SOFTWARE: Cooling Load Formulas - Version 1 Copyright 2008 by HVAC Prime Source. All rights reserved. See Disclaimer below PURPOSE To determine sensible, latent and total cooling load from air flow and temperature conditions. REQUIREMENT: MS Office software, and basic knowledge of Excel INSTRUCTIONS 1 Input the values in the green cells and the corresponding sensible load, latent load, and total cooling load will be calculated in the white cell. 2 Conversely, one of the other variables in the formula can be calculated in the cells below, by providing input for the remaining variables in the green cells. 3 All the units are in FPS system 4 Following are the abbreviations used SCFM Standard cubic feet/minute (flow at 70 F and sea level pressure) Tsa Supply air temp F Trm Room air temp F Wsa Supply air moisture (grains/Lb of dry air) Wrm Room air moisture (grains/Lb of dry air) Has Supply air enthalpy (Btu/Lb of dry air and associated moisture) Hrm Room air enthalpy (Btu/Lb of dry air and associated moisture) SH = Sensible Heat Load, Btuh LH = Latent Heat Load, Btuh TH = Total Heat Load, Btuh TH = SH + LH REFERENCES 1 Carrier Handbook of Air Condioning System Design, 1965 DISCLAIMER The user shall use this software at his or her discretion, and hereby relieves HVAC Prime Source of any liabilities. HVAC Prime Source shall not be held liable for the results obtained by using this software. Please see the disclaimer details on www.hvacprimesource.com web site.

HVAC PRIME SOURCE, LLC (www.hvacprimesource.com)


Cooling Load Formulas - Version 1 Copyright 2008 by HVAC Prime Source. All rights reserved. See Disclaimer below Input required Sensible Heat Load REF. 1, Page 1-150 Air flow Scfm 4000 = 1.08 x Scfm x (Tsa - Trm) Supply air Room Temp Temp Tsa F Trm F 101.2 76.24

SH Btuh 107827 107827 107827 107827 Scfm:

4000 101.2 76.24 4000 101.20 76.24 4000 101.2 76.24 Standard Cubic Ft per Minute at 70 F and 14.7 psia = 0.68 x Scfm x (Tsa - Trm)

Latent Heat Load REF. 1, Page 1-150

LH Btuh 132004

Air flow Scfm 2100

Supply air Room Moisture Moisture Wsa Wrm 99.56 7.12

132004 2100 99.56 7.12 132004 2100 99.56 7.12 132004 2100 99.56 7.12 Units of Moisture content W = grains of moisture / Lb of dry air W can be determined from the Psychrometric chart for given temperature conditions Total Heat Load REF. 1, Page 1-150 = 4.45 x Scfm x (Hsa - Hrm)

TH Btuh 94609

Air flow Scfm 2105

Supply air Room Enthalpy Enthalpy H sa H rm 38.6 28.5

94609 2105 38.6 28.5 94609 2105 38.60 28.5 94609 2105 38.6 28.50 Units of Enthalpy H = Btu per Lb of dry air and associated moisture H can be determined from the Psychrometric chart for given temperature conditions DISCLAIMER The user shall use this software at his or her discretion, and hereby relieves HVAC Prime Source of any liabilities. HVAC Prime Source shall not be held liable for the results obtained by using this software. Please see the disclaimer details on www.hvacprimesource.com web site.