Professional Documents
Culture Documents
Notas - Protecciones - Fallas
Notas - Protecciones - Fallas
August 2014
Contents
1 FAULT ANALYSIS AND PROTECTION SYSTEMS
1.1
1.2
. .
1.3
Modeling of Components . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
1.3.1
Symmetrical components . . . . . . . . . . . . . . . . . . . . . . . .
12
1.3.2
Sequence impedances . . . . . . . . . . . . . . . . . . . . . . . . . .
19
1.3.2.1
19
1.3.2.2
21
1.3.2.3
23
1.3.2.4
. . . . . . . . . . . .
24
1.3.2.5
29
1.4
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
Bibliography
32
36
Chapter 1
FAULT ANALYSIS AND
PROTECTION SYSTEMS
1.1
Short circuit: occurs when two or more points, which are at a dierent voltage under
normal operation conditions, accidentally come into contact with each other through a
small or zero impedance.
Generally happens when the insulation fails owing to:
Short-circuit studies are particularly important during selection and design of the system
conductors, system structures, and the relaying and protection system.
The damaging
eects of the faults are numerous and are mainly related to the high currents which can
appear in the system. Usually, these current values can be several times the value of the
normal operational current and can occasionally produce overvoltage phenomena.
The main eects of the faults are:
Voltage variations, which are voltage drops in the failed phases and eventual voltage
increases in the others.
the three phases are short circuited at the same point and time, and therefore
the resulting circuit is also balanced. For this reason, the study can be carried out using a single-phase equivalent circuit.
it is necessary to use
Figure 1.1: Circuits before the fault and during the fault: (a) initial circuit and (b) fault
circuit.
1.2
Usual techniques for modeling and studying electric networks can be classied into three
dierent operational time frames:
1. Steady state.
2. Electro-mechanic transient.
3. Electromagnetic transient.
Fault analysis is an electromagnetic process, where the network under steady-state operation conditions suers an abrupt topology modication.
modeled by resorting to the dierential equations characterizing its components to accurately analyze any fault. This detailed dierential equation modeling of the fault process
can be studied for certain cases, it is not practical while dealing with networks of hundreds
of nodes and branches. For this reason, common practice for short-circuit calculation uses
a quasi steady-state model of the electric network as an adequate approximation. To establish the equations for the transient behavior of a network in a fault situation, a simple
case of an RL branch in series with a voltage-source feeding a load will be studied, as
shown in Figure 1.1. A more realistic analysis should consider the transient behavior of
real voltage sources, where the magnetic inertia of rotating machines becomes crucial.
The following dierential equation represents the behavior of the previous circuit during
a fault:
e (t) = Ri + L
where:
R = Rg + RL
and
di
dt
(1.1)
L = Lg + LL .
(1.2)
where ist
from
(t) is the steady-state current of the faulted circuit, and K is a constant obtained
the currents at the initial instant, K = i (0) ist (0). If the voltage source has the
following expression:
e (t) =
the current
i (t)
2Esin (t + )
R
E
Icc = q
R2 + (L)2
L
X
=
R
R
tg () =
i (0) =
2I0 sin ( 0 )
E
I0 = q
(R + Rc )2 + (L + Xc )2
tg (0 ) =
L + Xc
R + Rc
Rc + jXc =
1
=Z
Y
(1.3)
t>
5L
s (beginning of the steady state).
R
This unidirectional or asymmetrical component corresponds to the circuit's natural response (in mathematical terminology, it is the solution of the homogeneous
equation).
2. The second term, the sinusoidal component (also called the symmetric or periodic
component) represents the steady state or permanent response of the circuit (in
mathematical terminology, the particular solution of the dierential equation).
Owing to the comparatively small value of the series elements
the corresponding values of the load to which systems are typically connected, the rated
current
I0
i (t)
R
i (t) = 2Icc sin ( ) e L t + 2Icc sin (t + )
(1.4)
2 2Icc .
i (0)
R
2Icc sin () 1 + e L t
(1.5)
is neglected:
imax (t) =
R
2Icc sin () 1 + e X t
(1.6)
Thus, a way to calculate the maximum transient short-circuit current has been established as a function of the steady-state short-circuit current
imax (t)
is divided by
2,
Icc .
For a more general electric network, the current Equation 1.6 becomes:
R
Xeq t
imax (t) = 2Icc sin (eq ) 1 + e eq
where
Req , Xeq ,
and
eq
These values are calculated at the faulted node and are obtained using the nodal impedance
matrix (Thevenin impedance at the faulted node).
the calculation of the equivalent impedance not taking into account shunt elements (such
as loads, line capacitances, and regulating transformers).
imax (t),
t = , t = 10ms
(1/2 cycle). This maximum current value is called the peak current.
The largest possible value for this peak current for the circuit shown in Figure 1.1b is as
follows:
Ipeak
R
X
= 2Icc sin () 1 + e
In the same way, the minimum short-circuit current value occurs when
t = ,
such that:
Imin =
(1.7)
= 0
and
2Icc
The IEC 909 standard recommends the following three methods to calculate the peak
current:
Method A is the least exact and calculates the peak current as:
Ipeak
3R
2Icc 1.02 + 0.98e X
where R/X is the minimum existing value in all the network branches.
In Method B the short-circuit peak current is calculated dierently for LV, MV, and
HV as follows:
3R
Ipeak 1.15 2Icc 1.02 + 0.98e X
where
and
Ipeak 2 2Icc
are the real and reactive parts of the nodal impedance at the
faulted point.
Ipeak
3R
X
20Rc/50Xc ,
Rc
and
Xc
reactive parts of the nodal impedance at the short-circuit point respectively, both
dened using a network steady-state frequency of 20 Hz, when the rated network
frequency is 50 Hz (typical in Europe). In the case of a rated network frequency of
60 Hz, the calculation frequency should be 24 Hz.
Assignment:
Assign values for the circuit components and obtain all quantities of interest
an order to the circuit breakers to carry out the fault clearing, and in this way interrupt
the current owing to the fault as shown in Figure 1.2.
The main objectives of system protection are [1]:
Minimize the duration of a fault reducing its thermal and mechanical eects, and
In general, the maximum fault current values are useful to determine the required interrupting rating of fuses and circuit breakers. The minimum fault values are useful to
determine and coordinate the operation of the various switching devices (relay operation).
The switching device behavior is evaluated under the worst conditions (maximum
current situations). Hence, if in the circuit of Figure 1.1a there is a circuit breaker between
the generation and the short circuit (Figure 1.1b), it should be designed and calculated to
withstand the following conditions:
When the breaker is closed (nonactive), it has to permanently withstand the steadystate rated current
In
(sinusoidal periodic).
When the breaker is closed (nonactive), it has to withstand the following current
from the onset of the fault (t
= 0)
imax =
until it clears at
t = tc .
R
2Icc sin () 1 + e L t
When the breaker is closed, it should be in a position to break the maximum current in the worst conditions to clear the fault. For the clearing (or breaking) time
10
(tc )normally between 0.06 and 0.08 s (3 and 4 cycles)the maximum current will
be:
Ic =
R
2Icc sin () 1 + e L tc
Ia =
Ia
dc
current, a
is dened as:
R
2Icc e L tc
rms
Sb =
total
p
2
Ia2 + Icc
3Un I ,
where
Un
is the
rms
is dened as follows:
I=
dc
Icc
is the
SCC =
3Un Icc ,
where
Un
is the
rms
rated
As mentioned before, the order to open the breaking element is delivered by the socalled protection relay after it detects the presence of the short circuit, and the worst
detection condition is when the short-circuit current has the value
Imin =
2Icc .
(t)],
Icc .
current is calculated based on the assumption of all generators in service and solid
(zero impedance) fault.
short-circuit current (Imin ). The minimum fault current is calculated based on the
minimum likely number of generators and non-solid faults.
11
1.3
Modeling of Components
This section describes the models (or equivalent circuits) of the following electrical system
components suitable for short-circuit analysis:
Transmission lines
Three-phase transformers
Generators
Loads
The models are based on symmetrical component theory. The application of symmetrical
component theory to the dierent electric network elements (lines, transformers, generators, and loads) produces the so-called symmetrical component models, also known as
sequence network. These sequence networks are useful for the analysis of power systems
where a portion can be isolated for study (the fault location), with the rest of the system
remaining balanced [2, 3].
For this purpose, a revisit of the symmetrical component theory is needed to properly
understand the component models used in the short-circuit studies.
1.3.1
Symmetrical components
In this section, the symmetrical components method is discussed. When applied to unbalanced faults studies allows the treatment of the problem on a simple per phase basis.
Furthermore, two functions developed in [4] and shown in Appendix A are used for the
symmetrical components transformations.
These are
abc2sc,
sc2abc
transformation.
In three-phase system the phase sequence is dened as the order in which they pass
through a positive maximum.
12
(1.8)
that:
(1.9)
a3 = 1360 = 1 + j0
It is easy to prove that:
1 + a + a2 = 0
The order of the phasors is
order is
(1.10)
acb as in Figure 1.3b, it is designated the negative phase sequence. The negative
13
(1.11)
1, 2,
and
0, 1, 2.
(1.12)
0, +, - is used instead of
1918. Based on his theory, three-phase unbalanced phasors of a three-phase system can
be resolved into three balanced systems of phasors as follows:
1. Positive-sequence components consisting of a set of balanced three-phase components
with a phase sequence
abc.
2. Negative-sequence components consisting of a set of balanced three-phase components with a phase sequence
acb.
Ia , Ib ,
and
Ic
The
(1.13)
(1.14)
0
Ia
1 1 1
Ia
1
2
Ib = 1 a a Ia
Ia2
Ic
1 a a2
(1.15)
I abc = AIa012
(1.16)
or in matrix form:
In matrix notation:
where
15
Iabc
Ia012 ,
and is:
1 1 1
A = 1 a2 a
1 a a2
(1.17)
The inverse of
Substituting for
is given by:
A1
Ia012 = A1 I abc
(1.18)
1
A1 = A
3
(1.19)
Ia0
1 1 1
Ia
1 1
Ia = 1 a a2 Ib
3
1 a2 a
Ic
Ia2
(1.20)
Ia0 = 13 (Ia + Ib + Ic )
Ia1 = 31 (Ia + aIb + a2 Ic )
Ia2 = 31 (Ia + a2 Ib + aIc )
(1.21)
It is important to mention that from Equation 1.21 the zero-sequence component of current
is equal to one-third of the sum of the phase currents. Therefore, when the phase currents
sum to zero, e.g., in a three-phase system with ungrounded neutral, the zero-sequence
current cannot exist. If the neutral of the power system is grounded, zero-sequence current
ows between the neutral and the ground.
Similar expressions exist for voltages. Thus the unbalanced phase voltages in terms of
the symmetrical components voltages are:
16
(1.22)
V abc = AVa012
(1.23)
in matrix notation:
Va012 = A1 V abc
(1.24)
The apparent power may also be expressed in terms of the symmetrical components. The
three-phase complex power is:
(1.25)
T
012
S(3) = AV 012
AI
a
a
T
T
012
A
A
I
= V 012
a
a
Since
AT = A,
AT A = 3,
S(3) = 3 V
012T
012
Assignment:
Proof that
(1.26)
(1.27)
AT A = 3.
Equation 1.27 shows that the total unbalanced power can be obtained from the sum of the
Assignments:
1. Obtain the remaining symmetrical components as described before.
17
2. Obtain the symmetrical components of the following set of unbalanced currents using
Matlab
Ia = 1.625
Ib = 1180
Ic = 0.9132
Plot the
resulting currents.
Va0 = 0.690
Va1 = 130
Va2 = 0.8 30
Obtain the original unbalanced phasors using Matlab.
4. Obtain the Symmetrical components of the set of unbalanced voltages:
Va = 300 120
Vb = 20090
Vc = 100 30
5. The symmetrical components of a set of unbalanced three-phase currents are:
Ia0 = 3 30
Ia1 = 590
Ia2 = 430
Obtain the original unbalanced phasors.
6. Based on the denition of
(a)
(1+a)
(1+a2 )
= 1120
(b)
(1a)2
(1+a)2
= 3 180
(c)
(a a2 ) (a2 a) = 30
(d)
1
Van
=
1 V 1 90
3 bc
(e)
2
Van
=
1 V 2
3 bc
90
18
1.3.2
Sequence impedances
Z 1.
Z 2.
When
zero-sequence currents ow, the impedance is called the zero-sequence impedance, shown
by
Z 0.
1.3.2.1
A three-phase balanced load with self and mutual elements is shown in Figure 1.5. The
load neutral is grounded through an impedance
Zn .
Va = Zs Ia + Zm Ib + Zm Ic + Zn In
Vb = Zm Ia + Zs Ib + Zm Ic + Zn In
Vc = Zm Ia + Zm Ib + Zs Ic + Zn In
(1.28)
In = Ia + Ib + Ic
(1.29)
Substituting for In from Equation 1.29 into Equation 1.28 and rewriting this equation in
19
Va
Zs + Zn Zm + Zn Zm + Zn
Ia
Vb = Zm + Zn Zs + Zn Zm + Zn Ib
Vc
Zm + Zn Zm + Zn Zs + Zn
Ic
(1.30)
or in compact form:
(1.31)
where:
Z abc
writing
V abc
and
I abc
Zs + Zn Zm + Zn Zm + Zn
= Zm + Zn Zs + Zn Zm + Zn
Zm + Zn Zm + Zn Zs + Zn
(1.32)
= Z abc AI 012
AV 012
a
a
Multiplying Equation 1.33 by
(1.33)
A1 :
V 012
= A1 Z abc AI012
a
a
012 012
= Z Ia
(1.34)
Z 012 = A1 Z abc A
(1.35)
1 1 1
Zs + Zn Zm + Zn Zm + Zn
1 1 1
1
= 1 a a2 Zm + Zn Zs + Zn Zm + Zn 1 a2 a
3
1 a2 a
Zm + Zn Zm + Zn Zs + Zn
1 a a2
(1.36)
where:
Z 012
20
Z 012
Zs + 3Zn + 2Zm
0
0
=
0
Zs Zm
0
0
0
Zs Zm
Zm = 0,
(1.37)
Z 012
Zs + 3Zn 0 0
=
0
Zs 0
0
0 Zs
(1.38)
The impedance matrix has nonzero elements appearing only on the principal diagonal,
and it is a diagonal matrix.
independent. That is, currents of each phase sequence will produce voltage drops of the
same phase sequence only. This is a very important property, as it permits the analysis of
each sequence network on a per phase basis.
1.3.2.2
For static devices such as transmission lines, the phase sequence has no eect on the
impedance, because the voltages and currents encounter the same geometry of the line,
irrespective of the sequence. Thus, positive- and negative-sequence impedances are equal,
i.e.,
Z 1 = Z 2.
Thus,
Z 0,
Z1
and
Z 2.
Z0
with equilaterally spaced conductors as shown in Figure 1.6. The phase conductors carry
zero-sequence (single-phase) currents with return paths through a grounded neutral. The
ground surface is approximated to an equivalent ctitious conductor located at the average
distance
Dn
21
in opposite direction:
and since
(1.39)
In = 3Ia0
(1.40)
results in:
Utilizing the relation for the ux linkages of a conductor in a group, the total ux linkage
of phase a conductor is:
a0 = 2 10
Assignment:
Ia0
1
1
1
1
ln 0 + Ib0 ln + Ic0 ln + In ln
r
D
D
Dn
(1.41)
Substituting for
Ib0 , Ic0 ,
and
In
in terms of
Ia0 :
a0 = 2 107 Ia0 ln r10 + ln D1 + ln D1 3 ln D1n
3
L0 = a0/Ia0 ,
22
(1.42)
W b/m
mH
(1.43)
mH/Km
X 0 = X 1 + 3Xn
where:
Xn = 2f
1.3.2.3
Dn
0.2 ln
D
(1.44)
m/Km
(1.45)
circuit analysis are balanced circuits dened for the fault periods of interest (subtransient,
transient, and eventually, steady state).
It has been studied in previous courses that the generator positive-sequence reactance
varies depending on the phase order of the sequence current relative to the direction of
rotation of the rotor. As consequence, one of the reactances
Xd00 , Xd0 ,
and
Xd
can be used
for the balanced three-phase fault studies. When negative-sequence currents are impressed
in the stator, the net ux in the air gap rotates at opposite direction to that of the rotor.
That is, the net ux rotates at twice synchronous speed relative to the rotor. Since the
eld voltage is associated with the positive-sequence variables, the eld winding has no
inuence. Consequently, only the damper winding produces an eect in the quadrature
axis. Hence, there is no distinction between the transient and subtransient reactances in
the quadrature axis as there is in the direct axis. The negative-sequence reactance is close
to the positive-sequence subtransient reactance, i.e.:
X 2 ' Xd
23
(1.46)
The machine oers a very small reactance due to the leakage ux. Therefore, the zerosequence reactance is approximated to the leakage reactance, i.e.:
X0 = Xl
1.3.2.4
(1.47)
In power transformers, the core losses and the magnetization current are on the order of one
percent of the rated value; therefore, the magnetizing branch is neglected. The transformer
is modeled with the equivalent series leakage impedance. Since the transformer is a static
device, the leakage impedance will not change if the phase sequence is changed. Therefore,
the positive- and negative-sequence impedances are the same.
permits zero-sequence current ow at all, the phase impedance to zero-sequence is equal
to the leakage impedance, then:
Z0 = Z1 = Z2 = Zl
It is necessary to recall that in a
or a
(1.48)
transformer, the positive-sequence
line voltage on HV side leads the corresponding line voltage on the LV side by
negative-sequence voltage the corresponding phase shift is
the zero-sequence impedance depends on the winding connections and also upon whether
or not the neutrals are grounded.
Assignment:
Proof that the positive-sequence line voltage on HV side leads the corre-
30.
Figure 1.7 shows some of the more common transformer congurations and their zerosequence equivalent circuits which can be explained as follows:
1.
Y Y
connections with both neutrals grounded. As the zero sequence current equals
the sum of phase currents and since both neutrals are grounded, there is a path for
the zero sequence current to ow in the primary and secondary, and the transformer
exhibits the equivalent leakage impedance per phase as shown in Figure 1.7a.
24
25
2.
Y Y
grounded, but since the secondary neutral is isolated, the secondary phase current
must sum up to zero. This means that the zero-sequence current in the secondary
is zero. Consequently, the zero sequence current in the primary is zero, reecting
innite impedance or an open circuit as shown in Figure 1.7b.
3.
with grounded neutral. In this conguration the primary currents can ow
is isolated, zero sequence current cannot ow and the equivalent circuit reects an
innite impedance or an open as shown in Figure 1.7d.
5.
Notice that the neutral impedance plays an important part in the equivalent circuit. When
the neutral is grounded through an impedance
circuit the neutral impedance appears as
Example:
anced
3Zn
Zn ,
because
in the path of
In = 3I0 ,
I0 .
in the equivalent
The three
phase load consists of three mutually-coupled reactances. Each phase has a series
reactance of
Zs = j12,
Zm = j4.
De-
termine the line currents by mesh analysis without using symmetrical components,
and determine the line currents using symmetrical components.
To determine the line currents by mesh analysis it is necessary to apply the
the two independent mesh equations as follows:
26
KVL to
Figure 1.8:
connected load.
Zs Ia + Zm Ib Zs Ib Zm Ia = Va Vb = |VL | 6
Zs Ib + Zm Ic Zs Ic Zm Ib = Vb Vc = |VL | 2
From
KCL:
Ia + Ib + Ic = 0
Zs Zm (Zs Zm )
0
Ia
|VL | 6
0
Zs Zm
(Zs Zm ) Ib = |VL | 2
0
1
1
1
Ic
In compact form:
I abc = Z 1
mesh V mesh
and the result is:
Ia
12.5 90
Ib = 12.5150
12.530
Ic
27
V 012
= Va
0
Z 012
Zs + 2Zm
0
0
=
0
Zs Zm
0
0
0
Zs Zm
1 012
V
I 012 = Z 012
resulting in:
Ia
12.5 90
Ib = 12.5150
Ic
12.530
Assignment:
ages:
10010
= 300 50
40140
V abc
is applied to the circuit in Figure 1.5. The load series impedance per phase is
Zs =
neutrals are solidly grounded. Determine (a) The load sequence impedance matrix
Z 012 .
of current.
28
1.3.2.5
Zn .
The synchronous machine generates balanced three-phase internal voltages and is represented as a positive-sequence set of phasors as:
E abc
= a2 Ea
a
(1.49)
The machine is supplying a three-phase balanced load. Applying Kirchho 's voltage law
to each phase:
Va = Ea Zs Ia Zn In
Vb = Eb Zs Ib Zn In
Vc = Ec Zs Ic Zn In
29
(1.50)
Substituting for
In = Ia + Ib + Ic ,
Va
Ea
Zs + Zn
Zn
Zn
Ia
Zn
Zs + Zn
Zn
Vb = Eb
Ib
Vc
Ec
Zn
Zn
Zs + Zn
Ic
(1.51)
or in compact form:
V abc
I abc
(1.52)
is the phase current vector.
Transforming the terminal voltages and current phasors into their symmetrical components
results in:
abc
AI 012
= AE 012
AV 012
a
a Z
a
Multiplying the above equation by
(1.53)
A1 :
1 abc
V 012
= E 012
AI 012
a
a A Z
a
012 012
= E 012
Z
I
a
a
(1.54)
1 1 1
Zs + Zn
Zn
Zn
1 1 1
1
= 1 a a2
Zn
Zs + Zn
Zn
1 a2 a
3
1 a2 a
Zn
Zn
Zs + Zn
1 a a2
(1.55)
where:
Z 012
Z 012
Zs + 3Zn 0 0
Z
0 0
=
0
Zs 0 = 0 Z 1 0
0
0 Zs
0 0 Z2
30
(1.56)
Figure 1.10: Sequence networks: (a) positive-sequence; (b) negative-sequence; (c) zerosequence.
emf
E 012
a
Substituting for
Ea012
and
Z 012
= Ea
0
(1.57)
in Equation 1.54:
0
0
Z
0 0
Ia
0
Va0
1
1
1
0 Ia
Va = Ea 0 Z
Ia2
0
0 0 Z2
Va2
(1.58)
The above equation can be represented by the three equivalent sequence networks shown
in Figure 1.10. The following important observations can be made:
The positive-sequence network is the same as the one-line diagram used in studying
balanced three-phase currents and voltages.
Only the positive-sequence network has a voltage source. Therefore, the positivesequence current causes only positive-sequence voltage drops.
31
The neutral of the system is the reference for positive-and negative-sequence networks, but ground is the reference for the zero-sequence networks. Therefore, the
zero-sequence current can ow only if the circuit from the system neutrals to ground
is complete.
The three-sequence systems can be solved separately on a per phase basis. The phase
3Zn .
1.4
This type of fault is dened as the simultaneous short circuit across all three phases. It occurs infrequently, but it is the most severe type of fault encountered. Because the network
is balanced, it is solved on a per-phase basis. The other two phases carry identical currents
except for the phase shift. A fault represents a structural network change equivalent with
that caused by the addition of an impedance at the place of fault. If the fault impedance
is zero, the fault is referred to as the
bolted fault
or the
solid fault.
Example:
emf
impedances are expressed in p.u. on a common 100 MVA base, and for simplicity,
resistances are neglected. The following assumptions are made.
All generators are running at their rated voltage and rated frequency with their
in phase.
32
emfs
Determine the fault current, the bus voltages, and the line currents during the fault when
a balanced three-phase fault with a fault impedance
Zf = 0.16
Zf
1.11(b). Thevenin's theorem states that the changes in the network voltage caused by the
added branch (the fault impedance) shown in Figure 1.11(b) is equivalent to those caused
by the added voltage
I3 (F ) =
V3 (0)
Z33 + Zf
33
Appendix A
In the following section the routines
abc2sc
and
sc2abc
34
35
36
Bibliography
[1] T. Gonen,
McGraw-Hill, 1986.
[2] P. Anderson,
Ames (Iowa-USA),:
Iowa State
[4] H. Saadat,
37