Professional Documents
Culture Documents
ATDL[Enter]
You should see:
OK
ATDL
4567
To determine the 16-Bit Source Address, type:
ATMY[Enter]
You should see:
OK
ATMY
1234
Step 10. You also can use the AT commands to set parameters. Just follow
the AT command with a new parameter. To change the MY16-Bit Source
Address to 0040, type:
ATMY[Enter]
You should see:
OK
FIGURE 2.6 This message shows the X-CTU program successfully transferred the con-
guration information to an XBee module.
Introduction 11
ATMY
40
The X-CTU software does not display nor does it need leading zeros in
the Modem Conguration window, so the command ATMY0040 and ATMY40
have the same effect. In some cases, described later, commands must include
leading zeros, and instructions will explain those situations.
Step 11. To return an XBee module to its factory-default condition,
click on the Modem Conguration tab and then in the Modem Parameters
and Firmware box, click on Restore. This action resets all parameters to the
factory-default settings and automatically writes them into the XBee modules
ash memory. You do not have to click the Write button.
To conrm the default settings, click on Read and you will see the labels
for all the settings you can modify have returned to green and thus the factory-
set values. Before you go to the next experiment, I recommend you restore the
default values for the attached XBee module.
Step 12. So far, the XBee module does not transfer information wirelessly.
The next experiment takes that step.
Note: Unless specied otherwise, all modem parameters use hexadecimal
values. You will nd a hexadecimal-binary-decimal converter at: http://www.
mathsisfun.com/binary-decimal-hexadecimal-converter.html.