You are on page 1of 17

Standard 430

2008 STANDARD FOR

Central Station
Air-Handling Units

ISHRAE
( INDIAN SOCIETY OF HEATING,
REFRIGERATING & AIR
CONDITIONING ENGINEERS

4100 N. FAIRFAX DR., STE. 200

ARLINGTON, VIRGINIA 22203 USA

502, 5TH FLOOR, DDA COMMERCIAL COMPLEX, LAXMI NAGAR, DELHI 110 092

ISHRAE/ANSI/ARI STANDARD 430-2008

IMPORTANT
SAFETY RECOMMENDATIONS
It is strongly recommended that the product be designed, constructed,
assembled and installed in accordance with nationally recognized safety
requirements appropriate for products covered by this standard.
ARI-ISHRAE as an independent national body uses its best efforts to develop
standards employing state-of-the-art and accepted industry practices.
However, ARI-ISHRAE does not certify or guarantee safety of any products,
components or systems designed, tested, rated, installed or operated in
accordance with these standards or that any tests conducted under its
standards will be non-hazardous or free from risk.

ARI-ISHRAE CERTIFICATION PROGRAM PROVISIONS

Scope of the Certification Program


The Certification Program includes all sizes of central station air-handling
units as defined in Section 2.

Certified Ratings
The following Certification Program ratings are verified by test:
1. Fan Speed, rev/s [rpm]
2. Brake Horsepower, W [bhp]

Note:
This standard supersedes ARI Standard 430 99.

ISHRAE/ANSI/ARI STANDARD 430-2008

TABLE OF CONTENTS
SECTION

PAGE

Section 1.

Purpose................................................................................................. 1

Section 2.

Scope .................................................................................................... 1

Section 3.

Definitions ............................................................................................. 1

Section 4.

Classifications ....................................................................................... 3

Section 5.

Test Requirements ............................................................................... 3

Section 6.

Rating Requirements............................................................................. 7

Section 7.

Minimum Data Requirements for Published Ratings ............................. 7

Section 8.

Marking and Nameplate Data ............................................................. 10

Section 9.

Voluntary Conformance...................................................................... 10

FIGURES

Figure 1

Blow Through Central Station Air-Handling Unit ............................... 2

Figure 2

Draw Through Central Station Air-Handling Unit ............................... 2

Figure 3

Multiple Fan Outlet Test Configuration .................................................. 4

Figure 4

Dimensions for Inlet Vane Proportionality ............................................. 4

Figure 5

Draw Through Unit with Air Flow Direction change ............................ 6

Figure 6

Fan & Unit Characteristics Fan Rated and Unit Tested...................... 8

Figure 7

Fan & Unit Characteristics Fan Rated and Unit Calculated................ 9

ISHRAE/ANSI/ARI STANDARD 430-2008

APPENDICES

Appendix A.

References - Normative ...................................................................... 11

Appendix B.

References - Informative ..................................................................... 11

Appendix C.

Criteria for Proportionality - Informative............................................... 12

FIGURES FOR APPENDICES


Figure C1.

Dimensions Used for Proportionality Equations .................................. 13

ISHRAE/ANSI/ARI STANDARD 430-2008

CENTRAL STATION AIR-HANDLING UNITS


Section 1. Purpose
1.1

3.2

Purpose. The purpose of this standard is to


establish for central station air-handling units:
definitions; classifications; requirements for
testing and rating; minimum data requirements
for published ratings; marking and nameplate
data; and conformance conditions.

1.1.1 Intent.
This standard is intended for the
guidance
of
the
industry,
including
manufacturers,
engineers,
installers,
contractors, and users.
1.1.2 Review and Amendment. This standard is
subject to review and amendment as technology
advances.

Section 2. Scope
2.1

Scope. This standard applies to central station


air-handling units, as defined in Section 3.

2.2

Exclusions.

2.2.1 This standard does not apply to forcedcirculation,


free-delivery
air-coolers
for
refrigeration, which are covered in ARI-ISHRAE
Standard 420.

3.2.1 Blow-Through Central Station Air-Handling Unit


(see Figure 1). A unit containing a fan that
does not have a ducted fan outlet.
3.2.2 Draw-Through Central Station Air-Handling Unit
(see Figure 2). A unit that has a ducted fan
outlet.
3.2.3 Fan. An impeller and any other items, such as
housings and inlet vanes that are an integral
part of the impeller and/or housing that affect
the basic performance characteristics of the fan.
3.2.4 Unit Appurtenances. Equipment added for
purposes of control, isolation, safety, static
pressure regain, wear, etc. Such appurtenances
include coils, filters, dampers, air-mixers, sprays,
eliminators, etc.
3.3

2.2.2 This standard does not apply to unit heaters


intended for free delivery of heated air or to
room fan-coil air-conditioners as defined in
ARI-ISHRAE Standard 420.
2.2.3 This standard does not apply to units having
direct expansion coils which are incorporated by
the manufacturer in a matched split system airconditioner or as otherwise defined in the
product scope definition of the ARI-ISHRAE
Unitary Small Equipment and Unitary Large
Equipment Sections and covered in ARIISHRAE Standard 210/240 or in ARI-ISHRAE
Standard 340/360.
2.2.4 This standard does not apply to unit ventilators
as defined in ARI-ISHRAE Standard 840.
2.2.5 This standard does not apply to ratings for
plenum (plug) and axial fans.
Section 3 Definitions
3.1

Definitions. All terms in this document will follow


the standard industry definitions in the current
edition of ASHRAE Terminology of Heating,
Ventilation, Air Conditioning and Refrigeration
unless otherwise defined in this section.

Central Station Air-Handling Unit. A factorymade encased assembly consisting of a fan or


fans and other necessary equipment to perform
one or more of the functions of circulating,
cleaning,
heating,
cooling,
humidifying,
dehumidifying and mixing of air; and shall not
contain a source of cooling or heating other
than gas or electric heat. This device is capable
of use with duct work having a total static
resistance of at least 0.12 kPa [0.5 in. H2O].

Published Rating. A statement of the assigned


values of those performance characteristics,
under stated rating conditions, by which a unit
may be chosen to fit its application. These
values apply to all units of like nominal size and
type (identification) produced by the same
manufacturer.
As used herein, the term
"published rating" includes the rating of all
performance characteristics shown on the unit or
published in specifications, advertising or other
literature controlled by the manufacturer at
stated rating conditions.

3.3.1 Standard Rating.


A rating based on tests
performed at Standard Rating Conditions.
3.3.2 Application Rating. A rating based on tests
performed at Application Rating Conditions
(other than Standard Rating Conditions).
3.4

Rating Conditions.
Any set of operating
conditions under which a single level of
performance results, and which causes only that
level of performance to occur.

3.4.1 Standard Rating Conditions. Rating conditions


used as the basis
of comparison
for
performance characteristics.

ISHRAE/ANSI/ARI STANDARD 430-2008

3.5

"Shall," "Should," "Recommended" or "It Is


Recommended."
"Shall,"
"should,"
"recommended" or "it is recommended" shall be
interpreted as follows:

3.5.1 Shall. Where "shall" or "shall not" is used for a


provision specified, that provision is mandatory if
compliance with the standard is claimed.

2
3.5.2 Should, Recommended or It is Recommended.
"Should,"
"recommended"
or
"it
is
recommended" is used to indicate provisions
which are not mandatory
but which are
desirable as good practice.
3.6

Standard Air. Air weighing 1.2 kg/m3 [0.075


lb/ft3] which approximates dry air at 21.1C
[70.0F] and at a barometric pressure of 101.1
kPa [29.92 in. Hg]

Figure 1. BlowThrough Central Station Air-Handling Unit

Figure 2. Draw-Through Central Station Air-Handling Unit

ISHRAE/ANSI/ARI STANDARD 430-2008

Section 4. Classifications
4.1

Methods of Classification. Central station airhandling units may be classified according to the
following:
A. Unit Type
1. Blow-through
2. Draw-through
B. Application Type
1. Indoor
2. Outdoor

5.1.1.3Blow-Through Units. Blow-through units shall


be tested in accordance with ANSI/ASHRAE
Standard 51/AMCA Standard 210, except when
an outlet chamber with multiple nozzles within
the chamber is used. The test chamber crosssectional area may be sized so that the
maximum air velocity shall not exceed 400 fpm
[2 m/s]. The test chamber height and width shall
be at least 5% greater than the respective height
and width of the duct connection at the test
chamber.
Duct area at the test chamber
connection plane cannot exceed the duct area at
the unit connection plane.
5.2

Description of Test Unit. This standard permits


the omission of all appurtenances in the test unit
except the coil section, where used. Units to be
tested shall contain the largest cataloged face
area coil for that size and arrangement (where
applicable). The coil, fan sheave, and largest
internally mounted fan motor shall be mounted
in their most restrictive cataloged location
relative to the fan with the coil having a
pressure drop of at least 0.019 kPa [0.075 in.
H2O] at 2.54 m/s [500 fpm] coil face velocity with
Standard Air. The coil shall be de-energized
and the unit operating without coil by-pass. In
the case of a blow-through heating-cooling unit
with multiple discharge path, all but the cooling
coil position shall be blocked and the unit tested
with horizontal air discharge. The pressure
drop of the coils shall have been determined in
accordance with ARI-ISHRAE Standard 410.

5.3

Extension of Test Data. Test data may be


extended to other units in accordance with the
provisions of 5.3.1, 5.3.2 and 5.3.3.

Section 5. Test Requirements


5.1

Testing Requirements. All standard Ratings


shall be verified by tests conducted in
accordance with ANSI/ASHRAE Standard
51/AMCA Standard 210, except as modified by
5.1.1.3.

5.1.1 Arrangements for Testing.


5.1.1.1Single Outlet Draw-Through Units. Single outlet
draw-through units shall be tested in accordance
with
ANSI/ASHRAE
Standard
51/AMCA
Standard 210.
5.1.1.2Multiple Outlet Draw-Through Units. Multiple
outlet draw-through units shall be tested as
described above with each fan outlet ducted as
shown in Figure 3 to the air flow measuring
device. Individual fan outlet duct friction losses
shall not be included.

ISHRAE/ANSI/ARI STANDARD 430-2008

Figure 3. Multiple Fan Outlet Test Configuration

Figure 4. Dimensions for Inlet Vane Proportionality

ISHRAE/ANSI/ARI STANDARD 430-2008

5.3.1 Application of Fan Laws to Units with Inlet


Vanes. Units with inlet vanes may be rated one
of three ways:
1) using the fan laws as
described by 5.3.2 for proportional units with
proportional fans and inlet vanes; 2) using the
fan laws as described in 5.3.3 for proportional
units with non proportional fans and inlet vanes;
or 3) using the fan laws by applying the
appropriate inlet vane derate factors to units
without inlet vanes rated per Sections 5.3.2 or
5.3.3 when the inlet vanes of the test unit are
proportional to the inlet vanes of the rated units.
(Since all requirements for proportionality of
cabinets, fan
impellers, and
housing are
satisfied by provisions in either 5.3.2 or 5.3.3
without inlet vanes, rated units with inlet vanes
derived by inlet vane derate factors must only
meet inlet vane proportionality criteria.)
Inlet vanes are considered to be proportional
when the inlet vanes shall result in net air flow
areas not less than 92.5% of those derived from
exact proportionality (as defined in Section
5.3.2) when located within 0.5 impeller diameter
from the fan inlet. The test unit must be tested
with vanes in the wide open position as specified
by the manufacturer. Vane shaft angle, , (with
respect to fan shaft centerline) and the number
of vane blades for the rated unit must be the
same as for the test unit (see Figure 4). When
evaluating geometrical proportionality of inlet
vanes, the distance between vane and impeller
(defined as dimensions between impeller inlet
plane and the closest point of vanes with the
vanes at wide open position, as set by the
manufacturer) and the distance between cabinet
side and fan inlet shall be considered.
The method of rating one unit with inlet vanes
from the test of another is described in Sections
5.3.3.1 through 5.3.3.7.
5.3.2 Application of Fan Laws to Proportional Units
with Proportional Fans. Test data may be
extended by use of the fan laws to units
containing fans, geometrically proportional fan
cabinets and impellers (see Appendix C). The
fan impeller diameter of the unit to be calculated
shall not be less than 65% of the fan impeller
diameter of the test unit.
Fans are considered to be proportional when:
a.

Impeller width, housing development radii,


and housing width are proportional within
1.5%.

b.

Fan housing outlet area is proportional


within 3%.

Fan cabinets are considered to be proportional


when:
a. The clearance between the unit casing and
the nearest fan housing are proportional or
greater.
b. The clearance between adjacent fan
housings, as measured parallel to the fan
shaft, are proportional or greater.
c. The fan cabinet unit casing inlet and the fan
cabinet outlet air flow cross sectional areas
are not less than 92.5% of the respective
geometrically proportionate values.
d. Arrangement and location of internal
bearings and their supports, inlet vanes,
motors and drives, shall result in net air flow
areas not less than 92.5% of those derived
from exact proportionality when located
within 0.5 impeller diameter of the fan inlet.
The basis for proportionality in every case shall
be the respective impeller diameters; linear
dimensions shall be proportional to the diameter,
and areas shall be proportional to the square of
the diameter.
Single fan units may be rated from the test of a
multiple fan unit provided that the units are
otherwise proportional and that the clearance
between fans on the multiple fan unit is not more
than twice the proportionate clearance between
the cabinet and the fan housing on a single fan
unit. In no case, shall the ratings of a multiple
fan unit from tests of a single fan unit be
accepted. Air flow and fan shaft power are
considered to be proportional to the number of
fans.
Draw-through units which have a change in airflow direction between the coil and the fan
(Figure 5) may be rated from tests of units which
do not have this flow direction change (Figure 2)
provided the plenum causing the air direction
change be considered an appurtenance and the
effect of its application added to those of other
appurtenances as provided in 6.1.1 There is no
distinction in rating between a vertical discharge
and a horizontal discharge blow-through unit.
The effects of proportions of bolts, nuts, rivets,
etc., shall be considered to be negligible.

ISHRAE/ANSI/ARI STANDARD 430-2008

Figure 5. Draw-Through Unit With Air Flow Direction Change

5.3.3 Application of Fan Laws to Proportional Units


with Non-Proportional Fans. The requirements
for proportional fan impellers and scrolls set
forth in 5.3.2 are waived when all fans which are
not geometrically proportional are rated as fans
alone (as defined in 3.1) on the basis of tests
performed in accordance with ANSI/ASHRAE
Standard 51/AMCA Standard 210. This applies
only to fans of the same blade design.
Backward inclined fan impellers are not
considered to be the same design as airfoil
impellers. All other requirements of 5.3.2 shall
be met.
The method of rating one unit from the test of
another is as follows:
5.3.3.1Using the rating performance curve of the fan
alone (with or without inlet vanes) or unit
(without inlet vanes), create non-dimensional
performance curves including percentage wideopen cfm, percentage blocked tight static
pressure and percentage wide-open horsepower
(see Figure 6).

5.3.3.2To derive the rating performance curve for the


test unit without coil, add the test unit static
pressure data to the static resistance of the dry
coil as determined in accordance with ARIISHRAE Standard (see Figure 6).
5.3.3.3Superimpose on Figure 6 the unit rating
performance curve (with or without inlet vanes)
as derived under 5.3.3.2 at the same rev/s [rpm],
expressing the values in percentages of wideopen m3/s [cfm], blocked tight static pressure
and wide-open horsepower of the fan alone
(with or without inlet vanes) or unit (without inlet
vanes) (see Figure 6).
5.3.3.4For the unit which is to be rated, but not tested
use the rating performance curve of the fan
alone (with or without inlet vanes) or unit
(without inlet vanes) and plot percentages of
wide open m3/s [cfm], blocked tight static
pressure and wide-open horsepower in the
same way as for the solid line curve in Figure 6
(see Figure 7).

ISHRAE/ANSI/ARI STANDARD 430-2008


5.3.3.5Adjust the curves in Figure 7 by the
performance corrections between pairs of
curves as indicated in Figure 6. The resultant
curves are the calculated performance ratings
for the unit not tested, expressed in percentages
of performance of the fan alone (with or without
inlet vanes) or unit (without inlet vanes) (see
dashed lines in Figure 7).
5.3.3.6To determine the actual rating performance
values for the specific unit, multiply the
percentage values by the wide open cfm,
blocked tight static pressure and wide open
horsepower of the specific unit's fan alone (with
or without inlet vanes) or specific unit (without
inlet vanes) at the same rev/s [rpm] as in Figure
6 performance curves.

7
with coil in place, represent the performance of
the fan section alone without coil. Thus, as
appurtenance such as coils, filters, dampers,
etc., are added to the unit, their effects must be
taken into account in order to establish the
overall performance of the combined unit.
6.1.1.1The manufacturer shall provide the necessary
published data and procedures whereby the
effects of the appurtenances offered may be
taken into account. These effects shall be
stated in terms of pressure drop, in. kPa [H2O]
measured across the appurtenance over the
range of air quantities for which the unit is rated.
6.2

5.3.3.7The same procedure as for 5.3.3.6 applies to


multiple fan units, except that the cfm and
horsepower values for the fan alone (with or
without inlet vanes) are multiplied by the number
of fans before applying to the unit, with the
restrictions shown in the second paragraph of
5.3.2. Single fan units may be rated from the
tests of multiple fan units, but multiple fan units
shall not be rated from tests of single fan units.

Section 7. Minimum Data Requirements for


Published Ratings
7.1

Section 6. Rating Requirements


6.1

Air-Handling Ratings. Published air-handling


ratings shall be expressed in terms of the air
quantity, m3/s [scfm]; static pressure, in. kPa
[H2O] fan speed, rev/s [rpm]; and the power
required at the fan shaft, brake horsepower, W
[bhp] based on the procedures outlined in 5.2
and 5.3 of this standard.

6.1.1 Effect of Appurtenances.


The air-handling
ratings referred to in 6.1, while based on tests

Air-Handling Tolerances. To comply with this


standard, published air-handling ratings shall be
such that any unit shall produce its rated volume
and pressure with rpm not exceeding the
published rated rpm by more than 5% and
brake horsepower, W [bhp] not exceeding the
published rated brake horsepower, W [bhp] by
more than 7.5%.

Minimum Data Requirements for Published


Ratings.
Wherever application ratings are
published, they shall include a statement of the
conditions at which the ratings apply and be
accompanied by the pertinent Standard
Rating(s), clearly designated as such. The
following information shall be published for all
Standard Ratings.
a. Static Pressure, in kPa [H2O]
b. Air flow, m3/s [cfm]
c. Fan speed, rev/s [rpm]
d. Brake horsepower, W [bhp]

ISHRAE/ANSI/ARI STANDARD 430-2008

ISHRAE/ANSI/ARI STANDARD 430-2008

ISHRAE/ANSI/ARI STANDARD 430-2008

10

Section 8. Marking and Nameplate Data


8.1

Marking and Nameplate Data. As a minimum


the
nameplate
shall
display
the
manufacturers name and model designation.
Recommended nameplate voltages for 50
Hertz systems shall include one or more of the
utilization voltages shown in Table 1 of IEC
Standard Publication 38.

Section 9. Voluntary Conformance


9.1

Conformance. While conformance with this


standard is voluntary, conformance shall not
be claimed or implied for products or
equipment within its Purpose (Section 1) and
Scope (Section 2) unless such claims meet all
of the requirements of the Standard.

ISHRAE/ANSI/ARI STANDARD 430-2008

11

APPENDIX A. REFERENCES - NORMATIVE


A1

Listed here are all standards, handbooks and


other publications essential to the formation
and implementation of the standards. All
references in this appendix are considered as
part of the standard.

A1.1 ANSI/AMCA Standard 210-1997, Laboratory


Methods of Testing Fans for Rating, 1997,
and ANSI/ASHRAE Standard 51, Laboratory
Methods of Testing Fans for Ratings, 1985 (a
single
combined
standard),
American
National Standards Institute/Air Movement
and Control Association, Inc., 11 West 42nd
Street, New York, NY 10036, U.S.A./ 30
West University Drive, Arlington Heights, IL
60004, U.S.A./American National Standards
Institute/American Society of Heating,
Refrigerating,
and
Air-Conditioning
Engineers, Inc., 11 West 42nd Street, New
York, NY 10036, U.S.A./1791 Tullie Circle
N.E., Atlanta, GA 30329, U.S.A.

A1.2 ARI Standard 410-1991, Forced-Circulation


Air-Cooling and Air-Heating Coils, 1991,
4301 North Fairfax Drive, Suite 425,
Arlington, VA 22203, U.S.A.
A1.3 ARI Standard 110-1997, Air-Conditioning and
Refrigerating
Equipment
Nameplate
Voltages,
1997,
Air-Conditioning
and
Refrigeration Institute, 4301 North Fairfax
Drive, Suite 425, Arlington, VA 22203, U.S.A.
A1.4 ASHRAE
Terminology
of
Heating,
Ventilation,
Air-Conditioning
and
Refrigeration,
1991,
Second
Edition,
American Society of Heating, Refrigerating
and Air-Conditioning Engineers, Inc., 1791
Tullie Circle N.E., Atlanta, GA 30329, U.S.A.
A1.5 IEC Standard Publication 38, IEC Standard
Voltages, 1983, International Electrotechnical
Commission, 3, rue de Varembe, P.O. Box
131, 1211 Geneva 20, Switzerland.

APPENDIX B. REFERENCES - INFORMATIVE


B1

Listed here are standards, handbooks and


other publications which may provide useful
information and background but are not
considered essential. References in this
appendix are not considered part of the
standard.

B1.1 ANSI/ARI Standard 210/240-1994, Unitary


Air-Conditioning and Air-Source Heat Pump
Equipment,
1994,
American
National
Standards
Institute/Air-Conditioning
and
Refrigeration Institute, 11 West 42nd Street,
New York, NY 10036, U.S.A./4301 North
Fairfax Drive, Suite 425, Arlington, VA 22203,
U.S.A.
B1.2 ARI Standard 340/360-1993, Commercial
and Industrial Unitary Air-Conditioning and
Heat
Pump
Equipment,
1993,
Air-

Conditioning and Refrigeration Institute, 4301


North Fairfax Drive, Suite 425, Arlington, VA
22203, U.S.A.
B1.3 ARI Standard 420-1994, Unit Coolers for
Refrigeration, 1994, Air-Conditioning and
Refrigeration Institute, 4301 North Fairfax
Drive, Suite 425, Arlington, VA 22203, U.S.A.
B1.4 ARI Standard 440-1998, Room Fan Coils,
1998, Air-Conditioning and Refrigeration
Institute, 4301 North Fairfax Drive, Suite 425,
Arlington, VA 22203, U.S.A.
B1.5 ARI Standard 840-1998, Unit Ventilators,
1998, Air-Conditioning and Refrigeration
Institute, 4301 North Fairfax Drive, Suite 425,
Arlington, VA 22203, U.S.A.

ISHRAE/ANSI/ARI STANDARD 430-2008

12

APPENDIX C. CRITERIA FOR PROPORTIONALITY - INFORMATIVE


C1.

This appendix sets forth procedures and


equations that should be used to determine the
proportionality requirements of central standard.

C2

Basis of Proportionality.

C2.1

The following denotes the type of central station


unit being rated:

C.2.1.1

t refers to a unit with tested performance


rating.

C.2.1.2

c refers to a unit with calculated performance


rating.

C.2.2

Proportional linear dimensions (See Figure C1)


are determined using the following generic
equation:
(Linear Dimension) c

(Linear Dimension) t

Diameter c
Diameter t

(CI)

This ratio of the wheel diameters shall not be


less than 0.85.
C.2.3

3.1.6

The ratio of these distances shall be proportional


within + 1.5 percent.

C3.2

Areas

C.3.2.1

Fan Cabinet Air Inlet


2

GcWc

Area t

Diameter t

C3.1

Linear dimensions C, D, E1, E2, G


(See Figure CI).

The ratio of these areas shall be proportional


within + 3 percent.

C4.1

Proportional Linear Dimensions.

C4.1.1

Fan Wheel Width.

Mc
Mt

Ct

Kt
C.4.1.3

Dc
Dt

C3.1.3

E1 c
E1 t

C3.1.4

E2 c
E2 t

>

>

>

Diameter c
Diameter t

R MAX t

(C3)

Diameter c
Diameter t

(C4)

Diameter c
Diameter t

R MIN t

Gc
Gt

>

(C10)

(C5)

Diameter c

>

Diameter t

(C11)

Diameter c

>

Diameter t

Diameter c

>

Diameter t

C4.2

Proportional Areas.

C4.2.1

Fan Outlet Area


2

(C6)

JcKc

C4.2.2

Diameter c
Diameter t

(C13)

The ratio of these radii shall be proportional


within + 1.5 percent.

Diameter c
Diameter t

(C12)

C4.1.4

JtKt
C3.1.5

Diameter t

Fan Housing Radii

R MIN c
C3.1.2

Diameter c

>

Fan Outlet Width.

R MAX c
>

(C9)

Diameter t

C3.2.3

Kc

Cabinet Proportionality

Cc

Diameter c

(C2)

C3

C3.1.1

> 0.925

StTt

C4.1.2

Diameter c

(C8)

Diameter t

Fan Cabinet Air Outlet

ScTc

Proportional areas (See Figure CI) are


determined using the following generic equation:

Area c

> 0.925

GtWt
C3.2.2

Diameter c

(C7)

>

Diameter c
Diameter t

(C14)

The ratio of these areas shall be proportional


within + 3 percent.

ISHRAE/ANSI/ARI STANDARD 430-2008

S and T are inside dimensions of the cabinet outlet. R min and R max are measured from the
center of the shaft.

Figure C1. Dimensions Used for Proportionality Equations

13

You might also like