You are on page 1of 35

Static pressure for inline exhaust fans EF-27 serving Public Toilet in Ground floor

AFFAIR : EXHAUST AIR DUCT


DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
1
424
720.8
7.23
266.4
266.4
300
200
0.06
3.59
0.68
4.88

B-C
2
106
180.2
2.7
164.0
164.0
150
150
0.02
2.37
0.57
1.55

C-D
3

D-E
4

E-F
5

F-G G-H
6
7

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

9.9 ml

6.43 Pa
4

10

11

12

13

TOTAL

0.65
4.57
9.46

0.45
1.38
2.93

1.10
5.95 Pa
12.38 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
10
15
15
20
15
80
150
100
5
43
23
40

QTY

TOTAL

35
0
0
0
0
0
0
0
0
0
43
23
0
101 Pa

1
1

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

113 Pa
721 m/h
12 Pa
101 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

125 Pa
793 m/h
14 Pa
111 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

136 Pa
865 m/h
15 Pa
121 Pa

Static pressure for Roof exhaust fans EF-31 serving Public Toilet -1 in Level 1
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

23-01-2013

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
B-C
C-D D-E
1
2
3
4
847
424
283
142
1439.9 720.8 481.1 241.4
1.5
0.52 0.94
1.3
382.61 266.4 244.1 218.6
382.61 266.4 244.1 218.6
350
300
250
200
350
200
200
200
0.11
0.06 0.05 0.04
3.48
3.59 2.86 1.79
0.41
0.68 0.50 0.24
0.61
0.35 0.47 0.31
1

E-F
5

F-G G-H
6
7

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

4.3 ml

1.75 Pa
5

10

11

12

13

TOTAL

0.15
0.99
1.60

0.10
0.70
1.05

0.10
0.44
0.91

0.45
0.78
1.10

0.80
2.92 Pa
4.66 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
10
15
15
20
15
80
150
100
5
43
23
40

QTY

TOTAL

1
1

35
10
0
0
0
0
0
0
0
0
43
23
0
111 Pa

1
1

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

116 Pa
1440 m/h
5 Pa
111 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

127 Pa
1584 m/h
5 Pa
122 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

139 Pa
1728 m/h
6 Pa
133 Pa

Static pressure for inline exhaust fans EF-33 serving Public Toilet -2 in Level 1
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

23-01-2013

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
1
475
807.5
1.68
286.44
286.44
350
200
0.06
3.48
0.58
0.98
1

B-C
C-D
2
3
237
131
402.9 222.7
0.633 1.5
218.6 164
218.6 164
200
150
200
150
0.04 0.02
2.98 2.93
0.61 0.84
0.39 1.26
2

D-E
4

E-F
5

F-G G-H
6
7

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

3.8 ml

2.63 Pa

10

11

12

13

TOTAL

0.25
1.65
2.63

0.10
0.48
0.87

0.45
2.10
3.37

0.80
4.24 Pa
6.87 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
10
15
15
20
15
80
150
100
5
43
23
40

QTY

TOTAL

35
0
0
0
0
0
0
0
0
0
43
23
0
101 Pa

1
1

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

108 Pa
808 m/h
7 Pa
101 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

119 Pa
888 m/h
8 Pa
111 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

129 Pa
969 m/h
8 Pa
121 Pa

Static pressure for Smoke extract fans during high emission rate of fumes in more
than one floor under fire
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
B-C
C-D D-E
E-F
F-G
G-H
H-I
I-J
1
2
3
4
5
6
7
8
9
13216 13216 13216 13216 13216 13216 13216 13216 13216
22467 22467 22467 22467 22467 22467 22467 22467 22467
11.3
3.47
3.4
7.29
3.47
7.29 11.12 7.29 3.47
859
840
820
799
778
755
708
683
628
859
840
820
799
778
755
708
683
628
1050 1000 950
900
850
800
700
650
600
600
600
600
600
600
600
600
600
550
0.58
0.55 0.53 0.50
0.48
0.45
0.39 0.37 0.31
10.76 11.26 11.82 12.44 13.14 13.92 15.86 17.06 20.16
1.19
1.33 1.50 1.70
1.94
2.23
3.06 3.65 5.48
13.47 4.62 5.09 12.37 6.72 16.26 34.01 26.62 19.02
1

J-K
10
13216
22467
3.55
547
547
500
500
0.23
26.60
10.75
38.16

K-L
11
13216
22467
3.25
488
488
500
400
0.19
33.35
18.63
60.55

L-M
12
1652
2808
2.7
437
437
400
400
0.15
5.19
0.72
1.95

M-N
13
826
1404
2.5
328
328
300
300
0.08
4.62
0.83
2.07

240.92 Pa

10

11

12

13

TOTAL

0.50
47.03
53.75

0.15
15.85
32.11

0.10
1.47
3.42

0.50
5.81
7.88

0.10 0.10 0.10


6.91 7.61 8.43
11.54 12.71 20.80

70.1 ml

0.50
31.55
45.03

TOTAL

0.15 0.15 0.10 0.10


0.10
20.55 23.78 22.15 38.56 60.62
54.56 50.41 41.17 76.72 121.16

2.65
290.33 Pa
531.25 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
30
15
15
20
15
80
150
100
5
43
23
40

QTY

TOTAL

1
1

35
30
0
15
0
0
0
0
0
0
0
23
0
103 Pa

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

634 Pa
22467 m/h
531 Pa
103 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

698 Pa
24714 m/h
584 Pa
113 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

761 Pa
26961 m/h
638 Pa
124 Pa

Static pressure for smoke extract fans during low emission rate of fumes from all the floors
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
B-C
C-D D-E
E-F
F-G
G-H
H-I
1
2
3
4
5
6
7
8
13216 12390 11565 10738 9912 9086 7435 5782
22467 21063 19661 18255 16850 15446 12640 9829
11.3
3.47
3.4
3.4
3.47
7.29
7.24 7.29
859
840
820
799
778
755
708
683
859
840
820
799
778
755
708
683
1050 1000 950
900
850
800
700
650
600
600
600
600
600
600
600
600
0.58
0.55 0.53 0.50
0.48
0.45
0.39 0.37
10.76 10.56 10.34 10.11 9.85
9.57
8.92 7.46
1.19
1.18 1.17 1.16
1.15
1.13
1.07 0.81
13.47 4.11 3.99 3.95
3.98
8.22
7.77 5.91
1

I-J
9
4130
7021
3.47
628
628
600
550
0.31
6.30
0.66
2.29

J-K
10
3304
5617
3.55
547
547
500
500
0.23
6.65
0.86
3.06

K-L
11
2478
4213
3.25
488
488
500
400
0.19
6.25
0.89
2.88

L-M
12
1652
2808
2.7
437
437
400
400
0.15
5.19
0.72
1.95

M-N
13
826
1404
2.5
328
328
300
300
0.08
4.62
0.83
2.07

63.67 Pa

10

11

12

13

TOTAL

TOTAL

62.3 ml

0.26
16.41
29.88

0.50
30.38
34.49

0.10
5.83
9.82

0.10
5.57
9.52

0.50
26.45
30.43

0.15
7.49
15.71

0.10
2.16
4.45

0.10
2.41
5.47

0.10
2.13
5.01

0.10
1.47
3.42

0.50
5.81
7.88

0.15 0.15
6.50 4.55
14.28 10.47

2.81
117.17 Pa
180.84 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
30
15
15
20
15
80
150
100
5
43
23
40

QTY

TOTAL

1
1

35
30
0
15
0
0
0
0
0
0
0
23
0
103 Pa

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

284 Pa
22467 m/h
181 Pa
103 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

312 Pa
24714 m/h
199 Pa
113 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

341 Pa
26961 m/h
217 Pa
124 Pa

Static pressure for stair pressurization supply air fans ( SPF-1 AND SPF-2) to pressurize staircases 1 and 2
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
1
12073
20524
11.3
842
842
850
700
0.56
10.23
1.12
12.60
1

B-C
C-D D-E
E-F
F-G
G-H
H-I
2
3
4
5
6
7
8
11437 10802 10166 8896 8260 6989 5083
19443 18363 17282 15123 14042 11881 8641
3.47
3.4
7.29
3.47
7.29 11.12 7.29
828
807
792
737
711
683
656
828
807
792
737
711
683
656
820
780
750
650
650
600
600
700
700
700
700
650
650
600
0.54 0.51 0.49
0.43
0.40
0.37 0.34
10.04 9.96 9.75
9.84
9.84
9.02 7.10
1.10 1.12 1.10
1.22
1.28
1.15 0.78
3.82 3.80 8.02
4.24
9.31 12.74 5.68
2

J-K
10
3177
5401
3.55
573
573
500
550
0.26
5.82
0.64
2.26

K-L
11
2541
4320
3.25
547
547
500
500
0.23
5.11
0.53
1.74

12
1906
3240
2.7
488
488
500
400
0.19
4.81
0.55
1.48

13
1270
2159
2.5
400
400
450
300
0.13
4.78
0.69
1.73

14
635
1080
2.65
328
328
300
300
0.08
3.55
0.51
1.36

71.28 Pa

10

11

12

13

14

TOTAL

0.10
5.71
18.31

I-J
9
3812
6480
3.47
598
598
500
600
0.28
6.41
0.72
2.51

0.60 0.20 0.20


32.97 10.82 10.35
36.79 14.62 18.37

TOTAL

72.8 ml

1
2
1

1.00
52.78
57.01

0.15
7.91
17.22

0.20
8.87
21.61

0.15
4.13
9.80

0.10
2.24
4.74

0.10
1.84
4.11

0.10
1.43
3.16

0.10
1.26
2.74

0.10
1.25
2.98

0.50
3.43
4.79

3.60
144.97 Pa
216.25 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
30
15
15
20
15
80
150
100
5
43
23
40

QTY

TOTAL

1
2

35
60
0
15
0
0
0
0
0
0
0
23
0
133 Pa

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

349 Pa
20524 m/h
216 Pa
133 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

384 Pa
22577 m/h
238 Pa
146 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

419 Pa
24629 m/h
260 Pa
160 Pa

Static pressure for centrifugal inline exhaust fans PEF-05 & PEF-06 FOR BASEMENT-1
Static pressure of Exhaust fans with High air flow rate during high emission of smokes in car parking area
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

23-01-2013

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
B-C
C-D
D-E
E-F
F-G G-H
1
2
3
4
5
6
7
19188 14070 10234 6396 2558 1280
32620 23919 17398 10873 4348.6 2176
7.2
15.9
14.6
17.5
4.7
5.4
781.16 674.1 625.75 494.18 380.84 343.33
781.16 674.1 625.75 494.18 380.84 343.33
1400
1000 1000
900
500
400
400
400
350
250
250
250
0.48
0.36
0.31
0.19
0.11
0.09
18.91 18.62 15.71 15.75 10.60 6.53
3.74
4.35
3.50
4.68
3.13
1.47
26.90 69.16 51.07 81.95 14.73 7.94
1

2
1

1
2

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

65.3 ml

251.75 Pa
8

10

11

12

13

TOTAL

1.43
0.68
1.16
0.60
0.10
278.57 128.47 156.12 81.09 6.13
305.47 197.63 207.18 163.04 20.85

0.10
2.32
10.27

4.07
652.69 Pa
904.44 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
30
15
15
20
15
80
150
100
5
43
23
40

QTY

1
1

TOTAL

0
30
0
15
0
0
0
0
0
0
0
46
0
91 Pa

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

995 Pa
32620 m/h
904 Pa
91 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

1095 Pa
35882 m/h
995 Pa
100 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

1195 Pa
39144 m/h
1085 Pa
109 Pa

Static pressure for centrifugal inline exhaust fans PEF-05 & PEF-06 FOR BASEMENT-1
Static pressure of Exhaust fans with low air flow rate during Low emission of smokes in car parking area
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

23-01-2013

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
B-C
C-D D-E
E-F
1
2
3
4
5
9594 7035 5117 3198 1279
16310 11960 8699 5437 2174.3
7.2
15.9 14.6 17.5
4.7
781
674
626
494
381
781
674
626
494
381
1400 1000 1000 900
500
400
400
350
250
250
0.48
0.36 0.31 0.19
0.11
9.45
9.31 7.86 7.87
5.30
1.06
1.23 0.99 1.33
0.89
7.62 19.59 14.46 23.21 4.17
1

2
1

1
2

1.43
69.64
77.26

F-G G-H
6
7
640
1088
5.4
343
343
400
250
0.09
3.26
0.42
2.25

0.10
1.53
5.70

0.10
0.58
2.83

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

65.3 ml

71.30 Pa
8

10

11

12

13

TOTAL

0.68 1.16 0.60


32.12 39.03 20.27
51.71 53.49 43.48

4.07
163.17 Pa
234.47 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
30
15
15
20
15
80
150
100
5
43
23
40

QTY

1
1

TOTAL

0
30
0
15
0
0
0
0
0
0
0
46
0
91 Pa

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

325 Pa
16310 m/h
234 Pa
91 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

358 Pa
17941 m/h
258 Pa
100 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

391 Pa
19572 m/h
281 Pa
109 Pa

Static pressure for centrifugal inline exhaust fans for parking areas in Basement
PEF-03 & PEF-04 FOR BASEMENT-2 AND PEF-01 &PEF-02 FOR BASEMENT-3
Static pressure of Exhaust fans with High air flow rate during high emission of smokes in car parking area
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

23-01-2013

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
B-C
C-D
D-E
E-F
F-G G-H
1
2
3
4
5
6
7
19188 14070 10234 6396
2558 1280
32620 23919 17398 10873 4348.6 2176
7.2
15.9 14.6
17.5
4.7
5.4
781.16 674.1 625.8 494.18 380.84 343.33
781.16 674.1 625.8 494.18 380.84 343.33
1400
1000 1000
900
500
400
400
400
350
250
250
250
0.48
0.36 0.31
0.19
0.11
0.09
18.91 18.62 15.71 15.75 10.60 6.53
3.74
4.35 3.50
4.68
3.13
1.47
26.90 69.16 51.07 81.95 14.73 7.94
1

2
1

1
2

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

65.3 ml

251.75 Pa
8

10

11

12

13

TOTAL

0.10
6.13
20.85

0.10
2.32
10.27

1.43
0.20 0.20
0.60
278.57 37.79 26.92 81.09
305.47 106.94 77.98 163.04

2.63
432.81 Pa
684.55 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
30
15
15
20
15
80
150
100
5
43
23
40

QTY

1
1

TOTAL

0
30
0
15
0
0
0
0
0
0
0
46
0
91 Pa

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

776 Pa
32620 m/h
685 Pa
91 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

853 Pa
35882 m/h
753 Pa
100 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

931 Pa
39144 m/h
821 Pa
109 Pa

Static pressure for centrifugal inline exhaust fans for parking areas in Basement
PEF-03 & PEF-04 FOR BASEMENT-2 AND PEF-01 &PEF-02 FOR BASEMENT-3
Static pressure of Exhaust fans with low air flow rate during Low emission of smokes in car parking area
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

23-01-2013

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
B-C
C-D D-E
E-F
F-G G-H
1
2
3
4
5
6
7
9594
7035 5117 3198 1279
640
16310 11960 8699 5437 2174.3 1088
7.2
15.9 14.6 17.5
4.7
5.4
781.16 674.1 625.8 494.2 380.84 343.33
781.16 674.1 625.8 494.2 380.84 343.33
1400
1000 1000 900
500
400
400
400
350
250
250
250
0.48
0.36 0.31 0.19
0.11
0.09
9.45
9.31 7.86 7.87
5.30
3.26
1.06
1.23 0.99 1.33
0.89
0.42
7.62
19.59 14.46 23.21 4.17
2.25
1

2
1

1
2

1.43
69.64
77.26

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

65.3 ml

71.30 Pa
8

10

11

12

13

TOTAL

0.10
1.53
5.70

0.10
0.58
2.83

0.20 0.20 0.60


9.45 6.73 20.27
29.03 21.19 43.48

2.63
108.20 Pa
179.50 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
30
15
15
20
15
80
150
100
5
43
23
40

QTY

1
1

TOTAL

0
30
0
15
0
0
0
0
0
0
0
46
0
91 Pa

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

271 Pa
16310 m/h
180 Pa
91 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

298 Pa
17941 m/h
197 Pa
100 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

325 Pa
19572 m/h
215 Pa
109 Pa

Static pressure for centrifugal inline exhaust fans PEF-03, PEF-01 FOR BASEMENT-2 AND BASEMENT-3
Static pressure of Exhaust fans with High air flow rate during high emission of smokes in car parking area
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

23-01-2013

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
1
19188
32620
7.2
781.16
781.16
1400
400
0.48
18.91
3.74
26.90

B-C
2
14070
23919
15.9
674.1
674.1
1000
400
0.36
18.62
4.35
69.16

C-D
3
10234
17398
14.6
625.8
625.8
1000
350
0.31
15.71
3.50
51.07

D-E
4
6396
10873
17.5
494.2
494.2
900
250
0.19
15.75
4.68
81.95

E-F
F-G G-H
5
6
7
2558 1280
4348.6 2176
4.7
5.4
380.84 343.33
380.84 343.33
500
400
250
250
0.11
0.09
10.60 6.53
3.13
1.47
14.73 7.94
5

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

65.3 ml

251.75 Pa
8

10

11

12

13

TOTAL

1
2

0.55
0.20 0.20 0.60
0.10
107.14 37.79 26.92 81.09 6.13
134.04 106.94 77.98 163.04 20.85

0.10
2.32
10.27

1.75
261.38 Pa
513.13 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
30
15
15
20
15
80
150
100
5
43
23
40

QTY

1
1

TOTAL

0
30
0
15
0
0
0
0
0
0
0
46
0
91 Pa

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

604 Pa
32620 m/h
513 Pa
91 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

665 Pa
35882 m/h
564 Pa
100 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

725 Pa
39144 m/h
616 Pa
109 Pa

Static pressure for Parking exhaust fans PEF-03, PEF-01 FOR BASEMENT-2 AND BASEMENT-3
Static pressure of Exhaust fans with low air flow rate during Low emission of smokes in car parking area
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

23-01-2013

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
B-C
C-D D-E
E-F
F-G G-H
1
2
3
4
5
6
7
640
1279 3198 5117 7035 9594
1088 2174 5437 8699 11960 16310
5.4
4.7
17.5 14.6
15.9
7.2
343.33 380.8 494.2 625.8 674.06 781.16
343.33 380.8 494.2 625.8 674.06 781.16
400
500
900 1000 1000 1400
250
250
250
350
400
400
0.09
0.11 0.19 0.31
0.36
0.48
3.26
5.30 7.87 7.86
9.31
9.45
0.42
0.89 1.33 0.99
1.23
1.06
2.25
4.17 23.21 14.46 19.59 7.62
1

1
2

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

65.3 ml

0.00
8

10

11

12

71.30 Pa
13

TOTAL

0.10
0.00
2.25

0.10
0.00
4.17

0.60
0.00
1.00

0.20
0.00
14.46

0.20
0.00
19.59

0.55
0.00
7.62

0.00

0.00

0.00

0.00

0.00

1.75
0.00 Pa
49.09 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
30
15
15
20
15
80
150
100
5
43
23
40

QTY

1
1

TOTAL

0
30
0
15
0
0
0
0
0
0
0
46
0
91 Pa

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

140 Pa
16310 m/h
49 Pa
91 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

154 Pa
17941 m/h
54 Pa
100 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

168 Pa
19572 m/h
59 Pa
109 Pa

Static pressure for inline exhaust fans


AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

23-01-2013

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL
ROUGHNESS COEF.
SHEET THICKNESS
ALTITUDE
ALTITUDE COEF.
AIR DENSITY

:
:
:
:
:

GI DUCT
0.93
6 / 10 mm
623
Meters
0.000

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
1
2558
4348.6
11.3
380.84
380.84
500
250
0.11
10.60
3.13
35.40

B-C
2
6398
10877
20
494.2
494.2
900
250
0.19
15.75
4.69
93.71

C-D
3
10228
17388
15
625.8
625.8
1000
350
0.31
15.71
3.49
52.41

D-E
4
14076
23929
18
674.1
674.1
1000
400
0.36
18.63
4.35
78.35

E-F
5
19158
32569
23.9
781.16
781.16
1400
400
0.48
18.88
3.73
89.04

F-G G-H
6
7

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

88.2 ml

0.00
6

10

11

12

348.92 Pa
13

TOTAL

1
2

0.10
0.60 0.20 0.20
0.95
6.13 81.14 26.88 37.82 184.48
41.53 174.85 79.30 116.17 273.52

0.00

0.00

0.00

0.00

0.00

0.00

2.05
336.45 Pa
685.37 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
30
15
15
20
15
80
150
100
5
43
23
40

QTY

1
1

1
2

TOTAL

0
30
0
15
0
0
0
0
0
0
43
46
0
134 Pa

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

819 Pa
32569 m/h
685 Pa
134 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

901 Pa
35825 m/h
754 Pa
147 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

983 Pa
39082 m/h
822 Pa
161 Pa

Static pressure for inline exhaust fans serving Public Toilets


AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

23-01-2013

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
B-C
C-D D-E
1
2
3
4
932
805
423
127
1584.4 1369 719.1 215.9
3.15
2
2
2.1
368.45 327.9 244.1 164
368.45 327.9 244.1 164
380
300
250
150
300
300
200
150
0.11
0.08 0.05 0.02
4.13
4.50 4.27 2.84
0.59
0.79 1.03 0.80
1.85
1.58 2.06 1.67
1

0.73
6.78
8.62

0.15
1.66
3.24

1.11
11.03
13.09

0.58
2.55
4.22

E-F
5

F-G G-H
6
7

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

9.3 ml

0.00
5

10

11

12

7.16 Pa
13

TOTAL

2.57
22.01 Pa
29.17 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
10
15
15
20
15
80
150
100
5
43
23
40

QTY

TOTAL

35
0
0
0
0
0
0
0
0
0
43
23
0
101 Pa

1
1

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

130 Pa
1584 m/h
29 Pa
101 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

143 Pa
1743 m/h
32 Pa
111 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

156 Pa
1901 m/h
35 Pa
121 Pa

Static pressure calculation of inline exhaust fans EF-106 serving Electrical Rooms and Storage of Level 15
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

26-01-2014

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
1
403
685.1
2.35
266
266
300
200
0.06
3.41
0.62
1.45

B-C
2
202
343.4
1.3
219
219
200
200
0.04
2.54
0.46
0.60

C-D
3

D-E
4

E-F
5

F-G G-H
6
7

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

3.7 ml

2.04 Pa
4

10

11

12

13

TOTAL

1
1

0.40
2.54
3.99

0.10
0.35
0.95

0.50
2.89 Pa
4.94 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
L.SLOT DIFFUSER
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

QTY

TOTAL

35
10
15
15
20
15
80
150
100
5
30
23
40

35
0
0
15
0
0
0
0
0
0
0
23
0
73 Pa

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

78 Pa
685 m/h
5 Pa
73 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

86 Pa
754 m/h
5 Pa
80 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

94 Pa
822 m/h
6 Pa
88 Pa

Static pressure calculation of inline exhaust fans EF-101 serving Electrical Rooms and Storage of Level 14
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

26-01-2014

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
1
392
666.4
2.35
266
266
300
200
0.06
3.32
0.59
1.38

B-C
2
201
341.7
1.3
219
219
200
200
0.04
2.53
0.45
0.59

C-D
3

D-E
4

E-F
5

F-G G-H
6
7

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

3.7 ml

1.97 Pa
4

10

11

12

13

TOTAL

1
1

0.40
2.40
3.78

0.10
0.35
0.94

0.50
2.75 Pa
4.72 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
L.SLOT DIFFUSER
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

QTY

TOTAL

35
10
15
15
20
15
80
150
100
5
30
23
40

35
0
0
15
0
0
0
0
0
0
0
23
0
73 Pa

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

78 Pa
666 m/h
5 Pa
73 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

85 Pa
733 m/h
5 Pa
80 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

93 Pa
800 m/h
6 Pa
88 Pa

Static pressure calculation of inline exhaust fans EF-38 serving Electrical Rooms , Store Room and Storage of Level 2
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

26-01-2014

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
1
540
918
1.43
322
322
350
250
0.08
3.13
0.42
0.60

B-C
2
201
341.7
4.55
219
219
200
200
0.04
2.53
0.45
2.06

C-D
3

D-E
4

E-F
5

F-G G-H
6
7

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

6.0 ml

2.66 Pa
4

10

11

12

13

TOTAL

0.70
3.73
4.33

0.85
2.96
5.03

1.55
6.69 Pa
9.35 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
L.SLOT DIFFUSER
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

QTY

TOTAL

35
10
15
15
20
15
80
150
100
5
30
23
40

35
0
0
15
0
0
0
0
0
0
0
23
0
73 Pa

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

82 Pa
918 m/h
9 Pa
73 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

91 Pa
1010 m/h
10 Pa
80 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

99 Pa
1102 m/h
11 Pa
88 Pa

Static pressure calculation of inline exhaust fans EF-92A serving Manager's Toilet-3 & 4 of Level-13.
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
1
212
360.4
2
189
189
200
150
0.03
3.57
1.02
2.04

B-C
2
106
180.2
3.2
219
219
200
200
0.04
1.33
0.14
0.45

C-D
3

D-E
4

E-F
5

F-G
6

G-H
7

H-I
8

I-J
9

J-K
10

K-L
11

TOTAL

5.2 ml

2.49 Pa
4

10

11

TOTAL

1
2

0.55
3.83
5.87

0.55
3.83 Pa
6.32 Pa

0.45

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
10
15
15
20
15
80
150
100
5
43
23
40

QTY

TOTAL

35
0
0
0
0
0
0
0
0
0
43
23
0
101 Pa

1
1

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

107 Pa
360 m/h
6 Pa
101 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

118 Pa
396 m/h
7 Pa
111 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

129 Pa
432 m/h
8 Pa
121 Pa

Static pressure calculation of inline exhaust fans EF-28 and EF-33A serving Electrical Rooms of GF and L1.
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

26-01-2014

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
1
201
341.7
0.9
218.63
218.63
200
200
0.04
2.53
0.45
0.41

B-C
2

C-D
3

D-E
4

E-F
5

F-G G-H
6
7

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

0.9 ml

0.41 Pa
3

10

11

12

13

TOTAL

1
2

0.95
3.31
3.72

0.95
3.31 Pa
3.72 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
L.SLOT DIFFUSER
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
10
15
15
20
15
80
150
100
5
30
23
40

QTY

TOTAL

35
0
0
15
0
0
0
0
0
0
0
23
0
73 Pa

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

77 Pa
342 m/h
4 Pa
73 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

84 Pa
376 m/h
4 Pa
80 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

92 Pa
410 m/h
4 Pa
88 Pa

Static pressure calculation of inline exhaust fans EF-76,EF-81A and EF-87, serving Manager's Toilet of L10,L11 & L12
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
1
106
180.2
2
189
189
200
150
0.03
1.79
0.29
0.58

B-C
2

C-D
3

D-E
4

E-F
5

F-G
6

G-H
7

H-I
8

I-J
9

J-K
10

K-L
11

TOTAL

2.0 ml

0.58 Pa
3

10

11

TOTAL

0.85
1.48 Pa
2.06 Pa

0.85
1.48
2.06

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
10
15
15
20
15
80
150
100
5
43
23
40

QTY

TOTAL

35
0
0
0
0
0
0
0
0
0
43
23
0
101 Pa

1
1

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

103 Pa
180 m/h
2 Pa
101 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

113 Pa
198 m/h
2 Pa
111 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

124 Pa
216 m/h
2 Pa
121 Pa

Static pressure calculation of inline exhaust fans EF-102 serving President's Toilet of L15
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

28-01-2014

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
1
254
431.8
2.5
244.06
244.06
250
200
0.05
2.56
0.41
1.02

B-C
2

C-D
3

D-E
4

E-F
5

F-G
6

G-H
7

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

2.5 ml

1.02 Pa
3

10

11

12

13

TOTAL

0.85
3.05
4.06

0.85
3.05 Pa
4.06 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
10
15
15
20
15
80
150
100
5
43
23
40

QTY

TOTAL

35
0
0
0
0
0
0
0
0
0
43
23
0
101 Pa

1
1

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

105 Pa
432 m/h
4 Pa
101 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

116 Pa
475 m/h
4 Pa
111 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

126 Pa
518 m/h
5 Pa
121 Pa

Static pressure calculation of inline exhaust fans EF-97 serving Manager's Toilet of L14
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

23-01-2013

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
1
106
180.2
0.95
188.85
188.85
200
150
0.03
1.79
0.29
0.27

B-C
2

C-D
3

D-E
4

E-F
5

F-G
6

G-H
7

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

1.0 ml

0.27 Pa
3

10

11

12

13

TOTAL

1
2

0.15
0.26
0.54

0.15
0.26 Pa
0.54 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
10
15
15
20
15
80
150
100
5
43
23
40

QTY

TOTAL

35
0
0
0
0
0
0
0
0
0
43
23
0
101 Pa

1
1

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

102 Pa
180 m/h
1 Pa
101 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

112 Pa
198 m/h
1 Pa
111 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

122 Pa
216 m/h
1 Pa
121 Pa

Static pressure calculation of inline exhaust fans EF-35,EF-41A, EF-42,EF-47,EF-53, EF-59A,EF-63, EF-70, EF-75, EF-81,
EF-86, EF-92 serving Manager's Toilet of L2,L3, L4,L5,L6,L7,L8,L9,L10,L11,L12 & L13.
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
1
106
180.2
0.8
188.85
188.85
200
150
0.03
1.79
0.29
0.23

B-C
2

C-D
3

D-E
4

E-F
5

F-G
6

G-H
7

H-I
8

I-J
9

J-K
10

K-L
11

TOTAL

0.8 ml

0.23 Pa
3

10

11

TOTAL

0.00

0.85
1.48 Pa
1.71 Pa

0.85
1.48
1.71

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
10
15
15
20
15
80
150
100
5
43
23
40

QTY

TOTAL

35
0
0
0
0
0
0
0
0
0
43
23
0
101 Pa

1
1

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

103 Pa
180 m/h
2 Pa
101 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

113 Pa
198 m/h
2 Pa
111 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

123 Pa
216 m/h
2 Pa
121 Pa

Static pressure calculation of inline exhaust fans EF-37 and EF-40 serving Kitchen of Level 2 and Level 3.
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

23-01-2013

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
1
201
341.7
2.1
218.63
218.63
200
200
0.04
2.53
0.45
0.95

B-C
2

C-D
3

D-E
4

E-F
5

F-G G-H
6
7

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

2.1 ml

0.00
3

10

11

12

0.95 Pa
13

TOTAL

0.10
0.35
1.30

0.10
0.35 Pa
1.30 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
L.SLOT DIFFUSER
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

QTY

TOTAL

35
10
15
15
20
15
80
150
100
5
30
23

35
0
0
15
0
0
0
0
0
0
0
23
0
73 Pa

40

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

74 Pa
342 m/h
1 Pa
73 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

82 Pa
376 m/h
1 Pa
80 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

89 Pa
410 m/h
2 Pa
88 Pa

Static pressure for inline exhaust fans EF-103 serving Public Toilet L5-14 and toilet L5-27 in Level 15
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

23-01-2013

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
B-C
C-D D-E
E-F
1
2
3
4
5
1038
911
529
233
106
1764.6 1549 899.3 396.1 180.2
2.9
2
2.2
1.25
11
399.61 377.7 299.1 218.6 163.97
399.61 377.7 299.1 218.6 163.97
450
400
300
200
150
300
300
250
200
150
0.13
0.11 0.07 0.04
0.02
3.91
3.84 3.56 2.93
2.37
0.48
0.50 0.58 0.59
0.57
1.39
1.00 1.27 0.74
6.30
1

F-G G-H
6
7

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

19.4 ml

10.70 Pa
6

10

11

12

13

TOTAL

4
1

0.73
6.08
7.47

0.15
1.21
2.20

1.51
10.41
11.67

0.10
0.47
1.21

0.05
0.15
6.46

2.54
18.31 Pa
29.01 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
Disc Exhaust valve
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

35
10
15
15
20
15
80
150
100
5
43
23
40

QTY

TOTAL

35
0
0
0
0
0
0
0
0
0
43
23
0
101 Pa

1
1

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

130 Pa
1765 m/h
29 Pa
101 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

143 Pa
1941 m/h
32 Pa
111 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

156 Pa
2118 m/h
35 Pa
121 Pa

Static pressure calculation of inline exhaust fans EF-44,EF-50, EF-56,EF-62,EF-66, EF-72,EF-78, EF-83, EF-89, EF-94, EF-99,
EF-104 serving Kitchen of L4,L5,L6,L7,L8,L9,L10,L11,L12,L13,L14 & L15.
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

23-01-2013

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
1
201
341.7
5.5
218.63
218.63
200
200
0.04
2.53
0.45
2.50

B-C
2

C-D
3

D-E
4

E-F
5

F-G G-H
6
7

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

5.5 ml

2.50 Pa

0.00
3

10

11

12

13

TOTAL

0.10
0.35 Pa
2.84 Pa

0.10
0.35
2.84

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
L.SLOT DIFFUSER
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

QTY

TOTAL

35
10
15
15
20
15
80
150
100
5
30
23

35
0
0
15
0
0
0
0
0
0
0
23
0
73 Pa

40

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

76 Pa
342 m/h
3 Pa
73 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

83 Pa
376 m/h
3 Pa
80 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

91 Pa
410 m/h
3 Pa
88 Pa

Static pressure calculation of inline exhaust fans EF-41,EF-46, EF-52,EF-58, EF-61, EF-68, EF-74, EF-80 EF-85, EF-91 &
EF-96 serving Electrical Rooms of L3,L4,L5,L6,L7,L8,L9,L10,L11,L12 & L13
AFFAIR : EXHAUST AIR DUCT
DUCT NAME :

Date :

SITE : GENERAL AUDITING BUREAU

26-01-2014

Revision :

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL

GI DUCT

AIR DENSITY

1.09

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
AIR OUTLET
GRILLE
TOTAL
DUCTS PD
PRESSURE DROP

CFM
M3/H
M
mm
mm
mm
M2
M/S
Pa
Pa
KSI
0.18
0.24
0.4
0.3
1
1.5
0.05
0.25
0.05
1.1
0.44
KSI
Pa
Pa

A-B
1
201
341.7
0.9
218.63
218.63
200
200
0.04
2.53
0.45
0.41

B-C
2

C-D
3

D-E
4

E-F
5

F-G G-H
6
7

H-I
8

I-J
9

J-K
10

K-L
11

12

13

TOTAL

0.9 ml

0.41 Pa
3

10

11

12

13

TOTAL

1
2

0.95
3.31
3.72

0.95
3.31 Pa
3.72 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
Exhaust GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
PRIMARY HEATING COIL
L.SLOT DIFFUSER
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

QTY

TOTAL

35
10
15
15
20
15
80
150
100
5
30
23

35
0
0
15
0
0
0
0
0
0
0
23
0
73 Pa

40

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

77 Pa
342 m/h
4 Pa
73 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

84 Pa
376 m/h
4 Pa
80 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

92 Pa
410 m/h
4 Pa
88 Pa

PROJECT :- G.A.B. RIYADH

DATE- 25-01-2012

FAHU, AHUS. EXTERNAL STATIC PRESSURE CALCULATIONS SUMMERY SHEET:-

S.I.NO

AHU NO.

LOCATION

STATIC
PRESSURE
AT110% PA

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37

AHU-01
AHU-02
AHU-03
AHU-04
AHU-05
AHU-06
AHU-07
AHU-08
AHU-09
AHU-10
AHU-11
AHU-12
AHU-13
AHU-14
AHU-15
AHU-16
AHU-17
AHU-18
AHU-19
AHU-20
AHU-21
AHU-22
AHU-23
AHU-24
AHU-25
AHU-26
AHU-27
AHU-28
AHU-29
AHU-30
AHU-31
AHU-32
AHU-33
AHU-34
AHU-35
FAHU-01
FAHU-02

15TH FLOOR
15TH FLOOR
14TH FLOOR
14TH FLOOR
13TH FLOOR
13TH FLOOR
12TH FLOOR
12TH FLOOR
11TH FLOOR
11TH FLOOR
10TH FLOOR
10TH FLOOR
9TH FLOOR
9TH FLOOR
8TH FLOOR
8TH FLOOR
7TH FLOOR
7TH FLOOR
6TH FLOOR
6TH FLOOR
5TH FLOOR
5TH FLOOR
4TH FLOOR
4TH FLOOR
3RD FLOOR
3RD FLOOR
2ND FLOOR
2ND FLOOR
1ST FLOOR
1ST FLOOR
G.F FLOOR
G.F FLOOR
1ST FLOOR
1ST FLOOR
1ST FLOOR
ROOF
ROOF

258
302
256
249
237
244
250
254
267
249
285
272
270
251
232
271
236
215
265
213
287
246
254
234
239
215
260
221
230
223
232
229
256
263
248
607
476

AFFAIR : SUPPLY FRESH AIR DUCT


DUCT NAME : FAHU-01 ROOF

SITE :

GENERAL AUDITING BUREAU

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL
ROUGHNESS COEF.
SHEET THICKNESS
ALTITUDE
ALTITUDE COEF.
AIR DENSITY

:
:
:
:
:

GI DUCT
0.93
6 / 10 mm
623
0.000

1.09

Meters

DATE-25-01-2012
Revision :

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


A-B
SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter

CFM
M3/H
M
mm

mm
mm
M2
M/S
Pa
PD x LENGTH Pa
KSI
ELBOW 30
0.18
ELBOW 45
0.24
ELBOW 90
0.4
TEE 45
0.3
TEE 90
1
END TEE
1.5
BRANCH TEE 0.05
TRANSITION 0.25
CONTRACTION 0.05
AIR OUTLET
1.1
GRILLE
0.44
TOTAL
KSI
DUCTS PD

Pa

PRESSURE DROPPa

B-C
C-D
D-E
1
2
3
4
654
2080
3604
4844
1111.8
3536
6126.8
8234.8
5
3.7
3.7
3.7
327.9496 457.0125 597.2552 685.5187
327.9496 457.0125 597.2552 685.5187
300
600
900
900
300
300
350
450
0.08
0.16
0.28
0.37
3.66
5.99
6.07
6.20
0.54
0.89
0.66
0.58
2.71
3.279888
2.43
2.13
1

E-F
5
6094
10359.8
3.7
725.553
725.553
900
500
0.41
6.96
0.66
2.45

F-G
G-H
H-I
I-J
J-K
K-L
L-M
M-N
N-O
O-P
P-Q
6
7
8
9
10
11
12
13
14
15
16
7537
8692
10154
11432
12550
14470
15773
17214
18354
19685
20781
12812.9
14776.4
17261.8
19434.4
21335
24599
26814.1
29263.8
31201.8
33464.5
35327.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
8
799.22054 833.36037 897.19578 927.17974 983.84881 1010.7162 1036.7082 1086.3202 1110.0502 1133.1264 1177.4808
799.22054 833.36037 897.19578 927.17974 983.84881 1010.7162 1036.7082 1086.3202 1110.0502 1133.1264 1177.4808
900
900
900
900
900
950
1000
1100
1150
1200
1300
600
650
750
800
900
900
900
900
900
900
900
0.50
0.55
0.63
0.68
0.76
0.80
0.84
0.93
0.97
1.01
1.09
7.09
7.53
7.58
8.00
7.80
8.52
8.82
8.77
8.96
9.22
9.01
0.61
0.65
0.60
0.63
0.56
0.64
0.66
0.62
0.62
0.64
0.59
2.26
2.39
2.21
2.34
2.08
2.36
2.45
2.28
2.31
2.38
4.70

10

11

12

13

TOTAL

49.4 ml

31.38 Pa
TOTAL

1
1

1
1

0.45
3.28
5.99

1.60
31.26
34.54

0.10
2.01
4.44

0.10
2.09
4.22

0.10
2.64
5.09

0.10
2.74
5.00

0.10
3.09
5.47

0.10
3.13
5.35

0.10
3.48
5.83

0.10
3.31
5.39

0.10
3.95
6.32

0.10
4.24
6.69

0.10
4.19
6.48

0.10
4.37
6.68

0.10
4.63
7.01

3.00
132.78
137.49

6.35
211.22 Pa
251.99 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
RETURN GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
VAV
DIFFUSER
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

QTY

TOTAL

35
10
15
15
20
15
80
150
100

2
1

70
10
0
0
0
0
0
0
0
0
25
23
0
128 Pa

50
25
23
40

1
1

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

380 Pa
29264 m/h
252 Pa
128 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

418 Pa
32190 m/h
277 Pa
141 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

456 Pa
35117 m/h
302 Pa
154 Pa

AFFAIR : SUPPLY FRESH AIR DUCT

SITE :

DUCT NAME : FAHU-01 ROOF

GENERAL AUDITING BUREAU

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL
ROUGHNESS COEF.
SHEET THICKNESS
ALTITUDE
ALTITUDE COEF.
AIR DENSITY

:
:
:
:
:

GI DUCT
0.93
6 / 10 mm
623
0.000

1.09

Meters

DATE-25-01-2012
Revision :

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


A-B
SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter

CFM
M3/H
M
mm

mm
mm
M2
M/S
Pa
PD x LENGTH Pa
KSI
ELBOW 30
0.18
ELBOW 45
0.24
ELBOW 90
0.4
TEE 45
0.3
TEE 90
1
END TEE
1.5
BRANCH TEE 0.05
TRANSITION 0.25
CONTRACTION 0.05
AIR OUTLET
1.1
GRILLE
0.44
TOTAL
KSI
DUCTS PD

Pa

PRESSURE DROPPa

B-C
C-D
D-E
1
2
3
4
654
2080
3604
4844
1111.8
3536
6126.8
8234.8
5
3.7
3.7
3.7
273.29133 413.66203 532.81369 598.13052
273.29133 413.66203 532.81369 598.13052
250
600
600
600
250
250
400
500
0.06
0.13
0.22
0.28
5.26
7.31
7.63
8.14
1.31
1.44
1.14
1.12
6.57
5.3236734
4.23
4.13
1

E-F
5
6094
10359.8
3.7
655.8992
655.8992
600
600
0.34
8.52
1.08
4.01

F-G
G-H
H-I
I-J
J-K
6
7
8
9
10
7537
8692
10154
11432
12550
12812.9
14776.4
17261.8
19434.4
21335
3.7
3.7
3.7
3.7
3.7
707.92675 755.41763 799.22054 839.95861 859.33047
707.92675 755.41763 799.22054 839.95861 859.33047
700
800
900
1000
1050
600
600
600
600
600
0.39
0.45
0.50
0.55
0.58
9.04
9.16
9.56
9.74
10.22
1.10
1.04
1.05
1.02
1.09
4.07
3.85
3.88
3.79
4.02

10

K-L
11
14470
24599
3.7
896.6961
896.6961
1050
650
0.63
10.82
1.14
4.23
11

L-M
M-N
N-O
O-P
P-Q
12
13
14
15
16
15773
17214
18354
19685
20781
26814.1
29263.8
31201.8
33464.5
35327.7
3.7
3.7
3.7
3.7
8
916.48448 954.35411 992.95486 1012.0215 1030.5919
916.48448 954.35411 992.95486 1012.0215 1030.5919
1100
1200
1200
1250
1300
650
650
700
700
700
0.66
0.72
0.77
0.80
0.83
11.29
11.36
11.19
11.56
11.76
1.20
1.16
1.07
1.11
1.12
4.45
4.29
3.97
4.11
8.99
12

13

TOTAL

49.4 ml

56.84 Pa
TOTAL

1
1

1
1

0.45
6.80
13.36

1.60
46.58
51.90

0.10
3.18
7.41

0.10
3.61
7.74

0.10
3.95
7.96

0.10
4.46
8.53

0.10
4.57
8.42

0.10
4.98
8.86

0.10
5.17
8.96

0.10
5.69
9.71

0.10
6.38
10.61

0.10
6.95
11.40

0.10
7.04
11.32

0.10
6.83
10.80

0.10
7.28
11.39

3.00
226.26
235.25

6.35
349.72 Pa
423.63 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
RETURN GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
VAV
DIFFUSER
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

QTY

TOTAL

35
10
15
15
20
15
80
150
100

2
1

70
10
0
0
0
0
0
0
0
0
25
23
0
128 Pa

50
25
23
40

1
1

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

552 Pa
29264 m/h
424 Pa
128 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

607 Pa
32190 m/h
466 Pa
141 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

662 Pa
35117 m/h
508 Pa
154 Pa

AFFAIR : SUPPLY FRESH AIR DUCT

SITE :

DUCT NAME : FAHU-02 ROOF

GENERAL AUDITING BUREAU

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL
ROUGHNESS COEF.
SHEET THICKNESS
ALTITUDE
ALTITUDE COEF.
AIR DENSITY

:
:
:
:
:

GI DUCT
0.93
6 / 10 mm
623
0.000

1.09

Meters

DATE-25-01-2012
Revision :

Kg/m3

1.18 @ 22or 24 &50%

DUCTS PRESSURE LOSSES BOARD


A-B
SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter

CFM
M3/H
M
mm

mm
mm
M2
M/S
Pa
PD x LENGTH Pa
KSI
ELBOW 30
0.18
ELBOW 45
0.24
ELBOW 90
0.4
TEE 45
0.3
TEE 90
1
END TEE
1.5
BRANCH TEE 0.05
TRANSITION 0.25
CONTRACTION 0.05
AIR OUTLET
1.1
GRILLE
0.44
TOTAL
KSI
DUCTS PD

Pa

PRESSURE DROPPa

B-C
C-D
D-E
E-F
1
2
3
4
5
521
1993
2987
3983
4477
885.7
3388.1
5077.9
6771.1
7610.9
5
3.7
3.7
3.7
3.7
273.29133 413.66203 496.47743 566.56322 598.13052
273.29133 413.66203 496.47743 566.56322 598.13052
250
600
600
600
600
250
250
350
450
500
0.06
0.13
0.19
0.25
0.28
4.19
7.00
7.29
7.46
7.52
0.87
1.33
1.15
1.02
0.97
4.34
4.9253763
4.24
3.77
3.58
1

F-G
6
5399
9178.3
3.7
655.8992
655.8992
600
600
0.34
7.55
0.87
3.22

G-H
7
6151
10456.7
3.7
682.5449
682.5449
650
600
0.37
7.94
0.91
3.36

H-I
I-J
J-K
K-L
L-M
8
9
10
11
12
7268
8221
9141
10455
11499
12355.6
13975.7
15539.7
17773.5
19548.3
3.7
3.7
3.7
3.7
3.7
707.92675 755.41763 799.22054 876.28063 876.28063
707.92675 755.41763 799.22054 876.28063 876.28063
700
800
900
1000
1000
600
600
600
650
650
0.39
0.45
0.50
0.60
0.60
8.72
8.66
8.60
8.19
9.00
1.03
0.94
0.87
0.71
0.84
3.81
3.48
3.21
2.62
3.11
8

10

11

12

M-N
13
12582
21389.4
3.7
896.6961
896.6961
1050
650
0.63
9.41
0.89
3.28

N-O
O-P
P-Q
14
15
16
13500
15430
16788
22950
26231
28539.6
3.7
3.7
8
932.42396 992.95486 1029.9977
932.42396 992.95486 1029.9977
1050
1200
1200
700
700
750
0.68
0.77
0.83
9.34
9.41
9.51
0.83
0.78
0.76
3.08
2.90
6.11

13

TOTAL

49.4 ml

46.94 Pa
TOTAL

1
1

1
1

0.45
4.31
8.66

1.60
42.76
47.69

0.10
2.89
7.13

0.10
3.03
6.80

0.10
3.09
6.66

0.10
3.10
6.32

0.10
3.43
6.79

0.10
4.14
7.95

0.10
4.09
7.57

0.10
4.03
7.24

0.10
3.65
6.27

0.10
4.42
7.53

0.10
4.82
8.10

0.10
4.75
7.83

0.10
4.83
7.72

3.00
148.01
154.12

6.35
245.37 Pa
304.40 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
RETURN GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER
HOOD FILTER
VAV
DIFFUSER
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

QTY

TOTAL

35
10
15
15
20
15
80
150
100

2
1

70
10
0
0
0
0
0
0
0
0
25
23
0
128 Pa

50
25
23
40

1
1

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

432 Pa
21389 m/h
304 Pa
128 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

476 Pa
23528 m/h
335 Pa
141 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

519 Pa
25667 m/h
365 Pa
154 Pa

AFFAIR : SUPPLY FRESH AIR DUCT

SITE :

DUCT NAME : FAHU-02 ROOF

GENERAL AUDITING BUREAU

BUILDING : NORTH LOT

GENERAL DATA
DUCT MATERIAL
ROUGHNESS COEF.
SHEET THICKNESS
ALTITUDE
ALTITUDE COEF.
AIR DENSITY

:
:
:
:
:

GI DUCT
0.93
6 / 10 mm
623
0.000

1.09

Meters

DATE-25-

Kg/m3

DUCTS PRESSURE LOSSES BOARD


A-B
SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter

CFM
M3/H
M
mm

mm
mm
M2
M/S
Pa
PD x LENGTH Pa
KSI
ELBOW 30
0.18
ELBOW 45
0.24
ELBOW 90
0.4
TEE 45
0.3
TEE 90
1
END TEE
1.5
BRANCH TEE 0.05
TRANSITION 0.25
CONTRACTION 0.05
AIR OUTLET
1.1
GRILLE
0.44
TOTAL
KSI

Pa
PRESSURE DROPPa
DUCTS PD

B-C
C-D
D-E
1
2
3
4
521
1993
2987
3983
885.7
3388.1
5077.9
6771.1
5
3.7
3.7
3.7
299.06526 496.47743 566.56322 566.56322
299.06526 496.47743 566.56322 566.56322
300
600
600
600
250
350
450
450
0.07
0.19
0.25
0.25
3.50
4.86
5.59
7.46
0.56
0.55
0.60
1.02
2.80
2.0289236
2.23
3.77
1

E-F
5
4477
7610.9
3.7
655.8992
655.8992
600
600
0.34
6.26
0.62
2.29

F-G
G-H
H-I
6
7
8
5399
6151
7268
9178.3
10456.7
12355.6
3.7
3.7
3.7
707.92675 732.17978 777.73691
707.92675 732.17978 777.73691
600
750
850
700
600
600
0.39
0.42
0.48
6.48
6.90
7.22
0.60
0.65
0.65
2.22
2.39
2.41

1
1

0.45
3.01
5.81

1.60
20.61
22.64

0.10
1.71
3.94

0.10
3.03
6.80

0.10
2.13
4.42

0.10
2.29
4.51

0.10
2.59
4.98

0.10
2.84
5.26

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
DAMPER
SUPPLY GRILLE
RETURN GRILLE
FRESH AIR GRILLE
REJECT AIR GRILLE
PLANE FILTER
OIL BATH FILTER

PD (PA)

QTY

TOTAL

35
10
15
15
20
15
80
150

2
1

70
10
0
0
0
0
0
0

STATIC PRESSURE AT
FLOW AT 100%
* DUCTS PRESSURE D
* FITTING PRESSURE D

STATIC PRESSURE AT
FLOW AT 110%
* DUCTS PRESSURE D

HOOD FILTER
VAV
DIFFUSER
FLEXIBLE CONNECTION
SOUND ATTENUATOR
TOTAL

100
50
25
23
40

1
1

0
0
25
23
0
128 Pa

* FITTING PRESSURE D

STATIC PRESSURE AT
FLOW AT 120%
* DUCTS PRESSURE D
* FITTING PRESSURE D

DATE-25-01-2012
Revision :

1.18 @ 22or 24 &50%


I-J
J-K
K-L
L-M
9
10
11
12
8221
9141
10455
11499
13975.7
15539.7
17773.5
19548.3
3.7
3.7
3.7
3.7
819.94026 839.95861 916.48448 954.35411
819.94026 839.95861 916.48448 954.35411
950
1000
1100
1200
600
600
650
650
0.53
0.55
0.66
0.72
7.35
7.79
7.48
7.59
0.63
0.68
0.57
0.56
2.34
2.52
2.11
2.06
9

10

11

12

M-N
13
12582
21389.4
3.7
896.6961
896.6961
1050
650
0.63
9.41
0.89
3.28

N-O
O-P
P-Q
14
15
16
13500
15430
16788
22950
26231
28539.6
3.7
3.7
8
932.42396 992.95486 1029.9977
932.42396 992.95486 1029.9977
1050
1200
1200
700
700
750
0.68
0.77
0.83
9.34
9.41
9.51
0.83
0.78
0.76
3.08
2.90
6.11

13

TOTAL

49.4 ml

32.43 Pa
TOTAL

1
1

1
1

0.10
2.95
5.28

0.10
3.31
5.83

0.10
3.05
5.16

0.10
3.14
5.20

0.10
4.82
8.10

0.10
4.75
7.83

0.10
4.83
7.72

3.00
148.01
154.12

6.35
213.07 Pa
257.59 Pa

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

386 Pa
21389 m/h
258 Pa
128 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :

424 Pa
23528 m/h
283 Pa

* FITTING PRESSURE DROP :

141 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

463 Pa
25667 m/h
309 Pa
154 Pa

You might also like