Professional Documents
Culture Documents
VP 4400 427 001 All 002
VP 4400 427 001 All 002
Control Corp
INQ. NO.:
080360
JOB NO. :
APPROVED
AAN
APPROVED AS NOTED
RFC
NA
NOT APPLICABLE
J.Y.Chung
14.Jul.2011
DATE:
SIGNED BY :
01-JUL-2011
FOR APPROVAL
S. CHASE
S. CHASE
S. CHASE
07-JUN-2011
FOR APPROVAL
M. POPE
M. POPE
M. POPE
07-APR-2011
FOR APPROVAL
S. CHASE
S. CHASE
S. CHASE
23-FEB-2011
FOR APPROVAL
R. MILLER
R. MILLER
R. MILLER
12-JAN-2011
FOR APPROVAL
S. CHASE
S. CHASE
S. CHASE
S. CHASE
S. CHASE
S. CHASE
PREPARED
REVIEWED
APPROVED
01-OCT-2010
REV.
DATE
FOR APPROVAL
DESCRIPTION
SDS246953 REV 05
VP-4400-427-001 -ALL-002_05
Page 1 of 1 59
SDS246953 REV 05
TAG NUMBER
PAGE
2 1 1 -P S V -0 1 2 A
2 1 1 -P S V -0 2 0 A
2 1 1 -P S V -0 4 2
2 1 1 -P S V -0 4 3
10
2 1 4 -P S V -0 1 8
12
2 1 4 -P S V -0 2 1
14
2 1 4 -P S V -0 3 0 A
16
2 1 4 -P S V -0 3 1
18
2 1 4 -P S V -0 5 1
20
2 1 6 -P S V -0 2 8 A
22
2 1 6 -P S V -0 2 9 A
24
2 1 7 -P S V -0 0 3
26
2 1 7 -P S V -0 0 4
28
2 2 0 -P S V -0 0 5
30
2 2 0 -P S V -0 1 4 A
32
2 2 0 -P S V -0 1 5
34
2 2 0 -P S V -0 1 6 A
36
2 2 0 -P S V -0 1 7
38
2 2 0 -P S V -0 1 8
40
2 2 0 -P S V -0 2 0
42
2 2 0 -P S V -0 2 1
44
2 2 0 -P S V -0 2 3 A
46
2 2 0 -P S V -0 2 8
48
2 2 0 -P S V -0 3 1
50
2 2 0 -P S V -0 4 0
52
2 2 0 -P S V -0 4 7 A
54
2 2 0 -P S V -0 4 8 A
56
2 2 0 -P S V -0 4 9
58
2 2 2 -P S V -0 1 6
60
2 2 2 -P S V -0 1 9
62
2 2 4 -P S V -0 0 5
64
2 2 4 -P S V -0 0 9
66
2 2 4 -P S V -0 1 3
68
2 2 4 -P S V -0 1 8
70
2 2 4 -P S V -0 2 1
72
2 2 4 -P S V -0 3 0
74
2 2 5 -P S V -0 0 8
76
2 2 5 -P S V -0 1 1
78
2 2 5 -P S V -0 1 5
80
2 2 5 -P S V -0 1 6
82
2 2 5 -P S V -0 2 4
84
2 2 5 -P S V -0 4 0 A
86
2 2 5 -P S V -0 4 3
88
2 2 5 -P S V -0 5 0
90
2 2 5 -P S V -0 5 1
92
2 2 6 -P S V -0 4 0
94
2 2 6 -P S V -0 4 5
96
2 2 6 -P S V -0 5 0
98
2 2 6 -P S V -0 5 7
100
2 2 6 -P S V -0 6 2
102
2 2 6 -P S V -0 6 7
104
VP-4400-427-001 -ALL-002_05
Page 2 of 1 59
TAG NUMBER
SDS246953 REV 05
PAGE
2 2 6 -P S V -8 0 2
106
2 2 7 -P S V -0 1 4 A
108
2 2 7 -P S V -0 2 0 A
110
2 2 7 -P S V -0 2 8 A
112
2 2 7 -P S V -0 3 2 A
114
2 2 7 -P S V -0 4 3 A
116
2 2 7 -P S V -0 4 6 A
118
2 2 7 -P S V -0 5 3
120
2 2 7 -P S V -0 5 4
122
2 2 7 -P S V -0 5 7 A
124
2 2 7 -P S V -0 5 9 A
126
2 2 7 -P S V -0 6 0
128
2 2 7 -P S V -0 7 2 A
130
2 2 7 -P S V -0 7 8 A
132
2 2 7 -P S V -0 8 0 A
134
2 2 7 -P S V -0 8 1 A
136
2 2 7 -P S V -0 8 2 A
138
2 2 8 -P S V -0 0 4 A
140
2 2 8 -P S V -0 0 6
142
2 2 8 -P S V -0 1 1
144
2 2 8 -P S V -0 1 4
146
2 2 8 -P S V -0 1 5
148
2 2 8 -P S V -0 2 2
150
2 2 8 -P S V -0 3 3
152
2 2 8 -P S V -0 4 6
154
2 2 8 -P S V -0 4 8
156
3 1 1 -P S V -0 0 2
158
VP-4400-427-001 -ALL-002_05
Page 3 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Daelim
Job Description
PQ -1 01 790
Prepared By
Checked By
Approved By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 1 1 -PSV -01 2 A
P / ID
Discharge To
Revision #
Valve Selected
Plant #
Drawing #
Outlet Line #
Revised By
Sizing Basis
ASME Code
Fluid State
G AS EXPANSIO N
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
60 Bar G
36 Bar G
60 Bar G
Operating to Set %
60 %
Atm Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
Percent
Relief
Design T.
Constant Back
P.
Variable Back P.
0.32 Bar G
Over
Pressure
1 2 .6 Bar G
Cold
Diff. Test P.
4 2 .08 M ol Wt
Gas
1 .4 52 5 sp g r
Compressibility
4 1 C
304 C
Over P.
Pressure
Min.
90 C
21
-45 C
3 Bar G
60 Bar G
Compressible State
Fluid
Propylene
Molecular
400 kg /hr
Specific
Gravity
Calculated Area
0.01 3782 in
Specific
Heat Ratio
0.01 3782 in
Weight
( Resolved
1 .1 6
Flow Const.
0.92
by M aximum )
333
0.01 2404 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Bellows
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 2 2 92 SCFM
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
600
Out.
Rating
RF
Out.
Facing
Size
2 .0 in
1 50
RF
NACE
No
Model Materials
Body
Bonnet
Disc
31 6SS + STELLITE
(SP)
Guide
Bellows
Inconel Composite
Custom
31 6
SS
M aterial to be
A32 0-L7/A1 94 -4 .
(SP)
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6SS + STELLITE
(SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 4 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Over P.
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
G AS
EXPANSIO N
400 kg /hr
4353.5 kg /hr
304 C
1 62.4 4 lbs
1 06.07
79.551
0.01 3782 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
4 00 kg /hr
304 C
0.92
333
0.8577
Critical
1
73.61 3 Bar Abs
4 2 .08 M ol Wt
1
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Propylene
1 .4 52 5 sp g r
1 .1 6
0.953
0.01 3782 in
Tag Notes
15-OCT: The customer submitted new data sheets with back p ressure changed to constant and
variable.
Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 5 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 1 1 -PSV -02 0A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
CV FAILURE
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
4 .5 Bar G
Design T.
Operating
Temp.
Relief Temp.
55.556
Percent Over P.
1 0.3 Bar G
2 .5 Bar G
Operating to Set %
Atm Pressure
Relief
Pressure
Min.
4 7 C
Design T.
Constant Back
P.
Variable Back P.
0.35 Bar G
10 %
Over Pressure
0.4 5 Bar G
90 C
2 0 C
Cold
2 8.01 M ol Wt
Gas
0.96686 sp g r
Compressibility
-5 C
0.1 Bar G
Diff. Test P.
4 .4 Bar G
Compressible State
Low Pressure
N itrog en
Fluid
Molecular
Weight
3300 kg /hr
Specific
Gravity
Calculated Area
1 .2 4 95 in
Specific
Heat Ratio
1 .2495 in
( Resolved
1 .4
by M aximum )
Flow Const.
356
1 .1 246 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Conventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Air): 2 777 SCFM
Inlet
Size
1 .838 in
In.
Rating
2 .04 2 in
In.
Facing
Quantity
Yes
3.0 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
4 .0 in
1 50
RF
NACE
No
Model Materials
Body
Disc
SA-2 1 6 G r. WCB
31 6 SS + Stellite (SP)
Bellows
N /A
Bonnet
Guide
Custom
SA-2 1 6 G r. WCB
31 6
SS
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 6 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Vapor
CV
FAILURE
3300 kg /hr
5392 .9 kg /hr
4 7 C
1 2 3.8 lbs
1 05.05
78.79
1 .24 95 in
Relief Temperature
Compressibility
Flow
Rupture Disk Coefficient
Relief Pressure
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
3300 kg /hr
4 7 C
356
0.8577
Critical
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Low Pressure
Nitrog en
0.96686 sp g r
1 .4
0.953
1 .2 4 95 in
Tag Notes
Farris offers a 3 " x 4 " inlet/outlet "K" orifice valve as p er REVISED sizing calculations in
lieu of 4 " x 6" inlet/outlet "M" orifice valve as sp ecified on the p rocess data sheet
15-OCT: The customer submitted new data sheets with back p ressure changed to constant and
variable. The valve model changes from op en bonnet with op en lever to closed bonnet and
p acked lever.
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 7 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 1 1 -PSV -04 2
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
CV FAILURE
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
1 0 Bar G
Design T.
Operating
Temp.
Relief Temp.
73 %
Percent Over P.
1 1 0 Bar G
7.3 Bar G
Operating to Set %
Atm Pressure
Max.
Relief
Min.
Design T.
Constant Back
P.
Variable Back P.
1 55 C
1 2 0 C
1 2 1 C
-5 C
0.1 Bar G
0.9 Bar G
Over Pressure
10 %
Pressure
Gravity
0.94 22 sp g r
Cold
1 Bar G
Diff. Test P.
9.9 Bar G
Non-Compressible State
Fluid Type
Water
Specific
Viscosity
Type
Absolute
4 00 kg /hr
Viscosity
0.2 3 Centipoise
Calculated Area
0.006093 in
Reynolds #
554 38
0.006093 in
( Resolved
by M aximum )
0.005484 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Conventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 4 5 US g pm
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .5 in
Outlet
900
Out.
Rating
RF
Out.
Facing
Size
2 .0 in
300
RF
NACE
No
Model Materials
Body
Disc
SA-2 1 6 G r. WCB
31 6 SS + Stellite (SP)
Bellows
N /A
Bonnet
Guide
Custom
SA-2 1 6 G r. WCB
31 6
SS
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 8 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Liquid
CV
FAILURE
4 00 kg /hr
984 7 kg /hr
1 21 C
0.001 4 56 lbs
0.006093 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.942 2 sp g r
0.651 6
1 0 Bar G
1
User Defined
Absolute
0.2 3 Centipoise
554 38
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
4 00 kg /hr
0.72 4
1 2 1 C
0.006093 in
Tag Notes
WITH CURRENT PROCESS CONDITIONS FARRIS SIZED TO A 1D2 , IN ORDER TO HAVE A 1. 5X2 PER DATA
SHEET REQUEST A "E" ORIFICE WOULD BE REQUIRED, FARRIS HAS OFFERED A 1. 5E2
15-OCT: The customer submitted new data sheets with back p ressure changed to constant and
variable.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 1 1 -PSV -04 2 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 9 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 1 1 -PSV -04 3
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
01
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
CV Failure
Steam
NACE
N o
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
1 0 Bar G
4 Bar G
6 Bar G
Operating to Set %
66.667
Atm Pressure
1 62 C
1 69 C
Percent Over P.
Relief
Pressure
Min.
300 C
10 %
7.61 33 Bar Abs
Design T.
Constant Back
P.
Variable Back P.
0.1 Bar G
Over Pressure
0.6 Bar G
Cold
-5 C
0.5 Bar G
Diff. Test P.
5.959 Bar G
S team S tate
Calculated Area
0.971 8 in
Req.
0.971 8 in
Flow Cap.
( Resolved
Napier
21 50 kg /hr
by M aximum )
Superheat
0.87462 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6J A1 2 A-1 4 1 /SP
API
Area
1 .2 87 in
In.
Rating
1 .4 30 in
In.
Facing
Valve Design
Conventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Steam): 6975 lb/hr
Inlet
Size
Quantity
Yes
3.0 in
Outlet
Size
300
Out.
Rating
RF
Out.
Facing
NACE
4 .0 in
1 50
RF
No
Model Materials
Body
Disc
SA-2 1 6 G r. WCB
31 6 SS + Stellite (SP)
Bellows
Bonnet
Guide
Custom
N /A
SA-2 1 6 G r. WCB
31 6
Nozzle
31 6 SS + Stellite (SP)
Spring
SS
Chrome Alloy
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Steam
CV
Failure
2 1 50 kg /hr
31 63.7 kg /hr
1 69 C
2 011-02 -2 3 16: 05
SDS246953 REV 05
1 1 8.2 8 lbs
1 05.99
79.4 93
0.971 8 in
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 0 of 1 59
Relief Pressure
Vapor Flow Factor
Superheat Factor
Napier Factor
Wsteam
K
Gas
K
CCF
P
relief
K
b
K
v
K
sh
K
n
2 1 50 kg /hr
0.8577
1
1
Relief Temperature
Discharge Coefficient
Trelief
K
d
1 69 C
0.953
0.971 8 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes. The
valve model changed from a "K" orifice to a "J" orfice with a closed bonnet and p acked lever
due to change in back p ressure. Farris size master cannot sup p ort the requested "K" orifice
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 1 1 -PSV -04 3 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 1 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 1 4 -PSV -01 8
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
1 0 Bar G
Design T.
Operating
Temp.
Relief Temp.
60 %
Percent Over P.
1 0 Bar G
6 Bar G
Operating to Set %
Atm Pressure
Max.
Relief
Min.
90 C
Design T.
Constant Back
P.
Variable Back P.
10 %
Over Pressure
1 95 C
30 C
Pressure
Gravity
0.875 sp g r
Cold
-5 C
0.1 Bar G
0.9 Bar G
1 Bar G
Diff. Test P.
9.9 Bar G
Non-Compressible State
Compressor Lube
O il
Fluid Type
Specific
1 2 0 kg /hr
Calculated Area
0.00784 9 in
Viscosity
Type
Absolute
Viscosity
372 Centipoise
Reynolds #
1 0.2 83
0.007849 in
( Resolved
by M aximum )
0.007064 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
Conventional
ASME
Area
Cap Constrn
Plain
Test Gag
Name Plate Capacity (Water): 39 US g pm
0.1 2 5 in
Yes
Size
Quantity
0.75 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
1 .00 in
1 50
RF
No
Model Materials
Body
31 6
SS
Bonnet
31 6
SS
Nozzle
31 6
SS
Disc
31 6
SS
Guide
31 6
SS
Spring
31 6
SS
Custom
A-1 93-B8 CL
2/A-1 94 -8 NU TS &
BO LTS (SP)
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 2 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Liquid
Cause of
Over P.
Blocked
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
1 2 0 kg /hr
1 91 1 .1 kg /hr
90 C
0.00784 9 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.875 sp g r
0.6759
1 0 Bar G
0.2 32 99
User Defined
Absolute
372 Centipoise
1 0.2 83
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
1 2 0 kg /hr
0.751
90 C
0.00784 9 in
Tag Notes
15-OCT: The customer submitted new data sheets with back p ressure changed to constant and
variable.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 1 4 -PSV -01 8 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 3 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 1 4 -PSV -02 1
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
7 Bar G
Design T.
Operating
Temp.
Relief Temp.
40 %
Percent Over P.
7 Bar G
2 .8 Bar G
Operating to Set %
Atm Pressure
Max.
Relief
Min.
0.1 Bar G
90 C
Design T.
Constant Back
P.
Variable Back P.
10 %
Over Pressure
0.7 Bar G
Cold
6.9 Bar G
1 95 C
2 5 C
Pressure
Gravity
0.81 5 sp g r
-5 C
0.6 Bar G
Diff. Test P.
Non-Compressible State
Fluid Type
Propionald ehyde
Specific
Viscosity
Type
Absolute
1 50 kg /hr
Viscosity
0.3 Centipoise
Calculated Area
0.002877 in
Reynolds #
1 5938
0.002877 in
( Resolved
by M aximum )
0.00259 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
Conventional
Cap Constrn
Plain
Name Plate Capacity (Water): 32
ASME
Area
Test Gag
0.1 2 5 in
Yes
Size
Quantity
0.75 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
1 .00 in
1 50
RF
No
US g pm
Model Materials
Body
31 6
SS
Bonnet
31 6
SS
Nozzle
31 6
SS
Disc
31 6
SS
Guide
31 6
SS
Spring
31 6
SS
Custom
A-1 93-B8 CL
2/A-1 94 -8 NU TS &
BO LTS (SP)
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 4 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Liquid
Cause of
Over P.
Blocked
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
1 50 kg /hr
90 C
0.002 877 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.1 84 32 m/hr
0.81 5 sp g r
0.6759
7 Bar G
0.9838
User Defined
Absolute
0.3 Centipoise
1 5938
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
1 50 kg /hr
0.751
90 C
0.002 877 in
Tag Notes
15-OCT: The customer submitted new data sheets with back p ressure changed to constant and
variable.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 1 4 -PSV -02 1 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 5 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 1 4 -PSV -030A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
01
Sizing Basis
ASME Code
Fluid State
Liquid Vaporization
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
9 Bar G
4 Bar G
9 Bar G
Operating to Set %
4 4 .4 4 4
Atm Pressure
Relief
Pressure
Design T.
Constant Back
P.
Variable Back P.
-5 C
2 03 C
Percent Over P.
Min.
2 1 0 C
21
-25 C
0.1 Bar G
0.8 Bar G
Over Pressure
Cold
1 9.4 M ol Wt
Gas
1 .89 Bar G
Diff. Test P.
8.9 Bar G
Compressible State
Fluid
G lycol / Water
Molecular
Weight
900 kg /hr
Specific
Gravity
Calculated Area
0.2 5702 in
Specific
Heat Ratio
0.25702 in
( Resolved
34 6
Compressibility
0.66966 sp g r
1 .2 9
by M axim um )
Flow Const.
0.997
0.231 32 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Conventional
Cap Constrn
Screwed Cap
Name Plate Capacity (Air): 92 3 SCFM
ASME
Area
Test Gag
Inlet
Size
0.307 in
In.
Rating
0.371 in
In.
Facing
Quantity
Yes
1 .5 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
2 .0 in
1 50
RF
No
Model Materials
Body
Bonnet
Disc
31 6SS + STELLITE
(SP)
Guide
Bellows
N /A
Custom
31 6
SS
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6SS + STELLITE
(SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 6 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Liq uid
Vaporization
900 kg /hr
1 299.1 kg /hr
203 C
42 .88 lbs
1 02 .72
77.036
0.2 5702 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
900 kg /hr
2 03 C
0.997
34 6
0.8577
Critical
1
1 1 .903 Bar Abs
1 9.4 M ol Wt
1
-
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
G lycol / Water
0.66966 sp g r
1 .29
0.953
0.25702 in
Tag Notes
3 -JUNE: VALVE IS SIZED AND QUOTED AS CONVENTIONAL VALVE, BELLOWS MATERIAL HAS BEEN REMOVED
Farris offers a 1. 5" x 2 " inlet/outlet "F" orifice valve as p er sizing calculations in lieu
of 2 " x 3 " inlet/outlet "H" orifice valve as sp ecified on the p rocess data sheet. ( 2 5-Oct-10
15-OCT: The customer submitted new data sheets with back p ressure changed to constant and
variable.
Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 7 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 1 4 -PSV -031
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
8.5 Bar G
Design T.
Operating
Temp.
Relief Temp.
2 7.059
Percent Over P.
8.5 Bar G
2 .3 Bar G
Operating to Set %
Atm Pressure
Max.
Relief
Min.
90 C
Design T.
Constant Back
P.
Variable Back P.
0.75 Bar G
10 %
Over Pressure
0.85 Bar G
1 95 C
2 0 C
Pressure
Gravity
0.749 sp g r
Cold
-5 C
0.1 Bar G
Diff. Test P.
8.4 Bar G
Non-Compressible State
Fluid Type
Solvent(Isod od ecane)
Specific
Viscosity
Type
Absolute
1 70 kg /hr
Viscosity
1 .34 Centipoise
Calculated Area
0.0031 59 in
Reynolds #
4 044 .1
0.0031 59 in
( Resolved
by M aximum )
0.002843 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
Conventional
ASME
Area
Cap Constrn
Plain
Test Gag
Name Plate Capacity (Water): 36 US g pm
0.1 2 5 in
Yes
Size
Quantity
0.75 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
1 .00 in
1 50
RF
No
Model Materials
Body
31 6
SS
Bonnet
31 6
SS
Nozzle
31 6
SS
Disc
31 6
SS
Guide
31 6
SS
Spring
31 6
SS
Custom
A-1 93-B8 CL
2/A-1 94 -8 NU TS &
BO LTS (SP)
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 8 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Liquid
Cause of
Over P.
Blocked
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
1 70 kg /hr
6727.2 kg /hr
90 C
0.001 32 3 lbs
0.0031 59 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.22 73 m/hr
0.74 9 sp g r
0.6759
8.5 Bar G
0.961 4 6
User Defined
Absolute
1 .34 Centipoise
4 04 4 .1
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
1 70 kg /hr
0.751
90 C
0.0031 59 in
Tag Notes
15-OCT: The customer submitted new data sheets with back p ressure changed to constant and
variable.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 1 4 -PSV -031 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 9 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 1 4 -PSV -051
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
1 0 Bar G
2 .9 Bar G
1 0 Bar G
Operating to Set %
29
Atm Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
90 C
Design T.
Constant Back
P.
Variable Back P.
10 %
Over Pressure
30 C
Percent Over P.
Relief
Min.
1 95 C
Pressure
Gravity
0.859 sp g r
Cold
-5 C
0.1 Bar G
0.9 Bar G
1 Bar G
Diff. Test P.
9.9 Bar G
Non-Compressible State
Compressor
Cooling O il
Fluid Type
Specific
1 2 0 kg /hr
Calculated Area
0.005033 in
Viscosity
Type
Absolute
Viscosity
1 37 Centipoise
Reynolds #
2 7.92 1
0.005033 in
( Resolved
by M aximum )
0.004529 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
Conventional
ASME
Area
Cap Constrn
Plain
Test Gag
Name Plate Capacity (Water): 39 US g pm
0.1 2 5 in
Yes
Size
Quantity
0.75 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
1 .00 in
1 50
RF
No
Model Materials
Body
31 6
SS
Bonnet
31 6
SS
Nozzle
31 6
SS
Disc
31 6
SS
Guide
31 6
SS
Spring
31 6
SS
Custom
A-1 93-B8 CL
2/A-1 94 -8 NU TS &
BO LTS (SP)
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 1
VP-4400-427-001 -ALL-002_05
Page 20 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Liquid
Cause of
Over P.
Blocked
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
1 2 0 kg /hr
2 980.5 kg /hr
90 C
5.747e-4 lbs
0.005033 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.859 sp g r
0.6759
1 0 Bar G
0.36672
User Defined
Absolute
1 37 Centipoise
2 7.92 1
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
1 2 0 kg /hr
0.751
90 C
0.005033 in
Tag Notes
15-OCT: The customer submitted new data sheets with back p ressure changed to constant and
variable.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 1 4 -PSV -051 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 21 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 1 6-PSV -02 8A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
G AS EXPANSIO N
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
2 9 Bar G
Design T.
Operating
Temp.
Relief Temp.
86.2 07
Percent Over P.
2 9 Bar G
2 5 Bar G
Operating to Set %
Atm Pressure
Relief
Pressure
Min.
Design T.
Constant Back
P.
Variable Back P.
90 C
50 C
1 75 C
-5 C
0.1 Bar G
2 .8 Bar G
Over Pressure
6.09 Bar G
Cold
2 8.9 Bar G
2 8.96 M ol Wt
Gas
0.99965 sp g r
Compressibility
21
Diff. Test P.
Compressible State
Fluid
Molecular
AIR
Weight
1 4 000 kg /hr
Specific
Gravity
Calculated Area
1 .02 39 in
Specific
Heat Ratio
1 .0239 in
( Resolved
1 .4
by M aximum )
Flow Const.
356
1 .01
0.921 51 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6J A1 2A-1 4 1 /S3/SP
API
Area
1 .2 87 in
In.
Rating
1 .4 30 in
In.
Facing
Valve Design
Conventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Air): 1 0733 SCFM
Inlet
Size
Quantity
Yes
3.0 in
Outlet
300
Out.
Rating
RF
Out.
Facing
Size
4 .0 in
1 50
RF
NACE
No
Model Materials
Body
SA-351 G r. CF8M
Bonnet
Disc
31 6SS + STELLITE
(SP)
Guide
Bellows
N /A
Custom
SA-351 G r. CF8M
31 6
SS
A320-B8
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6SS + STELLITE
(SP)
Chrome Alloy N P
Page 1
VP-4400-427-001 -ALL-002_05
Page 22 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Over P.
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
G AS
1 4 000 kg /hr
EXPANS IO N
1 9553 kg /hr
1 75 C
1 1 3.85
85.391
1 .02 39 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
1 4 000 kg /hr
1 75 C
1 .01
356
0.8577
Critical
1
36.1 03 Bar Abs
2 8.96 M ol Wt
1
-
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
AIR
0.99965 sp g r
1 .4
0.953
1 .02 39 in
Tag Notes
2 -DEC: The customer submitted new data sheets with cap acity and back p ressure changes. The
valve model changed from a "K" orifice to a "J" orfice with a closed bonnet and p acked lever
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 23 of 1 59
T ag
P Q -1 0 1 7 9 0 : 2 1 6 -P S V
-0 2 9 A
- D a ta
D ate Prepared:
S h e e t
2 0 1 1 -0 7 -0 1 1 5 :2 6
C u sto m er
R eq u isitio n #
Job #
D aelim
J o b D e sc r ip tio n
P Q -1 0 1 7 9 0
P repared B y
C h eck ed B y
S a u d i K a y a n L D P E P ro je c t
A p p roved B y
J o b S ta tu s
R e v is io n #
S iz in g /S e le c tin g
PSV Identification
T ag
T ag D escrip tion
T a g S ta tu s
Drawing #
Issu e F o r
2 1 6 -P S V -0 2 9 A
Plant
P / ID
D isch a rg e T o
R e v is io n #
O utlet Line #
R e v is e d B y
V a lv e S e le c te d
Index #
S e r v ic e
Inlet Line #
S iz in g B a s is
ASM E
Code
C a u se o f O v e r P r e ssu r e
F luid State
C V Failure
V a p o r (M a ss)
NACE
N o
N o R u p tu re D isk , 1
P r o c e s s P a r a m e te r s
MAWP
M ax. D esign T.
1 0 .3 B a r G
O perating
4 .5 B a r G
P ressu re
S et P ressu re
O perating to Set %
4 3 .6 8 9
A tm P ressu re
Tem p.
P ercen t O ver P .
R e lie f P r e ssu r e
1 .0 1 3 3 B ar A b s
M in. Design T.
5 0 C
5 0 C
V ariable Back P.
0 .9 3 B a r G
O v e r P r e ssu r e
1 .0 3 B a r G
1 0 .2 B a r G
O perating
R elief T em p.
1 0 .3 B a r G
9 0 C
10
1 2 .3 4 3 B ar A b s
-5 C
C o n sta n t B a ck
0 .1 B a r G
P .
C o m p r e s s ib le S ta te
Fluid
Air
M olecular W eight
2 8 .9 6 Mol Wt
G a s F lo w C o n st.
0 .9 9 9 6 5 s p g r
C o m p ressib ility
3 0 0 0 kg/hr
S p ecific G ravity
C alculated A rea
0 .5 4 2 2 5 in
R e so lv e d A S M E A re a :
0 .5 4 2 2 5 in
1 .4
R e so lv e d A P I A re a :
(R eso lv ed b y M ax im u m )
356
0 .4 8 8 0 2 in
M o d e l S e le c tio n
F a rris
API Letter
2 6 G A 1 0 A -1 4 1 /S 3 /S P
API Area
ASME Area
Manufacturer
V a lv e D e sig n
C ap
C o n v e n tio n a l
C onstrn
Nam e
T est G a g
Packed L ever
Inlet Size
1 .5 in
O u tlet S ize
3 .0 in
0 .5 0 3 in
In. Rating
150
Out. Rating
150
0 .5 5 9 in
In. Facing
Quantity
Y es
RF
O ut. F acing
NACE
RF
N o
M odel M aterials
B ody
S A -351 G r. C F 8M
D is c
316
B e llo w s
B onnet
S A -351 G r. C F 8M
G uide
SS
C u sto m
N/A
316
N o z z le
S p rin g
SS
S P = P M I N o z z le a n d
D isc (S P )
316
SS
C hrom e A lloy N P
S iz in g S c e n a r io s
S c e n a r io
Fluid
C a u s e o f
R elief L oad
S ta te
O ver P.
C apacity
Relief T.
R e a c t. F o r c e
N o is e
N o is e
R equired
Atm (dBa)
Flare (dBa)
Area
CV
C ase A
V apor
3 0 0 0 k g /h r
3 0 9 2 .7 k g /h r
50 C
7 0 .1 4 8 lb s
1 0 3 .3 2
7 7 .4 9 3
0 .5 4 2 2 5 in
F a ilu re
2 0 1 1 -0 7 -0 1
1 5 :2 6
SDS246953 REV 05
P age
VP-4400-427-001 -ALL-002_05
Page 24 of 1 59
T ag
P Q -1 0 1 7 9 0 : 2 1 6 -P S V
-0 2 9 A
- D a ta
S h e e t
R e lie f T e m p e r a tu r e
W vapor
Trelief
Z
K
G as
Flow
K CCF
P relief
M vapor
Kb
Kv
C o m p r e s s ib ilit y
G a s F lo w C o n s t a n t
D is c h a r g e C o e ff. (0 .9 x K d )
F lo w
R u p tu r e D is k C o e ffic ie n t
R e lie f P r e s s u r e
M o le c u la r W e ig h t
V a p o r F lo w F a c to r
V a p o r F lo w F a c to r
3 0 0 0 k g /h r
5 0 C
356
0 .8 5 7 7
C ritical
F lu id T y p e (U s e r D e fin e d )
G gas
k
Kd
S p e c ific G r a v ity
1 2 .3 4 3 B a r A b s
R a t io o f S p e c if ic H e a t s
2 8 .9 6 M ol W t
D is c h a r g e C o e f f ic ie n t
Air
0 .9 9 9 6 5 s p g r
1 .4
0 .9 5 3
0 .5 4 2 2 5 in
T a g N o te s
F a r r is
in
o f f e r s
lie u
o f
1 "
(2 5 -O c t-1 0
1 .5 "
2 "
3 "
in le t/o u tle t
in le t/o u tle t
c u s to m e r
" D "
c o n firm e d
" G "
o r if ic e
o r if ic e
o rific e
v a lv e
v a lv e
a s
a s
p e r
R E V I S E D
s p e c if ie d
o n
th e
s iz in g
p r o c e s s
c a lc u la tio n s
d a ta
s h e e t.
s e le c tio n .)
F a rris
p ro p o s e s
th e r e o f
th e
f o r
r e v is e d
v a lv e s
to
c o n s ta n t
m e a n s
c h a n g e
th e s e
c u s to m e r
c o m p e n s a te
d o w n s tre a m
th a t
th e
in
v a lv e s .
d a ta
fo r
v a lv e
T h is
c o n s tru c tio n
d u e
s h e e ts .
th e
to
h e n
c o n s ta n t
p re s s u re
c o n s ta n t
is
in
b a c k
th e
th e
o p e n
p r o c e s s in g
b a c k
p re s s u re .
s y s te m
p r e s s u r e
fro m
a d d itio n
to
m a y
o f
th e s e
T h e
e s c a p e
n o t
b o n n e t
o p e n
o r
th e
m a y
o p e n
b a c k
v a lv e s ,
th ru
e x is t,
a n d
c o n s ta n t
le v e r
p r e s s u r e
F a r r is
w ill
o r
c o m b in a tio n
a s
" n e t
f o u n d
s e t"
b o n n e t/le v e r
d e s ig n
o p e n
a n d
/o r
to
f lu id
b e
b o n n e t
lo w e r
d u e
o n
th e
a llo w s
th e
le v e r.
T h is
e s c a p e .
I n
th e
f ie ld ,
th e
T h e re fo re ,
F a rris
to
s o
p a c k e d ,
th e
v a lv e
a y
n o t
w o u ld
lik e
to
v a lv e
w ill
b e
r e lie v e
c h a n g e
a t
th e
a s s u r e d
o f
th e
d e s ir e d
b o n n e t
p r o p e r
fro m
s e t
o p e n
p r e s s u r e
to
c lo s e d
( I t
a n d
ill
th e
r e lie v e
le v e r
e a r ly ) .
fro m
o p e n
o p e r a tio n .
S te a m
J a c k e t
S te a m
Jacket R em oved
P e r C u s to m e r R e q u e s t 0 9 -M A R -2 0 1 1
S iz e M a s te r 4 .3 .2 .9 , D B : K :\A p p s \P r o je c ts \2 0 1 0 O r d e r s \2 4 6 9 5 3 -
D A E L IM \S M P 2 4 6 9 5 3 _ 2 5 2 1 6 4
2 0 1 1 -0 7 -0 1
S h e e t
1 5 :2 6
SDS246953 REV 05
E n d o f 2 1 6 - P S V - 0 2 9 A D a ta
P ag e
VP-4400-427-001 -ALL-002_05
Page 25 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 1 7-PSV -003
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Liquid Vaporization
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
1 .034 3 Bar G
0.1 Bar G
1 .034 3 Bar G
Operating to Set %
9.6684
Atm Pressure
Relief
Pressure
Design T.
Constant Back
P.
Variable Back P.
50 C
1 50 C
Percent Over P.
Min.
2 50 C
21
2 .2 64 8 Bar Abs
-5 C
0.05 Bar G
0.05 Bar G
Over Pressure
0.2 1 72 Bar G
Cold
0.9843 Bar G
Diff. Test P.
Compressible State
Fluid
Molecular Weight
1 4 600 kg /hr
Specific
Gravity
Calculated Area
7.5739 in
Specific
Heat Ratio
7.5739 in
( Resolved
1 70.3 M ol Wt
Compressibility
5.8785 sp g r
1 .03
by M aximum )
31 9
6.81 65 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6Q A1 0-1 2 1 /SP
API
Area
Valve Design
Conventional
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 6309 SCFM
Inlet
Size
1 1 .05 in
In.
Rating
1 2 .2 7 in
In.
Facing
Quantity
Yes
6.0 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
8.0 in
1 50
RF
No
Model Materials
Body
SA-2 1 6 G r. WCB
Bonnet
Disc
31 6SS + STELLITE
(SP)
Guide
Bellows
N /A
Custom
SA-2 1 6 G r. WCB
31 6
SS
A1 93-B7/A1 94 -2 H
(SP)
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6SS + STELLITE
(SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 26 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Liquid
1 4 600 kg /hr
Vaporization
2 3652 kg /hr
1 50 C
2 36.1 lbs
89.054
66.791
7.5739 in
Relief Temperature
Compressibility
Flow
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
1 4 600 kg /hr
1 50 C
31 9
0.8577
Critical
1
2 .2 64 8 Bar Abs
Specific Gravity
1 70.3 M ol Wt
1
-
Discharge Coefficient
Ggas
k
K
d
5.8785 sp g r
1 .03
0.953
7.5739 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
Set p ressure adj usted to 1. 03 4 3 Barg to reflect 15 PSIG, to offer Code valve. Customer to
confirm.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 1 7-PSV -003 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 27 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 1 7-PSV -004
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Liquid Vaporization
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
1 .034 3 Bar G
0.1 Bar G
1 .034 3 Bar G
Operating to Set %
9.6684
Atm Pressure
Relief
Pressure
Design T.
Constant Back
P.
Variable Back P.
50 C
1 50 C
Percent Over P.
Min.
2 50 C
21
2 .2 64 8 Bar Abs
-5 C
0.05 Bar G
0.05 Bar G
Over Pressure
0.2 1 72 Bar G
Cold
0.9843 Bar G
Diff. Test P.
Compressible State
Fluid
Molecular Weight
1 4 600 kg /hr
Specific
Gravity
Calculated Area
7.5739 in
Specific
Heat Ratio
7.5739 in
( Resolved
1 70.3 M ol Wt
Compressibility
5.8785 sp g r
1 .03
by M aximum )
31 9
6.81 65 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6Q A1 0-1 2 1 /SP
API
Area
Valve Design
Conventional
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 6309 SCFM
Inlet
Size
1 1 .05 in
In.
Rating
1 2 .2 7 in
In.
Facing
Quantity
Yes
6.0 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
8.0 in
1 50
RF
No
Model Materials
Body
SA-2 1 6 G r. WCB
Bonnet
Disc
31 6SS + STELLITE
(SP)
Guide
Bellows
N /A
Custom
SA-2 1 6 G r. WCB
31 6
SS
A1 94 -B7/A1 94 -2 H
(SP)
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6SS + STELLITE
(SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 28 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Liquid
1 4 600 kg /hr
Vaporization
2 3652 kg /hr
1 50 C
2 36.1 lbs
89.054
66.791
7.5739 in
Relief Temperature
Compressibility
Flow
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
1 4 600 kg /hr
1 50 C
31 9
0.8577
Critical
1
2 .2 64 8 Bar Abs
Specific Gravity
1 70.3 M ol Wt
1
-
Discharge Coefficient
Ggas
k
K
d
5.8785 sp g r
1 .03
0.953
7.5739 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
Farris has increased set p ressure from 1 Barg to 1. 03 4 3 Barg to offer a Code valve with a set
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 1 7-PSV -004 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 29 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 0-PSV -005
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
G as Expansion
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
60 Bar G
Design T.
Operating
Temp.
Relief Temp.
50.833
Percent Over P.
60 Bar G
30.5 Bar G
Operating to Set %
Atm Pressure
Max.
Relief
Pressure
Min.
90 C
38 C
304 C
21
Design T.
Constant Back
P.
Variable Back P.
0.4 1 Bar G
Over Pressure
1 2 .6 Bar G
Cold
4 2 .08 M ol Wt
Gas
1 .4 52 5 sp g r
Compressibility
-46 C
3 Bar G
Diff. Test P.
60 Bar G
Compressible State
Fluid
Propylene
Molecular
800 kg /hr
Specific
Gravity
Calculated Area
0.02 7564 in
Specific
Heat Ratio
0.027564 in
Weight
( Resolved
1 .1 6
Flow Const.
0.92
by M aximum )
333
0.024808 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Bellows
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 2 2 92 SCFM
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
600
Out.
Rating
RF
Out.
Facing
Size
NACE
2 .0 in
1 50
RF
No
Model Materials
Body
Bonnet
Disc
31 6SS + STELLITE
(SP)
Guide
Bellows
Inconel Composite
Custom
31 6
SS
M aterial to be
A32 0-L7/A1 94 -4 .
(SP)
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6SS + STELLITE
(SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 30 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Vapor
G as
Expansion
800 kg /hr
4 353.5 kg /hr
304 C
1 62 .4 4 lbs
1 06.07
79.551
0.02 7564 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
800 kg /hr
304 C
0.92
333
0.8577
Critical
1
73.61 3 Bar Abs
4 2 .08 M ol Wt
1
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Propylene
1 .4 52 5 sp g r
1 .1 6
0.953
0.027564 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes. T
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 0-PSV -005 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 31 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 0-PSV -01 4 A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
Blocked O utlet
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
60 Bar G
Design T.
Operating
Temp.
Relief Temp.
80 %
Percent Over P.
60 Bar G
4 8 Bar G
Operating to Set %
Atm Pressure
Max.
Relief
Pressure
Min.
Design T.
Constant Back
P.
Variable Back P.
1 95 C
1 00 C
4 07 C
-46 C
3 Bar G
0.38 Bar G
Over Pressure
10 %
67.01 3 Bar Abs
Cold
4 2 .08 M ol Wt
Gas
1 .4 52 5 sp g r
Compressibility
6 Bar G
Diff. Test P.
60 Bar G
Compressible State
Fluid
Propylene
Molecular
2 000 kg /hr
Specific
Gravity
Calculated Area
0.052 1 87 in
Specific
Heat Ratio
0.0521 87 in
Weight
( Resolved
1 .1 1
Flow Const.
32 8
0.36
by M aximum )
0.046969 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Bellows
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Air): 2 2 92 SCFM
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Yes
Quantity
1 .0 in
Outlet
600
Out.
Rating
RF
Out.
Facing
Size
2 .0 in
1 50
RF
NACE
No
Model Materials
Body
Bonnet
Disc
31 6SS + STELLITE
(SP)
Guide
Bellows
31 6L SS (SP)
31 6
SS
Spring
31 6SS + STELLITE
(SP)
Chrome Alloy
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Page 1
VP-4400-427-001 -ALL-002_05
Page 32 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Vapor
Blocked
O utlet
2 000 kg /hr
4 07 C
1 4 3.24 lbs
1 07.8
80.848
0.0521 87 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
2000 kg /hr
4 07 C
0.36
32 8
0.8577
Critical
1
67.01 3 Bar Abs
4 2 .08 M ol Wt
1
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Propylene
1 .4 52 5 sp g r
1 .1 1
0.953
0.052 1 87 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 33 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 0-PSV -01 5
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Liquid Vaporization
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
9 Bar G
4 Bar G
9 Bar G
Operating to Set %
4 4 .4 4 4
Atm Pressure
Relief
Pressure
Design T.
Constant Back
P.
Variable Back P.
-5 C
2 05 C
Percent Over P.
Min.
90 C
21
-20 C
0.1 Bar G
0.8 Bar G
Over Pressure
Cold
2 2 .9 M ol Wt
Gas
1 .89 Bar G
Diff. Test P.
8.9 Bar G
Compressible State
Fluid
G lycol/Water
Molecular
Weight
1 1 00 kg /hr
Specific
Gravity
Calculated Area
0.2 8726 in
Specific
Heat Ratio
0.28726 in
( Resolved
Flow Const.
Compressibility
0.7904 7 sp g r
1 .2 9
0.98
by M axim um )
34 6
0.25854 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Conventional
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 1 391 SCFM
Inlet
Size
0.503 in
In.
Rating
0.559 in
In.
Facing
Quantity
Yes
1 .5 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
3.0 in
1 50
RF
No
Model Materials
Body
Bonnet
Disc
31 6 SS + Stellite (SP)
Guide
Bellows
N /A
Custom
31 6
SS
M aterial to be
A320-L7/A1 94 -4.
(SP)
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 34 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Liq uid
Vaporization
1 1 00 kg /hr
2 1 4 0.5 kg /hr
205 C
64 .61 lbs
1 04 .1 8
78.1 36
0.2 872 6 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
1 1 00 kg /hr
2 05 C
0.98
34 6
0.8577
Critical
1
1 1 .903 Bar Abs
2 2 .9 M ol Wt
1
-
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
G lycol/Water
0.7904 7 sp g r
1 .29
0.953
0.2872 6 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 0-PSV -01 5 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 35 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 0-PSV -01 6A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
01
Sizing Basis
ASME Code
Fluid State
Liquid Vaporization
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
7 Bar G
0.4 Bar G
7 Bar G
Operating to Set %
5.71 4 3
Atm Pressure
1 5 C
1 32 C
Percent Over P.
Relief
Pressure
Min.
2 00 C
21
Design T.
Constant Back
P.
Variable Back P.
0.76 Bar G
Over Pressure
1 .4 7 Bar G
Cold
58.08 M ol Wt
Gas
2 .004 8 sp g r
Compressibility
-5 C
3 Bar G
Diff. Test P.
7 Bar G
Compressible State
Fluid
3600 kg /hr
Specific
Gravity
Calculated Area
0.64 64 in
Specific
Heat Ratio
0.6464 in
( Resolved
1 .2
by M aximum )
Flow Const.
337
0.835
0.581 76 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Bellows
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 1 735 SCFM
Inlet
Size
0.785 in
In.
Rating
0.873 in
In.
Facing
Quantity
Yes
1 .5 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
3.0 in
1 50
RF
NACE
No
Model Materials
Body
Disc
Bellows
SA-351 G r. CF8M
31 6
SS
31 6L SS (SP)
Bonnet
Guide
Custom
SA-351 G r. CF8M
31 6
SS
A1 93-B8 CL.
2 /A1 94 -8 (SP)
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6
S S
Chrome Alloy N P
Page 1
VP-4400-427-001 -ALL-002_05
Page 36 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Liquid
Vaporization
3600 kg /hr
4 862 kg /hr
1 32 C
77.04 6 lbs
86.4 41
64 .831
0.6464 in
Relief Temperature
Compressibility
Flow
Rupture Disk Coefficient
Relief Pressure
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
3600 kg /hr
1 32 C
0.835
337
0.8577
Critical
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Propionic
Ald ehyd e
2 .004 8 sp g r
1 .2
0.953
0.64 64 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 37 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 0-PSV -01 7
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
G as Expansion
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
60 Bar G
Design T.
Operating
Temp.
Relief Temp.
83.333
Percent Over P.
60 Bar G
50 Bar G
Operating to Set %
Atm Pressure
Max.
Relief
Pressure
Min.
1 95 C
35 C
304 C
21
Design T.
Constant Back
P.
Variable Back P.
0.4 3 Bar G
Over Pressure
1 2 .6 Bar G
Cold
4 2 .08 M ol Wt
Gas
1 .4 52 5 sp g r
Compressibility
-46 C
3 Bar G
Diff. Test P.
60 Bar G
Compressible State
Fluid
Propylene
Molecular
800 kg /hr
Specific
Gravity
Calculated Area
0.02 7564 in
Specific
Heat Ratio
0.027564 in
Weight
( Resolved
1 .1 6
Flow Const.
0.92
0.024808 in
by M aximum )
333
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Bellows
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 2 2 92 SCFM
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
600
Out.
Rating
RF
Out.
Facing
Size
NACE
2 .0 in
1 50
RF
No
Model Materials
Body
Disc
31 6
Bellows
SS + S TELLITE (SP)
Inconel Composite
Bonnet
Guide
Custom
31 6
SS
M aterial to be
A32 0-L7/A1 94 -4 .
(SP)
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6
S S + STELLITE (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 38 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Vapor
G as
Expansion
800 kg /hr
4 353.5 kg /hr
304 C
1 62 .4 4 lbs
1 06.07
79.551
0.02 7564 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
800 kg /hr
304 C
0.92
333
0.8577
Critical
1
73.61 3 Bar Abs
4 2 .08 M ol Wt
1
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Propylene
1 .4 52 5 sp g r
1 .1 6
0.953
0.027564 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 0-PSV -01 7 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 39 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 0-PSV -01 8
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
G as Expansion
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
60 Bar G
Design T.
Operating
Temp.
Relief Temp.
83.333
Percent Over P.
60 Bar G
50 Bar G
Operating to Set %
Atm Pressure
Max.
Relief
Pressure
Min.
1 95 C
35 C
304 C
21
Design T.
Constant Back
P.
Variable Back P.
0.4 3 Bar G
Over Pressure
1 2 .6 Bar G
Cold
4 2 .08 M ol Wt
Gas
1 .4 52 5 sp g r
Compressibility
-46 C
3 Bar G
Diff. Test P.
60 Bar G
Compressible State
Fluid
Propylene
Molecular
800 kg /hr
Specific
Gravity
Calculated Area
0.02 7564 in
Specific
Heat Ratio
0.027564 in
Weight
( Resolved
1 .1 6
Flow Const.
0.92
0.024808 in
by M aximum )
333
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Bellows
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 2 2 92 SCFM
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
600
Out.
Rating
RF
Out.
Facing
Size
NACE
2 .0 in
1 50
RF
No
Model Materials
Body
Disc
31 6
Bellows
SS + S TELLITE (SP)
Inconel Composite
Bonnet
Guide
Custom
31 6
SS
M aterial to be
A32 0-L7/A1 94 -4 .
(SP)
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6
S S + STELLITE (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 40 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Vapor
G as
Expansion
800 kg /hr
4 353.5 kg /hr
304 C
1 62 .4 4 lbs
1 06.07
79.551
0.02 7564 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
800 kg /hr
304 C
0.92
333
0.8577
Critical
1
73.61 3 Bar Abs
4 2 .08 M ol Wt
1
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Propylene
1 .4 52 5 sp g r
1 .1 6
0.953
0.027564 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 0-PSV -01 8 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 41 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 0-PSV -02 0
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Pum p blocked in
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
1 1 5 Bar G
1 03 Bar G
1 1 5 Bar G
Operating to Set %
Atm Pressure
89.565
Max.
Design T.
Operating
Temp.
Relief Temp.
4 8.4 C
4 8.4 C
Percent Over P.
Relief
Min.
1 95 C
10 %
Pressure
Gravity
0.785 sp g r
Design T.
Constant Back
P.
Variable Back P.
0.39 Bar G
Over Pressure
1 1 .5 Bar G
Cold
-5 C
3 Bar G
Diff. Test P.
1 2 2 .02 Bar G
Non-Compressible State
Specific
(PA)
Fluid Type
1 1 0 kg /hr
Calculated Area
5.339e-4 in
5.339e-4 in
Viscosity
Type
Absolute
Viscosity
0.3 Centipoise
Reynolds #
1 1 688
( Resolved
by M aximum )
4.805e-4 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Bellows
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Water): 1 57 US g pm
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .5 in
Outlet
900
Out.
Rating
RF
Out.
Facing
Size
NACE
2 .0 in
300
RF
No
Model Materials
Body
SA-351 G r. CF8M
Bonnet
Disc
31 6 SS Stellite (SP)
Guide
Bellows
Inconel Composite
Custom
SA-351 G r. CF8M
31 6
SS
A-1 93-B8 CL
BO LTS (SP)
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6 SS Stellited (SP)
31 6
S S
Page 1
VP-4400-427-001 -ALL-002_05
Page 42 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Liquid
Pump
blocked in
1 1 0 kg /hr
30906 kg /hr
4 8.4 C
5.339e-4 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.785 sp g r
0.651 6
1 2 3.1 1 Bar G
0.98002
1
User Defined
Absolute
0.3 Centipoise
1 1 688
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
1 1 0 kg /hr
0.72 4
4 8.4 C
5.339e-4 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes. The
customer requested the valve model be changed from a p ilot control valve to a bellows typ e
Farris would like to p rop ose a 316SS stellited nozzle and disc in leiu of the 3 4 7SS stellited
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes. The
valve model changed from a "K" orifice to a "J" orfice with a closed bonnet and p acked lever
due to change in back p ressure. Farris size master cannot sup p ort the requested "K" orifice
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 0-PSV -02 0 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 43 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 0-PSV -02 1
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Pum p blocked in
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
1 1 5 Bar G
1 03 Bar G
1 1 5 Bar G
Operating to Set %
Atm Pressure
89.565
Max.
Design T.
Operating
Temp.
Relief Temp.
4 8.4 C
4 8.4 C
Percent Over P.
Relief
Min.
1 95 C
10 %
Pressure
Gravity
0.785 sp g r
Design T.
Constant Back
P.
Variable Back P.
0.39 Bar G
Over Pressure
1 1 .5 Bar G
Cold
-5 C
3 Bar G
Diff. Test P.
1 2 2 .02 Bar G
Non-Compressible State
Specific
(PA)
Fluid Type
1 1 0 kg /hr
Calculated Area
5.339e-4 in
5.339e-4 in
Viscosity
Type
Absolute
Viscosity
0.3 Centipoise
Reynolds #
1 1 688
( Resolved
by M aximum )
4.805e-4 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Bellows
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Water): 1 57 US g pm
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .5 in
Outlet
900
Out.
Rating
RF
Out.
Facing
Size
NACE
2 .0 in
300
RF
No
Model Materials
Body
SA-351 G r. CF8M
Bonnet
Disc
31 6 SS Stellited (SP)
Guide
Bellows
Inconel Composite
Custom
SA-351 G r. CF8M
31 6
SS
A-1 93-B8 CL
BO LTS (SP)
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6 SS Stellited (SP)
31 6
S S
Page 1
VP-4400-427-001 -ALL-002_05
Page 44 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Liquid
Pump
blocked in
1 1 0 kg /hr
30906 kg /hr
4 8.4 C
5.339e-4 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.785 sp g r
0.651 6
1 2 3.1 1 Bar G
0.98002
1
User Defined
Absolute
0.3 Centipoise
1 1 688
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
1 1 0 kg /hr
0.72 4
4 8.4 C
5.339e-4 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes. The
customer requested the valve model be changed from a p ilot control valve to a bellows typ e
Farris would like to p rop ose a 316SS stellited nozzle and disc in leiu of the 3 4 7SS stellited
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 0-PSV -02 1 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 45 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 0-PSV -02 3A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
CV FAILURE
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
8 Bar G
Design T.
Operating
Temp.
Relief Temp.
3.75 %
Percent Over P.
8 Bar G
0.3 Bar G
Operating to Set %
Atm Pressure
Relief
Pressure
Min.
1 C
Design T.
Constant Back
P.
Variable Back P.
10 %
Over Pressure
1 95 C
4 5 C
-5 C
3 Bar G
0.4 6 Bar G
0.8 Bar G
Cold
Diff. Test P.
2 8.05 M ol Wt
Gas
0.9682 4 sp g r
Compressibility
8 Bar G
Compressible State
Booster
Com pressor G as
Fluid
Molecular
Weight
4 74 00 kg /hr
Specific
Gravity
Calculated Area
9.7579 in
Specific
Heat Ratio
9.7579 in
( Resolved
1 .34
by M aximum )
Flow Const.
351
0.91
8.7821 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6RB1 2 -1 21 /SP
API
Area
Valve Design
Bellows
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 39789 SCFM
Inlet
Size
1 6.00 in
In.
Rating
1 7.78 in
In.
Facing
Quantity
Yes
6.0 in
Outlet
300
Out.
Rating
RF
Out.
Facing
Size
NACE
1 0.0 in
1 50
RF
No
Model Materials
Body
Disc
SA-2 1 6 G r. WCB
31 6
Bellows
SS + S TELLITE (SP)
31 6L SS (SP)
Bonnet
Guide
Custom
SA-2 1 6 G r. WCB
31 6
SS
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6
S S + STELLITE (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 46 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Vapor
CV
4 74 00 kg /hr
FAILURE
86368 kg /hr
1 C
2 1 82 .5 lbs
1 04 .4 3
78.32
9.7579 in
Relief Temperature
Compressibility
Flow
Rupture Disk Coefficient
Relief Pressure
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
4 74 00 kg /hr
1 C
0.91
351
0.8577
Critical
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Booster
Compressor G as
0.9682 4 sp g r
1 .34
0.953
9.7579 in
Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 47 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 0-PSV -02 8
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Steam
NACE
N o
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
1 0 Bar G
Design T.
Operating
Temp.
Relief Temp.
45 %
Percent Over P.
1 0 Bar G
4 .5 Bar G
Operating to Set %
Atm Pressure
Relief
Pressure
Min.
90 C
38 C
1 92 C
21
Design T.
Constant Back
P.
Variable Back P.
0.1 Bar G
Over Pressure
2 .1 Bar G
Cold
9.9 Bar G
-5 C
0.9 Bar G
Diff. Test P.
S team S tate
Calculated Area
0.2 624 2 in
Req.
0.26242 in
Flow Cap.
( Resolved
Napier
1 000 kg /hr
Superheat
0.2361 8 in
by M axim um )
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Conventional
ASME
Inlet
Area
Size
0.307 in
In.
Rating
0.371 in
In.
Facing
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Steam): 2 855 lb/hr
Quantity
Yes
1 .5 in
Outlet
Size
1 50
Out.
Rating
RF
Out.
Facing
NACE
2 .0 in
1 50
RF
No
Model Materials
Body
Disc
SA-2 1 6 G r. WCB
31 6
SS + S TELLITE (SP)
Bellows
Bonnet
Guide
31 6
Custom
N /A
SA-2 1 6 G r. WCB
Nozzle
31 6
Spring
SS
S S + STELLITE (SP)
Chrome Alloy
Sizing Scenarios
Scenario
Fluid
State
C ase A
Steam
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Liq uid
Vaporization
1 000 kg /hr
1 41 3.8 kg /hr
1 92 C
2 011-02 -2 3 16: 05
SDS246953 REV 05
52 .855 lbs
1 03.4 8
77.61 2
0.2624 2 in
Page 1
VP-4400-427-001 -ALL-002_05
Page 48 of 1 59
Relief Pressure
Vapor Flow Factor
Superheat Factor
Napier Factor
Wsteam
K
Gas
K
CCF
P
relief
K
b
K
v
K
sh
K
n
1 000 kg /hr
0.8577
1
1
Relief Temperature
Discharge Coefficient
Trelief
K
d
1 92 C
0.953
0.2 62 42 in
Tag Notes
9-JUNE: FLUID STATE HAS BEEN CHENGED TO VAPOR, VALVE CHENGED TO 1. 5F2
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 0-PSV -02 8 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 49 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Daelim
Job Description
PQ -1 01 790
Prepared By
Checked By
Approved By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 0-PSV -031
P / ID
Discharge To
Revision #
Valve Selected
Plant #
Drawing #
Index #
Issue For
Service
Inlet Line #
Outlet Line #
Revised By
Sizing Basis
ASME Code
Fluid State
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
7 Bar G
3.5 Bar G
7 Bar G
Operating to Set %
Atm Pressure
Percent
50 %
Relief
40 C
Design T.
Constant Back
P.
Variable Back P.
10 %
Over
Pressure
Cold
Diff. Test P.
2 8.05 M ol Wt
Gas
0.9682 4 sp g r
Compressibility
40 C
Over P.
Pressure
Min.
1 95 C
-5 C
3 Bar G
0.32 Bar G
0.7 Bar G
7 Bar G
Compressible State
Fluid
Ethylene
Molecular
Weight
3400 kg /hr
Specific
Gravity
Calculated Area
0.79696 in
Specific
Heat Ratio
0.79696 in
( Resolved
1 .6
Flow Const.
0.8
0.71 727 in
by M axim um )
372
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Bellows
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 1 735 SCFM
Inlet
Size
0.785 in
In.
Rating
0.873 in
In.
Facing
Quantity
Yes
1 .5 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
3.0 in
1 50
RF
No
Model Materials
Body
Disc
SA-2 1 6 G r. WCB
31 6
Bellows
SS + S TELLITE (SP)
31 6L SS (SP)
Bonnet
Guide
Custom
SA-2 1 6 G r. WCB
31 6
SS
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6
S S + STELLITE (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 50 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Over P.
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
Blocked
Flow : CV Failure
3400 kg /hr
40 C
83 lbs
89.072
66.804
0.79696 in
Wvapor
Relief Temperature Trelief
Compressibility
Z
Discharge Coeff.
K
Gas
(0.9 x K )
Flow
Flow
Rupture Disk
K
CCF
Coefficient
Relief Pressure
P
relief
Molecular Weight
M
vapor
Vapor Flow Factor K
b
Vapor Flow Factor
K
Required Flow
Capacity
3400 kg /hr
40 C
0.8
372
0.8577
Sub-Critical
Coefficient of Sub-Critical
Flow
Specific Gravity
2 8.05 M ol Wt
0.9352 4
Discharge Coefficient
F
2
Ggas
k
K
d
Ethylene
0.9682 4 sp g r
1 .6
0.953
0.79696 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
The change made to the required cap acity changes the valve model and orfice size from the 3 x4
inch "K" orifice valve to a 1. 5x3 inch "H" orifice. Customer to review and confirm change.
Farris cannot sup p ort a "K" orifice valve with a sizing calculation sheet.
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 46953_2 52 1 64 End of 2 2 0-PSV -031 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 51 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 0-PSV -040
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
1 0
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
1 4 Bar G
Design T.
Operating
Temp.
Relief Temp.
71 .42 9
Percent Over P.
1 4 Bar G
1 0 Bar G
Operating to Set %
Atm Pressure
Relief
Pressure
Min.
40 C
Design T.
Constant Back
P.
Variable Back P.
10 %
Over Pressure
1 .4 Bar G
Cold
1 4 Bar G
2 8.1 1 M ol Wt
Gas
0.97031 sp g r
Compressibility
1 95 C
40 C
-1 00 C
3 Bar G
0.35 Bar G
Diff. Test P.
Compressible State
Fluid
Ethylene
Molecular
Weight
4000 kg /hr
Specific
Gravity
Calculated Area
0.54445 in
Specific
Heat Ratio
0.54445 in
( Resolved
1 .2
by M axim um )
Flow Const.
337
0.9
0.49 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6G B1 2A-1 2 1 /S3/SP
API
Area
Valve Design
Bellows
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 2 092 SCFM
Inlet
Size
0.503 in
In.
Rating
0.559 in
In.
Facing
Quantity
Yes
1 .5 in
Outlet
300
Out.
Rating
RF
Out.
Facing
Size
3.0 in
1 50
RF
NACE
No
Model Materials
Body
SA-351 G r. CF8M
Disc
31 6 SS + Stellite (SP)
Bellows
31 6L SS (SP)
Bonnet
Guide
Custom
SA-351 G r. CF8M
31 6
SS
A32 0-B8 CL
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
Chrome Alloy N P
Page 1
VP-4400-427-001 -ALL-002_05
Page 52 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Vapor
BLO CKED
O UTLET
4000 kg /hr
41 06.9 kg /hr
40 C
85.385 lbs
1 02 .96
77.2 22
0.54445 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
4000 kg /hr
40 C
0.9
337
0.8577
Critical
1
1 6.41 3 Bar Abs
2 8.1 1 M ol Wt
1
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Ethylene
0.97031 sp g r
1 .2
0.953
0.54445 in
Tag Notes
Farris offers Standard 3 16 Stud/Nuts has been offered, customer to check & confirm.
Due to current p rocess data revisions valve hs now been sized to a 1. 5G3 , p lease advise
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 46953_2 52 1 64 End of 2 2 0-PSV -040 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 53 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 0-PSV -047A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
G AS EXPANSIO N
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
43.5 Bar G
39 Bar G
43.5 Bar G
Operating to Set %
89.655
Atm Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
Pressure
Design T.
Constant Back
P.
Variable Back P.
1 00 C
1 35 C
Percent Over P.
Relief
Min.
1 95 C
21
-46 C
3 Bar G
0.55 Bar G
Over Pressure
Cold
42 .08 M ol Wt
Gas
1 .452 5 sp g r
Compressibility
9.1 35 Bar G
Diff. Test P.
43.5 Bar G
Compressible State
Fluid
Propylene
Molecular
2 000 kg /hr
Specific
Gravity
Calculated Area
0.051 2 2 9 in
Specific
Heat Ratio
0.051 229 in
Weight
( Resolved
1 .58
Flow Const.
0.474
by M aximum )
371
0.0461 06 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Bellows
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 1 671 SCFM
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
600
Out.
Rating
RF
Out.
Facing
Size
NACE
2 .0 in
1 50
RF
No
Model Materials
Body
Disc
31 6 SS Stellite (SP)
Bellows
Inconel C omposite
Bonnet
Guide
Custom
31 6
SS
M aterial to be
A320-L7/A1 94-4.
(SP)
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6 SS Stellite (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 54 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Over P.
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
G AS
EXPANSIO N
2000 kg /hr
5856.1 kg /hr
1 35 C
1 09.52 lbs
1 07.1 9
80.395
0.051 2 29 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
2000 kg /hr
1 35 C
0.474
371
0.8577
Critical
1
53.648 Bar Abs
42 .08 M ol Wt
1
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Propylene
1 .452 5 sp g r
1 .58
0.953
0.051 2 2 9 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
The customer changed the valve model from a p ilot control valve to a bellows valve.
Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 55 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 0-PSV -048A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
G AS EXPANSIO N
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
43.5 Bar G
39 Bar G
43.5 Bar G
Operating to Set %
Atm Pressure
89.655
Relief
Pressure
Design T.
Constant Back
P.
Variable Back P.
40 C
1 96 C
Percent Over P.
Min.
1 00 C
21
-20 C
3 Bar G
0.35 Bar G
Over Pressure
Cold
2 8.05 M ol Wt
Gas
0.9682 4 sp g r
Compressibility
9.1 35 Bar G
Diff. Test P.
43.5 Bar G
Compressible State
Fluid
Ethylene
Molecular
Weight
3300 kg /hr
Specific
Gravity
Calculated Area
0.1 7097 in
Specific
Heat Ratio
0.1 7097 in
( Resolved
1 .2 4
Flow Const.
0.95
by M axim um )
341
0.1 5387 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6EB1 2 -1 2 1 /SP
API
Area
Valve Design
Bellows
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 2 507 SCFM
Inlet
Size
0.1 96 in
In.
Rating
0.2 2 5 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
300
Out.
Rating
RF
Out.
Facing
Size
NACE
2 .0 in
1 50
RF
No
Model Materials
Body
SA-2 1 6 G r. WCB
Bonnet
Disc
31 6 SS Stellite (SP)
Guide
Bellows
Inconel C omposite
Custom
SA-2 1 6 G r. WCB
31 6
SS
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6 SS Stellite (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 56 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Over P.
G AS
EXPANS IO N
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
3300 kg /hr
4343 kg /hr
1 96 C
1 82 .78 lbs
1 07.2 1
80.407
0.1 7097 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
3300 kg /hr
1 96 C
0.95
341
0.8577
Critical
1
53.648 Bar Abs
2 8.05 M ol Wt
1
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Ethylene
0.9682 4 sp g r
1 .24
0.953
0.1 7097 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
NOTE: The customer' s revised instrument data sheet changed the valve model from a p ilot
Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 57 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 0-PSV -049
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
CV Failure
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
8 Bar G
Design T.
Operating
Temp.
Relief Temp.
6.2 5 %
Percent Over P.
8 Bar G
0.5 Bar G
Operating to Set %
Atm Pressure
Relief
Pressure
Min.
Design T.
Constant Back
P.
Variable Back P.
1 95 C
40 C
42 .4 C
-1 00 C
3 Bar G
0.34 Bar G
Over Pressure
10 %
9.81 33 Bar Abs
Cold
2 8.05 M ol Wt
Gas
0.9682 4 sp g r
Compressibility
0.8 Bar G
Diff. Test P.
8 Bar G
Compressible State
Fluid
Ethylene
Molecular
Weight
7500 kg /hr
Specific
Gravity
Calculated Area
1 .72 1 9 in
Specific
Heat Ratio
1 .721 9 in
( Resolved
1 .2 8
by M aximum )
Flow Const.
345
0.95
1 .5497 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6M B1 0-1 2 1 /S3/SP
API
Area
3.600 in
In.
Rating
4.000 in
In.
Facing
Valve Design
Bellows
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 8951 SCFM
Inlet
Size
Quantity
Yes
4.0 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
6.0 in
1 50
RF
NACE
No
Model Materials
Body
SA-351 G r. CF8M
Disc
31 6 SS + Stellite (SP)
Bellows
31 6L SS (SP)
Bonnet
Guide
Custom
SA-351 G r. CF8M
31 6
SS
A32 0-B8 CL
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
Chrome Alloy N P
Page 1
VP-4400-427-001 -ALL-002_05
Page 58 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Vapor
CV
Failure
7500 kg /hr
1 7423 kg /hr
42 .4 C
379.4 lbs
98.894
74.1 71
1 .72 1 9 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
7500 kg /hr
42.4 C
0.95
345
0.8577
Critical
1
9.81 33 Bar Abs
2 8.05 M ol Wt
1
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Ethylene
0.9682 4 sp g r
1 .28
0.953
1 .72 1 9 in
Tag Notes
Farris offers "M" orifice valve as p er revised sizing calculations in lieu of "N" orifice
with same Inlet/Outlet Size & Ratings as sp ecified on the p rocess data sheet, customer to
Farris offers Standard 3 16 Stud/Nuts has been offered, customer to check & confirm.
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 46953_2 52 1 64 End of 2 2 0-PSV -049 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 59 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 2 -PSV -01 6
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
1 0 Bar G
Design T.
Operating
Temp.
Relief Temp.
25 %
Percent Over P.
1 3 Bar G
2 .5 Bar G
Operating to Set %
Atm Pressure
Max.
Relief
Min.
Design T.
Constant Back
P.
Variable Back P.
1 30 C
50 C
1 00 C
-1 00 C
0.1 Bar G
0.9 Bar G
Over Pressure
10 %
Pressure
Gravity
0.958 sp g r
Cold
1 Bar G
Diff. Test P.
9.9 Bar G
N on-Compressible State
Fluid Type
Water
Specific
Viscosity
Type
Absolute
400 kg /hr
Viscosity
0.2 8 C entipoise
Calculated Area
0.005866 in
Reynolds #
45538
0.005866 in
( Resolved
by M aximum )
0.00528 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
Conventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 39 US g pm
0.1 2 5 in
Yes
Size
0.75 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Quantity
Size
NACE
1 .00 in
1 50
RF
No
Model Materials
Body
Disc
31 6
SS
Stellite (SP)
Bonnet
31 6
SS
Nozzle
Guide
31 6
SS
Spring
2 011-02 -2 3 16: 05
SDS246953 REV 05
Stellite (SP)
31 6
SS
Page 1
VP-4400-427-001 -ALL-002_05
Page 60 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Liq uid
Cause of
Over P.
Blocked
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
400 kg /hr
8523.1 kg /hr
1 00 C
0.00572 6 lbs
0.005866 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.41 81 4 m/hr
0.958 sp g r
0.6759
1 0 Bar G
0.99303
User Defined
Absolute
0.2 8 Centipoise
45538
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
400 kg /hr
0.751
1 00 C
0.005866 in
Tag Notes
DATA SHEETS REQUEST ALL STAINLESS STEEL WITH SPRING VENDOR TO ADVISE, FARRIS 3 /4 " x 1"
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 46953_2 52 1 64 End of 2 2 2 -PSV -01 6 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 61 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 2 -PSV -01 9
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
1 0 Bar G
Design T.
Operating
Temp.
Relief Temp.
25 %
Percent Over P.
1 3 Bar G
2 .5 Bar G
Operating to Set %
Atm Pressure
Max.
Relief
Min.
Design T.
Constant Back
P.
Variable Back P.
1 30 C
50 C
1 00 C
-1 00 C
0.1 Bar G
0.9 Bar G
Over Pressure
10 %
Pressure
Gravity
0.958 sp g r
Cold
1 Bar G
Diff. Test P.
9.9 Bar G
N on-Compressible State
Fluid Type
Water
Specific
Viscosity
Type
Absolute
400 kg /hr
Viscosity
0.2 8 C entipoise
Calculated Area
0.005866 in
Reynolds #
45538
0.005866 in
( Resolved
by M aximum )
0.00528 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
Conventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 39 US g pm
0.1 2 5 in
Yes
Size
0.75 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Quantity
Size
NACE
1 .00 in
1 50
RF
No
Model Materials
Body
Disc
31 6
SS
Stellite (SP)
Bonnet
31 6
SS
Nozzle
Guide
31 6
SS
Spring
2 011-02 -2 3 16: 05
SDS246953 REV 05
Stellite (SP)
31 6
SS
Page 1
VP-4400-427-001 -ALL-002_05
Page 62 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Liq uid
Cause of
Over P.
Blocked
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
400 kg /hr
8523.1 kg /hr
1 00 C
0.00572 6 lbs
0.005866 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.41 81 4 m/hr
0.958 sp g r
0.6759
1 0 Bar G
0.99303
User Defined
Absolute
0.2 8 Centipoise
45538
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
400 kg /hr
0.751
1 00 C
0.005866 in
Tag Notes
DATA SHEETS REQUEST ALL STAINLESS STEEL WITH SPRING VENDOR TO ADVISE, FARRIS 3 /4 " x 1"
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 46953_2 52 1 64 End of 2 2 2 -PSV -01 9 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 63 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 4-PSV -005
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
1 9.5 Bar G
1 1 .3 Bar G
1 9.5 Bar G
Operating to Set %
57.949
Atm Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
80 C
2 1 0 C
Percent Over P.
Relief
Min.
2 40 C
10 %
Pressure
Gravity
0.853 sp g r
Design T.
Constant Back
P.
Variable Back P.
1 .85 Bar G
Over Pressure
1 .95 Bar G
Cold
1 9.4 Bar G
-5 C
0.1 Bar G
Diff. Test P.
N on-Compressible State
Fluid Type
Water
Specific
Viscosity
Type
Absolute
830 kg /hr
Viscosity
0.1 3 C entipoise
Calculated Area
0.0091 74 in
Reynolds #
2 0352 2
0.0091 74 in
( Resolved
by M aximum )
0.008256 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
Conventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 54 US g pm
0.1 2 5 in
Yes
Size
Quantity
0.75 in
Outlet
Size
300
Out.
Rating
RF
Out.
Facing
1 .00 in
1 50
RF
NACE
No
Model Materials
Body
Disc
Custom
31 6
31 6
Bonnet
SS
SS + S TELLITE (S P)
Guide
SA-2 1 6 , G r.
WC B/A1 05
31 6
SS
Spring
31 6
SS + STELLITE (SP)
31 6
SS
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Page 1
VP-4400-427-001 -ALL-002_05
Page 64 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Liq uid
Cause of
Over P.
Blocked
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
830 kg /hr
1 1 31 0 kg /hr
2 1 0 C
0.0091 74 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.97445 m/hr
0.853 sp g r
0.6759
1 9.5 Bar G
1
User Defined
Absolute
0.1 3 Centipoise
2 0352 2
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
830 kg /hr
0.751
2 1 0 C
0.0091 74 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes. T
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 46953_2 52 1 64 End of 2 2 4-PSV -005 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 65 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 4-PSV -009
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
31 .5 Bar G
1 4.5 Bar G
1 9.5 Bar G
Operating to Set %
74.359
Atm Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
65 C
2 1 0 C
Percent Over P.
Relief
Pressure
Min.
2 35 C
10 %
2 2 .463 Bar Abs
Design T.
Constant Back
P.
Variable Back P.
1 .85 Bar G
Over Pressure
1 .95 Bar G
Cold
1 9.4 Bar G
-5 C
0.1 Bar G
Diff. Test P.
N on-Compressible State
Fluid Type
Water
Specific
Gravity
Viscosity
853 sp g r
Type
Absolute
500 kg /hr
Viscosity
0.1 3 C entipoise
Calculated Area
1 .748e-4 in
Reynolds #
1 2 2 604
1 .748e-4 in
( Resolved
by M aximum )
1 .573e-4 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
Conventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 54 US g pm
0.1 2 5 in
Yes
Size
Quantity
0.75 in
Outlet
300
Out.
Rating
RF
Out.
Facing
Size
NACE
1 .00 in
1 50
RF
No
Model Materials
Body
31 6
Disc
Custom
Bonnet
SS
Stellite (SP)
Guide
SA-2 1 6 , G r.
WC B/A1 05
31 6
SS
Spring
Stellite (SP)
31 6
SS
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Page 1
VP-4400-427-001 -ALL-002_05
Page 66 of 1 59
Sizing Scenarios
Scenario
Fluid
State
C ase A
Liq uid
Cause of
Over P.
Blocked
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
500 kg /hr
357638 kg /hr
2 1 0 C
1 .005e-5 lbs
1 .748e-4 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
5.870e-4 m/hr
853 sp g r
0.6759
1 9.5 Bar G
1
User Defined
Absolute
0.1 3 Centipoise
1 2 2 604
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
500 kg /hr
0.751
2 1 0 C
1 .748e-4 in
Tag Notes
1. FARRIS DOES NOT MANUFACTURE A 0. 75 x 1" IN A "E" ORIFICE ( 1E1. 5) , HAVE OFFERED A "D"
ORIFICE
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 46953_2 52 1 64 End of 2 2 4-PSV -009 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 67 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 4-PSV -01 3
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
31 .5 Bar G
1 4.5 Bar G
1 9.5 Bar G
Operating to Set %
74.359
Atm Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
68 C
2 1 0 C
Percent Over P.
Relief
Min.
2 35 C
10 %
Pressure
Gravity
0.853 sp g r
Design T.
Constant Back
P.
Variable Back P.
1 .85 Bar G
Over Pressure
1 .95 Bar G
Cold
1 9.4 Bar G
-5 C
0.1 Bar G
Diff. Test P.
N on-Compressible State
Fluid Type
Water
Specific
Viscosity
Type
Absolute
500 kg /hr
Viscosity
0.1 3 C entipoise
Calculated Area
0.00552 6 in
Reynolds #
1 2 2 604
0.005526 in
( Resolved
by M aximum )
0.004974 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
Conventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 54 US g pm
0.1 2 5 in
Yes
Size
Quantity
0.75 in
Outlet
300
Out.
Rating
RF
Out.
Facing
Size
NACE
1 .00 in
1 50
RF
No
Model Materials
Body
31 6
Disc
Custom
Bonnet
SS
Stellite (SP)
Guide
SA-2 1 6 , G r.
WC B/A1 05
31 6
SS
Spring
Stellite (SP)
31 6
SS
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Page 1
VP-4400-427-001 -ALL-002_05
Page 68 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Liq uid
Cause of
Over P.
Blocked
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
500 kg /hr
1 1 31 0 kg /hr
2 1 0 C
0.00552 6 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.58702 m/hr
0.853 sp g r
0.6759
1 9.5 Bar G
1
User Defined
Absolute
0.1 3 Centipoise
1 2 2 604
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
500 kg /hr
0.751
2 1 0 C
0.00552 6 in
Tag Notes
1. FARRIS DOES NOT MANUFACTURE A 0. 75 x 1" IN A "E" ORIFICE ( 1E1. 5) , HAVE OFFERED A "D"
ORIFICE
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 46953_2 52 1 64 End of 2 2 4-PSV -01 3 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 69 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 4-PSV -01 8
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
31 .5 Bar G
1 4.7 Bar G
1 9.5 Bar G
Operating to Set %
75.385
Atm Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
45 C
2 1 0 C
Percent Over P.
Relief
Min.
2 35 C
10 %
Pressure
Gravity
0.853 sp g r
Design T.
Constant Back
P.
Variable Back P.
1 .85 Bar G
Over Pressure
1 .95 Bar G
Cold
1 9.4 Bar G
-5 C
0.1 Bar G
Diff. Test P.
N on-Compressible State
Fluid Type
Water
Specific
Viscosity
Type
Absolute
1 30 kg /hr
Viscosity
0.1 3 C entipoise
Calculated Area
0.001 451 in
Reynolds #
31 877
0.001 451 in
( Resolved
by M aximum )
0.001 306 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
Conventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 54 US g pm
0.1 2 5 in
Yes
Size
Quantity
0.75 in
Outlet
300
Out.
Rating
RF
Out.
Facing
Size
NACE
1 .00 in
1 50
RF
No
Model Materials
Body
31 6
Disc
Custom
Bonnet
SS
Stellite (SP)
Guide
SA-2 1 6 , G r.
WC B/A1 05
31 6
SS
Spring
Stellite (SP)
31 6
SS
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Page 1
VP-4400-427-001 -ALL-002_05
Page 70 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Liq uid
Cause of
Over P.
Blocked
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
1 30 kg /hr
1 1 2 01 kg /hr
2 1 0 C
6.793e-4 lbs
0.001 451 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.1 52 62 m/hr
0.853 sp g r
0.6759
1 9.5 Bar G
0.99041
User Defined
Absolute
0.1 3 Centipoise
31 877
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
1 30 kg /hr
0.751
2 1 0 C
0.001 451 in
Tag Notes
1. FARRIS DOES NOT MANUFACTURE A 0. 75 x 1" IN A "E" ORIFICE ( 1E1. 5) , HAVE OFFERED A "D"
ORIFICE
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 46953_2 52 1 64 End of 2 2 4-PSV -01 8 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 71 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 4-PSV -02 1
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
31 .5 Bar G
1 4.7 Bar G
1 9.5 Bar G
Operating to Set %
75.385
Atm Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
65 C
2 1 0 C
Percent Over P.
Relief
Min.
2 35 C
10 %
Pressure
Gravity
0.853 sp g r
Design T.
Constant Back
P.
Variable Back P.
1 .85 Bar G
Over Pressure
1 .95 Bar G
Cold
1 9.4 Bar G
-5 C
0.1 Bar G
Diff. Test P.
N on-Compressible State
Fluid Type
Water
Specific
Viscosity
Type
Absolute
1 30 kg /hr
Viscosity
0.1 3 C entipoise
Calculated Area
0.001 451 in
Reynolds #
31 877
0.001 451 in
( Resolved
by M aximum )
0.001 306 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
Conventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 54 US g pm
0.1 2 5 in
Yes
Size
Quantity
0.75 in
Outlet
300
Out.
Rating
RF
Out.
Facing
Size
NACE
1 .00 in
1 50
RF
No
Model Materials
Body
31 6
Disc
Custom
Bonnet
SS
Stellite (SP)
Guide
SA-2 1 6 , G r.
WC B/A1 05
31 6
SS
Spring
Stellite (SP)
31 6
SS
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Page 1
VP-4400-427-001 -ALL-002_05
Page 72 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Liq uid
Cause of
Over P.
Blocked
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
1 30 kg /hr
1 1 2 01 kg /hr
2 1 0 C
6.793e-4 lbs
0.001 451 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.1 52 62 m/hr
0.853 sp g r
0.6759
1 9.5 Bar G
0.99041
User Defined
Absolute
0.1 3 Centipoise
31 877
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
1 30 kg /hr
0.751
2 1 0 C
0.001 451 in
Tag Notes
1. FARRIS DOES NOT MANUFACTURE A 0. 75 x 1" IN A "E" ORIFICE ( 1E1. 5) , HAVE OFFERED A "D"
ORIFICE
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 46953_2 52 1 64 End of 2 2 4-PSV -02 1 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 73 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 4-PSV -030
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
01
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Vapor (M ass)
NACE
No
N o Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
2 0 Bar G
0.6 Bar G
1 5 Bar G
Operating to Set %
Atm Pressure
Relief
Pressure
Design T.
Constant Back
P.
Variable Back P.
1 50 C
2 1 0 C
Percent Over P.
Min.
2 35 C
-1 00 C
3 Bar G
0.39 Bar G
Over Pressure
10 %
1 7.51 3 Bar Abs
Cold
2 8.05 M ol Wt
Gas
0.9682 4 sp g r
Compressibility
1 .5 Bar G
Diff. Test P.
1 5.1 5 Bar G
Compressible State
Fluid
Ethylene
Molecular
Weight
2 700 kg /hr
Specific
Gravity
Calculated Area
0.44956 in
Specific
Heat Ratio
0.44956 in
( Resolved
1 .1 8
by M axim um )
Flow Const.
335
0.98
0.40461 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Bellows
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 2 2 32 SCFM
Inlet
Size
0.503 in
In.
Rating
0.559 in
In.
Facing
Quantity
Yes
1 .5 in
Outlet
300
Out.
Rating
RF
Out.
Facing
Size
NACE
3.0 in
1 50
RF
No
Model Materials
Body
Disc
Bellows
SA-2 1 6 G r. WCB
Stellite (SP)
31 6L SS (SP)
Bonnet
Guide
Custom
SA-2 1 6 G r. WCB
31 6
SS
(SP)
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
Stellite (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 74 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Over P.
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
Blocked
2 700 kg /hr
3357.2 kg /hr
2 1 0 C
90.22 lbs
1 03.99
77.995
0.44956 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
2700 kg /hr
2 1 0 C
0.98
335
0.8577
Critical
1
1 7.51 3 Bar Abs
2 8.05 M ol Wt
1
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Ethylene
0.9682 4 sp g r
1 .1 8
0.953
0.44956 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 46953_2 52 1 64 End of 2 2 4-PSV -030 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 75 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 5-PSV -008
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Steam
NACE
N o
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
31 .5 Bar G
1 1 Bar G
2 5 Bar G
Operating to Set %
44
Atm Pressure
1 05 C
2 31 C
Percent Over P.
Relief
Pressure
Min.
2 35 C
10 %
2 8.51 3 Bar Abs
Design T.
Constant Back
P.
Variable Back P.
0.1 Bar G
Over Pressure
2 .5 Bar G
Cold
-5 C
2 .4 Bar G
Diff. Test P.
2 4.9 Bar G
S team S tate
Calculated Area
0.32 586 in
Req.
0.32586 in
Flow Cap.
( Resolved
Napier
2700 kg /hr
Superheat
by M axim um )
0.29327 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
26FA1 2 -1 41 /SP
API
Area
Valve Design
Conventional
ASME
Inlet
Area
Size
0.307 in
In.
Rating
0.371 in
In.
Facing
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Steam): 6777 lb/hr
Quantity
Yes
1 .5 in
Outlet
Size
300
Out.
Rating
RF
Out.
Facing
NACE
2 .0 in
1 50
RF
No
Model Materials
Body
Disc
SA-2 1 6 G r. WCB
31 6 SS + Stellite (SP)
Bellows
Bonnet
Guide
31 6
Custom
N /A
SA-2 1 6 G r. WCB
Nozzle
31 6 SS + Stellite (SP)
Spring
SS
Chrome Alloy
Sizing Scenarios
Scenario
Fluid
State
C ase A
Steam
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Liq uid
Vaporization
2 700 kg /hr
3074.1 kg /hr
2 31 C
2 011-02 -2 3 16: 05
SDS246953 REV 05
1 50.1 1 lbs
1 07.87
80.904
0.32 586 in
Page 1
VP-4400-427-001 -ALL-002_05
Page 76 of 1 59
Relief Pressure
Vapor Flow Factor
Superheat Factor
Napier Factor
Wsteam
K
Gas
K
CCF
P
relief
K
b
K
v
K
sh
K
n
2 700 kg /hr
0.8577
1
1
Relief Temperature
Discharge Coefficient
Trelief
K
d
2 31 C
0.953
0.32 586 in
Tag Notes
1. FARRIS DOES NOT MANUFACTURE A 0. 75 x 1" IN A "F" ORIFICE ( 1. 5F2 ) , HAVE OFFERED A "D"
ORIFICE
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 46953_2 52 1 64 End of 2 2 5-PSV -008 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 77 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 5-PSV -01 1
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Blocked Discharg e
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
8 Bar G
0.5 Bar G
6 Bar G
Operating to Set %
Atm Pressure
8.3333
Relief
Pressure
Design T.
Constant Back
P.
Variable Back P.
2 40 C
2 40 C
Percent Over P.
Min.
300 C
-5 C
3 Bar G
0.38 Bar G
Over Pressure
10 %
7.61 33 Bar Abs
Cold
2 8.1 M ol Wt
Gas
0.6 Bar G
Diff. Test P.
6.06 Bar G
Compressible State
Fluid
Ethylene
Molecular
Weight
1 62 00 kg /hr
Specific
Gravity
Calculated Area
9.31 59 in
Specific
Heat Ratio
9.31 59 in
( Resolved
332 .6
Compressibility
0.96997 sp g r
1 .1 56
by M aximum )
Flow Const.
8.3843 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6Q B1 2-1 2 1 /SP
API
Area
Valve Design
Bellows
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 2 1 303 SCFM
Inlet
Size
1 1 .05 in
In.
Rating
1 2 .2 7 in
In.
Facing
Quantity
Yes
6.0 in
Outlet
300
Out.
Rating
RF
Out.
Facing
Size
NACE
8.0 in
1 50
RF
No
Model Materials
Body
SA-2 1 6 G r. WCB
Bonnet
Disc
31 6 SS Stellite (SP)
Guide
Bellows
Inconel C omposite
Custom
SA-2 1 6 G r. WCB
31 6
SS
Bolt-O n Steam
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6 SS Stellite (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 78 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Vapor
Blocked
1 6200 kg /hr
Discharg e
2 1 337 kg /hr
2 40 C
1 02 5.8 lbs
90.81 3
Coefficient of Sub-Critical
Flow
F
2
68.1 09
9.31 59 in
Wvapor
Relief Temperature Trelief
Compressibility
Z
Discharge Coeff.
K
Gas
(0.9 x K )
Flow
Flow
Rupture Disk
K
CCF
Coefficient
Relief Pressure
P
relief
Molecular Weight
M
vapor
Vapor Flow Factor K
b
Vapor Flow Factor
K
Required Flow
Capacity
1 6200 kg /hr
240 C
332 .6
0.8577
Sub-Critical
Specific Gravity
2 8.1 M ol Wt
0.69778
Discharge Coefficient
Ggas
k
K
d
0.69567
Ethylene
0.96997 sp g r
1 .1 56
0.953
9.31 59 in
Tag Notes
Farris is p rop osing a 6" 3 00# RF ' Q' 8" 150 RF bellows valve for this tag, and a 4 " 3 00# RF
This is because for a bellows valve, with this total BP, ( CBP= 3 barg + VBP= 0. 3 8 barg = 3 . 3 8
Since the Variable BP < 10% of Set, a Conventional valve can be sp ecified.
With the Conventional design, a 4 " 150# RF ' P' 6" 150# RF, can be sp ecified.
Please refer to the grap hs for BackPressure Sizing Factors, Kb and Kv, on p age 87 of the
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 46953_2 52 1 64 End of 2 2 5-PSV -01 1 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 79 of 1 59
T ag
P Q -1 0 1 7 9 0 : 2 2 5 -P S V
-0 1 5
- D a ta
D ate Prepared:
S h e e t
2 0 1 1 -0 7 -0 1 1 5 :2 6
C u sto m er
R eq u isitio n #
Job #
C h eck ed B y
A p p roved B y
D aelim
J o b D e sc r ip tio n
P Q -1 0 1 7 9 0
P repared B y
S a u d i K a y a n L D P E P ro je c t
J o b S ta tu s
R e v is io n #
S iz in g /S e le c tin g
PSV Identification
T ag
T ag D escrip tion
T a g S ta tu s
2 2 5 -P S V -0 1 5
Plant
P / ID
D isch a rg e T o
R e v is io n #
V a lv e S e le c te d
Drawing #
Index #
Issu e F o r
S e r v ic e
Inlet Line #
O utlet Line #
R e v is e d B y
S iz in g B a s is
ASM E
Code
C a u se o f O v e r P r e ssu r e
F luid State
B lo c k e d D isc h a rg e
V a p o r (M a ss)
NACE
N o
N o R u p tu re D isk , 1
P r o c e s s P a r a m e te r s
MAWP
M ax. D esign T.
8 B ar G
O perating
0 .5 B a r G
P ressu re
S et P ressu re
O perating to Set %
8 .3 3 3 3
A tm P ressu re
M in. Design T.
1 0 5 C
1 0 5 C
V ariable Back P.
O perating
Tem p.
R elief T em p.
6 B ar G
2 8 5 C
P ercen t O ver P .
R e lie f P r e ssu r e
1 .0 1 3 3 B ar A b s
10
-5 C
C o n sta n t B a ck
3 B ar G
P .
0 .3 6 B a r G
O v e r P r e ssu r e
7 .6 1 3 3 B ar A b s
0 .6 B a r G
6 B ar G
C o m p r e s s ib le S ta te
Fluid
E th y le n e
1 6 2 0 0 kg/hr
C alculated A rea
5 .4 3 1 in
R e so lv e d A S M E A re a :
M olecular W eight
2 8 .1 Mol Wt
S p ecific G ravity
0 .9 6 9 9 7 s p g r
5 .4 3 1 in
G a s F lo w C o n st.
338
C o m p ressib ility
0 .9 8
1 .2 1
R e so lv e d A P I A re a :
(R eso lv ed b y M ax im u m )
4 .8 8 7 9 in
M o d e l S e le c tio n
F a rris
API Letter
3 8 P C 1 2 - 1 2 5 /S P
API Area
6 .3 8 0 in
In. Rating
ASME Area
7 .0 8 7 in
In. Facing
Manufacturer
V a lv e D e sig n
Pilot
Pilot
C ontrol
Nam e
T est G a g
S n a p A c tin g
Inlet Size
4 .0 0 in
300
Out. Rating
6 .0 0 in
150
O ut. F acing
RF
Quantity
No
O u tlet S ize
NACE
RF
N o
M odel M aterials
B ody
S A 2 1 6, G r. W C B
P is to n
316
O-Ring
C over
S p rin g
SS
316
C u sto m
Viton
N o z z le
S A -1 0 5
3 1 6 S S S te llite (S P )
Pilot
SS
A -193-B 7 /A -194-2H
316
SS
S iz in g S c e n a r io s
S c e n a r io
Fluid
C a u s e o f
R elief L oad
S ta te
O ver P.
C apacity
Relief T.
R e a c t. F o r c e
N o is e
N o is e
R equired
Atm (dBa)
Flare (dBa)
Area
B locked
C ase A
V apor
1 6 2 0 0 k g /h r
2 1 1 4 0 k g /h r
105 C
6 0 7 .4 4 lb s
8 9 .8 3 4
6 7 .3 7 6
5 .4 3 1 in
D is c h a rg e
2 0 1 1 -0 7 -0 1
1 5 :2 6
SDS246953 REV 05
P age
VP-4400-427-001 -ALL-002_05
Page 80 of 1 59
T ag
P Q -1 0 1 7 9 0 : 2 2 5 -P S V
-0 1 5
- D a ta
S h e e t
W vapor
R equired F low
C apacity
R e lie f
1 6 2 0 0 k g /h r
1 0 5 C
0 .9 8
338
0 .8 5 8 6
S u b -C ritic a l
Trelief
Z
T e m p e r a tu r e
C o m p r e s s ib ilit y
G a s F lo w C o n s t a n t
K
G as
D is c h a r g e C o e f f .
(0 .9 x K d )
F lo w
R u p tu r e D isk
C o e f f ic ie n t
R e lie f P r e s s u r e
M o le c u la r W e ig h t
V apor
F lo w F a c to r
V a p o r F lo w F a c to r
Flow
K CCF
P relief
M vapor
Kb
Kv
F2
C o e ffic ie n t o f S u b -C r itic a l
F lo w
F lu id T y p e (U s e r D e fin e d )
7 .6 1 3 3 B a r A b s
2 8 .1 M ol W t
G gas
k
Kd
S p e c ific G r a v ity
R a t io o f S p e c if ic H e a t s
D is c h a r g e C o e f f ic ie n t
E th y le n e
0 .9 6 9 9 7 s p g r
1 .2 1
0 .7 0 4 8 2
0 .9 5 4
5 .4 3 1 in
T a g N o te s
3 -J U N E : D U E T O P R E S S U R E /T E M P E R A T U R E L IM IT A T IO N S A N D C U R R E N T P R O C E S S C O N D IT IO N S T H IS T A G IS
S IZ E D T O 3 0 0 # IN L E T , 1 5 0 # IN L E T N O T A P P L IC A B L E
F a r r is
o f f e r s
In le t/O u tle t
c o n f ir m
o n
" T "
S iz e
th e
&
o r if ic e
R a tin g s
v a lv e
a s
a s
p e r
s p e c ifie d
s iz in g
c a lc u la tio n s
o n
p ro c e s s
th e
d a ta
in
lie u
s h e e t,
o f
" Q "
o r if ic e
c u s to m e r
to
w ith
c h e c k
s a m
&
s e le c tio n .
1 5 -O C T :
to
p ilo t
V a lv e
s iz e s
o p e r a te d
b y
to
th e
o rific e
p ilo t
o p e ra te d
v a lv e
S iz e M a s te r 4 .3 .2 .9 , D B : K :\A p p s \P r o je c ts \2 0 1 0 O r d e r s \2 4 6 9 5 3 -
D A E L IM \S M P 2 4 6 9 5 3 _ 2 5 2 1 6 4
2 0 1 1 -0 7 -0 1
to
th e
c h a n g e
fro m
c o n v e n tio n a l
E n d o f 2 2 5 - P S V - 0 1 5 D a ta
S h e e t
1 5 :2 6
SDS246953 REV 05
d u e
c u s to m e r .
P ag e
VP-4400-427-001 -ALL-002_05
Page 81 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 5-PSV -01 6
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Thermal Relief
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
1 7 Bar G
Design T.
Operating
Temp.
Relief Temp.
2 6.471
Percent Over P.
1 7 Bar G
4.5 Bar G
Operating to Set %
Atm Pressure
Max.
Relief
Min.
2 35 C
38 C
1 40 C
10 %
Pressure
Gravity
0.926 sp g r
Design T.
Constant Back
P.
Variable Back P.
0.1 Bar G
Over Pressure
1 .7 Bar G
Cold
-5 C
1 .6 Bar G
Diff. Test P.
1 6.9 Bar G
N on-Compressible State
Fluid Type
Viscosity
Type
Absolute
1 70 kg /hr
Viscosity
0.2 Centipoise
Calculated Area
0.001 953 in
Reynolds #
2 7095
0.001 953 in
( Resolved
by M aximum )
0.001 758 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
Conventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 50 US g pm
0.1 2 5 in
Yes
Size
Quantity
0.75 in
Outlet
300
Out.
Rating
RF
Out.
Facing
Size
NACE
1 .00 in
1 50
RF
No
Model Materials
Body
31 6
Disc
Custom
Bonnet
SS
Stellite (SP)
Guide
SA-2 1 6 , G r.
WC B/A1 05
31 6
SS
Spring
Stellite (SP)
31 6
SS
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Page 1
VP-4400-427-001 -ALL-002_05
Page 82 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Liq uid
Thermal
Relief
1 70 kg /hr
1 0882 kg /hr
1 40 C
0.001 07 lbs
0.001 953 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.92 6 sp g r
0.6759
1 7 Bar G
0.98906
User Defined
Absolute
0.2 Centipoise
2 7095
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
1 70 kg /hr
0.751
1 40 C
0.001 953 in
Tag Notes
0. 75" x1" THERMAL RELIEF VALVE IS NOT AVAILABLE WITH OPEN BONNET, TAG IS LIQUID PROCESS
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 46953_2 52 1 64 End of 2 2 5-PSV -01 6 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 83 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 5-PSV -02 4
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Blocked Flow
Steam
NACE
N o
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
40 Bar G
Design T.
Operating
Temp.
Relief Temp.
72.5 %
Percent Over P.
40 Bar G
2 9 Bar G
Operating to Set %
Atm Pressure
Relief
Pressure
Min.
Design T.
Constant Back
P.
Variable Back P.
300 C
50 C
2 58 C
-5 C
0.1 Bar G
3.9 Bar G
Over Pressure
10 %
45.01 3 Bar Abs
Cold
4 Bar G
Diff. Test P.
39.9 Bar G
S team S tate
Calculated Area
0.1 452 5 in
Req.
0.1 4525 in
Flow Cap.
( Resolved
Napier
1 900 kg /hr
Superheat
by M axim um )
0.1 3073 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Conventional
ASME
Inlet
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Steam): 6489 lb/hr
Size
0.1 96 in
In.
Rating
0.2 2 5 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
Size
600
Out.
Rating
RF
Out.
Facing
NACE
2 .0 in
1 50
RF
No
Model Materials
Body
Disc
SA-2 1 6 G r. WCB
31 6 SS + Stellite (SP)
Bellows
Bonnet
Guide
Custom
N /A
SA-2 1 6 G r. WCB
31 6
Nozzle
31 6 SS + Stellite (SP)
Spring
SS
Chrome Alloy
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Steam
Blocked
Flow
1 900 kg /hr
2 943.2 kg /hr
258 C
1 41 .75 lbs
2 011-02 -2 3 16: 05
SDS246953 REV 05
1 08.08
81 .061
0.1 452 5 in
Page 1
VP-4400-427-001 -ALL-002_05
Page 84 of 1 59
Relief Pressure
Vapor Flow Factor
Superheat Factor
Napier Factor
Wsteam
K
Gas
K
CCF
P
relief
K
b
K
v
K
sh
K
n
1 900 kg /hr
0.8577
1
1
Relief Temperature
Discharge Coefficient
Trelief
K
d
2 58 C
0.953
0.1 4525 in
Tag Notes
9-JUNE: WITH CURRENT PROCESS CONDITIONS FARRIS SIZES VALVE TO A 1" x 1. 5" IN 2 700 SERIES
THREMAL VALVE, THUS DUE TO 1. 5" OUTLET NOT ALLOWED ON PROJECT, FARRIS OFFERED A 1D2 , PLEASE
ADVISE
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 46953_2 52 1 64 End of 2 2 5-PSV -02 4 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 85 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 5-PSV -040A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
CV FAILURE
Steam
NACE
N o
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
2 8 Bar G
Design T.
Operating
Temp.
Relief Temp.
89.2 86
Percent Over P.
40 Bar G
2 5 Bar G
Operating to Set %
Atm Pressure
Relief
Min.
Design T.
Constant Back
P.
Variable Back P.
300 C
2 2 6 C
2 36.3 C
Pressure
-5 C
0.1 Bar G
2 .65 Bar G
Over Pressure
10 %
31 .81 3 Bar Abs
Cold
2 .8 Bar G
Diff. Test P.
28.1 79 Bar G
S team S tate
Calculated Area
0.6382 in
Req.
0.6382 in
Flow Cap.
( Resolved
Napier
5900 kg /hr
by M aximum )
Superheat
0.57438 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Conventional
ASME
Inlet
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Steam): 1 7793 lb/hr
Size
0.785 in
In.
Rating
0.873 in
In.
Facing
Quantity
Yes
2 .0 in
Outlet
Size
600
Out.
Rating
RF
Out.
Facing
NACE
3.0 in
1 50
RF
No
Model Materials
Body
Disc
SA-2 1 6 G r. WCB
31 6 SS + Stellite (SP)
Bellows
Bonnet
Guide
Custom
N /A
SA-2 1 6 G r. WCB
31 6
Nozzle
31 6 SS + Stellite (SP)
Spring
SS
Chrome Alloy
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Steam
CV
FAILURE
5900 kg /hr
8070.7 kg /hr
2 36.3 C
2 011-02 -2 3 16: 05
SDS246953 REV 05
41 1 .43 lbs
1 1 2.1 8
84.1 32
0.6382 in
Page 1
VP-4400-427-001 -ALL-002_05
Page 86 of 1 59
Relief Pressure
Vapor Flow Factor
Superheat Factor
Napier Factor
Wsteam
K
Gas
K
CCF
P
relief
K
b
K
v
K
sh
K
n
5900 kg /hr
0.8577
1
1
Relief Temperature
Discharge Coefficient
Trelief
K
d
2 36.3 C
0.953
0.6382 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 87 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 5-PSV -043
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
NACE
No
N o Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
1 0 Bar G
Design T.
Operating
Temp.
Relief Temp.
45 %
Percent Over P.
1 0 Bar G
4.5 Bar G
Operating to Set %
Atm Pressure
Relief
Min.
Design T.
Constant Back
P.
Variable Back P.
90 C
45 C
65.5 C
-5 C
0.1 Bar G
0.9 Bar G
Over Pressure
10 %
Pressure
Gravity
0.983 sp g r
Cold
1 Bar G
Diff. Test P.
9.9 Bar G
N on-Compressible State
Fluid Type
WATER
Specific
Viscosity
Type
Absolute
432 00 kg /hr
Viscosity
0.44 C entipoise
Calculated Area
0.6442 7 in
Reynolds #
1 29731 7
0.64427 in
( Resolved
by M axim um )
0.57984 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6H A1 0L-1 41 /SP
API
Area
Valve Design
Conventional
Cap Constrn
Packed Lever
Name Plate Capacity (Water): 59.052
ASME
Area
Test Gag
Inlet
Size
0.785 in
In.
Rating
0.873 in
In.
Facing
Quantity
Yes
1 .5 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
3.0 in
1 50
RF
No
m3/hr
Model Materials
Body
Disc
SA-2 1 6 G r. WCB
31 6 SS + Stellite (SP)
Bellows
N /A
Bonnet
Guide
Custom
SA-2 1 6 G r. WCB
31 6
SS
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 88 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Liq uid
Cause of
Over P.
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
BLO CKED
43200 kg /hr
FLO W -TUBE RUPTURE
58537 kg /hr
65.5 C
7.2 32 2 lbs
0.64427 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
44.01 1 m/hr
0.983 sp g r
0.651 6
1 0 Bar G
1
User Defined
Absolute
0.44 Centipoise
1 2 9731 7
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
432 00 kg /hr
0.72 4
65.5 C
0.6442 7 in
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P246953_2 52 1 64 End of 2 2 5-PSV -043 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 89 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 5-PSV -050
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
THERM AL RELIEF
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
1 0 Bar G
Design T.
Operating
Temp.
Relief Temp.
40 %
Percent Over P.
1 0 Bar G
4 Bar G
Operating to Set %
Atm Pressure
Max.
Relief
Min.
49 C
Design T.
Constant Back
P.
Variable Back P.
10 %
Over Pressure
90 C
44 C
Pressure
Gravity
0.993 sp g r
Cold
-5 C
0.1 Bar G
0.9 Bar G
1 Bar G
Diff. Test P.
9.9 Bar G
N on-Compressible State
Fluid Type
C ooling Water
Specific
Viscosity
Type
Absolute
1 500 kg /hr
Viscosity
0.61 C entipoise
Calculated Area
0.02 1 457 in
Reynolds #
78386
0.021 457 in
( Resolved
by M aximum )
0.01 931 2 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
Conventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 39 US g pm
0.1 2 5 in
Yes
Size
Quantity
0.75 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
1 .00 in
1 50
RF
No
Model Materials
Body
31 6
Bonnet
SS
Disc
31 6 SS + Stellite (SP)
Guide
Custom
SA-2 1 6 , G r.
WC B/A1 05
31 6
SS
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
31 6
SS
Page 1
VP-4400-427-001 -ALL-002_05
Page 90 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Liq uid
THERM AL
RELIEF
1 500 kg /hr
8738.3 kg /hr
49 C
0.077685 lbs
0.021 457 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
1 .51 2 8 m/hr
0.993 sp g r
0.6759
1 0 Bar G
1
User Defined
Absolute
0.61 Centipoise
78386
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
1 500 kg /hr
0.751
49 C
0.02 1 457 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 46953_2 52 1 64 End of 2 2 5-PSV -050 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 91 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 5-PSV -051
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
THERM AL RELIEF
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
1 0 Bar G
Design T.
Operating
Temp.
Relief Temp.
40 %
Percent Over P.
1 0 Bar G
4 Bar G
Operating to Set %
Atm Pressure
Max.
Relief
Min.
49 C
Design T.
Constant Back
P.
Variable Back P.
10 %
Over Pressure
90 C
44 C
Pressure
Gravity
0.993 sp g r
Cold
-5 C
0.1 Bar G
0.9 Bar G
1 Bar G
Diff. Test P.
9.9 Bar G
N on-Compressible State
Fluid Type
C ooling Water
Specific
Viscosity
Type
Absolute
1 500 kg /hr
Viscosity
0.61 C entipoise
Calculated Area
0.02 1 457 in
Reynolds #
78386
0.021 457 in
( Resolved
by M aximum )
0.01 931 2 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
Conventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 39 US g pm
0.1 2 5 in
Yes
Size
Quantity
0.75 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
1 .00 in
1 50
RF
No
Model Materials
Body
31 6
Disc
Custom
Bonnet
SS
Stellite (SP)
Guide
SA-2 1 6 , G r.
WC B/A1 05
31 6
SS
Spring
Stellite (SP)
31 6
SS
2 011-02 -2 3 16: 05
SDS246953 REV 05
Nozzle
Page 1
VP-4400-427-001 -ALL-002_05
Page 92 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Case A
Liq uid
THERM AL
RELIEF
1 500 kg /hr
8738.3 kg /hr
49 C
0.077685 lbs
0.021 457 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
1 .51 2 8 m/hr
0.993 sp g r
0.6759
1 0 Bar G
1
User Defined
Absolute
0.61 Centipoise
78386
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
1 500 kg /hr
0.751
49 C
0.02 1 457 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4.3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 46953_2 52 1 64 End of 2 2 5-PSV -051 Data Sheet
2 011-02 -2 3 16: 05
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 93 of 1 59
T ag
P Q -1 0 1 7 9 0 : 2 2 6 -P S V
-0 4 0
- D a ta
D ate Prepared:
S h e e t
2 0 1 1 -0 7 -0 1 1 5 :2 6
C u sto m er
R eq u isitio n #
Job #
C h eck ed B y
A p p roved B y
D aelim
J o b D e sc r ip tio n
P Q -1 0 1 7 9 0
P repared B y
S a u d i K a y a n L D P E P ro je c t
J o b S ta tu s
R e v is io n #
S iz in g /S e le c tin g
PSV Identification
T ag
T ag D escrip tion
T a g S ta tu s
2 2 6 -P S V -0 4 0
Plant
P / ID
D isch a rg e T o
R e v is io n #
V a lv e S e le c te d
Drawing #
Index #
Issu e F o r
S e r v ic e
Inlet Line #
O utlet Line #
R e v is e d B y
S iz in g B a s is
ASM E
Code
C a u se o f O v e r P r e ssu r e
F luid State
PCV FAILURE
V a p o r (M a ss)
NACE
N o
N o R u p tu re D isk , 1
P r o c e s s P a r a m e te r s
MAWP
M ax. D esign T.
4 .5 B a r G
O perating
3 B ar G
P ressu re
Tem p.
4 .5 B a r G
R elief T em p.
O perating to Set %
6 6 .6 6 7
P ercen t O ver P .
A tm P ressu re
R e lie f P r e ssu r e
1 .0 1 3 3 B ar A b s
M in. Design T.
4 5 C
4 5 C
V ariable Back P.
0 .3 5 B a r G
O v e r P r e ssu r e
0 .4 5 B a r G
O perating
S et P ressu re
9 0 C
10
5 .9 6 3 3 B ar A b s
-5 0 C
C o n sta n t B a ck
0 .1 B a r G
P .
4 .4 B a r G
C o m p r e s s ib le S ta te
Fluid
M olecular W eight
N itrogen
S p ecific G ravity
2 8 6 8 1 kg/hr
C alculated A rea
0 .9 6 6 5 2 s p g r
1 0 .7 9 8 in
R e so lv e d A S M E A re a :
2 8 Mol Wt
1 0 .7 9 8 in
G a s F lo w C o n st.
C o m p ressib ility
1 .4 1
R e so lv e d A P I A re a :
(R eso lv ed b y M ax im u m )
357
9 .7 1 7 9 in
M o d e l S e le c tio n
F a rris
API Letter
2 6 Q A 1 0 -1 4 1 /S 3 /S P
API Area
ASME Area
Manufacturer
V a lv e D e sig n
C ap
C o n v e n tio n a l
C onstrn
Nam e
T est G a g
Packed L ever
Inlet Size
6 .0 in
O u tlet S ize
8 .0 in
1 1 .0 5 in
In. Rating
150
Out. Rating
150
1 2 .2 7 in
In. Facing
Quantity
Y es
O ut. F acing
RF
NACE
RF
N o
M odel M aterials
B ody
D is c
S A -351 G r. C F 8M
3 1 6 S S + S te llite (S P )
B e llo w s
B onnet
G uide
C u sto m
N/A
S A -351 G r. C F 8M
316
N o z z le
3 1 6 S S + S te llite (S P )
S p rin g
SS
A 320-B8 CL
2 /A 1 9 4 -8 (S P )
C hrom e A lloy N P
S iz in g S c e n a r io s
S c e n a r io
Fluid
C a u s e o f
R elief L oad
S ta te
O ver P.
C apacity
Relief T.
R e a c t. F o r c e
N o is e
N o is e
R equired
Atm (dBa)
Flare (dBa)
Area
PCV
C ase A
V apor
2 8 6 8 1 k g /h r
3 2 5 9 2 k g /h r
45 C
7 4 7 .0 8 lb s
1 1 2 .8 7
8 4 .6 5 3
1 0 .7 9 8 in
FAILURE
2 0 1 1 -0 7 -0 1
1 5 :2 6
SDS246953 REV 05
P age
VP-4400-427-001 -ALL-002_05
Page 94 of 1 59
T ag
P Q -1 0 1 7 9 0 : 2 2 6 -P S V
-0 4 0
- D a ta
S h e e t
R e lie f T e m p e r a tu r e
W vapor
Trelief
Z
K
G as
Flow
K CCF
P relief
M vapor
Kb
Kv
C o m p r e s s ib ilit y
G a s F lo w C o n s t a n t
D is c h a r g e C o e ff. (0 .9 x K d )
F lo w
R u p tu r e D is k C o e ffic ie n t
R e lie f P r e s s u r e
M o le c u la r W e ig h t
V a p o r F lo w F a c to r
V a p o r F lo w F a c to r
2 8 6 8 1 k g /h r
4 5 C
357
0 .8 5 7 7
C ritical
F lu id T y p e (U s e r D e fin e d )
G gas
k
Kd
S p e c ific G r a v ity
5 .9 6 3 3 B a r A b s
R a t io o f S p e c if ic H e a t s
2 8 M ol W t
D is c h a r g e C o e f f ic ie n t
N itro g e n
0 .9 6 6 5 2 s p g r
1 .4 1
0 .9 5 3
1 0 .7 9 8 in
T a g N o te s
" Q "
o r if ic e
a r e a
is
to
s m a ll
a f te r
r e v is e d
p r o c e s s
c o n d itio n s
h a v e
b e e n
a d d e d
F a rris
o ffe rs
S ta n d a rd
3 1 6
S tu d /N u ts
h a s
b e e n
o ffe re d ,
c u s to m e r
to
c h e c k
&
c o n f ir m .
1 5 -O C T :
T h e
c u s to m e r
s u b m itte d
n e w
d a ta
s h e e ts
w ith
c a p a c ity
a n d
b a c k
p re s s u re
c h a n g e s .
F a rris
p ro p o s e s
th e r e o f
th e
f o r
r e v is e d
v a lv e s
to
c o n s ta n t
m e a n s
c h a n g e
th e s e
c u s to m e r
c o m p e n s a te
d o w n s tre a m
th a t
th e
in
v a lv e s .
d a ta
fo r
v a lv e
T h is
c o n s tru c tio n
d u e
s h e e ts .
th e
to
h e n
c o n s ta n t
p re s s u re
c o n s ta n t
is
in
b a c k
th e
th e
o p e n
p r o c e s s in g
b a c k
p re s s u re .
s y s te m
p r e s s u r e
fro m
a d d itio n
to
m a y
o f
th e s e
T h e
e s c a p e
n o t
b o n n e t
e x is t,
a n d
c o n s ta n t
v a lv e s ,
o p e n
th ru
o r
th e
m a y
o p e n
b a c k
le v e r
p r e s s u r e
F a r r is
w ill
o r
c o m b in a tio n
a s
" n e t
f o u n d
s e t"
b o n n e t/le v e r
d e s ig n
o p e n
a n d
/o r
to
f lu id
b e
b o n n e t
lo w e r
d u e
o n
th e
a llo w s
th e
le v e r.
T h is
e s c a p e .
I n
th e
f ie ld ,
th e
T h e re fo re ,
F a rris
to
s o
p a c k e d ,
th e
v a lv e
a y
n o t
w o u ld
lik e
to
v a lv e
w ill
b e
r e lie v e
c h a n g e
a t
th e
a s s u r e d
o f
th e
d e s ir e d
b o n n e t
p r o p e r
fro m
S iz e M a s te r 4 .3 .2 .9 , D B : K :\A p p s \P r o je c ts \2 0 1 0 O r d e r s \2 4 6 9 5 3 -
to
c lo s e d
( I t
a n d
ill
th e
r e lie v e
le v e r
e a r ly ) .
fro m
o p e n
E n d o f 2 2 6 - P S V - 0 4 0 D a ta
S h e e t
1 5 :2 6
SDS246953 REV 05
p r e s s u r e
o p e r a tio n .
D A E L IM \S M P 2 4 6 9 5 3 _ 2 5 2 1 6 4
2 0 1 1 -0 7 -0 1
s e t
o p e n
P ag e
VP-4400-427-001 -ALL-002_05
Page 95 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Daelim
Job Description
PQ -1 01 790
Prepared By
Checked By
Approved By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 6-PSV -04 5
Plant #
P / ID
Discharge To
Revision #
Valve Selected
Drawing #
Index #
Issue For
Service
Inlet Line #
Outlet Line #
Revised By
Sizing Basis
ASME Code
Fluid State
PC V FAILURE
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
4 .5 Bar G
Operating to Set %
Max.
90 C
4 .5 Bar G
Design T.
Operating
Temp.
Relief Temp.
66.667
Percent
3 Bar G
Atm Pressure
Relief
4 5 C
Design T.
Constant Back
P.
Variable Back P.
0.35 Bar G
10 %
Over
Pressure
0.4 5 Bar G
Cold
Diff. Test P.
4 .4 Bar G
2 8 M ol W t
Gas
4 5 C
Over P.
Pressure
Min.
-50 C
0.1 Bar G
C ompressible State
Fluid
N itrog en
Molecular
Weight
2 8681 kg /hr
Specific
Gravity
Calculated Area
1 0.798 in
Specific
Heat Ratio
1 0.798 in
( Resolved
357
Compressibility
0.96652 sp g r
1 .4 1
by M aximum )
Flow Const.
9.71 79 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6Q A1 0-1 4 1 /S3/SP
API
Area
Valve Design
C onventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Air): 1 6686 SC FM
Inlet
Size
1 1 .05 in
In.
Rating
1 2 .2 7 in
In.
Facing
Quantity
Yes
6.0 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
8.0 in
1 50
RF
NACE
No
Model Materials
Body
SA-351 G r. C F8M
Disc
31 6 SS + Stellite (SP)
Bellows
N /A
Bonnet
Guide
Custom
SA-351 G r. C F8M
31 6
SS
A32 0-B8 C L
2 /A1 94 -8 (SP)
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
C hrome Alloy N P
Page 1
VP-4400-427-001 -ALL-002_05
Page 96 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
C ase A
Vapor
PC V
2 8681 kg /hr
FAILURE
32 592 kg /hr
4 5 C
74 7.08 lbs
1 1 2 .87
84 .653
1 0.798 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
2 8681 kg /hr
4 5 C
357
0.8577
C ritical
1
5.9633 Bar Abs
2 8 M ol Wt
1
-
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Nitrog en
0.96652 sp g r
1 .41
0.953
1 0.798 in
Tag Notes
"Q" orifice area is to small after revised p rocess conditions have been added
Farris offers Standard 3 16 Stud/Nuts has been offered, customer to check & confirm.
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
SizeM aster 4 .3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 6-PSV -04 5 Data Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 97 of 1 59
T ag
P Q -1 0 1 7 9 0 : 2 2 6 -P S V
-0 5 0
- D a ta
D ate Prepared:
S h e e t
2 0 1 1 -0 7 -0 1 1 5 :2 6
C u sto m er
R eq u isitio n #
Job #
C h eck ed B y
A p p roved B y
D aelim
J o b D e sc r ip tio n
P Q -1 0 1 7 9 0
P repared B y
S a u d i K a y a n L D P E P ro je c t
J o b S ta tu s
R e v is io n #
S iz in g /S e le c tin g
PSV Identification
T ag
T ag D escrip tion
T a g S ta tu s
2 2 6 -P S V -0 5 0
Plant
P / ID
D isch a rg e T o
R e v is io n #
V a lv e S e le c te d
Drawing #
Index #
Issu e F o r
S e r v ic e
Inlet Line #
O utlet Line #
R e v is e d B y
S iz in g B a s is
ASM E
Code
C a u se o f O v e r P r e ssu r e
F luid State
PCV FAILURE
V a p o r (M a ss)
NACE
N o
N o R u p tu re D isk , 1
P r o c e s s P a r a m e te r s
MAWP
M ax. D esign T.
4 .5 B a r G
O perating
3 B ar G
P ressu re
Tem p.
4 .5 B a r G
R elief T em p.
O perating to Set %
6 6 .6 6 7
P ercen t O ver P .
A tm P ressu re
R e lie f P r e ssu r e
1 .0 1 3 3 B ar A b s
M in. Design T.
4 5 C
4 5 C
V ariable Back P.
0 .3 5 B a r G
O v e r P r e ssu r e
0 .4 5 B a r G
O perating
S et P ressu re
9 0 C
10
5 .9 6 3 3 B ar A b s
-5 0 C
C o n sta n t B a ck
0 .1 B a r G
P .
4 .4 B a r G
C o m p r e s s ib le S ta te
Fluid
M olecular W eight
N itrogen
S p ecific G ravity
2 8 6 8 1 kg/hr
C alculated A rea
0 .9 6 6 5 2 s p g r
1 0 .7 9 8 in
R e so lv e d A S M E A re a :
2 8 Mol Wt
1 0 .7 9 8 in
G a s F lo w C o n st.
C o m p ressib ility
1 .4 1
R e so lv e d A P I A re a :
(R eso lv ed b y M ax im u m )
357
9 .7 1 7 9 in
M o d e l S e le c tio n
F a rris
API Letter
2 6 Q A 1 0 -1 4 1 /S 3 /S P
API Area
ASME Area
Manufacturer
V a lv e D e sig n
C ap
C o n v e n tio n a l
C onstrn
Nam e
T est G a g
Packed L ever
Inlet Size
6 .0 in
O u tlet S ize
8 .0 in
1 1 .0 5 in
In. Rating
150
Out. Rating
150
1 2 .2 7 in
In. Facing
Quantity
Y es
O ut. F acing
RF
NACE
RF
N o
M odel M aterials
B ody
D is c
S A -351 G r. C F 8M
3 1 6 S S + S te llite (S P )
B e llo w s
B onnet
G uide
C u sto m
N/A
S A -351 G r. C F 8M
316
N o z z le
3 1 6 S S + S te llite (S P )
S p rin g
SS
A 320-B8 CL
2 /A 1 9 4 -8 (S P )
C hrom e A lloy N P
S iz in g S c e n a r io s
S c e n a r io
Fluid
C a u s e o f
R elief L oad
S ta te
O ver P.
C apacity
Relief T.
R e a c t. F o r c e
N o is e
N o is e
R equired
Atm (dBa)
Flare (dBa)
Area
PCV
C ase A
V apor
2 8 6 8 1 k g /h r
3 2 5 9 2 k g /h r
45 C
7 4 7 .0 8 lb s
1 1 2 .8 7
8 4 .6 5 3
1 0 .7 9 8 in
FAILURE
2 0 1 1 -0 7 -0 1
1 5 :2 6
SDS246953 REV 05
P age
VP-4400-427-001 -ALL-002_05
Page 98 of 1 59
T ag
P Q -1 0 1 7 9 0 : 2 2 6 -P S V
-0 5 0
- D a ta
S h e e t
R e lie f T e m p e r a tu r e
W vapor
Trelief
Z
K
G as
Flow
K CCF
P relief
M vapor
Kb
Kv
C o m p r e s s ib ilit y
G a s F lo w C o n s t a n t
D is c h a r g e C o e ff. (0 .9 x K d )
F lo w
R u p tu r e D is k C o e ffic ie n t
R e lie f P r e s s u r e
M o le c u la r W e ig h t
V a p o r F lo w F a c to r
V a p o r F lo w F a c to r
2 8 6 8 1 k g /h r
4 5 C
357
0 .8 5 7 7
C ritical
F lu id T y p e (U s e r D e fin e d )
G gas
k
Kd
S p e c ific G r a v ity
5 .9 6 3 3 B a r A b s
R a t io o f S p e c if ic H e a t s
2 8 M ol W t
D is c h a r g e C o e f f ic ie n t
N itro g e n
0 .9 6 6 5 2 s p g r
1 .4 1
0 .9 5 3
1 0 .7 9 8 in
T a g N o te s
" Q "
o r if ic e
a r e a
is
to
s m a ll
a f te r
r e v is e d
p r o c e s s
c o n d itio n s
h a v e
b e e n
a d d e d
F a rris
o ffe rs
S ta n d a rd
3 1 6
S tu d /N u ts
h a s
b e e n
o ffe re d ,
c u s to m e r
to
c h e c k
&
c o n f ir m .
1 5 -O C T :
T h e
c u s to m e r
s u b m itte d
n e w
d a ta
s h e e ts
w ith
c a p a c ity
a n d
b a c k
p re s s u re
c h a n g e s .
F a rris
p ro p o s e s
th e r e o f
th e
f o r
r e v is e d
v a lv e s
to
c o n s ta n t
m e a n s
c h a n g e
th e s e
c u s to m e r
c o m p e n s a te
d o w n s tre a m
th a t
th e
in
v a lv e s .
d a ta
fo r
v a lv e
T h is
c o n s tru c tio n
d u e
s h e e ts .
th e
to
h e n
c o n s ta n t
p re s s u re
c o n s ta n t
is
in
b a c k
th e
th e
o p e n
p r o c e s s in g
b a c k
p re s s u re .
s y s te m
p r e s s u r e
fro m
a d d itio n
to
m a y
o f
th e s e
T h e
e s c a p e
n o t
b o n n e t
e x is t,
a n d
c o n s ta n t
v a lv e s ,
o p e n
th ru
o r
th e
m a y
o p e n
b a c k
le v e r
p r e s s u r e
F a r r is
w ill
o r
c o m b in a tio n
a s
" n e t
f o u n d
s e t"
b o n n e t/le v e r
d e s ig n
o p e n
a n d
/o r
to
f lu id
b e
b o n n e t
lo w e r
d u e
o n
th e
a llo w s
th e
le v e r.
T h is
e s c a p e .
I n
th e
f ie ld ,
th e
T h e re fo re ,
F a rris
to
s o
p a c k e d ,
th e
v a lv e
a y
n o t
w o u ld
lik e
to
v a lv e
w ill
b e
r e lie v e
c h a n g e
a t
th e
a s s u r e d
o f
th e
d e s ir e d
b o n n e t
p r o p e r
fro m
S iz e M a s te r 4 .3 .2 .9 , D B : K :\A p p s \P r o je c ts \2 0 1 0 O r d e r s \2 4 6 9 5 3 -
to
c lo s e d
( I t
a n d
ill
th e
r e lie v e
le v e r
e a r ly ) .
fro m
o p e n
E n d o f 2 2 6 - P S V - 0 5 0 D a ta
S h e e t
1 5 :2 6
SDS246953 REV 05
p r e s s u r e
o p e r a tio n .
D A E L IM \S M P 2 4 6 9 5 3 _ 2 5 2 1 6 4
2 0 1 1 -0 7 -0 1
s e t
o p e n
P ag e
VP-4400-427-001 -ALL-002_05
Page 99 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 6-PSV -057
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
PC V FAILURE
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
4 .5 Bar G
Design T.
Operating
Temp.
Relief Temp.
66.667
Percent Over P.
4 .5 Bar G
3 Bar G
Operating to Set %
Atm Pressure
Relief
Pressure
Min.
4 5 C
Design T.
Constant Back
P.
Variable Back P.
0.35 Bar G
10 %
Over Pressure
0.4 5 Bar G
90 C
4 5 C
Cold
2 8 M ol W t
Gas
-50 C
0.1 Bar G
Diff. Test P.
4 .4 Bar G
C ompressible State
Fluid
N itrog en
Molecular
Weight
2 8681 kg /hr
Specific
Gravity
Calculated Area
1 0.798 in
Specific
Heat Ratio
1 0.798 in
( Resolved
357
Compressibility
0.96652 sp g r
1 .4 1
by M aximum )
Flow Const.
9.71 79 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6Q A1 0-1 4 1 /S3/SP
API
Area
Valve Design
C onventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Air): 1 6686 SC FM
Inlet
Size
1 1 .05 in
In.
Rating
1 2 .2 7 in
In.
Facing
Quantity
Yes
6.0 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
8.0 in
1 50
RF
NACE
No
Model Materials
Body
SA-351 G r. C F8M
Disc
31 6 SS + Stellite (SP)
Bellows
N /A
Bonnet
Guide
Custom
SA-351 G r. C F8M
31 6
SS
A32 0-B8 C L
2 /A1 94 -8 (SP)
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
C hrome Alloy N P
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 00 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
C ase A
Vapor
PC V
2 8681 kg /hr
FAILURE
32 592 kg /hr
4 5 C
74 7.08 lbs
1 1 2 .87
84 .653
1 0.798 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
2 8681 kg /hr
4 5 C
357
0.8577
C ritical
1
5.9633 Bar Abs
2 8 M ol Wt
1
-
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Nitrog en
0.96652 sp g r
1 .41
0.953
1 0.798 in
Tag Notes
"Q" orifice area is to small after revised p rocess conditions have been added
Farris offers Standard 3 16 Stud/Nuts has been offered, customer to check & confirm.
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
SizeM aster 4 .3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 6-PSV -057 Data Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 01 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 6-PSV -062
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
PC V FAILURE
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
4 .5 Bar G
Design T.
Operating
Temp.
Relief Temp.
66.667
Percent Over P.
4 .5 Bar G
3 Bar G
Operating to Set %
Atm Pressure
Relief
Pressure
Min.
4 5 C
Design T.
Constant Back
P.
Variable Back P.
0.35 Bar G
10 %
Over Pressure
0.4 5 Bar G
90 C
4 5 C
Cold
2 8 M ol W t
Gas
-50 C
0.1 Bar G
Diff. Test P.
4 .4 Bar G
C ompressible State
Fluid
N itrog en
Molecular
Weight
2 8681 kg /hr
Specific
Gravity
Calculated Area
1 0.798 in
Specific
Heat Ratio
1 0.798 in
( Resolved
357
Compressibility
0.96652 sp g r
1 .4 1
by M aximum )
Flow Const.
9.71 79 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6Q A1 0-1 4 1 /S3/SP
API
Area
Valve Design
C onventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Air): 1 6686 SC FM
Inlet
Size
1 1 .05 in
In.
Rating
1 2 .2 7 in
In.
Facing
Quantity
Yes
6.0 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
8.0 in
1 50
RF
NACE
No
Model Materials
Body
SA-351 G r. C F8M
Disc
31 6 SS + Stellite (SP)
Bellows
N /A
Bonnet
Guide
Custom
SA-351 G r. C F8M
31 6
SS
A32 0-B8 C L
2 /A1 94 -8 (SP)
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
C hrome Alloy N P
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 02 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
C ase A
Vapor
PC V
2 8681 kg /hr
FAILURE
32 592 kg /hr
4 5 C
74 7.08 lbs
1 1 2 .87
84 .653
1 0.798 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
2 8681 kg /hr
4 5 C
357
0.8577
C ritical
1
5.9633 Bar Abs
2 8 M ol Wt
1
-
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Nitrog en
0.96652 sp g r
1 .41
0.953
1 0.798 in
Tag Notes
"Q" orifice area is to small after revised p rocess conditions have been added
Farris offers Standard 3 16 Stud/Nuts has been offered, customer to check & confirm.
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
SizeM aster 4 .3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 6-PSV -062 Data Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 03 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 6-PSV -067
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
PC V FAILURE
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
4 .5 Bar G
Design T.
Operating
Temp.
Relief Temp.
66.667
Percent Over P.
4 .5 Bar G
3 Bar G
Operating to Set %
Atm Pressure
Relief
Pressure
Min.
4 5 C
Design T.
Constant Back
P.
Variable Back P.
0.35 Bar G
10 %
Over Pressure
0.4 5 Bar G
90 C
4 5 C
Cold
2 8 M ol W t
Gas
-50 C
0.1 Bar G
Diff. Test P.
4 .4 Bar G
C ompressible State
Fluid
N itrog en
Molecular
Weight
2 8681 kg /hr
Specific
Gravity
Calculated Area
1 0.798 in
Specific
Heat Ratio
1 0.798 in
( Resolved
357
Compressibility
0.96652 sp g r
1 .4 1
by M aximum )
Flow Const.
9.71 79 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6Q A1 0-1 4 1 /S3/SP
API
Area
Valve Design
C onventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Air): 1 6686 SC FM
Inlet
Size
1 1 .05 in
In.
Rating
1 2 .2 7 in
In.
Facing
Quantity
Yes
6.0 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
8.0 in
1 50
RF
NACE
No
Model Materials
Body
SA-351 G r. C F8M
Disc
31 6 SS + Stellite (SP)
Bellows
N /A
Bonnet
Guide
Custom
SA-351 G r. C F8M
31 6
SS
A32 0-B8 C L
2 /A1 94 -8 (SP)
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
C hrome Alloy N P
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 04 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
C ase A
Vapor
PC V
2 8681 kg /hr
FAILURE
32 592 kg /hr
4 5 C
74 7.08 lbs
1 1 2 .87
84 .653
1 0.798 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
2 8681 kg /hr
4 5 C
357
0.8577
C ritical
1
5.9633 Bar Abs
2 8 M ol Wt
1
-
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Nitrog en
0.96652 sp g r
1 .41
0.953
1 0.798 in
Tag Notes
"Q" orifice area is to small after revised p rocess conditions have been added
Farris offers Standard 3 16 Stud/Nuts has been offered, customer to check & confirm.
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
SizeM aster 4 .3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 6-PSV -067 Data Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 05 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 6-PSV -802
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
NACE
N o
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
1 5 Bar G
Design T.
Operating
Temp.
Relief Temp.
66.667
Percent Over P.
- Bar G
1 0 Bar G
Operating to Set %
Atm Pressure
Max.
Relief
Pressure
Min.
0.1 Bar G
90 C
Design T.
Constant Back
P.
Variable Back P.
10 %
Over Pressure
1 .5 Bar G
90 C
30 C
Cold
- C
1 .4 Bar G
Diff. Test P.
1 4 .9 Bar G
Fluid Type
WATER
2 0 kg /hr
Viscosity
0.79 C entipoise
Calculated Area
2 .533e-4 in
Reynolds #
807.01
Specific
2.533e-4 in
Gravity
( Resolved
Viscosity
1 .04 sp g r
by M aximum )
Type
Absolute
2.280e-4 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
C onventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 2 6 US g pm
0.068 in
Yes
Size
Quantity
0.75 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
1 .00 in
1 50
RF
No
Model Materials
Body
31 6
SS
Bonnet
31 6
SS
Nozzle
31 6
SS
Disc
31 6
SS
Guide
31 6
SS
Spring
31 6
SS
Custom
A1 93-B8 C L.
2 /A1 94 -8 (SP)
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 06 of 1 59
Sizing Scenarios
Scenario
Fluid
State
C ase A
Liquid
Cause of
Over P.
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
BLO C KED
20 kg /hr
5368.9 kg /hr
90 C
2 .533e-4 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.01 92 59 m/hr
1 .04 sp g r
0.6759
1 5 Bar G
0.901 1
User Defined
Absolute
0.79 C entipoise
807.01
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
2 0 kg /hr
0.751
90 C
2 .533e-4 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4 .3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 6-PSV -802 Data Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 07 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 7-PSV -01 4 A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
C V Failure
Steam
NACE
N o
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
1 0.5 Bar G
5.2 Bar G
1 0.5 Bar G
Operating to Set %
4 9.52 4
Atm Pressure
1 60 C
4 00 C
Percent Over P.
Relief
Pressure
Min.
1 95 C
10 %
1 2 .563 Bar Abs
Design T.
Constant Back
P.
Variable Back P.
0.95 Bar G
Over Pressure
1 .05 Bar G
Cold
-5 C
0.1 Bar G
Diff. Test P.
1 0.504 Bar G
S team S tate
Calculated Area
8.9752 in
Req.
8.9752 in
Flow Cap.
( Resolved
Napier
2 7000 kg /hr
by M aximum )
Superheat
0.82 4
8.0777 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6Q A1 2-1 4 1 /SP
API
Area
Valve Design
C onventional
ASME
Inlet
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Steam): 98760 lb/hr
Size
1 1 .05 in
In.
Rating
1 2 .2 7 in
In.
Facing
Quantity
Yes
6.0 in
Outlet
Size
300
Out.
Rating
RF
Out.
Facing
NACE
8.0 in
1 50
RF
No
Model Materials
Body
Disc
SA-2 1 6 G r. WC B
Stellite (SP)
Bellows
Bonnet
Guide
Custom
N /A
SA-2 1 6 G r. WC B
31 6
SS
Nozzle
Spring
Stellite (SP)
C hrome Alloy
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
C ase A
Steam
C V
Failure
2 7000 kg /hr
3691 2 kg /hr
4 00 C
2 011-02 -2 3 16: 06
SDS246953 REV 05
21 2 1 .5 lbs
1 1 9.04
89.2 82
8.9752 in
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 08 of 1 59
Relief Pressure
Vapor Flow Factor
Superheat Factor
Napier Factor
Wsteam
K
Gas
K
CCF
P
relief
K
b
K
v
K
sh
K
n
27000 kg /hr
0.8577
0.82 4
1
Relief Temperature
Discharge Coefficient
Trelief
K
d
4 00 C
0.953
8.9752 in
Tag Notes
Farris offers a 6" x 8" inlet/outlet "Q" orifice valve as p er revised sizing calculations in
lieu of 8" x 10" inlet/outlet "T" orifice valve as sp ecified on the p rocess data sheet,
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
Fluid has been changed from Liquid to Steam, cap acity has been changed to 2 7000 kg/hr. Valve
model has been changed from a liquid trim valve to a gas/vap or valve for steam fluid.
Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 09 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 7-PSV -02 0A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
Steam
NACE
N o
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
1 7 Bar G
Design T.
Operating
Temp.
Relief Temp.
4 0.588
Percent Over P.
1 7 Bar G
6.9 Bar G
Operating to Set %
Atm Pressure
Relief
Min.
2 1 5 C
1 70 C
4 00 C
10 %
Pressure
Design T.
Constant Back
P.
Variable Back P.
0.1 Bar G
Over Pressure
1 .7 Bar G
Cold
-5 C
1 .6 Bar G
Diff. Test P.
1 7.069 Bar G
S team S tate
Calculated Area
5.651 3 in
Req.
5.651 3 in
Flow Cap.
( Resolved
Napier
2 7000 kg /hr
by M aximum )
Superheat
0.834
5.0862 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6PA1 2 -1 4 1 /SP
API
Area
Valve Design
C onventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Steam): 89506 lb/hr
Inlet
Size
6.380 in
In.
Rating
7.087 in
In.
Facing
Quantity
Yes
4 .0 in
Outlet
300
Out.
Rating
RF
Out.
Facing
Size
NACE
6.0 in
1 50
RF
No
Model Materials
Body
Disc
SA-2 1 6 G r. WC B
31 6 SS + Stellite (SP)
Bellows
Bonnet
Guide
Custom
N /A
Nozzle
SA-2 1 6 G r. WC B
31 6
Spring
SS
31 6 SS + Stellite (SP)
C hrome Alloy
Sizing Scenarios
Scenario
Fluid
State
C ase A
Steam
Cause of
Over P.
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
2 7000 kg /hr
33859 kg /hr
4 00 C
2 011-02 -2 3 16: 06
SDS246953 REV 05
21 76.7 lbs
1 1 9.23
89.4 2 2
5.651 3 in
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 1 0 of 1 59
Relief Pressure
Vapor Flow Factor
Superheat Factor
Napier Factor
Wsteam
K
Gas
K
CCF
P
relief
K
b
K
v
K
sh
K
n
27000 kg /hr
0.8577
0.834
1
Relief Temperature
Discharge Coefficient
Trelief
K
d
4 00 C
0.953
5.651 3 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 1 1 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 7-PSV -02 8A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
C V FAILURE
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
6 Bar G
3.5 Bar G
6 Bar G
Operating to Set %
58.333
Atm Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
1 4 8 C
1 1 8 C
Percent Over P.
Relief
Min.
2 00 C
10 %
Pressure
Gravity
0.933 sp g r
Design T.
Constant Back
P.
Variable Back P.
0.1 Bar G
Over Pressure
0.6 Bar G
Cold
5.9 Bar G
-5 C
0.5 Bar G
Diff. Test P.
Fluid Type
Steam
Specific
Viscosity
Type
Absolute
1 4 3000 kg /hr
Viscosity
0.2 3 C entipoise
Calculated Area
2 .82 6 in
Reynolds #
4 31 1 2 2 6
2.826 in
( Resolved
by M aximum )
2.5434 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
3.600 in
In.
Rating
4 .000 in
In.
Facing
Valve Design
C onventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 2 09.86 m3/hr
Inlet
Size
Quantity
Yes
4 .0 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
6.0 in
1 50
RF
No
Model Materials
Body
Disc
SA-2 1 6 G r. WC B
Stellite (SP)
Bellows
N /A
Bonnet
Guide
Custom
SA-2 1 6 G r. WC B
31 6
SS
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
Stellite (SP)
C hrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 1 2 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
S team
C ase A
Liquid
C V
Failure
2500 kg /hr
8773.5 kg /hr
200 C
330.85 lbs
1 1 0.72
83.036
1 .1 398 in
C V
1 4 3000 kg /hr
FAILURE
2 024 03 kg /hr
1 1 8 C
2 0.873 lbs
2 .82 6 in
Relief Pressure
Vapor Flow Factor
Superheat Factor
Napier Factor
Wsteam
K
Gas
K
CCF
P
relief
K
b
K
v
K
sh
K
n
2 500 kg /hr
0.8577
0.991 4
1
Relief Temperature
Discharge Coefficient
Trelief
K
d
2 00 C
0.953
1 .1 398 in
1 4 3000 kg /hr
0.72 4
1 1 8 C
2 .826 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
1 53.4 9 m/hr
0.933 sp g r
0.651 6
6 Bar G
1
User Defined
Absolute
0.2 3 C entipoise
431 1 2 2 6
Discharge Coefficient
Relief Temperature
Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Qliquid
K
d
Trelief
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 1 3 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 7-PSV -032 A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
C V FAILURE
Steam
NACE
N o
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
6 Bar G
0.2 Bar G
6 Bar G
Operating to Set %
3.3333
Atm Pressure
1 05 C
1 71 C
Percent Over P.
Relief
Pressure
Min.
2 1 5 C
10 %
7.61 33 Bar Abs
Design T.
Constant Back
P.
Variable Back P.
0.1 Bar G
Over Pressure
0.6 Bar G
Cold
5.9 Bar G
-5 C
0.5 Bar G
Diff. Test P.
S team S tate
Calculated Area
4 .1 1 32 in
Req.
4.1 1 32 in
Flow Cap.
( Resolved
Napier
91 00 kg /hr
Superheat
3.701 9 in
by M aximum )
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
C onventional
ASME
Inlet
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Steam): 1 0668 kg /hr
Size
4 .34 0 in
In.
Rating
4 .82 2 in
In.
Facing
Quantity
Yes
4 .0 in
Outlet
Size
1 50
Out.
Rating
RF
Out.
Facing
NACE
6.0 in
1 50
RF
No
Model Materials
Body
Disc
SA-2 1 6 G r. WC B
Stellite (SP)
Bellows
Bonnet
Guide
Custom
N /A
SA-2 1 6 G r. WC B
31 6
SS
Nozzle
Spring
Stellite (SP)
C hrome Alloy
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
C ase A
Steam
C V
FAILURE
91 00 kg /hr
1 0668 kg /hr
1 71 C
2 011-02 -2 3 16: 06
SDS246953 REV 05
398.84 lbs
1 1 1 .29
83.4 67
4.1 1 32 in
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 1 4 of 1 59
Relief Pressure
Vapor Flow Factor
Superheat Factor
Napier Factor
Wsteam
K
Gas
K
CCF
P
relief
K
b
K
v
K
sh
K
n
91 00 kg /hr
0.8577
1
1
Relief Temperature
Discharge Coefficient
Trelief
K
d
1 71 C
0.953
4.1 1 32 in
Tag Notes
15-OCT: The Revised data sheet submitted by the customer changes the cap acity and back
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 1 5 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 7-PSV -04 3A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
C V Failure
Steam
NACE
N o
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
1 7 Bar G
Design T.
Operating
Temp.
Relief Temp.
64 .706
Percent Over P.
52 Bar G
1 1 Bar G
Operating to Set %
Atm Pressure
Relief
Pressure
Min.
4 00 C
2 09.1 C
4 00 C
10 %
1 9.71 3 Bar Abs
Design T.
Constant Back
P.
Variable Back P.
0.1 Bar G
Over Pressure
1 .7 Bar G
Cold
0 C
1 .6 Bar G
Diff. Test P.
1 7.069 Bar G
S team S tate
Calculated Area
3.5582 in
Req.
3.5582 in
Flow Cap.
( Resolved
Napier
1 7000 kg /hr
by M aximum )
Superheat
0.834
3.2024 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6PA1 2 -1 4 1 /SP
API
Area
Valve Design
C onventional
ASME
Inlet
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Steam): 89506 lb/hr
Size
6.380 in
In.
Rating
7.087 in
In.
Facing
Quantity
Yes
4 .0 in
Outlet
Size
300
Out.
Rating
RF
Out.
Facing
NACE
6.0 in
1 50
RF
No
Model Materials
Body
Disc
SA-2 1 6 G r. WC B
Stellite (SP)
Bellows
Bonnet
Guide
Custom
N /A
SA-2 1 6 G r. WC B
31 6
SS
Nozzle
Spring
Stellite (SP)
C hrome Alloy
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
C ase A
Steam
C V
Failure
1 7000 kg /hr
33859 kg /hr
4 00 C
2 011-02 -2 3 16: 06
SDS246953 REV 05
21 76.7 lbs
1 1 9.23
89.4 2 2
3.5582 in
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 1 6 of 1 59
Relief Pressure
Vapor Flow Factor
Superheat Factor
Napier Factor
Wsteam
K
Gas
K
CCF
P
relief
K
b
K
v
K
sh
K
n
1 7000 kg /hr
0.8577
0.834
1
Relief Temperature
Discharge Coefficient
Trelief
K
d
4 00 C
0.953
3.5582 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 1 7 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 7-PSV -04 6A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
C V Failure
Steam
NACE
N o
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
6 Bar G
4 Bar G
6 Bar G
Operating to Set %
66.667
Atm Pressure
1 56 C
2 1 0 C
Percent Over P.
Relief
Pressure
Min.
360 C
10 %
7.61 33 Bar Abs
Design T.
Constant Back
P.
Variable Back P.
0.1 Bar G
Over Pressure
0.6 Bar G
Cold
-5 C
0.5 Bar G
Diff. Test P.
5.959 Bar G
S team S tate
Calculated Area
9.1 31 7 in
Req.
9.1 31 7 in
Flow Cap.
( Resolved
Napier
1 9900 kg /hr
by M aximum )
Superheat
0.985
8.21 86 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6Q A1 0-1 4 1 /SP
API
Area
Valve Design
C onventional
ASME
Inlet
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Steam): 5984 9 lb/hr
Size
1 1 .05 in
In.
Rating
1 2 .2 7 in
In.
Facing
Quantity
Yes
6.0 in
Outlet
Size
1 50
Out.
Rating
RF
Out.
Facing
NACE
8.0 in
1 50
RF
No
Model Materials
Body
Disc
SA-2 1 6 G r. WC B
31 6 SS + Stellite (SP)
Bellows
Bonnet
Guide
Custom
N /A
SA-2 1 6 G r. WC B
31 6
Nozzle
31 6 SS + Stellite (SP)
Spring
SS
C hrome Alloy
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
C ase A
Steam
C V
Failure
1 9900 kg /hr
2 6739 kg /hr
2 1 0 C
2 011-02 -2 3 16: 06
SDS246953 REV 05
1 01 4.9 lbs
1 1 5.65
86.734
9.1 31 7 in
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 1 8 of 1 59
Relief Pressure
Vapor Flow Factor
Superheat Factor
Napier Factor
Wsteam
K
Gas
K
CCF
P
relief
K
b
K
v
K
sh
K
n
1 9900 kg /hr
0.8577
0.985
1
Relief Temperature
Discharge Coefficient
Trelief
K
d
2 1 0 C
0.953
9.1 31 7 in
Tag Notes
15-OCT: Customer submitted revised data sheets with change in cap acity and back p ressure
valve model changes from a "P" to "Q" orifce valve with a p acked lever due to steam service.
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 1 9 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 7-PSV -053
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
1 0 Bar G
2 .5 Bar G
1 0 Bar G
Operating to Set %
25
Atm Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
72 C
Design T.
Constant Back
P.
Variable Back P.
10 %
Over Pressure
50 C
Percent Over P.
Relief
Min.
90 C
Pressure
Gravity
0.988 sp g r
Cold
-5 C
0.1 Bar G
0.9 Bar G
1 Bar G
Diff. Test P.
9.9 Bar G
Fluid Type
C ooling Water
Specific
Viscosity
Type
Absolute
81 0 kg /hr
Viscosity
0.5 C entipoise
Calculated Area
0.01 1 61 6 in
Reynolds #
51 64 1
0.01 1 61 6 in
( Resolved
by M aximum )
0.01 0455 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
C onventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 39 US g pm
0.1 2 5 in
Yes
Size
Quantity
0.75 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
1 .00 in
1 50
RF
No
Model Materials
Body
31 6
Disc
Custom
Bonnet
SS
Stellite (SP)
Guide
SA-2 1 6 , G r.
WC B/A1 05
31 6
SS
Spring
Stellite (SP)
31 6
SS
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 20 of 1 59
Sizing Scenarios
Scenario
Fluid
State
C ase A
Liquid
Cause of
Over P.
Blocked
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
81 0 kg /hr
72 C
0.01 1 61 6 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.821 03 m/hr
0.988 sp g r
0.6759
1 0 Bar G
1
User Defined
Absolute
0.5 C entipoise
51 64 1
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
81 0 kg /hr
0.751
72 C
0.01 1 61 6 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4 .3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 7-PSV -053 Data Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 21 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 7-PSV -054
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
1 0 Bar G
2 .5 Bar G
1 0 Bar G
Operating to Set %
25
Atm Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
72 C
Design T.
Constant Back
P.
Variable Back P.
10 %
Over Pressure
50 C
Percent Over P.
Relief
Min.
90 C
Pressure
Gravity
0.988 sp g r
Cold
-5 C
0.1 Bar G
0.9 Bar G
1 Bar G
Diff. Test P.
9.9 Bar G
Fluid Type
C ooling Water
Specific
Viscosity
Type
Absolute
81 0 kg /hr
Viscosity
0.5 C entipoise
Calculated Area
0.01 1 61 6 in
Reynolds #
51 64 1
0.01 1 61 6 in
( Resolved
by M aximum )
0.01 0455 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
C onventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 39 US g pm
0.1 2 5 in
Yes
Size
Quantity
0.75 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
1 .00 in
1 50
RF
No
Model Materials
Body
31 6
Disc
Custom
Bonnet
SS
Stellite (SP)
Guide
SA-2 1 6 , G r.
WC B/A1 05
31 6
SS
Spring
Stellite (SP)
31 6
SS
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 22 of 1 59
Sizing Scenarios
Scenario
Fluid
State
C ase A
Liquid
Cause of
Over P.
Blocked
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
81 0 kg /hr
72 C
0.01 1 61 6 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.821 03 m/hr
0.988 sp g r
0.6759
1 0 Bar G
1
User Defined
Absolute
0.5 C entipoise
51 64 1
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
81 0 kg /hr
0.751
72 C
0.01 1 61 6 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4 .3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 7-PSV -054 Data Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 23 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 7-PSV -057A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
Vapor (M ass)
NACE
No
N o Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
52 Bar G
Design T.
Operating
Temp.
Relief Temp.
86.538
Percent Over P.
52 Bar G
4 5 Bar G
Operating to Set %
Atm Pressure
Relief
Pressure
Min.
0.1 Bar G
4 5 C
Design T.
Constant Back
P.
Variable Back P.
10 %
Over Pressure
5.2 Bar G
2 70 C
4 5 C
Cold
2 8 M ol W t
Gas
-5 C
5.1 Bar G
Diff. Test P.
51 .9 Bar G
C ompressible State
Fluid
Molecular
N itrog en
Weight
2 1 00 kg /hr
Specific
Gravity
Calculated Area
0.07964 9 in
Specific
Heat Ratio
0.079649 in
( Resolved
363
Compressibility
0.96652 sp g r
1 .4 8
by M aximum )
Flow Const.
0.071 684 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
C onventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Air): 1 991 SC FM
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
600
Out.
Rating
RF
Out.
Facing
NACE
Size
2 .0 in
300
RF
No
Model Materials
Body
SA-351 G r. C F8M
Disc
31 6 SS + Stellite (SP)
Bellows
N /A
Bonnet
SA-351 G r. C F8M
Guide
Outlet
31 6
Flange
SS
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
Custom
31 6 SS + Stellite (SP)
C hrome Alloy NP
A320-B8 C L
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 24 of 1 59
Sizing Scenarios
Scenario
Fluid
State
C ase A
Vapor
Cause of
Over P.
Blocked
Flow : PC V Failure
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
2 1 00 kg /hr
3954 .8 kg /hr
4 5 C
1 2 1 .89 lbs
1 05.83
79.371
0.07964 9 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
21 00 kg /hr
4 5 C
363
0.8577
C ritical
1
58.2 1 3 Bar Abs
2 8 M ol Wt
1
-
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Nitrog en
0.96652 sp g r
1 .48
0.953
0.07964 9 in
Tag Notes
Farris offers Standard 3 16 Stud/Nuts has been offered, customer to check & confirm.
15-OCT: The customer submitted revised data sheets changing the back p ressure and required
cap acity. The valve model changes from an op en bonnet, op en lever to a closed bonnet and
p acked lever.
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
to p acked or bolted in some cases, so the valve will be assured of p rop er op eration.
Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 25 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 7-PSV -059A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
Steam
NACE
N o
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
52 Bar G
39 Bar G
52 Bar G
Operating to Set %
75
Atm Pressure
Relief
Pressure
Design T.
Constant Back
P.
Variable Back P.
2 30 C
2 79 C
Percent Over P.
Min.
2 70 C
21
-5 C
0.1 Bar G
5.1 Bar G
Over Pressure
Cold
1 0.92 Bar G
Diff. Test P.
52 .4 1 9 Bar G
S team S tate
Calculated Area
0.059207 in
Req.
0.059207 in
Flow Cap.
( Resolved
Napier
1 1 00 kg /hr
Superheat
0.053287 in
by M aximum )
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
C onventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Steam): 5594 lb/hr
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
Size
600
Out.
Rating
RF
Out.
Facing
2 .0 in
300
RF
NACE
No
Model Materials
Body
Disc
SA-2 1 6 G r. WC B
31 6 SS + Stellite (SP)
Bellows
Bonnet
Guide
Outlet
N /A
SA-2 1 6 G r. W C B
31 6
Flange
SS
Nozzle
31 6 SS + Stellite (SP)
Spring
C hrome Alloy
Custom
Sizing Scenarios
Scenario
Fluid
State
C ase A
S team
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Liq uid
Vaporization
1 1 00 kg /hr
2786.8 kg /hr
2 79 C
2 011-02 -2 3 16: 06
SDS246953 REV 05
1 31 .77 lbs
1 08.1 2
81 .088
0.0592 07 in
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 26 of 1 59
Relief Pressure
Vapor Flow Factor
Superheat Factor
Napier Factor
Wsteam
K
Gas
K
CCF
P
relief
K
b
K
v
K
sh
K
n
1 1 00 kg /hr
0.8577
1
1
Relief Temperature
Discharge Coefficient
Trelief
K
d
2 79 C
0.953
0.0592 07 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
Tne sizing bases changed to gas/vap or, fluid steam. The valve model has changed form a 1x2
inch "D" orfice liquid valve to a 1. 5 x 3 inch "G" orfice gas/vap or. Customer to conmfim.
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 27 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 7-PSV -060
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
64 Bar G
Design T.
Operating
Temp.
Relief Temp.
73.4 38
Percent Over P.
64 Bar G
4 7 Bar G
Operating to Set %
Atm Pressure
Max.
Relief
Pressure
Min.
0.1 Bar G
90 C
Design T.
Constant Back
P.
Variable Back P.
10 %
Over Pressure
6.4 Bar G
2 65 C
1 4 5 C
Cold
-5 C
6.3 Bar G
Diff. Test P.
63.9 Bar G
Fluid Type
WATER
4 0 kg /hr
Viscosity
0.1 9 C entipoise
Calculated Area
2 .4 1 9e-4 in
Reynolds #
671 0.9
Specific
2.41 9e-4 in
Gravity
( Resolved
Viscosity
0.92 sp g r
Type
by M aximum )
Absolute
2.1 77e-4 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
C onventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 2 2 .2 58 m3/hr
0.1 2 5 in
Size
Quantity
Yes
0.75 in
Outlet
600
Out.
Rating
RF
Out.
Facing
Size
NACE
1 .00 in
300
RF
No
Model Materials
Body
Disc
Outlet Flange
31 6
SS
31 6 SS + Stellite (SP)
300# Flang e (SP)
Bonnet
Guide
Custom
SA-2 1 6 , G r.
WC B/A1 05
31 6
SS
A1 93-B8 C L
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
31 6
SS
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 28 of 1 59
Sizing Scenarios
Scenario
Fluid
State
C ase A
Liquid
Cause of
Over P.
blocked
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
4 0 kg /hr
20673 kg /hr
90 C
5.963e-5 lbs
2 .4 1 9e-4 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.92 sp g r
0.6759
64 Bar G
0.971 58
User Defined
Absolute
0.1 9 C entipoise
671 0.9
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
4 0 kg /hr
0.751
90 C
2 .4 1 9e-4 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4 .3.2.9, DB: C :\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 7-PSV -060 Data Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 29 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 7-PSV -072 A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
Blocked Flow
Steam
NACE
N o
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
52 Bar G
Design T.
Operating
Temp.
Relief Temp.
86.1 54
Percent Over P.
52 Bar G
4 4 .8 Bar G
Operating to Set %
Atm Pressure
Relief
Pressure
Min.
4 2 7 C
4 00 C
4 2 7 C
10 %
58.21 3 Bar Abs
Design T.
Constant Back
P.
Variable Back P.
0.1 Bar G
Over Pressure
5.2 Bar G
Cold
0 C
5.1 Bar G
Diff. Test P.
52 .938 Bar G
S team S tate
Calculated Area
1 .7788 in
Req.
1 .7788 in
Flow Cap.
( Resolved
Napier
2 5000 kg /hr
Superheat
by M aximum )
0.83081
1 .6009 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
C onventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Steam): 761 56 lb/hr
Inlet
Size
1 .838 in
In.
Rating
2 .04 2 in
In.
Facing
Quantity
Yes
3.0 in
Outlet
Size
600
Out.
Rating
RF
Out.
Facing
4 .0 in
300
RF
NACE
No
Model Materials
Body
Disc
SA-2 1 6 G r. WC B
31 6 SS + Stellite (SP)
Bellows
Bonnet
Guide
Outlet
N /A
SA-2 1 6 G r. W C B
31 6
Flange
SS
Nozzle
31 6 SS + Stellite (SP)
Spring
C hrome Alloy
Custom
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
C ase A
Steam
Blocked
Flow
2 5000 kg /hr
2 8699 kg /hr
4 2 7 C
2 011-02 -2 3 16: 06
SDS246953 REV 05
1 1 9.21
89.4 1
1 .7788 in
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 30 of 1 59
Relief Pressure
Vapor Flow Factor
Superheat Factor
Napier Factor
Wsteam
K
Gas
K
CCF
P
relief
K
b
K
v
K
sh
K
n
25000 kg /hr
0.8577
0.83081
1
Relief Temperature
Discharge Coefficient
Trelief
K
d
4 2 7 C
0.953
1 .7788 in
Tag Notes
15-OCT: The customer submitted new data sheets with back p ressure changed to constant and
variable. The op en lever changes to a p acked lever due to the p resence of constant back
p ressure.
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 31 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 7-PSV -078A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
PC V FAILURE
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
2 5 Bar G
Design T.
Operating
Temp.
Relief Temp.
80 %
Percent Over P.
72 Bar G
2 0 Bar G
Operating to Set %
Atm Pressure
Relief
Min.
1 70 C
1 55 C
1 55 C
10 %
Pressure
Gravity
0.901 sp g r
Design T.
Constant Back
P.
Variable Back P.
0.3 Bar G
Over Pressure
2 .5 Bar G
Cold
-5 C
2 .2 Bar G
Diff. Test P.
24 .947 Bar G
Fluid Type
Water
Specific
Viscosity
Type
Absolute
1 60 kg /hr
Viscosity
0.1 75 C entipoise
Calculated Area
0.001 593 in
Reynolds #
2 91 4 5
0.001 593 in
( Resolved
by M aximum )
0.001 433 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
C onventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 71 US g pm
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
600
Out.
Rating
RF
Out.
Facing
Size
2 .0 in
300
RF
NACE
No
Model Materials
Body
Disc
Bellows
SA-2 1 6 G r. WC B
Stellite (SP)
N /A
Bonnet
Guide
SA-2 1 6 G r. W C B
Outlet
31 6
Flange
SS
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
Custom
Stellite (SP)
C hrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 32 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
C ase A
Liquid
PC V
FAILURE
1 60 kg /hr
1 5068 kg /hr
1 55 C
2.435e-4 lbs
0.001 593 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.901 sp g r
0.651 6
25 Bar G
0.98968
User Defined
Absolute
0.1 75 C entipoise
2 91 4 5
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
1 60 kg /hr
0.72 4
1 55 C
0.001 593 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 33 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 7-PSV -080A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
PC V FAILURE
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
1 0 Bar G
Design T.
Operating
Temp.
Relief Temp.
60 %
Percent Over P.
72 Bar G
6 Bar G
Operating to Set %
Atm Pressure
Relief
Min.
Design T.
Constant Back
P.
Variable Back P.
1 70 C
1 55 C
1 70 C
-5 C
0.3 Bar G
0.7 Bar G
Over Pressure
10 %
Pressure
Gravity
0.897 sp g r
Cold
1 Bar G
Diff. Test P.
9.797 Bar G
Desuperheated
W ater
Fluid Type
Specific
2 2 0 kg /hr
Calculated Area
0.0034 6 in
0.00346 in
Viscosity
Type
Absolute
Viscosity
0.1 6 C entipoise
Reynolds #
4 3831
( Resolved
by M axim um )
0.0031 1 4 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
C onventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 4 5 US g pm
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
600
Out.
Rating
RF
Out.
Facing
Size
NACE
2 .0 in
1 50
RF
No
Model Materials
Body
Disc
SA-2 1 6 G r. WC B
Stellite (SP)
Bellows
N /A
Bonnet
Guide
Custom
SA-2 1 6 G r. WC B
31 6
SS
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
Stellite (SP)
C hrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 34 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
C ase A
Liquid
PC V
FAILURE
22 0 kg /hr
9538.4 kg /hr
1 70 C
4 .625e-4 lbs
0.0034 6 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
0.897 sp g r
0.651 6
1 0 Bar G
0.992 77
User Defined
Absolute
0.1 6 C entipoise
4 3831
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
2 2 0 kg /hr
0.72 4
1 70 C
0.0034 6 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes. T
Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 35 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 7-PSV -081 A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
1 3 Bar G
Design T.
Operating
Temp.
Relief Temp.
69.2 31
Percent Over P.
1 3 Bar G
9 Bar G
Operating to Set %
Atm Pressure
Relief
Pressure
Min.
1 70 C
1 55 C
1 55 C
10 %
1 5.31 3 Bar Abs
Design T.
Constant Back
P.
Variable Back P.
0.3 Bar G
Over Pressure
1 .3 Bar G
Cold
-5 C
1 Bar G
Diff. Test P.
1 2 .827 Bar G
Fluid Type
Water
Specific
Gravity
Viscosity
0.9 sp g r
Type
Absolute
54 000 kg /hr
Viscosity
0.1 75 C entipoise
Calculated Area
0.7381 8 in
Reynolds #
4 0772 83
0.7381 8 in
( Resolved
by M axim um )
0.66436 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
C onventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 2 97 US g pm
Inlet
Size
0.785 in
In.
Rating
0.873 in
In.
Facing
Quantity
Yes
1 .5 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
3.0 in
1 50
RF
No
Model Materials
Body
Disc
SA-2 1 6 G r. WC B
Stellite (SP)
Bellows
N /A
Bonnet
Guide
Custom
SA-2 1 6 G r. WC B
31 6
SS
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
Stellite (SP)
C hrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 36 of 1 59
Sizing Scenarios
Scenario
Fluid
State
C ase A
Liq uid
Cause of
Over P.
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
54 000 kg /hr
C ontrol Valve Failure
63863 kg /hr
1 55 C
1 2.34 3 lbs
0.7381 8 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
60.087 m/hr
0.9 sp g r
0.651 6
1 3 Bar G
1
User Defined
Absolute
0.1 75 C entipoise
40772 83
Discharge Coefficient
Relief Temperature
54000 kg /hr
0.72 4
1 55 C
0.7381 8 in
Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Qliquid
K
d
Trelief
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 37 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 7-PSV -082 A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
C V Failure
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
6 Bar G
5.2 Bar G
6 Bar G
Operating to Set %
86.667
Atm Pressure
1 60 C
1 80 C
Percent Over P.
Relief
Pressure
Min.
1 95 C
10 %
Design T.
Constant Back
P.
Variable Back P.
0.1 Bar G
Over Pressure
0.6 Bar G
Cold
1 8.02 M ol Wt
Gas
0.62 2 02 sp g r
Compressibility
-5 C
0.5 Bar G
Diff. Test P.
5.959 Bar G
C ompressible State
Fluid
Steam
Molecular
Weight
64 500 kg /hr
Specific
Gravity
Calculated Area
28.1 1 7 in
Specific
Heat Ratio
28.1 1 7 in
( Resolved
1 .36
by M aximum )
Flow Const.
352
0.96
25.306 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
26TA1 2 -1 4 1 /SP
API
Area
Valve Design
C onventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Air): 502 4 4 SC FM
Inlet
Size
2 6.00 in
In.
Rating
2 8.94 in
In.
Facing
Quantity
Yes
8.0 in
Outlet
300
Out.
Rating
RF
Out.
Facing
Size
NACE
1 0.0 in
1 50
RF
No
Model Materials
Body
Disc
SA-2 1 6 G r. WC B
31 6 SS + Stellite (SP)
Bellows
N /A
Bonnet
Guide
Custom
SA-2 1 6 G r. WC B
31 6
SS
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
C hrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 38 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
C ase A
Vapor
C V
Failure
64500 kg /hr
66387 kg /hr
1 80 C
3060.6 lbs
1 1 9.51
89.634
28.1 1 7 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
64 500 kg /hr
1 80 C
0.96
352
0.8577
C ritical
1
7.61 33 Bar Abs
1 8.02 M ol Wt
1
-
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Steam
0.62 2 02 sp g r
1 .36
0.953
2 8.1 1 7 in
Tag Notes
The customer submitted new data sheets with back p ressure changed to constant and variable.
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 39 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 8-PSV -004 A
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Drawing #
Sizing Basis
ASME Code
Fluid State
C V Failure
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
4 .2 Bar G
Design T.
Operating
Temp.
Relief Temp.
78.571
Percent Over P.
6 Bar G
3.3 Bar G
Operating to Set %
Atm Pressure
Relief
Pressure
Min.
2 5 C
Design T.
Constant Back
P.
Variable Back P.
0.32 Bar G
10 %
Over Pressure
0.4 2 Bar G
90 C
2 5 C
Cold
2 8.02 M ol Wt
Gas
0.9672 1 sp g r
Compressibility
-5 C
0.1 Bar G
Diff. Test P.
4 .1 Bar G
C ompressible State
Fluid
N itrog en
Molecular
40 kg /hr
Specific
Gravity
Calculated Area
0.01 54 2 6 in
Specific
Heat Ratio
0.01 5426 in
Weight
( Resolved
1 .4 1
Flow Const.
357
0.01 3884 in
by M aximum )
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
C onventional
Cap Constrn
Packed Lever
Name Plate Capacity (Air): 1 93 SC FM
ASME
Area
Test Gag
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
2 .0 in
1 50
RF
NACE
No
Model Materials
Body
Disc
SA-351 G r. C F8M
31 6
Bellows
SS
N /A
Bonnet
Guide
Custom
SA-351 G r. C F8M
31 6
SS
A1 93-B8 C L
2 /A1 94 -8 (SP)
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
31 6
S S
C hrome Alloy N P
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 40 of 1 59
Sizing Scenarios
Noise
Required
Scenario
Fluid
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
State
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
C ase A
Vapor
C V
Failure
4 0 kg /hr
388.94 kg /hr
25 C
8.62 76 lbs
93.296
69.972
0.01 54 2 6 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
4 0 kg /hr
2 5 C
357
0.8577
C ritical
1
5.6333 Bar Abs
2 8.02 M ol Wt
1
-
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Nitrog en
0.9672 1 sp g r
1 .41
0.953
0.01 54 2 6 in
Tag Notes
15-OCT: The customer submitted new data sheets with back p ressure changed to constant and
variable. The lever changes from an op en lever to a p acked lever due to the constant back
p ressure.
Farris p rop oses a change in valve construction from op en bonnet and op en lever or combination
thereof for these valves. This is due to the addition of constant back p ressure as found on
the revised customer data sheets. When p rocessing these valves, Farris will "net set" the
valves to comp ensate for the constant back p ressure. The op en bonnet/lever design allows the
constant downstream p ressure in the system to escap e thru the op en bonnet and /or lever. This
means that , the constant back pressure may not exist, or may be lower due to fluid escap e.
In the field, the valve may not relieve at the desired set p ressure ( It will relieve early) .
Therefore, Farris would like to change the bonnet from op en to closed and the lever from op en
Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 41 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Daelim
Job Description
PQ -1 01 790
Prepared By
Checked By
Approved By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
2 2 8-PSV -006
Plant #
P / ID
Discharge To
Revision #
Valve Selected
Drawing #
Index #
Issue For
Service
Inlet Line #
Outlet Line #
Revised By
Sizing Basis
ASME Code
Fluid State
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
9 Bar G
4 Bar G
9 Bar G
Operating to Set %
4 4 .4 4 4
Atm Pressure
Percent
Relief
Design T.
Constant Back
P.
Variable Back P.
0 C
1 93 C
Over P.
Pressure
Min.
90 C
-20 C
0.1 Bar G
0.8 Bar G
Over
Pressure
1 .89 Bar G
Cold
Diff. Test P.
8.9 Bar G
1 8.44 M ol Wt
Gas
0.63652 sp g r
Compressibility
21
Compressible State
Fluid
300 kg /hr
Specific
Gravity
Calculated Area
0.083373 in
Specific
Heat Ratio
0.083373 in
( Resolved
1 .366
Flow Const.
0.952
by M aximum )
352 .6
0.075036 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Conventional
Cap Constrn
Screwed Cap
Name Plate Capacity (Air): 373 SCFM
ASME
Area
Test Gag
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
2 .0 in
1 50
RF
No
Model Materials
Body
Bonnet
Disc
31 6 SS + Stellite (SP)
Guide
Bellows
N /A
Custom
31 6
SS
M aterial to be
A32 0-L7/A1 94 -4 .
(SP)
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 42 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Liq uid
Vaporization
300 kg /hr
539.74 kg /hr
1 93 C
1 7.886 lbs
99.2 77
74 .4 58
0.083373 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
300 kg /hr
1 93 C
0.952
352 .6
0.8577
Critical
1
1 1 .903 Bar Abs
1 8.4 4 M ol Wt
1
-
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
0.63652 sp g r
1 .366
0.953
0.083373 in
Tag Notes
15-OCT: The customer submitted new data sheets with back p ressure changed to constant and
variable.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 8-PSV -006 Data Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 43 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 8-PSV -01 1
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
9 Bar G
4 Bar G
9 Bar G
Operating to Set %
4 4 .4 4 4
Atm Pressure
Relief
Pressure
Design T.
Constant Back
P.
Variable Back P.
0 C
1 93 C
Percent Over P.
Min.
90 C
21
-20 C
0.1 Bar G
0.8 Bar G
Over Pressure
Cold
1 8.44 M ol Wt
Gas
0.63652 sp g r
Compressibility
1 .89 Bar G
Diff. Test P.
8.9 Bar G
Compressible State
Fluid
200 kg /hr
Specific
Gravity
Calculated Area
0.055582 in
Specific
Heat Ratio
0.055582 in
( Resolved
1 .366
Flow Const.
0.952
by M aximum )
352 .6
0.050024 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Conventional
Cap Constrn
Screwed Cap
Name Plate Capacity (Air): 373 SCFM
ASME
Area
Test Gag
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
2 .0 in
1 50
RF
No
Model Materials
Body
Bonnet
Disc
31 6 SS + Stellite (SP)
Guide
Bellows
N /A
Custom
31 6
SS
M aterial to be
A32 0-L7/A1 94 -4 .
(SP)
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 44 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Liq uid
Vaporization
2 00 kg /hr
539.74 kg /hr
1 93 C
1 7.886 lbs
99.2 77
74 .4 58
0.055582 in
Relief Temperature
Compressibility
Flow
Rupture Disk Coefficient
Relief Pressure
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
2 00 kg /hr
1 93 C
0.952
352 .6
0.8577
Critical
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
G lycol Cooling
Fluid
0.63652 sp g r
1 .366
0.953
0.055582 in
SizeM aster 4 .3.2 .9, DB: C:\Documents and Setting s\rlmiller\Desktop\SM P24 6953_252 1 64 End of 2 2 8-PSV -01 1 Data Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 45 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 8-PSV -01 4
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
9 Bar G
4 Bar G
9 Bar G
Operating to Set %
4 4 .4 4 4
Atm Pressure
Relief
Pressure
Design T.
Constant Back
P.
Variable Back P.
0 C
1 93 C
Percent Over P.
Min.
90 C
21
-20 C
0.1 Bar G
0.8 Bar G
Over Pressure
Cold
1 8.44 M ol Wt
Gas
0.63652 sp g r
Compressibility
1 .89 Bar G
Diff. Test P.
8.9 Bar G
Compressible State
Fluid
22 0 kg /hr
Specific
Gravity
Calculated Area
0.061 1 4 in
Specific
Heat Ratio
0.061 1 4 in
( Resolved
1 .366
Flow Const.
0.952
by M axim um )
352 .6
0.055026 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Conventional
Cap Constrn
Screwed Cap
Name Plate Capacity (Air): 373 SCFM
ASME
Area
Test Gag
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
2 .0 in
1 50
RF
No
Model Materials
Body
Bonnet
Disc
31 6 SS + Stellite (SP)
Guide
Bellows
N /A
Custom
31 6
SS
M aterial to be
A32 0-L7/A1 94 -4 .
(SP)
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 46 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Liq uid
Vaporization
2 20 kg /hr
539.74 kg /hr
1 93 C
1 7.886 lbs
99.2 77
74 .458
0.061 1 4 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
2 2 0 kg /hr
1 93 C
0.952
352 .6
0.8577
Critical
1
1 1 .903 Bar Abs
1 8.4 4 M ol Wt
1
-
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
0.63652 sp g r
1 .366
0.953
0.061 1 4 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 8-PSV -01 4 Data Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 47 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 8-PSV -01 5
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
9 Bar G
4 Bar G
9 Bar G
Operating to Set %
4 4 .4 4 4
Atm Pressure
Relief
Pressure
Design T.
Constant Back
P.
Variable Back P.
0 C
1 93 C
Percent Over P.
Min.
90 C
21
-20 C
0.1 Bar G
0.8 Bar G
Over Pressure
Cold
1 8.44 M ol Wt
Gas
0.63652 sp g r
Compressibility
1 .89 Bar G
Diff. Test P.
8.9 Bar G
Compressible State
Fluid
22 0 kg /hr
Specific
Gravity
Calculated Area
0.061 1 4 in
Specific
Heat Ratio
0.061 1 4 in
( Resolved
1 .366
Flow Const.
0.952
by M axim um )
352 .6
0.055026 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Conventional
Cap Constrn
Screwed Cap
Name Plate Capacity (Air): 373 SCFM
ASME
Area
Test Gag
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
2 .0 in
1 50
RF
No
Model Materials
Body
Bonnet
Disc
31 6 SS + Stellite (SP)
Guide
Bellows
N /A
Custom
31 6
SS
M aterial to be
A32 0-L7/A1 94 -4 .
(SP)
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 48 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Liq uid
Vaporization
2 20 kg /hr
539.74 kg /hr
1 93 C
1 7.886 lbs
99.2 77
74 .458
0.061 1 4 in
Relief Temperature
Compressibility
Flow
Rupture Disk Coefficient
Relief Pressure
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
2 2 0 kg /hr
1 93 C
0.952
352 .6
0.8577
Critical
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
G lycol Cooling
fluid
0.63652 sp g r
1 .366
0.953
0.061 1 4 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 8-PSV -01 5 Data Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 49 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 8-PSV -02 2
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
9 Bar G
4 Bar G
9 Bar G
Operating to Set %
4 4 .4 4 4
Atm Pressure
Relief
Pressure
Design T.
Constant Back
P.
Variable Back P.
0 C
1 93 C
Percent Over P.
Min.
90 C
21
-20 C
0.1 Bar G
0.8 Bar G
Over Pressure
Cold
1 8.44 M ol Wt
Gas
0.63652 sp g r
Compressibility
1 .89 Bar G
Diff. Test P.
8.9 Bar G
Compressible State
Fluid
22 0 kg /hr
Specific
Gravity
Calculated Area
0.061 1 4 in
Specific
Heat Ratio
0.061 1 4 in
( Resolved
1 .366
Flow Const.
0.952
by M axim um )
352 .6
0.055026 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Conventional
Cap Constrn
Screwed Cap
Name Plate Capacity (Air): 373 SCFM
ASME
Area
Test Gag
Inlet
Size
0.1 1 0 in
In.
Rating
0.1 50 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
2 .0 in
1 50
RF
No
Model Materials
Body
Bonnet
Disc
31 6 SS + Stellite (SP)
Guide
Bellows
N /A
Custom
31 6
SS
M aterial to be
A32 0-L7/A1 94 -4 .
(SP)
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 50 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Liq uid
Vaporization
2 20 kg /hr
539.74 kg /hr
1 93 C
1 7.886 lbs
99.2 77
74 .458
0.061 1 4 in
Relief Temperature
Compressibility
Flow
Rupture Disk Coefficient
Relief Pressure
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
2 2 0 kg /hr
1 93 C
0.952
352 .6
0.8577
Critical
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
G lycol Cooling
fluid
0.63652 sp g r
1 .366
0.953
0.061 1 4 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 8-PSV -02 2 Data Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 51 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 8-PSV -033
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
9 Bar G
4 Bar G
9 Bar G
Operating to Set %
4 4 .4 4 4
Atm Pressure
Relief
Pressure
Design T.
Constant Back
P.
Variable Back P.
0 C
1 93 C
Percent Over P.
Min.
90 C
21
-20 C
0.1 Bar G
0.8 Bar G
Over Pressure
Cold
1 8.44 M ol Wt
Gas
0.63652 sp g r
Compressibility
1 .89 Bar G
Diff. Test P.
8.9 Bar G
Compressible State
Fluid
550 kg /hr
Specific
Gravity
Calculated Area
0.1 52 85 in
Specific
Heat Ratio
0.1 5285 in
( Resolved
1 .366
Flow Const.
0.952
by M axim um )
352 .6
0.1 3757 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Conventional
Cap Constrn
Screwed Cap
Name Plate Capacity (Air): 560 SCFM
ASME
Area
Test Gag
Inlet
Size
0.1 96 in
In.
Rating
0.2 2 5 in
In.
Facing
Quantity
Yes
1 .0 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
2 .0 in
1 50
RF
No
Model Materials
Body
Bonnet
Disc
31 6 SS + Stellite (SP)
Guide
Bellows
N /A
Custom
31 6
SS
M aterial to be
A32 0-L7/A1 94 -4 .
(SP)
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
31 6 SS + Stellite (SP)
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 52 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Liq uid
Vaporization
550 kg /hr
809.61 kg /hr
1 93 C
26.83 lbs
1 01 .04
75.779
0.1 5285 in
Relief Temperature
Compressibility
Flow
Rupture Disk Coefficient
Relief Pressure
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
550 kg /hr
1 93 C
0.952
352 .6
0.8577
Critical
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
G lycol Cooling
fluid
0.63652 sp g r
1 .366
0.953
0.1 52 85 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 8-PSV -033 Data Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 53 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 8-PSV -04 6
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
8.5 Bar G
Design T.
Operating
Temp.
Relief Temp.
80 %
Percent Over P.
9 Bar G
6.8 Bar G
Operating to Set %
Atm Pressure
Relief
Pressure
Min.
Design T.
Constant Back
P.
Variable Back P.
90 C
4 8.4 C
350 C
21
-20 C
0.1 Bar G
0.75 Bar G
Over Pressure
Cold
1 70.3 M ol Wt
Gas
5.8785 sp g r
Compressibility
1 .785 Bar G
Diff. Test P.
8.4 Bar G
Compressible State
Fluid
Isod od ecane
Molecular
Weight
81 00 kg /hr
Specific
Gravity
Calculated Area
0.772 09 in
Specific
Heat Ratio
0.77209 in
( Resolved
1 .1 5
Flow Const.
0.61 8
by M axim um )
332
0.69488 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
2 6HA1 2 -1 21 /SP
API
Area
Valve Design
Conventional
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 2 063 SCFM
Inlet
Size
0.785 in
In.
Rating
0.873 in
In.
Facing
Quantity
Yes
2 .0 in
Outlet
300
Out.
Rating
RF
Out.
Facing
Size
NACE
3.0 in
1 50
RF
No
Model Materials
Body
Disc
SA-2 1 6 G r. WCB
31 6
Bellows
SS
N /A
Bonnet
Guide
Custom
SA-2 1 6 G r. WCB
31 6
SS
A1 93-B8 CL
2 /A1 94 -8 (SP)
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
31 6
S S
Chrome Alloy
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 54 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Liq uid
Vaporization
81 00 kg /hr
91 58.6 kg /hr
350 C
89.549 lbs
1 02 .35
76.765
0.77209 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
81 00 kg /hr
350 C
0.61 8
332
0.8577
Critical
1
1 1 .2 98 Bar Abs
1 70.3 M ol Wt
1
-
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
Isod od ecane
5.8785 sp g r
1 .1 5
0.953
0.772 09 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 8-PSV -04 6 Data Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 55 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
2 2 8-PSV -04 8
Plant #
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
Vapor (M ass)
NACE
No
No Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
Max.
Design T.
Operating
Temp.
Relief Temp.
2 .5 Bar G
0.04 Bar G
2 .5 Bar G
Operating to Set %
1 .6
Atm Pressure
Relief
Pressure
Design T.
Constant Back
P.
Variable Back P.
4 8.4 C
1 77 C
Percent Over P.
Min.
90 C
21
-5 C
0.1 Bar G
0.1 5 Bar G
Over Pressure
Cold
1 70 M ol Wt
Gas
0.52 5 Bar G
Diff. Test P.
2 .4 Bar G
Compressible State
Fluid
Molecular
Weight
6500 kg /hr
Specific
Gravity
Calculated Area
1 .74 93 in
Specific
Heat Ratio
1 .7493 in
( Resolved
356
Compressibility
5.8681 sp g r
1 .4
by M aximum )
Flow Const.
1 .5744 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
API
Area
Valve Design
Conventional
ASME
Area
Cap Constrn
Screwed Cap
Test Gag
Name Plate Capacity (Air): 1 752 SCFM
Inlet
Size
1 .838 in
In.
Rating
2 .04 2 in
In.
Facing
Quantity
Yes
3.0 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
4 .0 in
1 50
RF
NACE
No
Model Materials
Body
Disc
SA-351 G r. CF8M
31 6
Bellows
SS
N /A
Bonnet
Guide
Custom
SA-351 G r. CF8M
31 6
SS
A1 93-B7/A1 94 -2 H
(SP)
2 011-02 -2 3 16: 06
SDS246953 REV 05
Nozzle
Spring
31 6
S S
Chrome Alloy N P
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 56 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Vapor
Cause of
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Over P.
Capacity
Atm (dBa)
Flare (dBa)
Area
Liq uid
Vaporization
6500 kg /hr
7587.5 kg /hr
1 77 C
83.836 lbs
99.833
74 .875
1 .7493 in
Relief Temperature
Compressibility
Molecular Weight
Wvapor
Trelief
K
Gas
Flow
K
CCF
P
relief
M
vapor
K
b
K
v
6500 kg /hr
1 77 C
356
0.8577
Critical
1
4 .0383 Bar Abs
1 70 M ol Wt
1
-
Specific Gravity
Discharge Coefficient
Ggas
k
K
d
5.8681 sp g r
1 .4
0.953
1 .74 93 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64 End of 2 2 8-PSV -04 8 Data Sheet
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 57 of 1 59
Date Prepared:
Customer
Requisition #
Job #
Checked By
Approved By
Daelim
Job Description
PQ -1 01 790
Prepared By
Job Status
Revision #
Sizing /Selecting
PSV Identification
Tag #
Tag Description
Tag Status
Drawing #
Issue For
31 1 -PSV-002
P / ID
Discharge To
Revision #
Outlet Line #
Revised By
Valve Selected
Plant #
Index #
Service
Inlet Line #
Sizing Basis
ASME Code
Fluid State
NACE
N o
N o Rupture Disk, 1
Process Parameters
MAWP
Operating
Pressure
Set Pressure
1 5 Bar G
Design T.
Operating
Temp.
Relief Temp.
66.667
Percent Over P.
1 5 Bar G
1 0 Bar G
Operating to Set %
Atm Pressure
Max.
Relief
Min.
0.1 Bar G
90 C
Design T.
Constant Back
P.
Variable Back P.
10 %
Over Pressure
1 .5 Bar G
90 C
30 C
Pressure
Gravity
1 .004 sp g r
Cold
- C
1 .4 Bar G
Diff. Test P.
1 4 .9 Bar G
Non-Compressible State
Fluid Type
WATER
2 0 kg /hr
Viscosity
0.79 Centipoise
Calculated Area
2 .578e-4 in
Reynolds #
807.01
Specific
2.578e-4 in
( Resolved
by M aximum )
Viscosity
Type
Absolute
2.320e-4 in
Model Selection
Manufacturer
Model Number
Farris
API
Letter
Inlet
API
Area
In.
Rating
In.
Facing
Valve Design
Conventional
ASME
Area
Cap Constrn
Packed Lever
Test Gag
Name Plate Capacity (Water): 2 6 US g pm
0.068 in
Yes
Size
Quantity
0.75 in
Outlet
1 50
Out.
Rating
RF
Out.
Facing
Size
NACE
1 .00 in
1 50
RF
No
Model Materials
Body
31 6
SS
Bonnet
31 6
SS
Nozzle
31 6
SS
Disc
31 6
SS
Guide
31 6
SS
Spring
31 6
SS
Custom
A1 93-B8 CL. 2 /
A1 94 -8 (SP)
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 1
VP-4400-427-001 -ALL-002_05
Page 1 58 of 1 59
Sizing Scenarios
Scenario
Fluid
State
Case A
Liq uid
Cause of
Over P.
Relief Load
Max Rel Cap Relief T. React. Force
Noise
Noise
Required
Capacity
Atm (dBa)
Flare (dBa)
Area
BLO CKED
2 0 kg /hr
5275.1 kg /hr
90 C
1 .366e-5 lbs
2 .578e-4 in
Specific Gravity
Discharge Coeff. (0.9 x Kd )
P set
+ P over - P back
Viscosity Type
Viscosity
Reynolds #
V
liquid
Gliquid
K
liquid
K
CCF
K
u
K
w
1 .004 sp g r
0.6759
1 5 Bar G
0.901 1
User Defined
Absolute
0.79 Centipoise
807.01
Discharge Coefficient
Relief Temperature
Qliquid
K
d
Trelief
2 0 kg /hr
0.751
90 C
2 .578e-4 in
Tag Notes
15-OCT: The customer submitted new data sheets with cap acity and back p ressure changes.
SizeM aster 4 .3.2.9, DB: C:\Documents and Setting s\rlm iller\Desktop\SM P2 4 6953_2 52 1 64
2 011-02 -2 3 16: 06
SDS246953 REV 05
Page 2
VP-4400-427-001 -ALL-002_05
Page 1 59 of 1 59