Mixing Section
Optional Sections
General Unit Data
Size Coil Face Area Airflow Range1 Fan RPM Range2 Motor Hp (max - min) DX Circuits3 2" & 4" Flat Filter 3 2.8 1050-1800 650-1900 1 /2 - 2 1 (1) 20x25 6 5.63 2100-3600 650-1500 1 /2 - 3 1 (2) 20x25 8 7.45 2800-4800 650-1600 3 /4 - 5 1 or 2 (2) 20x25 10 9.74 3500-6000 650-1400 1-5 1 or 2 (1) 16x25 (2) 20x25 12 12.4 4200-7200 650-1200 1 - 7 1/2 2 (2) 16x20 (1) 16x25 (2) 20x20 (1) 20x25 (9) 20x20
Optional Section
14 14.34 4900-8400 650-1200 1 - 7 1/2 2 (2) 16x20 (1) 16x25 (2) 20x20 (1) 20x25 (9) 20x20
17 16.88 5950-10200 650-1000 1 - 10 2 (2) 16x20 (2) 16x25 (2) 20x20 (2) 20x25
21 20.63 7350-12600 650-1000 2 - 15 2 (2) 16x20 (2) 16x25 (2) 20x20 (2) 20x25
(2) 16x25
(4) 20x20
(4) 20x20
(6) 16x25 (6) 16x25 (4) 16x20 (12) 16x20 (6) 20x25 (6) 20x25 (12) 20x20 (8) 20x20 Notes: 1 Minimum cfm limit applies to units with hot water, steam, or electric heat. There is no airflow limit for cooling only units. Max cfm due to moisture carryover limits. 2 Fan rpm max is based on 60 hz motor. 3 Dimensions and Weights DX coils are 4 or 6 rows with 9, 12, or 14 fpi. Size Horizontal Unit1 Height Width Length Weight2 Vertical Unit1 Height Width Length Weight2 Length Weight Length Weight 3 24.5 31.22 54 164 47 31.22 40 189 21.5 50 21.5 46 21.5 80 6 30.5 44.22 57 232 59 44.22 46 275 24 68 24 64 24 119 8 34.5 48.22 48 240 66.5 48.22 34 286 27.25 82 27.25 78 27.25 135 10 34.5 60.22 52 277 66.5 60.22 38 316 25.5 89 25.5 83 25.5 168 12 42 68.22 56 462 82 68.22 42 526 27.25 126 27.25 112 27.25 186 14 42 68.22 56 473 82 68.22 42 539 27.25 126 27.25 112 27.25 199 17 52 76.22 62 594 102.5 76.22 45 709 29.25 179 29.25 164 29.25 274 21 52 76.22 62 636 102.5 76.22 45 750 34 179 34 164 34 301 25 59.5 78.22 64 771 35 200 35 184 35 318 28 248 30 59.5 91.22 65 967 35 217 35 201 35 355 28 271
Selection Procedure
1 Size = coil ft2 = design cfm max face velocity. Example: 6,600 cfm 500 fpm = 13.2 size 14 2 Consider your system and choose the appropriate sections. 3 Determine overall dimensions and weight. Note that for a given unit size, the height and width are the same for all sections. 4 Finalize fan/coil selections using the fan curves in catalog, CLCH-PRC001EN, or use the Trane Official Product Selection System, TOPSS.
Coil Access Length 24 24 24 24 24 24 24 24 Section Weight 69 100 106 119 162 157 204 196 1 Notes: Basic unit includes: fan, drives, reheat coil, main coil, 2" flat filter. 2 Weight of basic unit includes: cabinet, fan, average drive, wiring, and average filter. 3 Add 9 lbs. to basic weight for control box if applicable.
2002AmericanStandard,Inc.
208/60/1 6/9 6/18 7/18 8/28 230/60/1 6/11 6/20 7/20 8/30 277/60/1 6/13 6/24 7/24 8/38 208/60/3 6/13 6/26 7/28 8/41 10/50 12/50 230/60/3 6/13 6/26 7/32 8/41 10/53 12/59 460/60/3 6/13 6/24 7/32 8/44 10/53 12/63 575/60/3 6/13 6/26 7/34 8/44 10/53 12/63 380/50/3 6/13 6/26 7/32 8/44 10/53 12/63 415/50/3 6/13 6/26 7/32 8/44 10/53 12/63 Min cfm 1050 2100 2800 3500 4200 4900 Note: Refer to catalog CLCH-PRC007-EN for specific electric heat features.
Control box
control interface with transformer, fan contactor, disconnect, and customer connection terminal strip optional factory-installed and wired DDC controller, Tracer AH540
Other Options
electric heat with singlepoint power connections variable frequency drive factory mounted and wired
An American Standard Company www.trane.com For more information, contact your local Trane office or email us at comfort@trane.com