0FL-4141-001
The Xenta 300 is applied to the control of the full spectrum of HVAC and other facility equipment. The control of this equipment may be part of an automated or manual smoke control response.
The Xenta 300 series controllers are UL Listed (UL864) for application in a TAC Smoke Control System. This data sheet provides information, instructions and restrictions pertaining to the proper application of this specific product in a smoke control system. This data sheet takes precedence over other general product installation and application information for the Xenta 300 and must be used in conjunction with the Smoke Control Systems Manual (0-004-7897-1). The manual provides a system level view of the smoke control application and provides additional information regarding the various products that can be interconnected to form a system.
General Application
The Xenta 300 belongs to a family of freely programmable controllers designed for small and medium sized heating and air handling systems. The Xenta 300 controller provides a complete collection of full HVAC control and management functionality including DDC control loops, process monitoring, time scheduling, alarm handling, etc. Two models of the Xenta 300 series controller are offered with differing output configurations (Xenta 301 & Xenta 302). A variety of separate I/O expansion modules may be added to the Xenta 300 as required to address the control application. The modules which are UL864 listed and approved for application with the Xenta 300 are listed in the table to the right. The TAC Xenta 300 controller is simple to program, install and commission, using the graphical engineering tool TAC Menta. The controller communicates on a LONTALK TP/FT-10 free-topology network via a twistedpair, polarity insensitive cable.
Status indication of UI inputs when used as DI. 0/4-20ma, 0-1, 0/2-10 Vdc
0FL-4141-001
05/09
English
1(4)
Input Connections
The Xenta 300 controllers provides 4 digital inputs for monitoring discrete switch contacts; 4 thermistor inputs for monitoring temperature sensors and 4 universal inputs (UI) for monitoring contacts (DI), thermistor (TI) or 0-10V voltage output sensors. DI Excitation Voltage: 33 Vdc DI Closed Contact Current: 4ma DI Wire Length: 660 ft. Max. 22awg DI Pulse Duration: 20ms min. TI Thermistor: 1800 ohm @ 25oC TI Range: -58 to 302oF (-50 to 150 oC) o 250ft. Max.18awg TI Wire Length (to 75 C) : UI Voltage Input Signal: 0 - 10Vdc UI Voltage Input Impedance: 100K ohm VI Wire Length (Sensor self powered): 660ft. Max.22awg
Output Connections
The Xenta 300 controllers provides programmable discrete relay outputs for on/off control of field equipment and analog outputs for proportional control. DO Output Quantity: DO Control Voltage: DO Control Current: Power Factor: DO Wire Length: 6 on 301, 4 on 302 230 VAC max. 2A max 0.35 min. 660ft.14-18awg.
AO Output Quantity: 2 on 301, 4 on 302 AO Control Output: 0-10Vdc AO Control Current: 2ma max AO Wire Length (Actuator self powered): 660ft.22awg Unless noted otherwise, circuits are non-supervised.
Digital Inputs
11 12 13 14 15 16 17 18 19 20 B2 B3 M B4 X1 M X2 X3 M X4
24Vac Gnd
G G0 Y1 M Y2 Y3 M Y4 21 22 23 24 25 26 27 28 29
24 VAC
Supply
Earth Ground
Thermistor Inputs
0-10 V Outputs
Repeat wiring for AO Analog Output Y2 on 301 and Y2, Y3 & Y4 on 302. Model 302 only NC
Universal Inputs
Universal inputs U1 - U4 may be connected to voltage output sensor as shown or may be connected to thermistor (TI) sensor or discrete switch (DI) input as shown above for B and X inputs. 0-10V Voltage Output Signal Transmitter
5 6 7 8 9 10 U2 U3 M U4 B1 M
30
NC
Relay Outputs
1 2 3 4 C1 C2 U1 M
K1 Output
COM
Supply
Common K2 Output
Load
Repeat wiring for DO Relay Outputs K3 - K6 on 301 and K3 & K4 on 302. NC = No Connection When relay supply is not power limited, over current protection (e.g. fuse) must be supplied to limit current to max for wire size, or 4A max relay circuit fault current.
NC
0FL-4141-001
05/09
English
2(4)
1 2 C1 C2
COM
Enclosure
Rating: Type 3, Max: 5V, .1A, Power Limited, 8850ft @ 16awg cable. See smoke control system manual for table of cable and distance specifications. The Xenta 300 controller is housed within a plastic enclosure and must be plugged into an Xenta 300 mounting base (Part # 074-0901-x) ordered separately. To simplify installation, the mounting base can be premounted using mounting holes in the base, or snapped onto standard TS 35mm DIN rail (EN50022) and should be installed within one of the ENCL-.. series enclosures designated in the smoke control system manual.
Operating Environment
Operating Temperature: 32 to120oF (0 to 49oC) Storage Temperature: -4 to122oF (-20 to 50oC) Humidity: max. 93% RH non-condensing Dry - Indoor
Power
The Xenta 300 controller should be powered by one of the Class-2 24VAC transformers listed in the smoke control system manual. Power Input: 24VAC +-10% 60 Hz @ 10VA Max.
All inputs and outputs except relay output contacts are Power Limited.
Xenta 301/302 Power Input
24VAC Transformer
COM
24Vac Earth Ground
G G0 21 22
24 VAC
RS232
OP
0FL-4141-001
05/09
English
3(4)
0FL-4141-001
05/09
English
4(4)