You are on page 1of 3

TANK AND VESSELS

The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 1 of 3 of B.21 18 September 2007
TANKS AND VESSELS H THNG BN V BNH CHA
1 GENERAL 1 TNG QUT
1.1 FUNCTIONAL DESCRIPTION 1.1 M T
The tanks and vessels scope of works
covers the cold water storage tanks,
chilled water expansion tanks, as well as
the accessories for the in situ conrete
tanks for fire and domestic water.
The contractor shall also be responsible
for preparing tank dimension drawings
showing tank sizes, depths, penetrations,
access hatches, etc for the basement
tanks.
Note that the basement tanks are to be
constructed by others. This contractor is
to allow for tank fitments including, but
not limited to covers, puddle flanges,
vents, filling accessoires such as ball
valves, suction accessories such as anti-
vortex devices, etc.
Phm vi cng vic ca chng ny bao
gm cc bn cha t trn cc tng k
thut, tng mi, cc bnh gin n nc
ti lnh, cng vi cc ph kin cho cc
b b tng cha nc sinh hat v
nc cha chy
Nh thu c trch nhim th hin bn
v kch thc bn, chiu su, cc l
m, ca thm, cho bn tng hm

Lu rng bn tng hm c thi
cng bi Nh thu khc . Nh thu ny
ch thc hin cung cp v lp t cc
ph kin bao gm, nhng khng b gii
hn: np, mt bch khng thm nc,
ng thng hi, cc ph kin ng ng
cp nh van bi, ng ng ht nh
thit b chng xoy,
1.2 CROSS REFERENCES 1.2 THAM CHIU CHO
General
Comply with the General Requirements
worksection.
Tng qut
Ph hp vi chng Nhng yu cu
chung.
Related Worksections
Mechanical General Requirements,
Mechanical Piping, Mechanical
Insulation, Metals & Prefinishes,
Adhesives, Sealants & Fasteners
Nhng chng lin quan
Nhng yu cu chung v c kh, H
thng ng ng c kh, Cch nhit c
kh, Kim loi v hon thin s b, Keo
dn, Cht trt kn v Ph kin kp cht.
2 QUALITY 2 CHT LNG
2.1 PRE-COMPLETION TESTS 2.1 TH NGHIM TRC KHI
HON TT
Production tests
Pressure vessels: Leak test.
Th nghim sn xut
Bnh p sut: th nghim x chy.
2.2 SUBMISSIONS 2.2 TRNH DUYT
Tank drawings
Submit drawings for the use in the
construction of the concrete tanks,
showing all services requirements,
including penetrations, puddle flange
locations, sumps, access holes etc.
Bn v bn
Trnh duyt bn v s dng thi cng
bn bton, th hin tt c cc yu cu
cn cung cp bao gm cc l m, v tr
mt bch khng thm nc, h thu, l
thm,
Pressure vessels
For vessels designed by contractor,
submit design data and corrosion
allowances as supplied to statutory
authorities.


Bnh p sut
i vi cc bn cha c thit k bi
Nh thu, trnh duyt thng s thit k
v gii hn n mn cung cp cho c
quan nh nc thm quyn.

TANK AND VESSELS
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 2 of 3 of B.21 18 September 2007
Components
Submit product data for all tank fitments.
Ph kin
Trnh duyt ti liu sn phm ca tt c
cc ph kin s dng cho bn.
3 MATERIALS 3 VT T
3.1 WATER STORAGE TANKS 3.1 BN LU CHA NC
General
Allow for all mechanical items necessary
to complete the tanks as shown on the
drawings and described in these
specifications.

The cover shall be provided with an
access manway of not less than 460mm
dia. clear opening and positioned
adjacent to ball valve entries in each
compartment. Adequately sized screened
cowl vents will be fitted to ensure
unrestricted water flow from the tank.
A steel internal ladder shall be provided
for all tanks over 1220mm in depth upon
request.
External ladders will be provided in
accordance with BS4211:1994
The tank shall be supplied with all
necessary stays, cleats and pipe
connections that shall be factory fitted to
the tank and cover panels.
Submit puddle flanges for approval.
Tng qut
Nh thu t chu chi ph v tt c cc
chi tit, ph kin, thit b cn thit
hon tt bn nh th hin trn bn v
v m t trong b qui nh k thut
ny.
Np y c mt l ngi chui lt c
ng knh khng nh hn 460mm
khng b che chn v t gn van bi
cp nc vo trong mi gian. H thng
thng hi c che chn nc, li c
kch thc tng xng c lp t
m bo nc c th trn khi bn t
do.
Mt thang thp bn trong bn c lp
t cho tt c cc bn su hn 1220mm
khi c yu cu.
Thang bn ngoi c lp t theo tiu
chun BS4211:1994
Bn nc phi c y thanh ging,
dy no v u ni ng cn thit c
lp sn ti nh my vo bn v cc tm
np.
Trnh duyt mt bch khng thm nc.
Accessories
Provide thermometer, pressure gauge
with gauge cocks, valved supply, 25mm
drain, lifting lugs, air vent and inspection
personnel access with cover, gasketted
and bolted in position.
Ph kin
Lp t ng h nhit , ng h p
sut vi van x, van cp, 25mm ng x,
mc nng, ng thng hi v l thm c
np cho nhn vin kim tra, m kn v
bt bulon vo v tr.
3.2 HEAD TANKS 3.2 BN TRN CAO
Capacity
Sufficient to accommodate system
expansion without overflowing.
Ti trng
cha s gin n ca h thng m
khng b trn.
Materials
General: Select from the following:
- Tank: 1.2mm stainless steel or 0.7mm
corrugated or swaged copper.
- Cover: 0.6mm stainless steel or 0.7mm
copper.
- Safe tray: 0.6mm stainless steel or
0.7mm copper.
Stainless steel: Type 316L to ASTM
A240/A240M.
Copper: Hard rolled.
Vt liu
Tng qut: chn nh sau:
- Bn: thp khng r 1.2mm hoc ng
dn sng hay dp nng 0.7mm.
- Np che: thp khng r 0.6mm hoc
ng 0.7mm
- Mng an ton: thp khng r 0.6mm
hoc ng 0.7mm
Thp khng r: 316L theo
ASTM A240/A 240M.
ng: cn ngui.
Construction
Stainless steel: Gas tungsten arc welded.
Copper: Braze seams and reinforce tanks
at connections using an additional layer
Cu to
Thp khng r: hn h quang kh in
cc tungsten.
ng: mi hn hp kim ng v gia c
bn u ni s dng mt lp b sung

TANK AND VESSELS
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 3 of 3 of B.21 18 September 2007
of copper brazed to the tank surface. ng hn ln b mt bn.
Accessories
General: Provide float valve make-up,
fast fill make-up, overflow, tank drain,
safe tray drain and system connection.
Minimum connection sizes:
- Drains: 25mm valved.
- Fast fill make-up: 25mm valved.
- Cold water feed: 20mm float valve.
- System connection: 25mm.
Ph kin
Tng qut: lp t van phao cp nc,
ng cp nhanh, ng x trn, x
y, mng an ton v u ni h thng.
Kch thc u ni ti thiu:
ng x: 25mm, co van
Cp nhanh: 25mm c van
Cp nc: 20mm van phao
u ni h thng: 25mm
Tank stands
General: Provide galvanized steel
support stands with a 25mm thick
hardwood plank deck bolted to the
frame, to suit the size of the safe trays.
Access: Provide access to the tanks
conforming to AS 1657 for inspection
and cleaning.
Chn bn
Tng qut: lp t chn thp trng
km c vn sn g cng bt bulon vo
khung, ph hp vi kch thc ca
mng an ton.
L thm: lp t l thm cho bn tun
th tiu chun AS 1657 kim tra v
v sinh.

You might also like