AIR HANDLING PLANT

The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 1 of 14 of B.23 18 September 2007
AIR HANDLING PLANT H THNG THIT B X L
KHNG KH
1 GENERAL 1 TNG QUT
1.1 FUNCTIONAL DESCRIPTION 1.1 M T CHC NNG
The air conditioning equipment scope of
works covers the air handling units
(AHUs), primary air handling units
(PAUs) and fan coil units (FCUs) and
heat wheel.
Chng thit b dn lnh bao gm cc
cng tc thuc v dn lnh ln AHU &
dn lm lnh s b PAU, dn lnh nh
FCU, v bnh thu hi nhit.
1.2 CROSS REFERENCES 1.2 THAM CHIU CHO
General
Comply with the General Requirements
worksection.
Tng qut
Ph hp vi chng Nhng yu cu
chung.
Related worksections
Refer to the following worksections:
Mechanical General Requirements,
Chillers, Mechanical Piping,
Mechanical Insulation, Fans, Filters, Air
Coils, Ductwork, Mechanical Controls,
Mechanical Commissioning,
Switchboards, Switchboard Components,
Motor Starters, Power Cables, Electrical
Commissioning.
Nhng chng lin quan
Tham chiu n cc chng sau:
Nhng yu cu chung v c kh, H
thng my lm lnh nc Chillers, H
thng ngng c kh, Cch nhit
ng ng c kh, H thng Qut, H
thng Lc gi, Thit b dn lnh, ng
gi, iu khin c kh, Chy th v
nghim thu c kh, T in, Cu kin
trong t in, B khi ng moto, Dy
cp in, Chy th v nghim thu cc
h thng in.
1.3 STANDARD 1.3 TIU CHUN
Microbial control
To AS 4254
To AS/NZS 3666.1, AS/NZS 3666.2 and
the recommendations of SAA/SNZ
HB32.
Kim sot vi khun
Theo tiu chun AS 4254
Theo tiu chun AS/NZS 3666.1,
AS/NZS 3666.2 v cc yu cu ca
SAA/SNZ HB32.
1.4 INTERPRETATIONS 1.4 GII THCH
Definitions
Air handling plant: Proprietary and non-
proprietary pre-assembled plant and
prefabricated and site erected plant and
plenums. Includes room fan coil units
and air handling units.
Room Fan Coil Unit (FCU): Relatively
smaller units consisting of casing
housing coils and a direct drive fan
designed for mounting exposed within a
room. The casing may also house filters
and other items. Includes manufacturers
variations within a range of this type of
unit mounted concealed with or without
connected ducts.
Air handling unit (AHU): Larger units
consisting of a casing housing a fan and
coils. The casing may also house filters,
dampers and other items. Includes larger
sizes of units sometimes referred to as
Cc nh ngha
Cm thit b x l khng kh: dn lnh
nguyn b hoc lp rp sn v cc b
phn ch to sn hoc rp ti ch v
hp gi. Bao gm dn lnh x l khng
kh v dn lnh nh cho phng.
Dn lnh nh cho phng (FCU): thit
b nh hn tng i gm c hp cha
coil v mt qut dn ng trc tip
c thit k gn ni trong phng.
Hp cha c th c c b lc v cc chi
tit khc. Bao gm cc chng loi khc
nhau trong dy sn phm ny c loi
gn m ni hoc khng ni vi ng gi.

Dn lnh ln (AHU): thit b ln hn
bao gm hp cha qut v coil. Hp c
th cha c b lc, van gi v cc chi
tit khc. Bao gm cc thit b c cng

AIR HANDLING PLANT
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 2 of 14 of B.23 18 September 2007
fan coil units.
Primary air handling unit (PAU): Air
handling unit dedicated to the pre-
conditioning of 100% outside air.
sut ln i lc cng c gi l FCU.

Dn lm lnh s b (PAU): dn lnh
chuyn bit cho lm lnh s b 100%
gi ti bn ngoi.
2 QUALITY 2 CHT LNG
2.1 TESTS 2.1 TH NGHIM
Type Tests
All fan coil units must be type tested
(each size) in an independent testing
laboratory for scheduled performance,
not limited to noise, air flow, static
pressure, capacity, water flow, electrical
consumption, fan speed. The type tests
must be for the actual units
manufactured, from the same factory and
with the same physical components as
the offered units.
No fan coil units shall be considered
without such type tested data.
Otherwise, required for all coils (ARI) &
fans (BS or EN).
Th nghim mu
Tt c cc FCU phi c th nghim
mu cho mi mc cng sut ti phng
th nghim c lp v c tnh c lit
k, khng b gii hn bi n, lu
lng gi, p sut tnh, cng sut, lu
lng nc, tiu hao in nng, tc
qut. Th nghim mu phi thc hin
cho thit b thc t c sn xut, t
cng mt nh my v cng cc cu kin
nh l thit b cho bn.
Khng c FCU no c xem l khng
c nhng s liu th nghim mu nh
vy.
Mt khc, yu cu cho tt c cc coil
(ARI) & qut (BS hoc EN).
2.2 SUBMSSIONS 2.2 TRNH DUYT
General
Submit product & selection data for the
following:
- Air Handling Units
- Fan Coil Units
Include;
- Product data
- Dimensional drawings
- Coil selection data
- Fan selection data
- Acoustic performance from fan
$(induct)
- Acoustic performance of unit
$(breakout)
Submit product & selection data for the
following:
- Rotary heat wheel
Include
- Product data
- Dimensional drawings
- Performance data
- Psychrometric plot
- Acoustic performance
Tng qut
Trnh duyt ti liu k thut thit b v
s liu chn la cho:
- AHU
- FCU
Bao gm:
- Ti liu thit b
- Bn v kch thc
- D liu chn la coil
- D liu chn la qut
- c tnh n ca qut (induct)
- c tnh n ca thit b (breakout)

Trnh duyt thit b v d liu chn la
cho:
- Bnh thu hi nhit loi quay trn
Bao gm:
- Ti liu thit b
- Bn v kch thc
- D liu c tnh
- Gin m
- c tnh n

Sheet metal plenums
If providing proprietary ribbed
interlocking panel systems, submit
details of construction.
Hp kh bng tole tm
Trnh duyt chi tit cu to nu c cung
cp lp t h thng hp kh bng tole
tm c kha ln loi nguyn b ch to
sn.

AIR HANDLING PLANT
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 3 of 14 of B.23 18 September 2007
3 PRODUCTS 3 THIT B
3.1 GENERAL 3.1 TNG QUT
Equipment enclosures
Construction: Assembled and reinforced
to prevent flexing and drumming.
Provide for removal of major
components.
Access: Provide access for inspection
and maintenance.
- Access panels: Readily removable
with positive re-useable fasteners and
soft gaskets which provide an airtight
seal.
Insulation: Insulate enclosures to prevent
external surface condensation under
operational conditions.
Outdoor location: Provide enclosures,
materials and finishes which are
corrosion-resistant, and weatherproof if
necessary.
V my
Cu to: lp rp v c gia c trnh
cong vn v n. C th tho ri cc cu
kin chnh.

Li tip cn: Cung cp li vo cho cng
tc kim tra v bo tr.
- Np thm: loi c th tho lp c
bng cc ph kin cng cp c th ti
s dng v cc m mm lm kn
gi.
Cch nhit: cch nhit cho v my
ngn nga ng sng b mt bn
ngoi ch vn hnh.
Lp t ngoi tri: Cung cp v my,
vt liu v b mt hon thin chng n
mn, v chng nc nu cn.
Condensate trays
General: Provide a primary tray under
each cooling coil section, extending
downstream to collect water carry over,
and under components on which
condensation can occur.
Material: Corrosion-resistant.
Insulation: Insulate trays to prevent
condensation internally and on external
surfaces of the unit enclosure, under
operational conditions.
Condensate drains: Connect condensate
trays to nearest drain points by means of
trapped minimum DN 25 drain lines for
FCUs and minimum DN 40 drain lines
for AHUs. Allow for suitably sized
condensate drains whether shown on the
drawings or not.
Mng hng nc ngng t
Tng qut: cung cp mt mng theo
my di mi phn coil lnh, ko di
xui dng hng ht nc trn, v
bn di cc b phn no c th c
ng sng.
Vt liu: chng n mn.
Cch nhit: Bc cch nhit cho mng
ngn nga ng sng bn trong v
trn b mt ngoi ca v thit b ch
vn hnh.
Thot nc ngng t: Ni mng hng
ngng t n im thot nc gn nht
bng ng xiphone ng knh ti thiu
DN 25 cho FCU v DN 40 cho AHU.
Gi trng thu bao gm cc chi ph
thay i cc kch thc ng thot
khc cho thch hp khi c hoc khng
c th hin trn bn v.
Construction
Provide guards on belt driven fans
handling > 2000 L/s.
Leakage: Seal unit so no air leaks can be
felt or detected using a smoke pencil
under maximum system operating
pressure.
Finish: Not less than the standard
achieved with the paint system for zinc-
coated steel in the General requirements
worksection.
Cu to
Cung cp khung che cho qut dn ng
bng dy ai > 2000 L/s.
R r: Lm kn thit b sao cho khng
c r r gi c th cm thy hay pht
hin c bng bt ch khi p sut
lm vic ti a ca ca h thng.
Hon thin: Khng thp hn tiu chun
t c bng cch sn h thng thp
m km trong chng Nhng yu cu
chung.
Condensation control
Take all steps necessary to prevent
condensation on the outside of units
under any operating conditions
including:
- Insulate drain trays.
- Eliminate cold bridging.
Kim sot ngng t
Thc hin tt c cc cng vic cn thit
ngn nga ng sng trn b mt
ngoi ca thit b mi ch vn
hnh, bao gm:
- Cch nhit cho mng hng.
- Kh cu dn nhit.

AIR HANDLING PLANT
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 4 of 14 of B.23 18 September 2007
Casing stiffness
Maximum deflection of casing: Under
maximum internal-external pressure
difference, provide casings having the
lesser of
- maximum deflection permissible in
AS 4254 Section 4; and
- maximum deflection consistent with
correct operation and airtightness of
the air handling unit.
Gia c v my
vng ti a ca v: chnh lch p
sut trong ngoi ti a, cung cp v
my c vng nh hn theo
- lch ti a cho php theo
AS 4254 phn 4; v

- lch ti a m bo vn hnh tt
v kn kh ca ca dn lnh.
Coil separation
Units > 1000L/s: Provide 300mm
space between heating and cooling coils.
Provide access panel or door into space
between coils.
Tch ring cc coil
Thit b > 1000 L/s: m bo khong
cch 300 mm gia coil lnh v coil
nng. Lp t np thm hoc ca thm
vo khng gian gia cc coil.
Multizone units
If heating coils are not provided, provide
a perforated plate in the hot deck with
pressure drop approximately equal to
that of the cooling coil.
Thit b phc v nhiu phng
Nu coil nng khng km theo thit b,
lp t mt tm c l trong khoang
nng vi tr lc xp x bng tr lc ca
dn lnh
Coil access
Arrange coils so that both faces of each
coil are easily accessible for inspection
and cleaning. Provide suitably located
access panels and doors.
Li tip cn coil
Coil phi c sp xp sao cho vic ra
vo d dng c hai mt ca mi coil
kim tra v lau chi. Ca ra vo phi
t v tr thch hp
Sealants
Standard: To AS 4254 clause 2.2. Use
only sealants that do not foster microbial
growth.
Cht trt kn
Theo tiu chun AS 4254 mc 2.2. Ch
c dng cht trt kn loi khng to
mi trng cho vi khun pht trin
3.2 AIR HANDLING UNITS 3.2 DN LNH LN
General
General: Provide units consisting of
coils, piping, supply air fan, filters,
accessories and electrical connections,
mounted within an insulated enclosure.
Configuration: draw through coil, single
zone.
Tng qut
Tng qut: cung cp thit b bao gm
coil, ng ng, qut cp gi, phin lc,
ph kin v hp ni in. Lp trong
mt v cch nhit.
Cu hnh: coil loi ko ra c, n l
Enclosures
General: sectional or modular
construction.
Outer material: Galvanised sheet steel,
powder coated.
Inner material: Galvanised sheet steel,
powder coated.
Casing: With respect to EN1886
- Mechanical stability class 1A
- Casing leakage classe B
- Filter bypass leakage F9
- Thermal isolation T2
- Thermal bridging factor TB2

Access: Removable panels to provide
access to all components. Access panels
shall be secured with sash catches or
hexagonal socket bolts. Access to
commonly accessed items such as filters
V my
Tng qut: kt cu tng phn hay nhiu
phn ni li
Cht liu mt ngoi: bng thp tm
trng km, sn tnh in.
Cht liu mt trong: bng thp tm
trng km, sn tnh in.
Casing: With respect to EN1886
- Mechanical stability class 1A
- Casing leakage classe B
- Filter bypass leakage F9
- Thermal isolation T2
- Thermal bridging factor TB2

Li ra vo: c ca loi tho lp c
tip cn n tt c cc b phn. Ca
ra vo phi c gi bng cht ca hay
vt lc gic. Ca ra vo cc b phn
thng thng nh phin lc phi c tay

AIR HANDLING PLANT
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 5 of 14 of B.23 18 September 2007
shall be via metallic door handles.
Duct connections: Provide spigots or
flanged connections.
ca kim loi
u ni ng gi: bng cht ni hay
bng mt bch
Fans
Construction: as per worksection Fans.
Delivery: Scheduled capacity plus 5% at
scheduled static pressure.
Type: Double width, double inlet, multi-
blade, backward inclined centrifugal
aerofoil blade type.
Motors: Fan motors shall be selected at
120% of the fan mechanical power.

Belt drive: Fans shall be driven by a
minimum of 2 belts. A belt guard shall
be fitted. Motor slide rails to allow belt
adjustment. Drives to be multiple
matched V-belt, adjustable ratio type
rated at 1.5 times the motor wattage.
Isolation: Fan and motors to be mounted
on spring isolators of at least 40mm
static deflection. Fan discharge to be
connected to the enclosure discharge via
a fire rated flexible connector.
Variable speed drives: Where the fan
motor is to be driven from a variable
speed drive or other electronic speed
controller, ensure that the motor is
compatible to operate with the selected
drive or controller.
Note fan discharge velocity limitations.
Qut
Kt cu: nh m t trong phn Qut
Cng sut: cng sut danh nh cng
5% p sut tnh danh nh
Loi: bn i, hai ng vo, nhiu cnh,
cnh loi ly tm dc v pha sau

ng c: ng c phi c chn
120% cng sut c ca qut
Dy curoa dn ng: qut phi c
dn ng bng t nht hai dy curoa.
ng c phi lp trn thanh trt c
th cng chnh dy curoa. Pulley phi l
loi nhiu rnh ph hp dy curoa loi
V, t s iu chnh l 1.5 ln cng sut
in nng ng c.
Chng rung: qut v ng c phi c
lp trn l xo chng rung t nht l
40mm vng tnh. u ni thi ra
ca qut phi c ni bng ni mm
loi chu la
B iu tc bng tn s: nu ng c
qut c dn ng t b iu tc bng
tn s hay b iu khin tc bng
in t khc, phi bo m ng c
c tng thch hot ng vi b
iu tc
Lu : tc thi ra ca qut c gii
hn
Cooling coils
Construction: as per worksection Air
Coils.
Performance: Scheduled capacity.
Maximum 400 fins/m.
Minimum 4 rows
2.5m/s maximum face velocity.
Coil lnh
Kt cu: ging nh phn Coil khng
kh
Hiu sut: theo danh nh
Nhiu nht l 400 fin/m
Nh nht l 4 hng
Tc b mt ln nht 2.5 m/s
Electric reheat
General: Sheathed in steel or nickel
alloy, with brazed spiral steel fins.

Frames: Assemble elements in a
galvanized steel frame with terminal
connections contained in an enclosed
terminal box. Line frames with calcium
silicate or other fire rated product.
Heating section: Install to allow access
to the terminal box and removal of the
assembly without disturbing other
components.
Fin rating: < 20W/m.
High temperature limiting thermostats:
manual reset type with external
adjustable dial having range 60 120
o
C.

Air pressure switch: operate in series
in tr gia nhit
Tng qut: bc trong hp kim thp hay
nikel, c cnh tn nhit dng xoc c
bng thp ph ng thau
Khung: in tr c t trong mt
khung thp trng km, cc u ni in
lp trong hp u ni kn. Vin khung
bng calsium silicate hay sn phm
chu la khc.
Phn gia nhit: c lp t cho
php tip cn hp ni in v tho lp
cc ph kin m khng nh hng n
cc b phn khc
H s truyn nhit cnh: < 20 W/m.
Cng tc nhit chng qu nhit: loi
reset bng tay vi nm xoay chnh bn
ngoi c dy chnh nhit t 60-
120
0
C
Cng tc p sut kh: hot ng ni tip

AIR HANDLING PLANT
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 6 of 14 of B.23 18 September 2007
with an air pressure switch.
Electrical power supply: 3 phase
vi mt cng tc p sut kh
Ngun in: 3 pha
Filter Section Box
To be provided on all AHUs by the AHU
manufacturer. For filter details refer to
the worksection Filters.
Hp cha lc gi
c lp t cho tt c AHU do cng
nh ch to AHU. Tham kho chng
Phin lc bit thm chi tit
Mixing Section Box
Where mixing boxes are required, to be
by the AHU manufacturer. Note dampers
to be opposed blade type as per
ductwork specification.
Hp trn
Khi cn thit c khoang ha trn, phi
do nh ch to AHU sn xut. Lu
van gi phi l loi cnh i nhau nh
m t trong phn qui nh k thut
ng gi.
Sound power levels
Sound power levels shall not exceed the
scheduled values.
n
n khng c vt qu gi tr cho
php
Instrumentation points
Provide for each section a means of
measuring temperature and pressure
using testing & commissioning
instruments. Such test points may be
field installed, however are to be
provided by the AHU manufacturer and
their installation shall not diminish the
warranty on the units.
im lp thit b o c
Lp t mi b phn mt l ch cho
vic gn thit b o c nhit v p
sut dng cho mc ch th nghim &
chy th v nghim thu. Nhng im
th ny c th thc hin cng trng,
tuy nhin phi c cung cp bi nh
ch to AHU v vic lp t chng
khng lm gim vic bo hnh thit b.
3.3 PRIMARY AIR HANDLING
UNITS
3.3 DN LM LNH S B
As per Section 3.2 Air Handling Units,
though coils shall have copper tubes and
copper fins.
Ging nh mc 3.2 dn lnh ln, cun
coil phi lm t ng ng v cnh tn
nhit bng ng.
3.4 FAN COIL UNITS 3.4 DN LNH NH
General
General: Provide units consisting of
coils, piping, supply air fan, filters,
accessories and electrical connections,
mounted within an insulated enclosure.
Configuration: draw through coil, single
zone.
Tng qut
Tng qut: cung cp dn lnh bao gm
coil, ng ng, qut cp gi, phin lc,
ph kin v hp ni in. Lp trong
mt v cch nhit.
Cu hnh: coil loi ko ra c, n l.
Fan Coil Units - Horizontal Concealed
Type
To be provided with discharge collar and
connected to discharge grille by means
of flexible, fire retardant, pressure tight
collar, or fiberglass transition duct, or
acoustically lined galvanised sheet metal
duct with a flexible connection between
duct and fan coil housing. Acoustical
lining and fiberglass duct shall be NFPA
Class 1 or equal.
Installation to include control valve(s),
shut off valves with 16 mm O.D.,
threaded connections and automatic air
vents on each coil.



Dn lnh nh - Loi m trn nm
ngang
c cung cp vi ming thi dng
trn v c ni ti ming gi bng
ng mm, chu la, ai sit, hay ng
gi bng si thy tinh, hay ng gi
bng tole trng km c cch m qua
phn ni mm gia ng gi v khoang
dn lnh. ng gi cch m v cch
nhit bng si thy tinh phi theo tiu
chun NFPA class 1 hay tng ng.
Vic lp t bao gm van iu khin,
van ng m c ng knh ngoi
16mm, ni ren v c van t ng x kh
trn mi coil
Enclosures V my

AIR HANDLING PLANT
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 7 of 14 of B.23 18 September 2007
General: sectional or modular
construction.
Outer material: Galvanised sheet steel,
powder coated.
Inner material: Galvanised sheet steel,
powder coated.
Insulation: Polyurethane 19mm
thickness, or the supplier to guarantee no
condensation problems at wet bulb 25
deg C.
Frame: Insulated and designed to avoid
cold bridging The supplier to guarantee
no condensation problems at the design
wet bulb plus 1 deg C.
Access: Removable panels to provide
access to all components. Access to
commonly accessed items such as filters
shall be via metallic door handles.
Duct connections: Provide spigots or
flanged connections.
Tng qut: kt cu tng phn hay nhiu
phn ni li
Cht liu mt ngoi: bng thp tm
trng km, sn tnh in.
Cht liu mt trong: bng thp tm
trng km, sn tnh in.
Cch nhit: bng Polyurethane dy
19mm, hay nh cung cp phi m bo
khng xy ra ng sng nhit
bu t 25
0
C.
Khung: khung c cch nhit v thit
k trnh cu nhit. Nh cung cp
phi m bo khng xy ra ng sng
nhit bu t 1
0
C.
Li ra vo: c np loi tho lp c
ra vo tt c cc b phn. Ca ra vo
cc b phn thng phi tip cn nh
phin lc phi c tay ca kim loi.
Phn ni ng gi: bng u ni hay
bng mt bch.
Fans
Construction: as per worksection Fans.
Delivery: Scheduled capacity plus 5% at
scheduled static pressure.
Type: Double width, double inlet, multi-
blade, forward curved centrifugal type.
Double fan wheels to be statically and
dynamically balanced, and resiliently
isolated at all contact points with
housing.
Motors: Fan motors shall be selected at
120% of the fan mechanical power. 3-
speed (Off-Low-Medium-High) split
capacitor type with thermal overload
protection. Permanently sealed,
lubricated bearings
Drive: Fans shall be direct driven.
Isolation: Fan and motors to be mounted
on rubber isolators of at least 5mm static
deflection. Enclosure discharge to be
connected to ductwork via a flexible
connector.
Qut
Kt cu: nh m t trong phn Qut.
Cng sut: cng sut danh nh cng
5% p sut tnh danh nh.
Loi: bn i, hai ng vo, nhiu cnh,
cnh loi ly tm dc v pha trc.
Bnh qut phi c cn bng ng v
tnh, v c cch ly n hi nhng
im tip xc vi khoang qut

ng c: ng c phi c chn
120% cng sut c ca qut. Ba tc
(Tt Chm Trung bnh Cao), t
chia v c phn bo v qu nhit.
trc c bi trn v hon ton kn.
Dn ng: qut c dn ng trc
tip.
Chng rung: qut v ng c phi c
lp trn cao su chng rung t nht l
5mm vng tnh. u ni thi ra ca
qut c ni vi ng gi bng ni
mm.
Cooling coils
Construction: as per worksection Air
Coils.
Performance: Scheduled capacity.
Maximum 400 fins/m.
Minimum 3 rows
2.5 m/s maximum face velocity.
Selection: select FCU to exceed air
volume initially at high speed, and
cooling capacity at medium or low fan
speed (so that they are oversized).




Coil lnh
Kt cu: ging nh phn Coil khng
kh
Hiu sut: theo bng lit k.
Nhiu nht l 400 fin/m
Nh nht l 3 hng
Tc b mt ln nht 2.5 m/s
Chn my: chn FCU vt qua lu
lng gi ban u tc cao v cng
sut lnh ti tc qut trung bnh v
thp (v vy my l ln hn)
Filter Section Box Hp cha lc gi

AIR HANDLING PLANT
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 8 of 14 of B.23 18 September 2007
To be provided on all FCUs by the FCU
manufacturer. To be at minimum 25 mm
permanent cleanable aluminium mesh, or
12 mm permanent NFPA class 1 foam
pad, or Panel Filter as per work section
Air Filters.
c lp t cho tt c FCU do nh
ch to FCU. Li nhm phi l t nht
25mm c nh c th chi ra c
hay l tm foam 12mm c nh theo
NFPA class 1, hay l tm lc nh trong
chng Phin lc.
Controls
To be equipped with a quiet operating,
two way hydraulic, or electric valve(s)-
3-speed (Off-Low-Medium-High) fan
control button and a heat/cool selector
where required.
iu khin
c trang b vi van hai ng loi hat
ng m bng in hay thu lc.
nhng ni c yu cu, lp t nt
iu khin 3 tc (Tt Thp
Trung bnh Cao) v cng tc chnh
nng / lnh.
Dehumidification
Generally dehumidification shall be
provided by the PAUs.
Kh m
Mt cch tng qut, vic kh m c
thc hin bi PAU
Electric Reheat
Units to have:
- Factory installed magnetic contactor
- Air flow switch
- High temperature cutout with
automatic reset
- Coils shall be of low surface
temperature type
in tr gia nhit
Thit b phi c:
- B khi ng t lp rp ti xng
- Cng tc dng gi
- B bo v qu nhit c reset t ng

- Coil phi l lai c nhit b mt
thp
Sound power levels
Sound power levels shall not exceed the
following.
n
n khng c vt qu chi tit
nh bng sau

Max allowable dB-Lw re 10
-12
watts in duct sound power level
n cho php cc i dB-Lw re 10
-12
watts trong ng gi
Frequency
Tn s
125 250 500 1k 2k 4k
Design noise criteria / Tiu chun n thit k
Fan Coil units less than 1000 CMH / Dn lnh nh hn 1000 CMH
Medium speed
Tc trung bnh
59 55 49 46 44 42
High speed
Tc cao
62 58 52 49 47 45
Fan coil units greater than 1000 CMH / Dn lnh ln hn 1000 CMH
Medium speed
Tc trung bnh
63 59 53 50 48 46
High speed
Tc trung bnh
66 62 56 53 51 49

3.5 COIL SUPPORTS 3.5 CHI TIT COIL
General
General: Support coils using one of the
following:
- The internal support frame of
conditioners.
- Baffle plates around the coils.
- Prefabricated, predrilled, hot dipped
galvanized steel frames.
Tng qut
Tng qut: chi tit coil dng mt
trong cc phng php sau:
- Khung bn trong ca thit b iu
ha khng kh
- Tm ngn xung quanh coil
- Khung thp ch to sn khoan l c
m km nhng nng

AIR HANDLING PLANT
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 9 of 14 of B.23 18 September 2007
Coil banks: Provide coil banks if coil
sizes exceed maximum limits.
Dissimilar metals: Provide neoprene
gaskets to separate the mating surfaces
of dissimilar metals. Provide non-
metallic top hat washers in enlarged
holes under nuts and bolts connecting
dissimilar metals.

coil: cung cp nu kch thc
coil vt qu gii hn cho php.
Kim lai khng ng dng: lp ron
neoprene ngn cch nhng v tr tip
xc b mt gia cc kim lai khng
ng dng. Lp t vng m c ph
vt liu phi kim loi trong l rng hn
bn di v bulon v ai c ni kim
lai khng ng dng.
3.6 MOTORISED DAMPERS 3.6 VAN GI IU KHIN BNG
MT
Construction
Comply with the Volume control
dampers clause in the Ductwork
worksection, and the following:
- Side seals: Aluminium or stainless
steel.
- Blade tip seals: Neoprene or silicone
rubber.
- Leakage: 25 L/s.m2 at 1.5 kPa
pressure differential.
- Bearings: Sealed-for-life ball bearings
only.
Mounting: Sufficiently rigid to prevent
flexing or distortion of the frame or
ductwork during operation.
Operation: If two sets of dampers are
connected to a single motor, provide
linkages that allow either damper to be
adjusted without affecting the other.
Cu to
Tun theo mc Van iu khin lu
lng trong chng ng gi, v theo
cc iu sau:
- Kn mt: nhm hay thp khng r

- Kn nh trc cnh: neoprene hay cao
su silicone
- R r: 25 L/s.m2 chnh lch p
sut 1.5 kPa
- trc: ch s dng bi loi kn.
Lp t: chc chn chng li s un
hay xon ca khung hay ng gi trong
khi hat ng.
Hat ng: nu hai b van gi c ni
ti mt ng c, lp t b ni cho
php mi van c iu chnh m
khng khng nh hng ti van kia.
3.7 COOLING COIL
CONDENSATE TRAYS
3.7 MNG NC NGNG T
CHO COIL LNH
Tray design
Design trays to:
- Collect condensate and allow
complete drainage so that no water
remains inside the tray when the fan
has been off for 5 minutes.
- Extend under upstream and
downstream sides of the coil.
- Extend under uninsulated piping and
fittings.
- Permit inspection of all parts of coils
and trays. Provide radiused corners to
facilitate cleaning.

Thit k mng
Mng c thit k :
- Thu nc ngng t v cho php thi
ht nc bn trong mng sau khi qut
dng c trong 5 pht.

- Ko di mng ti qua di phn u
v phn ui ca coil.
- Ko di mng ti qua di phn ng
v ph kin khng cch nhit
- Cho php kim tra tt c cc phn ca
coil v mng. Mng phi c cc gc bo
trn d dng v sinh.
Material
Fabricate wetted parts from one of the
following and seal all joints:
- Copper alloy sheet designation
C11000.
- Aluminium to AS/NZS 1734.
- Stainless steel sheet grade 304L.
-
Vt liu
Ch to nhng phn b t t mt trong
nhng vt liu sau v lm kn tt c
nhng ch ni:
- Tm hp kim ng C11000
- Nhm theo AS/NZS 1734
- Thp khng r tm 304L
Tray insulation Cch nhit mng

AIR HANDLING PLANT
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 10 of 14 of B.23 18 September 2007
Insulate trays using non-hygroscopic
material to achieve same R-value as
specified for the unit casing.
Cch nhit mng dng vt liu khng
ht m t c gi tr R theo tiu
chun cho khoang thit b
Stacked coils
General: Provide each coil with a tray
and run a minimum DN 40 drain pipe
from the upper tray to the lowest tray.
Lowest tray construction: Protect from
mechanical damage to maintain
complete drainage.
Thot nc Coil
Tng qut: lp t mi coil mt mng
v lp ng nh nht l D40 that
nc t mng trn xung mng di.
Mng bn di: bo v chng va chm
c hc duy tr vic that nc hon
ton.
Tray installation
Fixing: Locate trays against coil support
channels. Provide continuous silicone
sealant around tray bases between the
base and the floor.
Flashing: Provide 0.6 mm stainless steel
flashing:
- Between the tray upstand and the coil
frame, falling towards the tray.
- Between the tray upstand and the
casing, falling towards the tray.
Lp t mng
C nh: t mng trn dn khung
coil. Trt silicone lin tc quanh chn
mng v y mng

Tm ngn nc: lp t tm ngn bng
thp khng r dy 0.6mm:
- Gia thnh ng ca mng v khung
coil, dc xung v pha mng
- Gia thnh ng ca mng v v, dc
xung v pha mng
Secondary condensate drain pans
Provide insulated secondary condensate
drain pans under all fan coil units and all
valves above suspended ceilings, or
above passageways.
Mng hng ngng t th cp
Lp t mng ngng t cch nhit th
cp di tt c dn lnh nh v tcac cc
van lp trn trn treo, hay trn hnh
lang.
3.8 HEAT WHEELS 3.8 BNH TRAO I NHIT
General
General: Provide units consisting of
wheel, controls, motor, accessories and
electrical connections, mounted within
an insulated enclosure.
Tng qut
Tng qut: thit b bao gm bnh, phn
iu khin, ng c, ph kin v t ni
in, c treo trong khoang cch nhit
Substrate
Aluminium foil.
Lp nn
Tm l nhm
Desicant
Water molecule selective and non-
migratory.
Non-masking porous binder.
Capable of sensible and latent heat
recovery, matching the sensible heat
ratio required of the application.
Demonstrate that structure of wheel is
suited for latent/sensible heat ratio of the
application.
Lifetime: 10 years.

Cht lm kh
C tnh chn la phn t nc v
khng dch chuyn.
L cht dnh xp khng to mng che
C kh nng thu hi nhit hin v nhit
n, chuyn thnh nhit hin. t l theo
yu cu ng dng.
Chng minh c l kt cu ca bnh
th thch hp cho t l nhit n / nhit
hin ca ng dng
Tui th: 10 nm
Enclosure
General: sectional or modular
construction.
Outer material: Galvanised sheet steel,
powder coated.
Access: Removable panels to provide
access to all components. Access to
commonly accessed items such as filters
shall be via metallic door handles.
Duct connections: Provide spigots or
V my
Tng qut: kt cu tng phn hay nhiu
phn ni li
Cht liu mt ngoi: bng thp tm
trng km, sn tnh in.
Li ra vo: c tm tho lp c tip
cn tt c cc b phn. Ca ra vo cc
b phn thng xuyn tip cn nh
phin lc phi c tay ca kim loi.
Phn ni ng gi: bng u ni hay

AIR HANDLING PLANT
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 11 of 14 of B.23 18 September 2007
flanged connections. bng mt bch
Rotor
Rotate at lower than 25 rpm.
The media shall be cleanable with
compressed air, or light detergent,
without degrading the heat recovery.

Rto
Quay tc thp hn 25v/p
Phn trao i nhit phi l lai c th
v sinh c bng kh nn, cht ty nh
m khng lm suy gim cht lng
vic thu hi nhit.
Purge
Field adjustable purge mechanism,
allowing a portion of potential supply air
to purge exhaust air.
B kh lm sch
C cu c th iu chnh c, cho
php mt phn ca nng lng khng
kh cp kh sch kh ht.
Seals
Face and radial seals: 4 pass non-contact
labyrinthe.
Lm kn
m kn b mt v hng tm: 4 rnh
khng tip xc nhau.
Efficiency
Latent transfer: Minimum 80%
Sensible transfer: Minimum 80%.
Hiu qu
Chuyn nhit n: t nht 80%
Chuyn nhit hin: t nht 80%
Filters
Air entering heat wheel from outside air
and from exhaust air to be filtered to heat
wheel manufacturers recommendations,
or to scheduled performance, whichever
is the minimum.
B lc
Khng kh vo b bnh thu hi nhit t
khng kh bn ngai v khng kh thi
ra c lc theo tiu chun ca nh ch
to bnh thu hi nhit hay theo hiu
sut trong bng lit k, theo iu no l
t nht
3.9 AIR LEAKAGE 3.9 R R GI
Baffle plates
Close the space between the coil frames,
fans and filters and the surrounding
structure or equipment, with baffle
plates.
Fabricate baffle plates from:
- Copper alloy designation C11000.
- Galvanized steel to coating class
G2/Z275.
- Aluminium to AS/NZS 1734.
- Grade 304L stainless steel.
- Sandwich panel material complying
with Casings and plenums -
Sandwich panel.
Tm ngn
Dng tm ngn che kn khong khng
gia khung coil, qut v phin lc v
xung quanh kt cu hay thit b.

Tm ngn c ch to t:
- Hp kim ng C11000.
- Thp trng km t G2/Z275

- Nhm theo AS/NZS 1734
- Thp khng r 304L
- Tm c kt cu nhiu lp tng thch
vi mc V v khoang tm c kt
cu nhiu lp
Sealing
Seal gaps between coils and surrounding
structure or equipment.
Lm kn
Lm kn khong h gia coil v kt cu
xung quanh hay thit b
3.10 ACCESS DOORS AND
PANELS
3.10 CA THM V NP THM
Location
Provide an access door or panel in each
section of the air handling units to which
access is required for maintenance,
inspection or removal of components.
Alternative: Provide removable panels
the full height of the unit instead of
doors where access is required only for
removal of coils or fans.
V tr
i vi cc b phn c yu cu bo tr,
kim tra, hay tho lp sau ny, lp t
mt ca hay np thm cho mi b phn
.
Chn la khc: cung cp np tho ri
c c chiu cao bng thit b thay
cho ca ni ch cn tho lp coil hay
qut.
Sizes Kch thc

AIR HANDLING PLANT
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 12 of 14 of B.23 18 September 2007
Minimum clear openings:
- Access panels for personnel access:
450 x 600mm.
- Access panels for hand access: 200 x
300mm.
- Doors: 1350mm high x 600mm or
larger if necessary to permit safe
removal of equipment inside the
section.
Kch thc nh nht phi nh sau:
- Np thm cho ngi: 450 x 600 mm
- Np thm cho cnh tay: 200 x 300
mm

- Ca: 1350 mm cao x 600 mm hay ln
hn nu cn thit cho php tho lp
an ton thit b bn trong phn
Access panels
Construction and insulation: To match
unit casing or comply with the Access
panels clause in the Ductwork
worksection.
Frames: Provide rigid matching
galvanized steel frames securely attached
to the duct. Do not protrude any part of
the panel or frame into the airstream.
Seals: Silicone rubber or soft neoprene
gaskets mechanically fixed to either the
panel or the frame provide an airtight
seal against the operating pressure when
latched in the closed position.
Latches: Wedge type sash latches.
Number of latches:
- For personnel access: 4.
- For hand access: 2.
Handles: Provide a handle on each panel
for personnel access.
Np thm
Kt cu v cch nhit: phi ging vi
v thit b hay tng thch vi mc
Np thm trong chng ng gi

Khung: lp t khung thp trng km
gn chc chn vo ng gi. Khng
nh ra bt c phn no ca np hay
khung vo pha ng gi.
Lm kn: dng silicone hay ron
neoprene mm dn ln np hay khung
lm kn kh trong trng hp c
p sut khi cht ng np thm.

Cht ci: cht nm dng ko trt
S cht ci:
- Cho ngi ra vo: 4.
- Cho tay ra vo: 2.
Tay nm: lp t mt tay nm trn mi
np cho ngi ra vo.
Doors
General: Provide rigid, reinforced access
doors hinged so that internal air pressure
holds doors closed.
Door swing: Against air pressure.
Frames: Rigid galvanized steel or
extruded aluminium.
Door hardware: Provide 2 proprietary
clamping-type latches with permanently
attached handles that can be operated
from both the inside and the outside of
the door.
Seals: Silicone rubber or soft neoprene
gaskets mechanically fixed to the door to
provide an airtight seal when latched
closed.
Ca
Tng qut: lp t mt ca thm c bn
l chc chn p sut khng kh bn
trong s gi ca v tr ng.
Chiu quay ca ca: ngc vi p lc
kh.
Khung: bng thp trng km cng hay
nhm nh hnh.
Ph kin ca: lp t 2 cht ci dng
nm loi nguyn b ch to sn, c tay
nm bt c nh c th ng m t
c pha bn trong ln bn ngoi ca
ca.
Lm kn: dng silicone hay neoprene
mm dn quanh ca lm cho ca kn
kh khi ci kha ca.
3.11 SERVICE LIGHTS 3.11 N CHIU SNG
General
Provide waterproof fluorescent
luminaires in each compartment with an
access door or removable panel:
- Air handling units <500 L/s: Not
required.
- Air handling units 500 L/s <
10,000L/s: One 18 watt compact
fluorescent luminaire.
- Air handling units 10,000L/s: One
36 watt fluorescent luminaire or two
Tng qut
Lp t n hy quang chng thm
nc trong mi b phn vi mt ca
hay np thm c th tho lp c:
- Dn lnh ln < 500 L/s: khng yu
cu
- Dn lnh ln 500 L/s < 10,000 L/s:
mt bng hunh quang compact 18w
- Dn lnh ln 10000 L/s: mt bng
hunh quang 36w hay hai bng hunh
quang compact 18w

AIR HANDLING PLANT
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 13 of 14 of B.23 18 September 2007
18 watt compact fluorescent
luminaires.
Switching: Connect to a common switch
located outside the chamber. Label the
switch and provide pilot light.

Cng tc: ni n mt cng tc chung
t ngoi khoang. Dn nhn ln cng
tc v lp mt n bo.
4 EXECUTION 4 THI CNG
4.1 AIR HANDLING UNIT
INSTALLATION
4.1 LP T DN LNH
Access and removal
Ducts: Keep adjacent equipment and
ductwork clear of air handling units.
Provide flanges or spigots for connection
to adjacent equipment and ductwork.
Piping: Install piping to coils to allow
access to equipment, and to minimise
disturbance to piping when coils are
removed. Arrange piping and isolating
valves to minimise drain-down if coil is
removed.
Coils and fans: Arrange air handling
units and adjacent equipment to permit
safe removal of coils, fans and fan shafts
without disturbing other adjacent items
or building.
Motorised dampers: Locate dampers and
damper motors in accessible positions,
for blade and motor maintenance and
blade seal replacement. Do not install
dampers on top of mixing box unless
ducted.
Li tip cn v tho lp
ng gi: t thit b ln cn v ng gi
cch xa dn lnh ln.
Lp t mt bch hay u ni dng ci
cho thit b ln cn v ng gi.
ng: lp ng vo coil sao cho c th
tip cn thit b, v hn ch nh hng
n ng ng khi tho lp coil. Sp
xp ng v van chn hn ch vic
nc b x khi tho lp coil.
Coil v qut: sp xp dn lnh ln v
thit b bn cnh sao cho vic tho lp
cc b phn sau an ton m khng nh
hng n cc b phn khc hay ta
nh: coil, qut, v trc qut.

Van gi iu khin mt: t van gi
v ng c v tr c th tip cn cho
vic bo tr cnh v ng c v thay th
ron. Khng lp van gi trn hp ha
trn tr khi l c bc bao che.
Vibration
Duct connections: Provide either internal
or external flexible duct connections at
fan.
Fan vibration isolation: Either mount
fans and motors on vibration isolation
within the unit or mount the whole unit
on specified vibration isolating mounts.
Rung ng
Phn ni ng gi: lp t phn ni mm
bn trong hoc bn ngoi qut

L xo chng rung cho qut: lp cho c
qut v ng c bn trong thit b hay
lp cho c thit bi bng l xo chng
rung theo tiu chun.
Supports and fixings
Suspended units: Provide 4 hangers.
Floor mounted units: Fix in position at
4 points to prevent horizontal or vertical
movement.
Fixings: Do not restrict effectiveness of
vibration isolation.
Chi tit treo v gi cht
Treo thit b: lp 4 ty treo.
Lp trn sn: c nh 4 im
trnh s di chuyn ngang hay thng
ng.
Lp c nh: khng lm gim hiu qu
ca l xo chng rung.
4.2 PIPING 4.2 NG NG
General
Pipe connections to unit: Provide unions
on pipes DN 50 and flanges on pipes >
DN 50.
Support: Prevent stress on coils by
independently supporting piping to coils.

Tng qut
ng ng ni ti thit b: lp t khp
ni i vi ng DN 50 v mt bch
i vi ng > DN 50
Gi : ngn nga ng sut ln coil
bng gi treo ng c lp.
4.3 CONDENSATE DRAINS 4.3 THOT NC NGNG T

AIR HANDLING PLANT
The English language version prevails. u tin ting Anh khi c tranh ci.
Centrepoint Page 14 of 14 of B.23 18 September 2007
General
Condensate drains: Provide trapped drain
lines to connect condensate trays to the
nearest building drain point. Discharge
outside the air handling unit.
Trap depth: To withstand > 2 times the
fan static pressure.
Provide drains from:
- Each cooling coil.
- Each safety tray.
- Other moisture collecting areas.
Size: The greater of unit drain
connection size and DN 20.
Fall: Provide drains with uniform and
continuous fall.
Sealing: Seal drain pipes to casing with
rubber grommets.
Test: Test drains by pouring a measured
quantity of water in upstream end.

Tng qut
Thot nc ngng t: lp t ng
thot c xiphone ni vo mng hng
nc ngng t v i v im thot nc
gn nht trong ta nh.
su ca xiphone: chu c > 2 ln
p sut tnh ca qut
Lp t ng thot t:
- Mi coil lnh
- Mi mng nc th cp
- Nhng khu vc c t nc khc
Kch thc: theo ci ln hn gia l
thot ca thit b v DN 20.
dc: lp t ng dng v dc u
lin tc
Lm kn: lm kn gia ng thot v v
my bng vng cao su
Th nghim: th nghim ng thot
bng vic mt lng nc vo u
thng ngun
Material
Copper: To AS 1432 Type B.
UPVC: To AS/NZS 1477, installed to
AS 2032.
Trap material: Transparent, kink
resistant hose.
Vt liu
ng ng: theo AS 1432 loi B
UPVC: theo AS/NZS 1477, lp t
theo AS 2032.
Vt liu lm xiphone: ng trong sut,
chng tht.