PACKAGED AIRCONDITIONING

The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 1 of 16 of B.22 18 September 2007
PACKAGED AIRCONDITIONING MY IU HO KHNG KH
LOI NH
1 GENERAL 1 TNG QUT
1.1 FUNCTIONAL DESCRIPTION 1.1 M T
The Packaged Air Conditioning scope of
work covers the split air conditioning
units.
Where water cooled package units are
provided (eg for 24/7 applications or
retail), they should also follow this
specification.

Phm vi cng vic ca h thng my
iu ha khng kh cc b bao gm
my lnh cc b hai.
Nhng ni s dng my lnh cc b
gii nhit nc (ng dng chy 24/7
hoc khu bn hng), theo c tnh k
thut ny.
1.2 CROSS REFERENCES 1.2 THAM CHIU CHO
General
Refer to the General Requirements
worksection.
Tng qut
Ph hp vi chng Nhng yu cu
chung.
Related Worksections
Mechanical General Requirements,
Cooling Towers, Air Filters, Air Coils,
Ductwork, Ductwork Insulation, Fire
Stopping, Acoustic & Vibration Control,,
Mechanical Electrical..
Nhng chng lin quan
Tham chiu n cc chng sau:
Nhng yu cu chung v c kh, Thp
gii nhit, Lc gi, ng gi, Cch nhit
ng gi, Cht ngn chy, Kim sot n
v rung n, in c kh.
1.3 STANDARDS 1.3 TIU CHUN
General
Refrigeration systems: To AS/NZS
1677.2 and the recommendations of
SAA HB40.1 and SAA HB40.2.
Performance labelling: To AS/NZS
3823.1.1, AS/NZS 3823.1.2 and
AS/NZS 3823.2.
Microbial control: To AS/NZS 3666.1
and the recommendations of SAA/SNZ
HB32.
Ductwork and insulation: To AS 4254.
Air filter performance and construction:
To AS 1324.1.
Tng qut
H thng lm lnh: theo
AS/NZS 1677.2 v cc yu cu trong
SAA HB40.1 v SAA HB40.2.
Cng sut ghi nhn: theo
AS/NZS 3823.1.1, AS/NZS 3823.1.2
v AS/NZS 3823.2.
Kim sot vi khun: theo tiu chun
AS/NZS 3666.1 v cc yu cu trong
SAA/SNZ HB32.
ng gi v cch nhit: theo AS 4254.
c tnh lc gi v cu to: theo tiu
chun AS 1324.1.

1.4 INTERPRETATION 1.4 KHI NIM
Definitions
Direct expansion split systems with total
cooling capacity when tested to AS/NZS
3823.1.1 or AS/NZS 3823.1.2, Standard
test condition T1:
- Room airconditioner: < 7.5kW.
- Packaged airconditioner: 7.5kW.
Split systems: Supply only indoor and
outdoor units of split systems designed
and rated by the manufacturer to operate
together.
Cc nh ngha
H thng gin n trc tip hai mnh c
tng cng sut lnh khi th nghim
theo AS/NZS 3823.1.1 hoc
AS/NZS 3823.1.2, iu kin th
nghim tiu chun T1:
My DHKK cho phng: <7.5KW
- My iu ho package: 7.5 kW
H thng hai mnh: Ch cung cp dn
nng v dn lnh ca h thng hai
mnh c thit k v phn cp bi
mt nh sn xut hot ng chung

PACKAGED AIRCONDITIONING
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 2 of 16 of B.22 18 September 2007
vi nhau.
2 QUALITY 2 CHT LNG
2.1 PRE-COMPLETION TESTS 2.1 TH NGHIM TRC KHI
HON TT
Standards
Provide airconditioning equipment that
has been subjected to physical test in
conformance to the following:
- Non-ducted airconditioners: To
AS/NZS 3823.1.1.
- Ducted airconditioners: To AS/NZS
3823.1.2.
Labelling
Required: To AS/NZS 3823.2.
Tiu chun
Cung cp thit b HKK c kim
tra vt l theo hnh dng nh sau:
- My iu ho khng s dng ng
gi: theo AS/NZS 3823.1.1.
- My iu ho s dng ng gi:
theo AS/NZS 3823.1.2.
Ghi nhn:
Yu cu: theo AS/NZS 3823.2
3 PRODUCTS 3 THIT B
3.1 ROOM AIRCONDITIONER
GENERAL
3.1 TNG QUT MY IU HO
CC B
Safety
General: Comply with AS/NZS
3350.2.34 and AS/NZS 3350.2.40.
An ton
Tng qut: tun th theo
AS/NZS 3350.2.34 and
AS/NZS 3350.2.40.
Construction
Insulation: Insulate and vapour seal to
prevent external condensation under all
operating conditions.
Supply fan: Centrifugal with multi-speed
or variable speed motor.
Filter performance to AS 1324.1: G2
rating, Type 1, Class C.
Condenser fans: Low speed propeller or
axial.
Coils: Copper tube, aluminium plate fin
type with no moisture carry over.
Drains: Provide aluminium, stainless
steel or plastic drain trays to collect all
moisture generated inside unit. Provide
trapped drain to waste.
Cu to
Cch nhit: cch nhit v lm kn m
trnh ngng t nc mt ngoi tt c
cc iu kin hot ng.
Qut gi cp: qut ly tm nhiu tc
hoc loi thay i tc
Lc gi thc hin theo AS 1324.1: c
G2, Loi 1, phn lp C.
Qut dn ngng: qut hng trc t
cnh hoc nhiu cnh tc thp
Dn coil: ng ng, l tn nhit nhm
khng mang hi m
Mng nc ngng: cung cp bng
nhm, thp khng r hay khay plastic
hng nc ngng t bn trong dn
lnh. Cung cp by nc ngng.
Refrigeration system
Refrigerant: R22, R407C or R410A.
Provide:
- Expansion device.
- High-pressure and low-pressure
compressor cutouts.
- Suction pressure gauge connection
points.
- Isolating valves between split units.
- Defrost timer/thermostat with sensing
bulb (reverse cycle units only).
Refrigerant reversing valve (reverse
cycle units only).


H thng gas lnh
Gas lnh: R22, R407C or R410A
Cung cp:
- Thit b gin n.
- Ngt cao v thp p my nn.
- u ni ng h p sut ng ht.
- Van cch ly gia dn nng v lnh.
- nh gi x tuyt / iu chnh nhit
c bu cm bin nhit (ch cho
my hai chiu).
Van o chiu gas lnh (ch cho my
hai chiu).

PACKAGED AIRCONDITIONING
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 3 of 16 of B.22 18 September 2007
3.2 ROOM AIRCONDITIONER
SPLIT SYSTEMS
3.2 H THNG MY IU HA
KHNG KH CC B
General
Provide split room airconditioning
systems including indoor supply air
units, outdoor condensing sections,
interconnecting refrigeration piping,
insulation and operating and safety
controls.
General
Cung cp h thng my iu ha khng
kh cc b bao gm dn nng v dn
lnh, ng ng gas ni, cch nhit v
iu khin hot ng v an ton

Ceiling mounted Slim Line duct type
Type: Above ceiling type with duct
connections. Provide proprietary filter
and secondary drain pan under unit. The
unit is to be of the slimline type to fit
within the architectural requirements.
Dn lnh ni ng gi loai mnh
Loi: gn bn trn trn ni ng gi.
Cung cp lc gi v mng nc ngng
pha di my. My l loi b dy nh
ph hp vi yu cu ca nh kin
trc.
Wall mounted (hiwall) indoor units
Type: Slim line construction, with
adjustable louvre blades to allow
horizontal or 45 downward air
discharge.
Installation: Mount 100mm minimum
below ceiling level.
My iu ho (dn lnh) treo tng
Loi: Cu to mng, cnh hng gi
iu chnh theo phng ngang hoc gi
ra hng xung 45o

Lp t: treo ti thiu cch trn 100mm
Ceiling mounted exposed indoor units
Type: Indoor unit surface mounted or
partially recessed into ceiling. Provide
return air grille and filter, internal access
and perimeter air distribution system.
Dn lnh treo di trn
Loi: c treo hoc m mt phn
trong trn. Bao gm ming gi hi, lc
gi, ca thm, h thng phn phi gi
vng
Control location
Mount on wall to sense representative
room temperature.
V tr iu khin
Treo trn tng cm bin nhit
i din cho phng
Outdoor units
Type: Fully weatherproofed units
suitable for outdoor operation, housing
compressor, outdoor coil and main
electric controls.
Dn nng
Loi: hon ton chu c thi tit khi
vn hnh ngoi tri, v bc my nn,
dn coil ngng v iu khin cp in.
3.3 ROOM AIRCONDITIONER
CONTROLS
3.3 IU KHIN MY LNH CC
B
Selector switch control
Provide selector switches on the unit for
the following functions:
- FAN: Runs fan only.
- COOL: Runs fan and forces cooling to
operate continuously.
- HEAT: Runs fan and forces heating to
operate continuously.
- AUTO: Runs fan and thermostatically
controls heating or cooling.
- OFF: All functions off.
iu khin cng tc v tr
Cung cp cng tc v tr cho my theo
cc chc nng sau:
- Qut: ch ch chy qut
- Lm lnh: qut v lm lnh vn hnh
lin tc.
- Si: qut v si vn hnh lin tc
- T ng: qut v iu khin nh
nhit lm lnh hoc si
- Tt: tt tt c cc hot ng
Microprocessor control
Provide microprocessor controller with
the following functions:
- ON/OFF switch.
- Evaporator fan speed selector switch.
Minimum of three speeds
- Timer selector switches (Time on,
Time off, no timer control). Time
iu khin bng b vi x l
Cung cp b iu khin vi x l theo
cc chc nng sau
- Cng tc bt/tt
- Cng tc v tr tc qut dn lnh.
Ti thiu 3 tc .
- Cng tc v tr nh gi (nh gi bt,
nh gi tt, khng nh gi) Thi

PACKAGED AIRCONDITIONING
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 4 of 16 of B.22 18 September 2007
switch adjustable in hourly increments
up to 12 hours.
- Mode selector switch: COOL - HEAT
- AUTO.
- Indicating lamps, LEDs or LCD
display for:
. Unit operating.
. Filter clean reminder.
gian iu chnh cng tc hng gi
trong vng 12 gi
- Cc ch trn cng tc v tr: Lm
lnh - Si -T ng
- n ch th, n LED hoc mn hnh
tinh th lng cho:
. My ang hot ng
. Nhc nh v sinh lc gi

3.4 PACKAGE AIRCONDITIONER
GENERAL
Operating conditions
Provide equipment that operates within
an ambient temperature range of 0C to
45C, without excessive head pressure,
unstable operation or icing.
Split systems
Outdoor units: Provide packaged
condensing units consisting of
refrigerant condensers, compressors and
associated piping and electrical
connections, mounted within the
condenser enclosure.
Indoor units: Provide units consisting of
coils, piping, supply air fan, accessories
and electrical connections, mounted
within an insulated enclosure.
Filters
Filters: Type A, B or C to AS 1324.1
with performance to AS 1324.2 as
follows:
Test Dust No. 1: 20% efficiency.
Test Dust No. 4: 85% arrestance.
3.4 MY IU HO HAI MNH
TNG QUT
iu kin lm vic
Cung cp thit b hot ng trong
khong nhit mi trng t 0C n
45C, khng b qu p, hot ng
khng n nh hoc b ng .
H thng hai mnh
Dn nng: Cung cp dn nng bao gm
dn ngng mi cht lnh, my nn v
h thng ng ng cn thit, cc u
ni in, g lp bn trong v bao che
dn ngng.
Dn lnh: Cung cp dn lnh bao gm
dn coil, ng ng, qut cp gi, v
cc u ni in, g lp bn trong mt
v bao che cch nhit.
Lc gi
Lc gi: Chng loi A, B hoc C theo
AS 1324.1 c c tnh theo AS 1324.2
nh sau:
Th nghim bi s 1: 20% hiu sut.
Th nghim bi s 4: 85% gi li.
3.5 EQUIPMENT ENCLOSURES 3.5 V THIT B
General
General: Provide enclosures, materials
and finishes that are weatherproof and
corrosion-resistant, assembled and
reinforced to prevent flexing and
drumming.
Material and finishes
Materials:
- Metallic-coated steel: Base and legs
1.6 mm with 1.0 mm panels.
- Aluminium: Base and legs 2.0 mm
with 1.6 mm panels.
Outdoor equipment finishes: Powder
coat all metallic-coated steel interior and
exterior surfaces to AS 3715 or
AS/NZS 4506 as appropriate, using
APAS-0155/2.
Indoor equipment finish: Manufacturers
standard finish.
Moisture retention: All parts free
draining with no pockets in which
condensation and/or rainwater may be
Tng qut
Cung cp v bao che, vt liu v hon
thin b mt chu c thi tit v
chng n mn, lp rp v g chng
bin dng v g p

Vt liu v hon thin b mt
Thp m kim loi: v chn:
1.6 mm vi tm: 1.0 mm
Nhm: v chn: 2.0 mm vi tm:
1.6 mm

Hon thin dn nng: Sn tnh in tt
c b mt bn trong v b mt bn
ngoi thp m kim loi theo AS 3715
hoc AS/NZS 4506, s dng APAS-
0155/2.
Hon thin dn lnh: theo tiu chun
nh sn xut.
S gi m: Tt c cc chi tit phi thot
nc t do khng c ch ng nc
c th nc ngng t hay nc ma b

PACKAGED AIRCONDITIONING
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 5 of 16 of B.22 18 September 2007
retained.
Access
General: Provide access to the interior of
the unit for routine inspection and
maintenance and for removal of major
components. Provide doors and panels
with handles and captive fasteners and,
where they are for access to the
conditioned air stream, provide soft
gaskets ensuring an airtight seal. Provide
weatherproof doors and panels on
outdoor enclosures. Do not use self
tapping screws on removable panels.
Access: As a minimum, provide access
to the following:
- Condensate tray (underside of access
panel to be within 300 mm of tray).
- Supply fan motor and drive.
- Compressor section.
- Condenser section.
- Filter section.
Access panel fasteners:
- Units < 1000 L/s: Metal thread screws
or camlock fasteners.
- Units 1000 L/s: Camlock fasteners.
Handles: Provide handles to permit easy
and safe removal and replacement of
panels.
- < 450 mm diagonal panel dimension:
1 handle.
- 450 mm diagonal panel dimension:
2 handles.
Insulation
General: Insulate enclosures to prevent
external surface condensation under all
operating conditions. Fix insulation to
panels with waterproof adhesive applied
to at least 50% of the panel area.
Material properties:
- Thermal conductivity:
0.035 W/m.K.
- Thickness: 25 mm.
- Facing: Reinforced aluminium foil.
- Moisture absorption: Non-
hygroscopic.
- Fire hazard properties: To AS 4254
clause 2.7.1.
Condensate trays
General: Provide a tray under each
cooling coil extending downstream to
collect water carry over and under any
other components on which
condensation may occur. Grade trays and
sumps to the outlet to prevent water
retention. Provide radiused corners and
arrange to facilitate cleaning.
gi li.
Tip cn
Cung cp li tip cnvo bn trong my
kim tra v bo tr, tho ri cc
cu kin chnh.
Cung cp ca v np c tay nm v
kha nhanh nhng ni mun tip cn
vo dng khng kh iu ha, cung cp
m mm lm kn gi. Cung cp ca v
np thm chu thi tit trn v bao che
dn nng. Khng s dng vt t lm ren
trn v tho ri

Tip cn: Ti thiu, cung cp li tip
cn nh sau:
- Mng hng nc ngng t (mt di
ca tm thm phi khng xa hn
300mm t mng)
- Mt qut cp gi v phn dn ng.
- My nn
- Dn ngng
- B lc

Phng thc c nh np thm:
- Thit b < 1000 L/s: Vis ren kim loi
hoc ci kp lch tm kiu kha cam.
- Thit b 1000 L/s: ci kp lch tm
kiu kha cam.
Tay cm: Cung cp tay cm d dng
v an ton tho ri v thay th cc np
thm.
- ng cho < 450 mm: 1 tay.
- ng cho 450 mm: 2 tay.
Cch nhit
Cch nhit cho v bao che ngn
nga s ngng t xy ra trn b mt
bn ngoi di mi ch hot ng.
Lp cch nhit vo cc tm vi bng
keo chng nc dn ti thiu 50% din
tch tm.
c tnh vt liu:
- Tnh dn nhit: 0.035 W/m.K
- Chiu dy: 25 mm.
- B mt: Mng nhm c gia c.
- S hp th hi m: khng ht m
Ch s bt chy: theo AS 4254 khong
2.7.1

Mng hng ngng t
Cung cp mt mng hng bn di mi
dn coil lnh ko di ra thu ht nc
mang sang v bn di cc chi tit c
th xy ra ngng t. t mng v phu
hng nghing dc v ph l thot
ngn nga s ng vng. Cung cp cc
gc c bo trn v lp rp sao cho d
dng v sinh.

PACKAGED AIRCONDITIONING
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 6 of 16 of B.22 18 September 2007
Material: Fabricate wetted parts from
aluminium to AS/NZS 1734 or stainless
steel sheet grade 304L.
Protection
General: Provide metallic coated steel
mesh protection to outdoor fans and
exposed faces of outdoor coils.
Vt liu: Gia cng cc chi tit t bng
nhm theo AS/NZS 1734 hoc thp
khng r mc 304L.
Bo v
Tng qut: cung cp li thp m kim
loi bo v qut dn nng v mt bn
ngoi ca dn giu nhit.
3.6 SUPPLY FAN 3.6 QUT DN LNH
Performance
Performance: Select fans and fan motors
so the air flow can be increased 5%
above the specified design air flow rate,
against the corresponding increased
system resistance by fan speed change
alone and without unstable operation.
Fans with multi-speed motors: Select for
required duty at second highest speed.

Construction
Forward curved impellers: Metallic-
coated steel blades and wheel.
Backward inclined impellers: Backward
inclined, steel or extruded aluminium,
aerofoil or single thickness blades, and
non-overloading power characteristic.
Casing: Metallic-coated steel sheet,
riveted or spot-welded with joints sealed.
Provide 1.2 mm minimum thickness
scroll and 2 mm minimum thickness side
plates.
Bases: Formed from pressed metallic-
coated steel sheets, bolted to casings.
Provide at least 4 brackets for mounting.
Inlet bells: Shaped for aerodynamically
efficient air entry and small clearance
from impeller.
Shaft: Steel treated with solvent
removable petroleum based protective
coating.
Bearings: Self-aligning sealed for life
ball or roller type.
Finish: Brush and prime spot welds with
zinc-rich organic primer to APAS-2916.

Drive
Type: Direct or belt drive as scheduled
in Selections.
Direct drive: Multi speed or electronic
variable speed.
Belt drive: To suit a minimum 125% of
motor power and capable of transmitting
the full starting torque without slip.
Provide adjustable motor pulley. Provide
pulleys with shaft keys or taper lock
bushes.

Hot ng
Chn qut dng khng kh c th
tng ln cao hn nh nc dng khng
kh thit k, chu c tr lc h thng
lin quan tng ln bng cch ch thay
i tc qut v khng xy ra hot
ng mt n nh.
Qut s dng mt a tc: chn theo
cng sut yu cu tc cao nht th
hai.
Cu to
Cnh cong v pha trc: cnh v bnh
m km cong v pha trc.
Cnh nghing v pha sau: thp hay
nhm c, nghing ra sau, cnh kiu
my bay hoc bn n, v c c tnh
cng sut khng b qu ti.
V hp: thp tm trng km, bt rivet
hoc hn bm c cc mi ni c lm
kn.
- Thp cn: dy ti thiu 1.2mm
- Tm mt bn: dy ti thiu 2mm
: c gia cng t thp tm trng
km dp, bt bulon vo v. Cung cp
ti thiu 4 chn cho g lp.
Vm u vo: c hnh dng kh ng
hc h tr gi vo v c khe h nh vi
cnh.
Trc: thp c x l bng lp ph bo
v dng dung dch gc du c th lm
sch c cho cc trc v chi tit my.
trc: loi bi hoc a, t la,
nim kn.
Hon thin: Chi sch v sn lt nhng
im hn bm bng sn lt hu c giu
km theo APAS-2916.
Dn ng
Chng loi: trc tip hoc dng dy ai
nh thit k.
Dn ng trc tip: a tc hoc bin
tc in t.
Dn ng ai: c th p ng c ti
thiu 125% cng sut mt v truyn
momen quay khi ng y ti m
khng b trt.
S dng bnh ai trn mt loi iu
chnh c. S dng bnh ai vi then
trn trc hoc bc kha cn.


PACKAGED AIRCONDITIONING
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 7 of 16 of B.22 18 September 2007
3.7 CONDENSER FANS 3.7 QUT DN NNG
Type
Propeller fan: Direct drive with single
thickness fixed pitch aluminium or UV
protected polypropylene blades.
Aerofoil axial flow fan: Direct drive with
adjustable pitch aerofoil section blades
of UV protected GRP or polypropylene,
or aluminium.
Centrifugal fan:
- Drive: Direct or belt driven
- Impeller: Forward curved or backward
inclined .

Guards: Provide easily removable
powder coat finished metallic coated
steel guards over condenser fans.

Chng loi
Qut kiu chong chng: dn ng trc
tip c cnh nhm bc chia c nh
bn n hoc polypropylene chu c
tia cc tm.
Qut kiu cnh my bay hng trc:
cnh kiu my by c bc chia iu
chnh, GRP hoc polypropylene chu
c tia cc tm.
Qut ly tm: cnh nghing ra sau hoc
cong v trc dn ng trc tip hoc
dy ai theo bng lit k. Cu to, dn
ng v mc mt theo nh trong bng
lit k.
Truyn ng: trc tip hoc ai
Dng cnh: cnh cong nghing v pha
trc hoc sau
Bo v: cung cp tm bo v bng thp
m kim loi ph sn bt d tho ri bao
che qut.
3.8 FAN MOTORS 3.8 NG C QUT
General
Power rating of supply fans: At least the
power required by the fan when the air
flow is increased by 10% above the
design air flow rate stated in the
schedules, against the corresponding
increased system resistance as installed.
Single phase motors: 0.37 kW only.
Speed: < 25 rev/s.
Bearings: Sealed for life ball bearings.
Minimum degree of protection:
- Supply fans: IP54.
- Condenser fans: IP55.
Insulation to AS 1359.101:
- Single phase motors: Minimum Class
B.
- Three phase motors: Minimum Class
F.
Tng qut
Mc cng sut: ti thiu bng cng sut
yu cu ca qut khi lu lng khng
kh tng ln 10% cao hn nc lu
lng thit k trong bng lit k, chu
c tr lc h thng tng ln lin
quan khi lp t.
Mt 1 pha: ch s dng 0.37 kW
Tc : < 25 vng/giy.
trc: bi nim kn.
Cp bo v ti thiu:
- Qut dn lnh: IP54
- Qut dn nng: IP55
Cch in:
- Mt 1 pha: ti thiu lp B
- Mt 3 pha: phn lp F

3.9 COMPRESSORS 3.9 MY NN
General
Enclosure: Welded or accessible
hermetic steel enclosure with 3
mounting feet. Provide the following:
- Mounting: Vibration isolating
mountings.
- Service valves: Packed and capped,
backseating refrigerant suction valve.
- Charging connections: Schreader type
connections for evacuation and
refrigerant charging.
Crankcase heaters: Provide integral
positive temperature coefficient type
Tng qut
V bao che: thp kn c th tip cn
hoc hn c 3 chn lp, c cc chi tit
sau:
- Chn lp: loi cch ly rung ng
- Van: van ht mi cht lnh ta sau
ng gi v chp kn.
- u ni np gas: kiu Schreader
rt chn khng v np gas.


in tr si hp cacte: cung cp tch
hp in tr si hp cacte kiu h s

PACKAGED AIRCONDITIONING
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 8 of 16 of B.22 18 September 2007
crankcase heaters if required for safe
compressor operation.
nhit dng nu c yu cu cho hot
ng ca my nn mi ch
3.10 COILS 3.10 DN COIL
Design
Coil face velocity: 2.5 m/s.
Fin pitch: 550 fins/m.
Cooling coil air pressure drop: 150 Pa.

Construction
Tubes: Copper to AS/NZS 1571 or
AS 1572 designation C12200.
Fins: Aluminium alloy plate fins
0.12 mm thick to AS 2848.1,
designation 3003 or 8011.
Coil frames:
- Aluminium alloy to AS 2848.1,
designation 5005.
- Metallic-coated steel sheet coating
class Z275.
Condenser coil: To provide at least 5 K
subcooling.
Access
General: Arrange coils and casing so that
both sides of coils are easily accessible
for inspection and cleaning.
Additional coil treatment
General: If scheduled in Selections,
protect condenser coil with factory
applied air drying phenolic coating
resistant to dilute acids, dilute alkalis,
solvents, inorganic salts and salt laden
air, if required in the schedule.
Thit k
Tc b mt coil: 2.5 m/s
Bc l tn nhit: 550 fins/m
st p khng kh qua dn lnh:
150 Pa
Cu to
ng: ng ng theo tiu chun
AS/NZS 1571 hoc AS 1572 phn
C12200.
L tn nhit: hp kim nhm dy
0.12 mm theo tiu chun AS 2848.1,
phn 3003 hoc 8011.
Khung dn coil: hp kim nhm theo
AS 2848.1, phn 5005, hoc thp trng
km, lp m G2/Z275.
Dn ngng: cung cp s qu ngui ti
thiu 5 K.


Tip cn
Lp t coil v v hp cho c hai
mt ca coil c th d dng tip cn
thc hin kim tra v bo tr.
X l b sung cho dn coil
Bo v dn ngng bng lp ph
phenolic kh t nhin ti nh my,
chu c axit long, kim long, cht
ha tan, mui v c, khng kh c hi
mui, nu c yu cu trong bng lit
k.
3.11 WATER COOLED
CONDENSERS
3.11 DN NGNG GII NHIT
NC
General
Water cooled condensers:
- Mechanically cleanable type:
. Shell and tube type.
. Stainless steel plate type, bolted
construction.
- Chemically cleanable type:
. Stainless steel plate type, welded
construction.
. Double pipe type.
Condenser water system strainer:
Provide a strainer having mesh smaller
than smallest passage in heat exchangers.
Drains: Provide drains and vent valves at
each condenser. Arrange to permit
complete drainage of the water in the
condenser.
Water treatment: Provide condensers that
will not face corrosion problems from
Tnq qut
Bnh ngng gii nhit nc:
- Loi lm sch c kh
. Loi ng nc nm ngang
. Loi tm bng thp khng r,
kt cu bt bulng
- Loi lm sch bng ha cht:
. Loi tm bng thp khng r,
kt cu hn.
. Loi ng i.
Lc cho h thng nc ngng:
Cung cp mt ci lc c li nh hn
on nh nht ca b trao i nhit.
ng thot: cung cp ng thot v van
thng hi mi bnh ngng. Lp t
cho php x hon ton nc trong bnh
ngng.
X l nc: cung cp bnh ngng
khng gp phi vn n mn t
ng ng nc chnh bit trc, v t

PACKAGED AIRCONDITIONING
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 9 of 16 of B.22 18 September 2007
the anticipated local mains water, a nd
from the same water used in open type
cooling towers with the specified water
treatment systems.
ng nc tng t dng trong cc
thp gii nhit loi h vi h thng x
l nc trn danh ngha.

3.12 REFRIGERATION SYSTEM 3.12 TC NHN LNH
Components
Refrigerant: R22, R407C or R410A.
Copper pipe: To AS/NZS 1571.
Pipe insulation within unit: Insulate
pipes that operate below ambient
temperature with elastomeric foam
10 mm thick.
Multiple compressor units: Provide
separate refrigeration circuit for each
compressor.
Refrigerant expansion device:
- < 20 kW total capacity: Eliminator or
similar, non-capillary expansion
device, thermostatic expansion valve
or electronic expansion valve.
- 20 kW total capacity: Thermostatic
expansion valve or electronic
expansion valve.
Refrigeration circuits: Provide each
refrigeration circuit with a sight glass-
moisture indicator, filter dryer and
manual reset high pressure and auto reset
low pressure cutouts. Provide a suction
accumulator if compressor is liable to
damage by liquid slugs.

Cu kin
Mi cht lnh: R22, R407C hoc
R410A.
ng ng: theo AS/NZS 1571.
Cch nhit cho ng bn trong thit b:
Thc hin cch nhit cho ng hot
ng nhit thp hn nhit mi
trng bng bt cch nhit co gin dy
10 mm.
Thit b c nhiu my nn: Cung cp
mch lm lnh ring r cho mi my
nn.
- Kh c gin n mi cht lnh:
. Tng cng sut < 20 Kw: loi y
hoc tng t, khng mao dn, van
gin n nhit tnh hoc van gin n
in t .
. Tng cng sut 20 Kw: van gin
n nhit tnh hoc van gin n in
t.
- Mch gas: knh quan st hi m cho
tng mch gas, b lc kh, mch
cutout t ng reset p sut thp v
reset tay p sut cao.
Cung cp b tch ly ht nu my nn
c th b h do ngp cht lng.

3.13 CONTROLS & ELECTRICAL 3.13 IU KHIN & CP IN
Components
General: Provide factory wired control
panel for each unit containing the
following:
- Plug-in relays.
- Terminal strips numbered to
correspond to wiring diagram.
- Starter and overload protection for
each motor.
- Short circuit protection: Provide each
compressor and each 3-phase motor
with short circuit protection by either
. High rupture coefficient (HRC)
fuses or
. Circuit breaker with adequate
interrupting capacity.
. Starter contactor with manual reset
thermal or magnetic overload.
- Provide automatic lead/lag
changeover for units with multiple
compressors.
Cu kin
Cung cp t in iu khin u dy ti
nh my cho tng thit b c cc chi tit
sau:
- Rle kiu n vo
- Trm u ni c nh s tng ng
vi s u dy.
- B khi ng v bo v chng qu
ti cho mi mt.
- Bo v ngn mch: trang b bo v
ngn mch cho mi my nn v mt
3 pha bng
. Cu ch c h s ct cao (HRC)
. CB c cng sut ngt thch hp
. Cu dao t ng v contactor c
nt reset tay cho qu ti nhit hoc
t.
- Trang b b chuyn i trc/sau t
ng cho thit b c nhiu my nn.
- Chc nng nh gi chu k khi
ng ngn: gii hn s ln khi
ng my nn.


PACKAGED AIRCONDITIONING
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 10 of 16 of B.22 18 September 2007
- Short cycle timer function: To limit
compressor starts.
- Separate control and electrical circuit
for each compressor.
- HRC fuse or circuit breaker short
circuit protection for each crankcase
heater (if fitted) and control circuit.
- Phase failure protection on motors
5.5 kW.
- Terminals for remote indication of run
and fault conditions.
- Permanent, weatherproof, wiring
diagram fixed on or next to the control
panel.
Safety controls: Arrange so that
operation of one item does not shut
down other items that are not directly
dependent on its operation.
Isolating switch: Provide system isolator
to AS/NZS 3000 for each system.
Condenser head pressure control: If
scheduled in Selections, provide
electronic condenser fan speed control to
maintain minimum condenser head
pressure at all operating ambient
conditions.
Pump-down control: If scheduled in
Selections, provide solenoid valve and
automatic pump-down control.
- Phn tch mch iu khin v mch
ng lc cho mi my nn.
- Cu ch HRC hoc cu dao t ng
bo v ngn mch cho mi in tr
si cacte (nu c trang b) v mch
iu khin.
- Bo v chng mt pha cho ng c
5.5 kW.
- Trm u ni cho ch th t xa cc
trng thi chy v bo s c.
- S u dy thng trc, chu thi
tit, gn trn hay bn cnh t in
iu khin.

Kim sot an ton: Lp t sao cho
hot ng ca mt thit b khng lm
tt cc thit b khc m khng trc tip
ph thuc vo hot ng ca n.
Thit b ngt in: trang b thit b ngt
in cho mi h thng theo tiu chun
AS/NZS 3000.
Kim sot ct p dn ngng: nu c
thit k, trang b b iu khin tc
qut dn ngng dng in t duy tr
ct p dn ngng thp nht mi iu
kin mi trng vn hnh.
Kim sot bm: Nu c thit k, trang
b van iu khin in v iu khin t
ng qu trnh bm.

4 EXECUTION 4 LP T
4.1 REFRIGERATION PIPEWORK 4.1 NG NG LNH
General
Conform to equipment manufacturers
recommendations for the refrigerant
used.
Tng qut
Tun th yu cu ca nh sn xut v
mi cht lnh s dng.
Design
Suction lines: Size for pressure drop
<1.0 K saturated suction temperature at:
- Scheduled supply air flow.
- Scheduled cooling coil entering
condition.
- Scheduled condenser air entering
condition.
- Unit manufacturers rated total
capacity, saturated condensing
temperature and saturated suction
temperature under the above
conditions.
Oil return: Size for oil return to
compressor. Where velocity for oil
return would result in the suction line
pressure drop exceeding pressure drop
limit, provide double suction risers.
Liquid lines: Size for pressure drop <
1.0 K saturated liquid temperature when
handling the manufacturers unit
Thit k
Tuyn ng ht: c kch thc cho
st p < 1.0 K nhit ht bo ha :
- Lu lng gi cp thit k.
- iu kin u vo dn coil lnh thit
k.
- iu kin gi vo dn ngng thit k.
- Tng cng sut thit b danh nh ca
nh sn xut, nhit ngng bo ha
v nhit ht bo ha di nhng
ch trn.

S hi du: c kch thc du hi v
my nn. Ni no tc hi du c th
dn n s st p trong ng ht vt
qu gii hn st p cho php, th phi
thc hin 2 on ng ht ng.
ng cht lng: c kch thc cho
st p < 1.0 K nhit cht lng bo
ha khi t cng sut danh nh thit b

PACKAGED AIRCONDITIONING
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 11 of 16 of B.22 18 September 2007
capacity under the operating
temperatures stated in the schedules.
nhit vn hnh thit k.
Layout
Install pipework in straight lines and
uniform grades without sags. Grade
horizontal hot gas lines and suction lines
at not less than 1 in 200 in the direction of
gas flow.
Location: When possible, run suction
and liquid lines inside common
insulation.
B tr
Lp t ng ng trn ng thng v
dc u khng b vng. (t nghing
ng ng gas nng trn phng ngang
v ng ht khng t hn 1:200 theo
chiu dng gas.
V tr: khi kh thi, t ng ht v ng
cht lng bn trong lp cch nhit
thng thng.
Pipe support
Provide hangers, brackets, saddles, clips,
etc., incorporating provisions for
adjustment of spacing, alignment,
grading and load distribution. Support
pipework from associated equipment or
building structure. Support valves,
strainers and major line fittings so that
no load is placed on adjacent tubes or
transmitted to them during operation and
maintenance.
Support type: Proprietary galvanized
channel section with clamps and hangers
sized match external diameter of pipe
being supported.
Uninsulated pipes: Clamp piping
supports directly to pipes.
Insulated pipe support:
- Spacers: Provide spacers at least as
thick as the insulation between piping
supports and pipes. Extend either side
of the support by at least 20 mm.
- Spacer material: Rigid insulation
material of sufficient strength to
support the piping and suitable for the
temperature application.
- Vapour barriers: For cold pipes apply
aluminium foil tape over the
circumference of the spacer to form a
vapour barrier.
- Metal sheathing: Provide a 0.55mm
thick zinc-coated steel band between
the aluminium foil tape and the
support, for the full width of the
spacer.
Treo ng
Trang b mc treo, bt treo, bt ch u,
kp, kt hp cc trang b iu
chnh khong cch, s ng trc,
dc v phn b ti. Treo ng t cc
thit b ph tr hoc t kt cu xy
dng. Treo van, lc Y v cc ph
kin ng ng chnh yu cho
khng c ti tc ng ln ng k cn
hoc lan truyn n ng trong khi vn
hnh v bo tr.
Chng loi thanh treo : thp hnh
trng km mua sn c kp v mc c
kch thc tng xng vi ng knh
ngoi ca ng c treo .
ng khng cch nhit: Kp chi tit treo
trc tip ln ng.
Treo ng cch nhit:
- Ming m: lp t ming m ti
thiu dy bng lp cch nhit gia
chi tit treo ng v ng. Ko di
ra hai bn ca chi tit ti thiu
20mm.
- Vt liu ca lp m: vt liu cch
nhit cng chu ni ng v ph hp
vi nhit s dng.
- Lp ngn m: i vi ng lnh, s
dng bng keo mng nhm dn ln
ton b chu vi ca ming m to
thnh lp ngn m.
- V bc kim loi: Cung cp di thp
m km dy 0,55mm gia lp bng
keo mng nhm v chi tit treo ,
trn ton b chiu rng ca ming
m.






Pipe support spacing table
Bng khong cch gia cc chi tit treo ng
Maximum spacing (m) / Khong cch ti a (m) Nominal pipe size, DN
Kch thc danh nh ng
Horizontal/ Phng ngang Vertical/ Phng ng
10 1 2

PACKAGED AIRCONDITIONING
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 12 of 16 of B.22 18 September 2007
Maximum spacing (m) / Khong cch ti a (m) Nominal pipe size, DN
Kch thc danh nh ng
Horizontal/ Phng ngang Vertical/ Phng ng
15, 20 1.5 2.5
25 2 3
32 2.5 3
40 2.5 4
50 3 4
65 3 4

Pipes
Standard: To AS/NZS 1571.
Temper designation: H temper. 0 temper
may be used for pipes < DN 25 or for
pulled bends or flared joints.
Pipe wall thickness:
- Pipes DN50: To AS1432 Type B.
- Pipes > DN50: 1.6 mm, minimum.
Deemed to comply for split systems
under 7.5kW cooling capacity: Split
system manufacturers standard pre-
charged piping kit.
ng
Tiu chun: theo tiu chun
AS/NZS 1571
ti: H. 0 c th s dng cho
ng < DN 25 hoc ng ko cong hoc
mi ni l u.
Chiu dy ng:
- ng DN 50: theo AS 1432 Type B.
- ng > DN 50: 1.6 mm, ti thiu.
Cho h thng hai mnh di 7,5kW
cng sut lnh: h ng np trc theo
tiu chun nh sn xut h thng hai
mnh.
Bends
Pulled bends: Form bends without
flattening or wrinkling using the correct
tool size for the pipe diameter.
Minimum inside radius: 3 pipe
diameters.
ng cong
Ko cong ng: to ng cong m khng
lm phng ng hay gp ng bng cch
s dng dng c c kch thc ng
vi kch thc ng.
Bn knh trong ti thiu: 3 ln ng
knh ng.
Pipe fittings
Copper alloy fittings: To AS 3688,
dezincification resistant, welded, brazed
or compression type only.
Preformed fittings: Preformed refrigerant
capillary line tees, bushes, couplings and
elbows. Wherever possible make
reductions at elbows, tees, line devices
or equipment connections with reducing
fittings, otherwise provide reducing
bushes or reducing couplings.
Compression fittings: Flareless twin
ferrule, torque free, mechanical grip
fittings which can be gauged using a
precision ground and hardened metal gap
inspection gauge.
Ph kin ng ng
Ph kin hp kim ng; theo tiu chun
AS 3688, khng b oxy ho kh km,
hn, hoc dp.
Ph kin to hnh trc: S dng ng
ba, ng lt, khp ni v khy ng mao
dn mi cht lnh to hnh trc. Ni
no c th gim khy, ng 3, thit b
ng ng hoc u ni thit b bng
ph kin gim, ngoi ra th s dng ng
lt hoc khp ni gim.
Ph kin dp nn: ph kin hai u
khng l, khng xon, cn rnh c th
o bng dng c o chnh xc v b
dng kim tra khe h lm bng kim
loi cng.
Brazed joints
General: Provide preformed capillary
fittings or form capillary unions by
expanding one pipe end. Prevent flux
and brazing alloy from entering pipes.
Use dry nitrogen to purge air from pipes
before brazing. During brazing, maintain
a flow of dry nitrogen through pipes to
prevent oxidation.

Brazing alloy: To AS 1167.1 Table 2 B4.
Hn thau
Tng qut: S dng ph kin mao dn
to hnh trc hoc racco mao dn
phnh rng mt u ng. Ngn nga
cht gy chy v hp kim hn i vo
trong ng. S dng nitrogen kh
kh gi trong ng trc khi hn. Trong
qu trnh hn, duy tr lung kh
nitrogen kh trong ng ngn nga s
oxy ha.
Hp kim hn: theo tiu chun
AS 1167.1 Table 2 B4. cha ti thiu

PACKAGED AIRCONDITIONING
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 13 of 16 of B.22 18 September 2007
15% min silver content.
Brazing alloy for jointing dissimilar
metals: To AS 1167.1 Table 1 A10. or an
alloy with an equivalent silver content
(minimum 34%).
15% bc.
Hp kim hn cc kim loi khng ng
nht: theo AS 1167.1 Table 1 A10.
hoc hp kim c thnh phn bc tng
ng (ti thiu 34%).
Sleeves
Provide pipe sleeves where pipes pass
through building elements.
Material: Copper or UPVC formed from
pipe sections. Do not use UPVC for fire
rated penetrations.
Sleeve thickness:
- Metal: 1mm.
- uPVC: 3mm.
ng lt
Lp t ng lt cho ng ni i ngang
qua cc kt cu xy dng.
Vt liu: ng hoc uPVC lm t cc
phn ca ng. Khng s dng uPVC
cho cc l xuyn ngn chy.
Chiu dy ng lt:
- Kim loi: 1 mm.
- uPVC: 3 mm.
Valves
Provide valves of the type and in the
location recommended by SAA HB40.1.
Van
Cung cp van c chng loi v v tr lp
t theo cc yu cu trong SAA
HB40.1.
Valve types
Service valves: Backseating type with
gasketed cap.
Solenoid line valves: Solenoid coil and
valve parts replaceable without
disturbing valve body or refrigerant
piping.
Chng loi van
Van cng tc: kiu ta sau c chp
m.
Van iu khin in lp trn ng: cun
dy v cc b phn ca van c th c
thay th m khng cn tho lp thn
van hay ng ng mi cht lnh.
4.2 CONDENSATE DRAINS 4.2 THOT NC NGNG T
General
Condensate drains: Provide trapped drain
lines to connect condensate trays to the
nearest building drain point.
Trap depth: To withstand > 2 times the
fan static pressure or 50mm whichever is
the greater.
Provide drains from:
- Each indoor coil.
- Each outdoor coil unless casing freely
drains to a roof or other location where
condensate and/or rain water will not
cause damage or pond.
- Each safety tray.
- Other moisture and rainwater
collecting areas.
Size: The greater of unit drain
connection size and DN 20.
Fall: Provide drains with uniform and
continuous fall.
Sealing: Seal drain pipes where they
penetrate casing.
Test: Test drains by pouring a measured
quantity of water into upstream end.
Tng qut
ng thot nc: Lp t ng thot c
xiphone ni mng hng n im thot
nc gn nht ca to nh.
Chiu su by xiphone: chu c > 2
ln p lc qut tnh hoc 50mm tu
theo ci no ln hn.
Lp t ng thot cho:
- mi dn coil lnh.
- mi dn coil nng tr khi thot t
nhin ra mi nh hoc v tr m nc
thot v/ hoc nc ma khng gy
h hng hoc ng vng.
- mi mng an ton.
- cc khu vc thu nc ma v hi m.
Kch thc: ci ln hn ca l thot
thit b v DN20.

dc: nghing u v lin tc.
Lm kn: nim kn ng thot ni i
ngang qua v my.
Th nghim: th nghim ng thot
bng cch mt lng nc xc nh
vo u trn.
Material
Copper: To AS 1432 Type B
UPVC: To AS/NZS 1477, installed to
AS 2032.
Trap material: Transparent, kink
Vt liu
ng: theo AS 1432 Type B
UPVC: theo AS/NZS 1477, lp t
theo tiu chun AS 2032.
Vt liu by nc: trong sut, ng

PACKAGED AIRCONDITIONING
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 14 of 16 of B.22 18 September 2007
resistant hose. chng xon.
4.3 SAFETY TRAY 4.3 MNG AN TON
Location
Provide a safety tray under indoor unit of
split systems if leaks or condensation
from these could cause nuisance or
damage to the building or its contents.
V tr
Lp t mng an ton bn di dn
lnh nu r r hoc ngng t t dn
lnh c th gy phin toi hoc h hng
cho to nh hay cc c bn trong.
Construction
Galvanized steel sheet, 1.2 mm thick
folded and stiffened, edges turned over
and with all joints sealed. Sides 50mm
high.
Size: Extend tray 150mm beyond unit
casing and any components that may
leak or drip condensation.
Drainage: Provide fall in tray and
provide drain at lowest point. Run drain
to visible waste.
Cu to
Thp trng km, dy 1,2mm gp m, c
gn tng cng v cc mi ni c lm
kn. Cnh cao 50 mm.
Kch thc: Lm mng rng hn
150mm t dn lnh v cc cu kin c
th r r hoc nhu nc ngng t.
Thot nc: Lp t mng dc v l
thot. Lp t ng thot n im thot
nc thi h, nhn thy.
4.4 REFRIGERATION PIPE
INSULATION
4.4 CCH NHIT CHO NG
NG LNH
Material
Thickness:
- Pipes DN 20: 13mm.
- Pipes > DN 20: 19mm.
Type: Chemically blown closed cell
nitrile rubber in tubular form.
Standard: To ASTM C534.
Physical properties:
- Maximum thermal conductivity: 0.04
W/mK at 0C.
- Moisture absorption: Non-
hygroscopic.
- Water vapour permeability:
0.065ng/Pa.m.s.
- Early fire hazard indices:
. Spread of flame index: 0.
. Smoke developed index: 3
(maximum).
Adhesive: Use only adhesive supplied by
the insulation manufacturer.
Vt liu
Chiu dy:
- ng DN 20: 13 mm.
- ng > DN 20: 19 mm.
Chng loi: cao su nitrile ng kn thi
ho cht dng ng..
Tiu chun: theo ASTM C534.
Tnh cht vt l:
- dn nhit ti a: 0.04 W/mK
0C.
- ht nc ng: khng hp th.
- ht hi nc: 0.065 ng/Pa.m.s.

- Ch s nguy chy sm:
. Ch s chy lan: 0.
. Ch s to khi: 3 (ti a).

Keo dn: ch s dng keo dn cung cp
bi nh sn xut cht cch nhit.
Protection
Insulation exposed to sunlight and
mechanical damage: Provide 0.6mm
zincanneal or 0.8mm aluminium
sheathing or run pipes in 0.8mm metal
trunking.
Insulation exposed to sunlight but not the
risk of mechanical damage: Provide
metal sheathing or trunking, or apply 2
coats of UV resistant paint supplied or
recommended by the insulation
manufacturer.
Bo v
Cch nhit l ra di nh nng v d b
va chm c hc: km cng 0,6mm hoc
v bc nhm 0,8mm hoc t bn trong
mng kim loi dy 0,8mm

Cch nhit l thin nhng khng b va
chm c hc: s dng v bc kim loi
hoc mng cha, hoc qut 2 lp sn
chng tia cc tm c cung cp hoc
yu cu bi nh sn xut cch nhit.
Installation
Insulate all refrigerant piping that may
sweat. Apply insulation un-slit where
possible. If slit, refix slit faces with
Lp t
Thc hin cch nhit cho tt c cc
ng ng mi cht lnh c th b ng
sng. Khng rch ng cch nhit ni

PACKAGED AIRCONDITIONING
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 15 of 16 of B.22 18 September 2007
adhesive applied to full area.

Timing: Leak test piping before
insulating joints, fittings and valves.
kh thi. Nu phi rch ng cch nhit,
dn kn b mt rch bng keo dn ton
b b mt rch.
Thi im: th nghim r r ng trc
khi bc cch nhit mi ni, ph kin v
van.
4.5 UNIT INSTALLATION 4.5 LP T THIT B
General
Supply all necessary components,
including but not limited to:
- Means of attachment to the structure.
- Anti-vibration mounting.
- Appropriate flexible connections.
- Trim and sealing around openings.
- Electrical connections.
- Drainage connections.
- Field connection of refrigerant lines in
split systems.
Alignment: Install units level, plumb and
to manufacturers recommendations.
Falls: Check that the condensate tray
falls comply with AS/NZS 3666.1 and in
particular that trays and sumps are
graded to the outlet to prevent moisture
retention.
Tng qut
Cung cp tt c cc ph kin cn thit,
bao gm nhng khng b gii hn bi:
Cc chi tit cn thit g lp ln kt
cu xy dng.
Chn chng rung
Cc u ni mm.
Ch vin v cht trt kn xung quanh
cc l.
u ni in
u ni thot nc
u ni ng mi cht lnh cho h
thng hai mnh.
dc: Kim tra rng mng hng
nghing theo tiu chun AS/NZS
3666.1 v c bit l mng v v nging
v pha l thot ngn nga nc
ng.
Outdoor equipment
Provide clearance around units for
condenser air flow and maintenance
access. Ensure discharge air does not
short-circuit to condenser intake.
Thit b t ngoi tri
Lp t thit b c khong trng xung
quanh cho lung khng kh thi vo
dn ngng v tip cn cho bo tr. m
bo rng kh thi ra khng b hi ngc
v u vo dn ngng.
Duct connections
Supply duct: Provide internal or external
flexible duct connection. Comply with
the Flexible connections clause in the
Ductwork worksection.
Return, outside air and condenser duct
connections: Provide external flexible
duct connection.
u ni ng gi
ng gi cp: S dng ng gi mm ni
bn trong hoc bn ngoi. Tun th
phn u ni mm trong chng ng
gi.
ng gi hi, gi ti v dn ngng: s
dng ng gi mm ni bn ngoi.
Vibration isolation
Suspended units: Metal spring or rubber-
in-shear isolation mountings with
25mm static deflection and 98%
isolation efficiency.
Floor mounted units: Neoprene waffle
pads.
Cch ly rung ng
Thit b treo: L xo kim loi hoc chn
cao su chu ko cch ly vi vng
tnh 25 mm v hiu sut cch ly 98%.
Thit b lp sn: tm lt neoprene kiu
t ong.
Fixings
Bolt units in place with minimum 4
anchors or suspension rods.

G lp
Bt bulon thit b vo v tr bng t nht
4 bulon neo hoc thanh treo.
4.6 COMMISSIONING
4.6 CHY TH & NGHIM THU
General
Packaged equipment: Common to the
manufacturer's recommendations and
record results.
Tng qut
Thit b nguyn b: ni chung theo yu
cu ca nh sn xut v kt qu ghi
nhn

PACKAGED AIRCONDITIONING
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 16 of 16 of B.22 18 September 2007
Refrigeration systems: Conform to the
recommendations of SAA HB40.1.

H thng gas lnh: ph hp theo
khuyn co ca SAA HB40.1.