: 32,50 sec.A 0.461 s 0,06 s Tset: Tripping Time: 9999,999 s

0.470 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV II\AL 03\51

1000

[pri.A]

0,01 10000 13,20 kV 10

100 13.2 kV II\AL 03\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudios EVCP SM Puerto Natales


10 51 IEC 255-3 inverse Ipset: 4,00 sec.A Tpset: 0,10 Tripping Time: 0,227 s I =1692,026 pri.A

Alimentador 3

Date: 12/3/2011 Annex:


DIgSILENT

Falla Monofsica con impedancia de falla de 20 Ohms


10

3*I0 =1692,026 pri.A 51N Ipset: 1,00 sec.A Tset: 0,45 s Tripping Time: 0,470 s

[s]

[s]

1 51 Ipset: 32,50 sec.A Tset: 0,06 s Tripping Time: 0,080 s

0.470 s

0,1 0.080 s

0,1

0,01 13,20 kV 10

100 13.2 kV II\AL 03\51

1000

[pri.A]

0,01 10000 13,20 kV 10

100 13.2 kV II\AL 03\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudios EVCP SM Puerto Natales

Alimentador 3

Date: 12/3/2011 Annex:

Falla Monofsica con impedancia de falla de 0 Ohms

Informe Tcnico

Pgina 90

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

100

I =357,164 pri.A

100

3*I0 =357,164 pri.A

[s]

51 IEC 255-3 very inverse Ipset: 3,00 sec.A Tpset: 0,14 Tripping Time: 0,382 s

[s] 51N Ipset: 1,00 sec.A Tset: 0,45 s Tripping Time: 0,470 s

10

10

51 Ipset: 32,50 sec.A Tset: 0,06 s Tripping Time: 9999,999 s

1 0.470 s

0.382 s

0,1

0,1

0,01 13,20 kV 10

100 13.2 kV II\AL01\51

1000

[pri.A]

0,01 10000 13,20 kV 10

100 13.2 kV II\AL01\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudios EVCP SM Puerto Natales


100 I =1692,026 pri.A

Alimentador 4

Date: 12/3/2011 Annex:


DIgSILENT

Falla Monofsica con impedancia de falla de 20 Ohms


100

3*I0 =1692,026 pri.A

[s]

51 IEC 255-3 very inverse Ipset: 3,00 sec.A Tpset: 0,14 Tripping Time: 0,099 s

[s] 51N Ipset: 1,00 sec.A Tset: 0,45 s Tripping Time: 0,470 s

10

10

51 Ipset: 32,50 sec.A Tset: 0,06 s Tripping Time: 0,080 s

1 0.470 s

0,1

0.080 s

0,1

0,01 13,20 kV 10

100 13.2 kV II\AL01\51

1000

[pri.A]

0,01 10000 13,20 kV 10

100 13.2 kV II\AL01\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudios EVCP SM Puerto Natales

Alimentador 4

Date: 12/3/2011 Annex:

Falla Monofsica con impedancia de falla de 0 Ohms

Informe Tcnico

Pgina 91

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X = 21,374 pri.A

I =351,533 pri.A

10

3*I0 =351,533 pri.A A01_51N Ipset: 1,00 sec.A Tset: 0,50 s Tripping Time: 0,520 s

A01_51 KYLE 112 (cesar) Ipset: 5,00 sec.A Tpset: 1,00 Tripping Time: 0,040 s

[s]

[s]

0.520 s

0,1

0,1

0.040 s

0,01 13,80 kV 10

100 13.8_A\AL01\A01_51

1000

[pri.A]

10000

0,01 13,80 kV 10

100 13.8_A\AL01\A01_51N

1000 Alimentador 1

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Porvenir 10 X = 21,374 pri.A I =1147,403 pri.A 10 A01_51N Ipset: 1,00 sec.A Tset: 0,50 s Tripping Time: 0,520 s Falla Monofsica con resistenciua de falla de 20 Ohms

Date: 12/3/2011 Annex:

3*I0 =1147,403 pri.A

A01_51 KYLE 112 (cesar) Ipset: 5,00 sec.A Tpset: 1,00 Tripping Time: 0,023 s

[s]

[s]

0.520 s

0,1

0,1

0.023 s

0,01 13,80 kV 10

100 13.8_A\AL01\A01_51

1000

[pri.A]

10000

0,01 13,80 kV 10

100 13.8_A\AL01\A01_51N

1000 Alimentador 1

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Porvenir Falla Monofsica con resistenciua de falla de 0 Ohms

Date: 12/3/2011 Annex:

Informe Tcnico

Pgina 92

DIgSILENT

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X = 21,095 pri.A

I =351,533 pri.A

10

3*I0 =351,533 pri.A A02_51N Ipset: 1,00 sec.A Tset: 0,50 s Tripping Time: 0,520 s

A02_51 KYLE 119 (cesar) Ipset: 7,00 sec.A Tpset: 1,00 Tripping Time: 0,070 s [s] [s]

0.520 s

0,1 0.070 s

0,1

0,01 13,80 kV 10

100 13.8_B\AL02\A02_51

1000

[pri.A]

10000

0,01 13,80 kV 10

100 13.8_B\AL02\A02_51N

1000 Alimentador 2

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Porvenir 10 X = 21,095 pri.A I =1147,403 pri.A 10 A02_51N Ipset: 1,00 sec.A Tset: 0,50 s Tripping Time: 0,520 s A02_51 KYLE 119 (cesar) Ipset: 7,00 sec.A Tpset: 1,00 Tripping Time: 0,049 s [s] [s] Falla Monofsica con resistenciua de falla de 20 Ohms

Date: 12/3/2011 Annex:

3*I0 =1147,403 pri.A

0.520 s

0,1

0,1

0.049 s

0,01 13,80 kV 10

100 13.8_B\AL02\A02_51

1000

[pri.A]

10000

0,01 13,80 kV 10

100 13.8_B\AL02\A02_51N

1000 Alimentador 2

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Porvenir Falla Monofsica con resistenciua de falla de 0 Ohms

Date: 12/3/2011 Annex:

Informe Tcnico

Pgina 93

DIgSILENT

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X = 81,001 pri.A

I =410,299 pri.A A03_51 KYLE 112 (cesar) Ipset: 5,00 sec.A Tpset: 1,00 Tripping Time: 0,036 s

10

3*I0 =410,299 pri.A A03_51N Ipset: 1,00 sec.A Tset: 0,50 s Tripping Time: 0,520 s

[s]

[s]

0.520 s

0,1

0,1

0.036 s

0,01 13,80 kV 10

100 13.8_B\AL03\A03_51

1000

[pri.A]

10000

0,01 13,80 kV 10

100 13.8_B\AL03\A03_51N

1000 Alimentador 3

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Porvenir 10 X = 81,001 pri.A I =1357,271 pri.A A03_51 KYLE 112 (cesar) Ipset: 5,00 sec.A Tpset: 1,00 Tripping Time: 0,022 s 10 A03_51N Ipset: 1,00 sec.A Tset: 0,50 s Tripping Time: 0,520 s Falla Monofsica con resistenciua de falla de 20 Ohms

Date: 12/3/2011 Annex:

3*I0 =1357,271 pri.A

[s]

[s]

0.520 s

0,1

0,1

0.022 s

0,01 13,80 kV 10

100 13.8_B\AL03\A03_51

1000

[pri.A]

10000

0,01 13,80 kV 10

100 13.8_B\AL03\A03_51N

1000 Alimentador 3

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Porvenir Falla Monofsica con resistenciua de falla de 0 Ohms

Date: 12/3/2011 Annex:

Informe Tcnico

Pgina 94

DIgSILENT

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X = 35,822 pri.A

I =351,533 pri.A

10

3*I0 =351,533 pri.A

A04_51 KYLE 112 (cesar) Ipset: 5,00 sec.A Tpset: 1,00 Tripping Time: 0,040 s [s] [s]

A04_51N Ipset: 1,00 sec.A Tset: 0,50 s Tripping Time: 0,520 s

0.520 s

0,1

0,1

0.040 s

0,01 13,80 kV 10

100 13.8_B\AL04\A04_51

1000

[pri.A]

10000

0,01 13,80 kV 10

100 13.8_B\AL04\A04_51N

1000 Alimentador 4

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Porvenir 10 X = 35,822 pri.A I =1147,403 pri.A 10 A04_51N Ipset: 1,00 sec.A Tset: 0,50 s Tripping Time: 0,520 s Falla Monofsica con resistenciua de falla de 20 Ohms

Date: 12/3/2011 Annex:

3*I0 =1147,403 pri.A

A04_51 KYLE 112 (cesar) Ipset: 5,00 sec.A Tpset: 1,00 Tripping Time: 0,023 s [s] [s]

0.520 s

0,1

0,1

0.023 s

0,01 13,80 kV 10

100 13.8_B\AL04\A04_51

1000

[pri.A]

10000

0,01 13,80 kV 10

100 13.8_B\AL04\A04_51N

1000 Alimentador 4

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Porvenir Falla Monofsica con resistenciua de falla de 0 Ohms

Date: 12/3/2011 Annex:

Informe Tcnico

Pgina 95

DIgSILENT

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X = 6,328 pri.A

I =268,848 pri.A

100

3*I0 =268,848 pri.A

51 KYLE 104 Ipset: 0,02 sec.A Tpset: 1,00 Tripping Time: 0,011 s [s]

[s] 51N KYLE 104 Ipset: 0,01 sec.A Tpset: 1,00 Tripping Time: 0,011 s 10

0,1

0,1

0.011 s 0,01 13,20 kV 1 10 13.2 kV II\AL 03\51 100 [pri.A] 1000 0,01 13,20 kV 10 13.2 kV II\AL 03\51N 100

0.011 s [pri.A] 1000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams


10 X = 6,328 pri.A I =417,574 pri.A

Alimentador 1

Date: 12/4/2011 Annex:


DIgSILENT

Falla Trifsica con resistencia de falla de 20 Ohms


100

3*I0 =417,574 pri.A

51 KYLE 104 Ipset: 0,02 sec.A Tpset: 1,00 Tripping Time: 0,011 s [s]

[s] 51N KYLE 104 Ipset: 0,01 sec.A Tpset: 1,00 Tripping Time: 0,011 s 10

0,1

0,1

0.011 s 0,01 13,20 kV 1 10 13.2 kV II\AL 03\51 100 [pri.A] 1000 0,01 13,20 kV 10 13.2 kV II\AL 03\51N 100 [pri.A]

0.011 s 1000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams

Alimentador 1

Date: 12/4/2011 Annex:

Falla Monofsica sin resistencia de falla

Informe Tcnico

Pgina 96

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

X = 12,871 pri.A

I =268,848 pri.A

10 51N KYLE 104 Ipset: 0,01 sec.A Tpset: 1,00 Tripping Time: 0,011 s [s]

3*I0 =268,848 pri.A

51 KYLE 104 Ipset: 0,02 sec.A Tpset: 1,00 Tripping Time: 0,011 s [s]

0,1

0,1

0.011 s 0,01 13,20 kV 10 100 [pri.A] 13.2 kV\AL C1 (Interruptor principal)\51 1000 0,01 13,20 kV 10

0.011 s 100 [pri.A] 13.2 kV\AL C1 (Interruptor principal)\51N 1000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams


10 X = 12,871 pri.A I =417,574 pri.A

Alimentador 2

Date: 12/4/2011 Annex:


DIgSILENT

Falla Trifsica con resistencia de falla de 20 Ohms


10 51N KYLE 104 Ipset: 0,01 sec.A Tpset: 1,00 Tripping Time: 0,011 s [s]

3*I0 =417,574 pri.A

51 KYLE 104 Ipset: 0,02 sec.A Tpset: 1,00 Tripping Time: 0,011 s [s]

0,1

0,1

0.011 s 0,01 13,20 kV 10 100 [pri.A] 13.2 kV\AL C1 (Interruptor principal)\51 1000 0,01 13,20 kV 10 100 [pri.A] 13.2 kV\AL C1 (Interruptor principal)\51N

0.011 s 1000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams

Alimentador 2

Date: 12/4/2011 Annex:

Falla Monofsica sin resistencia de falla

Informe Tcnico

Pgina 97

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

100

X = 17,680 pri.A

I =268,848 pri.A

100

3*I0 =268,848 pri.A

[s]

[s] 51N KYLE 104 Ipset: 0,01 sec.A Tpset: 1,00 Tripping Time: 0,011 s

10

51 KYLE 104 Ipset: 0,02 sec.A Tpset: 1,00 Tripping Time: 0,011 s

10

0,1

0,1

0.011 s 0,01 13,20 kV 10 13.2 kV II\AL01\51 100 [pri.A] 1000 0,01 13,20 kV 10 13.2 kV II\AL01\51N 100

0.011 s [pri.A] 1000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams


100 X = 17,680 pri.A I =417,574 pri.A

Alimentador 3

Date: 12/4/2011 Annex:


DIgSILENT

Falla Monofsica con resistencia de falla de 20 Ohms


100

3*I0 =417,574 pri.A

[s]

[s] 51N KYLE 104 Ipset: 0,01 sec.A Tpset: 1,00 Tripping Time: 0,011 s

10

51 KYLE 104 Ipset: 0,02 sec.A Tpset: 1,00 Tripping Time: 0,011 s

10

0,1

0,1

0.011 s 0,01 13,20 kV 10 13.2 kV II\AL01\51 100 [pri.A] 1000 0,01 13,20 kV 10 13.2 kV II\AL01\51N 100 [pri.A]

0.011 s 1000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams

Alimentador 3

Date: 12/4/2011 Annex:

Falla Monofsica sin resistencia de falla

Informe Tcnico

Pgina 98

DIgSILENT

3 Anexo 3 Curvas de Coordinacin de Lnea de Transmisin

ANEXOS

3 Anexo 3 Curvas de Coordinacin de Lnea de Transmisin

Informe Tcnico

Pgina 99

3 Anexo 3 Curvas de Coordinacin de Lnea de Transmisin

100

3*I0 =1138,237 pri.A

[s] 51 Linea 66 TP IEC 255-3 inverse Ipset: 1,58 sec.A Tpset: 0,05 Tripping Time: 0,156 s 10

51 Linea 66 TP(1) Ipset: 5,25 sec.A Tset: 1,00 s Tripping Time: 1,020 s

1.020 s

0,1 0.060 s

0,01 66,00 kV 100 L 66 TP\Cub_5\51 Linea 66 TP

1000 L 66 TP\Cub_5\51 Linea 66 TP(1)

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 10 X =755,831 pri.A 67 Linea 66 TP IEC 255-3 inverse Ipset: 3,99 sec.A Tpset: 0,07 Tripping Time: 0,564 s Fallas Extremo Tres Puentes

50N/51N Ext Tres Puentes

Date: 12/9/2011 Annex:


DIgSILENT

[s]

0.520 s

67 Linea 66 TP(1) Ipset: 9,20 sec.A Tset: 0,04 s Tripping Time: 0,060 s

0,1

0.060 s

0,01 66,00 kV 100 L 66 TP\Cub_5\67 Linea 66 TP

1000 L 66 TP\Cub_5\67 Linea 66 TP(1)

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Fallas Monofsicas y Trifsicas

67 Ext Tres Puentes

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 100

DIgSILENT

3 Anexo 3 Curvas de Coordinacin de Lnea de Transmisin

10 67 Linea 66 - PA IEC 255-3 inverse Ipset: 0,84 sec.A Tpset: 0,07 Tripping Time: 0,279 s

X I =376,989 =370,829 pri.A

[s]

0,1

0.060 0.060s s

67 Linea 66 - PA Ipset: 1,45 sec.A Tset: 0,04 s Tripping Time: 0,060 s

0,01 66,00 kV 10 C.P.A. - 66 kV\Cub_3\67 Linea 66 - PA

100

1000

[pri.A] 67 Ext Punta Arenas

10000 Date: 12/9/2011 Annex:

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Fallas Extremo Tres Puentes

Informe Tcnico

Pgina 101

DIgSILENT

3 Anexo 3 Curvas de Coordinacin de Lnea de Transmisin

10

X =312,512 pri.A

X =833,115 pri.A 67 Linea 66 TP IEC 255-3 inverse Ipset: 3,99 sec.A Tpset: 0,07 Tripping Time: 0,466 s

[s] Falla en lnea

0.506 s

67 Linea 66 TP(1) Ipset: 9,20 sec.A Tset: 0,04 s Tripping Time: 0,060 s

0,1

0.060 s

0,01 66,00 kV 100 L 66 TP\Cub_5\67 Linea 66 TP

1000 L 66 TP\Cub_5\67 Linea 66 TP(1)

[pri.A]

10000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas Fallas Monofsicas y Trifsicas

67 Ext Tres Puentes

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 102

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

ANEXOS

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

Informe Tcnico

Pgina 103

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

Sistema Punta Arenas

Informe Tcnico

Pgina 104

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

100

X =993,754 pri.A

X =2519,386 pri.A

I =7622,699 pri.A

51 IEC 255-3 inverse Ipset: 3,00 sec.A Tpset: 0,54 Tripping Time: 2,007 s

[s]

10

5.059 s

2.007 s

1 11,50 kV 100 Celdas 11.5 kV\G01\51 1000 10000 [pri.A] G1 Falla Trifsica cercana I =3513,208 pri.A 100000 Date: 12/4/2011 Annex:
DIgSILENT

Estudios Norma Tcnica


Estudios EVCP SM Punta Arenas 100 X =516,216 pri.A X =1161,154 pri.A

[s]

51 ANSI/IEEE moderately inverse Ipset: 5,89 sec.A Tpset: 3,00 Tripping Time: 1,227 s

10 7.440 s

1.227 s 1

0,1 11,50 kV 100 Celdas 11.5 kV Rhona\G04\51

1000

10000

[pri.A] G4

100000 Date: 12/4/2011 Annex:

Estudios Norma Tcnica


Estudios EVCP SM Punta Arenas Falla Trifsica cercana

Informe Tcnico

Pgina 105

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

100

X =130,525 pri.A

X I =776,583 =776,583 X =832,706 pri.A pri.A pri.A

51-50 ANSI/IEEE inverse Ipset: 4,25 sec.A Tpset: 1,00 Tripping Time: 0,567 s [s]

10

0.567 s 0.512 s

0,1 13,20 kV 100 13.2 kV T.P.\G05\51-50

1000

[pri.A] G5 Falla Trifsica cercana

10000 Date: 12/4/2011 Annex:


DIgSILENT

Estudios Norma Tcnica


Estudios EVCP SM Punta Arenas 100 X =657,238 pri.A X =2992,068 pri.A 51 IEC 255-3 inverse Ipset: 5,40 sec.A Tpset: 0,80 Tripping Time: 4,731 s [s] X =7851,270 pri.A

10 6.637 s

3.053 s

51 Ipset: 40,00 sec.A Tset: 0,00 s Tripping Time: 9999,999 s

0,1

0,01 11,50 kV 100 Extensin Celdas CTP\G07\51

1000

10000

[pri.A] G7

100000 Date: 12/4/2011 Annex:

Estudios Norma Tcnica


Estudios EVCP SM Punta Arenas Falla Trifsica cercana

Informe Tcnico

Pgina 106

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

X =252,740 pri.A

X =1064,388 pri.A

X I =3326,764 =3326,764pri.A pri.A

51-50 IEC 255-3 inverse Ipset: 5,75 sec.A Tpset: 0,07 Tripping Time: 0,376 s

3.356 s [s]

51-50 Ipset: 10,60 sec.A Tset: 0,00 s Tripping Time: 0,020 s

0,1

0.020 s

0,01 11,50 kV 100 Extensin Celdas CTP\G08\51-50

1000

10000

[pri.A] G8

100000 Date: 12/4/2011 Annex:


DIgSILENT

Estudios Norma Tcnica


Estudios EVCP SM Punta Arenas 100 X =709,410 pri.A X =1378,831 pri.A I =4171,816 pri.A Falla Trifsica cercana

[s]

10

2.897 s

0.301 s

0,1 11,50 kV 100 Extensin Celdas CTP\G09\51

1000

10000

[pri.A] G9

100000 Date: 12/4/2011 Annex:

Estudios Norma Tcnica


Estudios EVCP SM Punta Arenas Falla Trifsica cercana

Informe Tcnico

Pgina 107

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

Sistema Puerto Natales

Informe Tcnico

Pgina 108

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

X =190,530 pri.A X =1435,734 pri.A 51 Ipset: 7,00 sec.A Tset: 0,82 s Tripping Time: 0,840 s
Corriente de flujo de carga

10

X =3603,910 pri.A

[s]

[s]

0.840 s 50 Ipset: 15,00 sec.A Tset: 0,00 s Tripping Time: 0,020 s

51N Ipset: 1,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

0,1

0,1 0.070 s

0.020 s

0,01 3,30 kV 10

100 52G3\G03\50

1000

10000 [pri.A] 52G3\G03\51

100000

0,01 3,30 kV 10

100 52G3\G03\51N

1000

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales


10 X = 83,404 pri.A I =977,354 pri.A 51 IEC 255-3 inverse Ipset: 9,00 sec.A Tpset: 0,08 Tripping Time: 0,555 s 10

G3 Falla Trifsica y Monofsica

Date: 12/8/2011 Annex:


DIgSILENT

X =2631,750 pri.A

[s]

[s] 51N Ipset: 1,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

51 Ipset: 20,00 sec.A Tset: 0,00 s Tripping Time: 0,020 s

0,1

0,1 0.070 s

0.020 s

0,01 3,30 kV 10

100 52G4\G04\51

1000

[pri.A]

10000

0,01 3,30 kV 10

100 52G4\G04\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales Falla Trifsica y Monofsica

G4

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 109

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

X = 89,342 pri.A

I =977,354 51 pri.A IEC 255-3 inverse Ipset: 9,00 sec.A Tpset: 0,08 Tripping Time: 0,555 s

10

X =2631,750 pri.A

[s]

[s]

51N Ipset: 1,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

51 Ipset: 20,00 sec.A Tset: 0,00 s Tripping Time: 0,020 s

0,1

0,1 0.070 s

0.020 s

0,01 3,30 kV 10

100 52G5\G05\51

1000

[pri.A]

10000

0,01 3,30 kV 10

100 52G5\G05\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales


10 X = 25,253 pri.A I =439,847 pri.A 51 IEC 255-3 inverse Ipset: 9,00 sec.A Tpset: 0,08 Tripping Time: 0,621 s [s] 51N Ipset: 1,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s 1 10

G5 Falla Trifsica y Monofsica


X =130,181 pri.A

Date: 12/8/2011 Annex:


DIgSILENT

[s]

51 Ipset: 17,50 sec.A Tset: 0,30 s Tripping Time: 0,320 s

51 IEC 255-3 inverse Ipset: 9,00 sec.A Tpset: 0,08 Tripping Time: 0,621 s 0.320 s

0,1 0.070 s

0,1 13,20 kV 10

100 13.2 kV\G 06\51

1000

[pri.A]

0,01 10000 13,20 kV 10

100 13.2 kV\G 06\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales Falla Trifsica y Monofsica

G6

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 110

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

X =190,530 pri.A I =1435,734 pri.A 51 Ipset: 7,00 sec.A Tset: 0,82 s Tripping Time: 0,840 s

10

X =3603,910 pri.A

[s]

[s] 51N Ipset: 1,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

0.840 s

50 Ipset: 15,00 sec.A Tset: 0,00 s Tripping Time: 0,020 s

0,1

0,1 0.070 s

0.020 s

0,01 3,30 kV 10

100 52G8\G08\50

1000

10000 [pri.A] 52G8\G08\51

100000

0,01 3,30 kV 10

100 52G8\G08\51N

1000

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales


10 X =1869,434 pri.A

G8 Falla Trifsica y Monofsica

Date: 12/8/2011 Annex:


DIgSILENT

X =12301,581 X 51-51N =17410,497 pri.A pri.A Ipset: 4,50 sec.A Tset: 0,82 s Tripping Time: 0,850 s

[s]

51-51N Ipset: 1,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

51-51N Ipset: 10,00 sec.A Tset: 0,00 s Tripping Time: 0,030 s

In

0,1 0.080 s 0.080 s

0.030 s

0.030 s

0,01 0,40 kV 1000 52G9\G09\51-51N

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales Falla Trifsica y Monofsica

G9

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 111

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

X =1962,211 pri.A

X =12301,581 X =17561,048 pri.A pri.A 51 IEC 255-3 inverse Ipset: 7,00 sec.A Tpset: 0,09 Tripping Time: 0,580 s

[s]

1 51 Ipset: 16,50 sec.A Tset: 0,00 s Tripping Time: 0,020 s

0,1

0.020 s

0.020 s

0,01 0,40 kV 1000 52G10\G10\51

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales


10 X =2464,369 pri.A 51-51N Ipset: 4,50 sec.A Tset: 0,82 s Tripping Time: 0,850 s

G10 Falla Trifsica y Monofsica


X =19009,250 X =26357,701 pri.A pri.A

Date: 12/8/2011 Annex:


DIgSILENT

[s]

51-51N Ipset: 1,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

51-51N Ipset: 10,00 sec.A Tset: 0,00 s Tripping Time: 0,030 s

In

0,1 0.080 s 0.080 s

0.030 s

0.030 s

0,01 0,40 kV 1000 52G11\G11\51-51N

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales Falla Trifsica y Monofsica

G11

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 112

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

X =190,530 pri.A X =916,486 pri.A 51 Ipset: 7,00 sec.A Tset: 0,82 s Tripping Time: 0,840 s
Corriente de flujo de carga

10

[s]

[s]

0.840 s 50 Ipset: 15,00 sec.A Tset: 0,00 s Tripping Time: 9999,999 s

51N Ipset: 1,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

0,1

0,1

0,01 3,30 kV 10

100 52G3\G03\50

1000

10000 [pri.A] 52G3\G03\51

100000

0,01 3,30 kV 10

100 52G3\G03\51N

1000

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales


10 X = 83,404 pri.A I =660,383 pri.A 51 IEC 255-3 inverse Ipset: 9,00 sec.A Tpset: 0,08 Tripping Time: 0,917 s 10

G3 Falla Trifsica y Monofsica lejana

Date: 12/8/2011 Annex:


DIgSILENT

[s]

[s] 51N Ipset: 1,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

0.917 s

51 Ipset: 20,00 sec.A Tset: 0,00 s Tripping Time: 9999,999 s

0,1

0,1

0,01 3,30 kV 10

100 52G4\G04\51

1000

[pri.A]

10000

0,01 3,30 kV 10

100 52G4\G04\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales Falla Trifsica y Monofsica lejana

G4

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 113

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

X = 89,342 pri.A

I =660,383 pri.A 51 IEC 255-3 inverse Ipset: 9,00 sec.A Tpset: 0,08 Tripping Time: 0,917 s

10

[s]

[s]

0.917 s

51N Ipset: 1,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

51 Ipset: 20,00 sec.A Tset: 0,00 s Tripping Time: 9999,999 s

0,1

0,1

0,01 3,30 kV 10

100 52G5\G05\51

1000

[pri.A]

10000

0,01 3,30 kV 10

100 52G5\G05\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales


10 X = 25,253 pri.A I =334,839 pri.A 51 IEC 255-3 inverse Ipset: 9,00 sec.A Tpset: 0,08 Tripping Time: 0,897 s [s] 51N Ipset: 1,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s 1 10

G5 Falla Trifsica y Monofsica lejana

Date: 12/8/2011 Annex:


DIgSILENT

[s]

0.897 s

51 Ipset: 17,50 sec.A Tset: 0,30 s Tripping Time: 9999,999 s

51 IEC 255-3 inverse Ipset: 9,00 sec.A Tpset: 0,08 Tripping Time: 0,897 s

0,1

0,1 13,20 kV 10

100 13.2 kV\G 06\51

1000

[pri.A]

0,01 10000 13,20 kV 10

100 13.2 kV\G 06\51N

1000

[pri.A]

10000

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales Falla Trifsica y Monofsica lejana

G6

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 114

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

X =190,530 pri.A I =916,486 pri.A 51 Ipset: 7,00 sec.A Tset: 0,82 s Tripping Time: 0,840 s

10

[s]

[s] 51N Ipset: 1,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

0.840 s

50 Ipset: 15,00 sec.A Tset: 0,00 s Tripping Time: 9999,999 s

0,1

0,1

0,01 3,30 kV 10

100 52G8\G08\50

1000

10000 [pri.A] 52G8\G08\51

100000

0,01 3,30 kV 10

100 52G8\G08\51N

1000

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales


10 X =1869,434 pri.A I =7818,649 pri.A

G8 Falla Trifsica y Monofsica lejana


51-51N Ipset: 4,50 sec.A Tset: 0,82 s Tripping Time: 0,850 s

Date: 12/8/2011 Annex:


DIgSILENT

[s]

51-51N Ipset: 1,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

0.850 s

51-51N Ipset: 10,00 sec.A Tset: 0,00 s Tripping Time: 9999,999 s

0,1

0,01 0,40 kV 1000 52G9\G09\51-51N

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales Falla Trifsica y Monofsica lejana

G9

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 115

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

X =2464,369 pri.A

I =12747,864 pri.A 51-51N Ipset: 4,50 sec.A Tset: 0,82 s Tripping Time: 0,850 s

[s]

51-51N Ipset: 1,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

51-51N Ipset: 10,00 sec.A Tset: 0,00 s Tripping Time: 0,030 s

0,1

0.030 s

0,01 0,40 kV 1000 52G11\G11\51-51N

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales


10 X =1962,211 pri.A I =7424,003 pri.A 51 IEC 255-3 inverse Ipset: 7,00 sec.A Tpset: 0,09 Tripping Time: 1,100 s

G11 Falla Trifsica y Monofsica lejana

Date: 12/8/2011 Annex:


DIgSILENT

[s]

1.100 s 1 51 Ipset: 16,50 sec.A Tset: 0,00 s Tripping Time: 9999,999 s

0,1

0,01 0,40 kV 1000 52G10\G10\51

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Natales Falla Trifsica y Monofsica lejana

G10

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 116

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

Sistema Porvenir

Informe Tcnico

Pgina 117

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

X =723,266 pri.A

X =5233,824 pri.A G01_51-2 Ipset: 5,00 sec.A Tset: 0,85 s Tripping Time: 0,870 s

10

X =15562,793 pri.A

[s]

[s]

G01_51N Ipset: 20,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s 1 G01_51 Ipset: 20,00 sec.A Tset: 0,05 s Tripping Time: 0,070 s

0.870 s

36380.387 pri.A 0.170 s 39005.104 pri.A 0.170 s

0,1 0.070 s

0,1 0.070 s

0,01 0,40 kV 100

1000 52G1\G01\G01_51

10000 [pri.A] 52G1\G01\G01_51-2

100000

0,01 0,40 kV 1000 52G1\G01\G01_51N

10000

[pri.A] G1

100000 Date: 12/8/2011 Annex:

Estudios Norma Tcnica


Estudios EVCP SM Porvenir 100 X =802,045 pri.A X =9161,286 pri.A 100 Falla Trifsicas y Monofsicas

X =21129,853 pri.A

G04_51N IEC 255-3 inverse Ipset: 1,65 sec.A Tpset: 0,35 Tripping Time: 9999,999 s [s] [s]

G04_51 IEC 255-3 inverse Ipset: 5,00 sec.A Tpset: 0,15 Tripping Time: 0,680 s 10 10

G04_51-2 Ipset: 5,00 sec.A Tset: 0,85 s Tripping Time: 0,870 s 13418.748 pri.A 0.970 s 1

0.870 s 0.680 s

1 0.794 s

0,1 0,40 kV 100

1000 52G4\G04\G04_51

10000 [pri.A] 52G4\G04\G04_51-2

100000

0,1 0,40 kV 100

1000 52G4\G04\G04_51N

10000 G4

[pri.A]

100000

Estudios Norma Tcnica


Estudios EVCP SM Porvenir Falla Trifsicas y Monofsicas

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 118

DIgSILENT

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

100

X =161,188 pri.A

X =1044,636 pri.A X =1487,769 pri.A

[s]

G05_51 IEC 255-3 inverse Ipset: 2,50 sec.A Tpset: 0,16 Tripping Time: 0,772 s

In

10

2496.575 pri.A 0.970 s

0.870 s 0.772 s

0.870 s

0.617 s

G05_51-2 Ipset: 2,50 sec.A Tset: 0,85 s Tripping Time: 0,870 s

0,1 3,30 kV 100 52G5\G05\G05_51

1000 52G5\G05\G05_51-2

[pri.A]

10000

Estudios Norma Tcnica


Estudios EVCP SM Porvenir 100 X =1574,117 pri.A X =12301,581 pri.A 100 Falla Trifsicas y Monofsicas

G5

Date: 12/8/2011 Annex:

X =26247,791 pri.A

G06_51N IEC 255-3 inverse Ipset: 1,50 sec.A Tpset: 0,34 Tripping Time: 9999,999 s [s] G06_51 IEC 255-3 inverse Ipset: 5,00 sec.A Tpset: 0,16 Tripping Time: 0,692 s [s]

10

10

23374.478 pri.A 0.970 s

0.870 s 0.692 s

1 0.771 s

G06_51-2 Ipset: 5,00 sec.A Tset: 0,85 s Tripping Time: 0,870 s

0,1 0,40 kV 100

1000 52G6\G06\G06_51

10000 [pri.A] 52G6\G06\G06_51-2

100000

0,1 0,40 kV 100

1000 52G6\G06\G06_51N

10000 G6

[pri.A]

100000

Estudios Norma Tcnica


Estudios EVCP SM Porvenir Falla Trifsicas y Monofsicas

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 119

DIgSILENT

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

100

X =1574,117 pri.A

X =5342,965 pri.A

100 G07_51 IEC 255-3 inverse Ipset: 5,00 sec.A Tpset: 0,16 Tripping Time: 1,464 s

X =26247,791 pri.A

[s]

[s]

10

10

24445.576 pri.A 0.970 s

G07_51N Ipset: 16,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

1.464 s 1

0.870 s

77068.781 pri.A 0.170 s

0,1 0,1 G07_51-2 Ipset: 5,00 sec.A Tset: 0,85 s Tripping Time: 0,870 s 0.070 s

0,01 0,40 kV 1000 52G7\G07\G07_51

10000

[pri.A] 52G7\G07\G07_51-2

100000

0,01 0,40 kV 1000 52G7\G07\G07_51N

10000

[pri.A] G7

100000 Date: 12/8/2011 Annex:


DIgSILENT

Estudios Norma Tcnica


Estudios EVCP SM Porvenir 100 X =2252,457 pri.A Falla Trifsicas y Monofsicas X =12301,581 pri.A X =17075,375 pri.A

[s]

G08_51 IEC 255-3 inverse Ipset: 5,00 sec.A Tpset: 0,16 Tripping Time: 0,783 s

10

25581.083 pri.A 0.970 s

0.870 s

0.870 s

88770.059 pri.A 0.170 s G08_51 Ipset: 15,00 sec.A Tset: 0,05 s Tripping Time: 0,070 s

G08_51-2 Ipset: 5,00 sec.A Tset: 0,85 s Tripping Time: 0,870 s 0,1 0.070 s 0.070 s

0,01 0,40 kV 1000 52G08\G08\G08_51

10000 52G08\G08\G08_51-2

[pri.A]

100000

Estudios Norma Tcnica


Estudios EVCP SM Porvenir Falla Trifsicas y Monofsicas

G8

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 120

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

X =524,244 pri.A G09-51-2 Ipset: 5,00 sec.A Tset: 0,85 s Tripping Time: 0,870 s

X I =14215,166 =14215,166 X =19457,939 pri.A pri.A pri.A

[s]

In

0.870 s

0.870 s

87703.914 pri.A 0.170 s

0,1 0.070 s 0.070 s

G09-51 Ipset: 23,00 sec.A Tset: 0,05 s Tripping Time: 0,070 s

0,01 0,40 kV 100 52G9\G09\G09-51

1000 52G9\G09\G09-51-2

10000

[pri.A]

100000

Estudios Norma Tcnica


Estudios EVCP SM Porvenir 10 X =1519,113 pri.A X =11838,911 pri.A G10_51-2 Ipset: 5,00 sec.A Tset: 0,85 s Tripping Time: 0,870 s 10 Falla Trifsicas y Monofsicas

G9

Date: 12/8/2011 Annex:

X =25663,821 pri.A

[s]

[s]

G10_51N Ipset: 16,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s 1 0.870 s 1

G10_51 Ipset: 17,00 sec.A Tset: 0,05 s Tripping Time: 0,070 s 73860.462 pri.A 0.170 s

55694.177 pri.A 0.170 s

0,1 0.070 s

0,1 0.070 s

0,01 0,40 kV 1000 52G7(1)\G07\G10_51

10000

[pri.A] 52G7(1)\G07\G10_51-2

100000

0,01 0,40 kV 1000 52G7(1)\G07\G10_51N

10000

[pri.A] G10

100000 Date: 12/8/2011 Annex:

Estudios Norma Tcnica


Estudios EVCP SM Porvenir Falla Trifsicas y Monofsicas

Informe Tcnico

Pgina 121

DIgSILENT

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

X =723,266 pri.A

I =3014,093 pri.A G01_51-2 Ipset: 5,00 sec.A Tset: 0,85 s Tripping Time: 0,870 s

10

[s]

[s]

G01_51N Ipset: 20,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s 1 G01_51 Ipset: 20,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

0.870 s

36380.387 pri.A 0.170 s 39005.104 pri.A 0.170 s

0,1

0,1

0,01 0,40 kV 100

1000 52G1\G01\G01_51

10000 [pri.A] 52G1\G01\G01_51-2

100000

0,01 0,40 kV 1000 52G1\G01\G01_51N

10000

[pri.A] G1

100000 Date: 12/8/2011 Annex:


DIgSILENT

Estudios Norma Tcnica


Estudios EVCP SM Porvenir 100 X =802,045 pri.A I =4865,946 pri.A 100 Falla Trifsicas y Monofsicas lejanas

G04_51N IEC 255-3 inverse Ipset: 1,65 sec.A Tpset: 0,35 Tripping Time: 9999,999 s [s] [s]

G04_51 IEC 255-3 inverse Ipset: 5,00 sec.A Tpset: 0,15 Tripping Time: 1,170 s 10 10

G04_51-2 Ipset: 5,00 sec.A Tset: 0,85 s Tripping Time: 0,870 s 13418.748 pri.A 0.970 s 1.170 s 1 0.870 s 1

0,1 0,40 kV 100

1000 52G4\G04\G04_51

10000 [pri.A] 52G4\G04\G04_51-2

100000

0,1 0,40 kV 100

1000 52G4\G04\G04_51N

10000 G4

[pri.A]

100000

Estudios Norma Tcnica


Estudios EVCP SM Porvenir Falla Trifsicas y Monofsicas lejanas

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 122

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

100

X =161,188 pri.A

I =615,230 pri.A

[s]

G05_51 IEC 255-3 inverse Ipset: 2,50 sec.A Tpset: 0,16 Tripping Time: 1,233 s

10

2496.575 pri.A 0.970 s

1.233 s 1

0.870 s

G05_51-2 Ipset: 2,50 sec.A Tset: 0,85 s Tripping Time: 0,870 s

0,1 3,30 kV 100 52G5\G05\G05_51

1000 52G5\G05\G05_51-2

[pri.A]

10000

Estudios Norma Tcnica


Estudios EVCP SM Porvenir 100 X =1574,117 pri.A I =6547,377 pri.A 100 Falla Trifsicas y Monofsicas lejanas

G5

Date: 12/8/2011 Annex:


DIgSILENT

G06_51N IEC 255-3 inverse Ipset: 1,50 sec.A Tpset: 0,34 Tripping Time: 9999,999 s [s] G06_51 IEC 255-3 inverse Ipset: 5,00 sec.A Tpset: 0,16 Tripping Time: 1,152 s [s]

10

10

23374.478 pri.A 0.970 s

1.152 s 1 0.870 s 1

G06_51-2 Ipset: 5,00 sec.A Tset: 0,85 s Tripping Time: 0,870 s

0,1 0,40 kV 100

1000 52G6\G06\G06_51

10000 [pri.A] 52G6\G06\G06_51-2

100000

0,1 0,40 kV 100

1000 52G6\G06\G06_51N

10000 G6

[pri.A]

100000

Estudios Norma Tcnica


Estudios EVCP SM Porvenir Falla Trifsicas y Monofsicas lejanas

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 123

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

100

X =1574,117 pri.A

I =6547,377 pri.A

100 G07_51 IEC 255-3 inverse Ipset: 5,00 sec.A Tpset: 0,16 Tripping Time: 1,152 s

[s]

[s]

10

10

24445.576 pri.A 0.970 s

G07_51N Ipset: 16,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

1.152 s 1 0.870 s 1

77068.781 pri.A 0.170 s

0,1 0,1 G07_51-2 Ipset: 5,00 sec.A Tset: 0,85 s Tripping Time: 0,870 s

0,01 0,40 kV 1000 52G7\G07\G07_51

10000

[pri.A] 52G7\G07\G07_51-2

100000

0,01 0,40 kV 1000 52G7\G07\G07_51N

10000

[pri.A] G7

100000 Date: 12/8/2011 Annex:


DIgSILENT

Estudios Norma Tcnica


Estudios EVCP SM Porvenir 100 X =2252,457 pri.A I =6547,377 pri.A Falla Trifsicas y Monofsicas lejanas

[s]

G08_51 IEC 255-3 inverse Ipset: 5,00 sec.A Tpset: 0,16 Tripping Time: 1,424 s

10

25581.083 pri.A 0.970 s

1.424 s 1

0.870 s

88770.059 pri.A 0.170 s G08_51 Ipset: 15,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

G08_51-2 Ipset: 5,00 sec.A Tset: 0,85 s Tripping Time: 0,870 s 0,1

0,01 0,40 kV 1000 52G08\G08\G08_51

10000 52G08\G08\G08_51-2

[pri.A]

100000

Estudios Norma Tcnica


Estudios EVCP SM Porvenir Falla Trifsicas y Monofsicas lejanas

G8

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 124

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

X =524,244 pri.A

I =7279,890 pri.A G09-51-2 Ipset: 5,00 sec.A Tset: 0,85 s Tripping Time: 0,870 s

[s]

0.870 s

87703.914 pri.A 0.170 s

0,1

G09-51 Ipset: 23,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s

0,01 0,40 kV 100 52G9\G09\G09-51

1000 52G9\G09\G09-51-2

10000

[pri.A]

100000

Estudios Norma Tcnica


Estudios EVCP SM Porvenir 10 X =1519,113 pri.A I =6356,070 pri.A G10_51-2 Ipset: 5,00 sec.A Tset: 0,85 s Tripping Time: 0,870 s 10 Falla Trifsicas y Monofsicas lejanas

G9

Date: 12/8/2011 Annex:


DIgSILENT

[s]

[s]

G10_51N Ipset: 16,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s 1 0.870 s 1

G10_51 Ipset: 17,00 sec.A Tset: 0,05 s Tripping Time: 9999,999 s 73860.462 pri.A 0.170 s

55694.177 pri.A 0.170 s

0,1

0,1

0,01 0,40 kV 1000 52G7(1)\G07\G10_51

10000

[pri.A] 52G7(1)\G07\G10_51-2

100000

0,01 0,40 kV 1000 52G7(1)\G07\G10_51N

10000

[pri.A] G10

100000 Date: 12/8/2011 Annex:

Estudios Norma Tcnica


Estudios EVCP SM Porvenir Falla Trifsicas y Monofsicas lejanas

Informe Tcnico

Pgina 125

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

Sistema Puerto Williams

Informe Tcnico

Pgina 126

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

100

X =782,971 pri.A

X I =6175,913 =6175,913 pri.A pri.A

100

X =13429,457 pri.A

[s]

[s]

51N IEC 255-3 inverse Ipset: 1,65 sec.A Tpset: 0,15 Tripping Time: 9999,999 s

10 51-51N IEC 255-3 inverse Ipset: 4,00 sec.A Tpset: 0,03 Tripping Time: 0,153 s

10

0.340 s

0.153 s

0,1 0,40 kV 100

1000 52G1\G01\51-51N

10000

[pri.A]

100000

0,1 0,40 kV 100

1000 52G1\G01\51N

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams


10 X =436,578 pri.A I =5233,824 pri.A 100

G1 Fallas Trifsicas y Monofsicas

Date: 12/8/2011 Annex:


DIgSILENT

X =12457,367 pri.A

[s]

50 IEC 255-3 inverse Ipset: 4,00 sec.A Tpset: 0,02 Tripping Time: 0,117 s

[s] 51N(1) IEC 255-3 inverse Ipset: 4,00 sec.A Tpset: 0,10 Tripping Time: 9999,999 s

10

0.334 s 0.117 s 0,1

0,1

0,01 0,40 kV 100

1000 52G2\G02\50

10000

[pri.A]

100000

0,01 0,40 kV 100

1000 52G2\G02\51N(1)

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams Fallas Trifsicas y Monofsicas

G2

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 127

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

X =468,874 pri.A

I =3768,353 pri.A 50 IEC 255-3 inverse Ipset: 2,00 sec.A Tpset: 0,03 Tripping Time: 0,133 s

10

X =9814,087 pri.A 51N(1) IEC 255-3 inverse Ipset: 2,00 sec.A Tpset: 0,10 Tripping Time: 9999,999 s

[s]

[s]

0.272 s

0.133 s

0,1 0,40 kV 100

1000 52G3(1)\G03\50

10000

[pri.A]

100000

0,1 0,40 kV 100

1000 52G3(1)\G03\51N(1)

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams


100 X =369,191 pri.A I =2446,331 pri.A 10

G3 Fallas Trifsicas y Monofsicas


X =7633,405 pri.A

Date: 12/8/2011 Annex:


DIgSILENT

[s]

51N IEC 255-3 inverse Ipset: 4,00 sec.A Tpset: 0,06 Tripping Time: 9999,999 s

[s]

10

51 IEC 255-3 inverse Ipset: 2,50 sec.A Tpset: 0,04 Tripping Time: 0,310 s

0.265 s 0.310 s

0,1 0,40 kV 100

1000 52G6\G6\51

10000

[pri.A]

100000

0,1 0,40 kV 100

1000 52G6\G6\51N

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams Fallas Trifsicas y Monofsicas

G6

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 128

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

100

X =782,971I pri.A =2327,698 pri.A

100

[s]

[s]

51N IEC 255-3 inverse Ipset: 1,65 sec.A Tpset: 0,15 Tripping Time: 9999,999 s

10 51-51N IEC 255-3 inverse Ipset: 4,00 sec.A Tpset: 0,03 Tripping Time: 0,558 s

10

0.558 s

0,1 0,40 kV 100

1000 52G1\G01\51-51N

10000

[pri.A]

100000

0,1 0,40 kV 100

1000 52G1\G01\51N

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams


10 X =436,578 pri.AI =2162,219 pri.A 100

G1

Date: 12/8/2011 Annex:


DIgSILENT

Fallas Trifsicas y Monofsicas lejanas

[s]

50 IEC 255-3 inverse Ipset: 4,00 sec.A Tpset: 0,02 Tripping Time: 0,464 s

[s] 51N(1) IEC 255-3 inverse Ipset: 4,00 sec.A Tpset: 0,10 Tripping Time: 9999,999 s

10

0.464 s 1

0,1

0,1

0,01 0,40 kV 100

1000 52G2\G02\50

10000

[pri.A]

100000

0,01 0,40 kV 1000 52G2\G02\51N(1)

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams Fallas Trifsicas y Monofsicas

G2

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 129

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

X =468,874 I =1162,854 pri.A pri.A 50 IEC 255-3 inverse Ipset: 2,00 sec.A Tpset: 0,03 Tripping Time: 0,559 s

10 51N(1) IEC 255-3 inverse Ipset: 2,00 sec.A Tpset: 0,10 Tripping Time: 9999,999 s

[s]

[s]

0.559 s

0,1 0,40 kV 100

1000 52G3(1)\G03\50

10000

[pri.A]

100000

0,1 0,40 kV 100

1000 52G3(1)\G03\51N(1)

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams


100 X =369,191 pri.A I =1709,902 pri.A 10

G3 Fallas Trifsicas y Monofsicas

Date: 12/8/2011 Annex:


DIgSILENT

[s]

51N IEC 255-3 inverse Ipset: 4,00 sec.A Tpset: 0,06 Tripping Time: 9999,999 s

[s]

10

51 IEC 255-3 inverse Ipset: 2,50 sec.A Tpset: 0,04 Tripping Time: 0,519 s

0.519 s

0,1 0,40 kV 100

1000 52G6\G6\51

10000

[pri.A]

100000

0,1 0,40 kV 1000 52G6\G6\51N

10000

[pri.A]

100000

Estudios Norma Tcnica Estudio EVCP SM Puerto Williams Fallas Trifsicas y Monofsicas

G6

Date: 12/8/2011 Annex:

Informe Tcnico

Pgina 130