You are on page 1of 2

P.

O BOX No: 98769, Ph No: 0097142366212, Fax : 0097142366216


DUBAI, UAE.

Project :
Total Load
1.
2.
3.
4.
5.
6.
7.
8.

AC Unit
Booster Pump
Flood Light
Tube Light
Bath Room Light
Twin 13 A Switch
Exhaust Fan
Consider Spare Load

Total Load

3200 W
1500 W
750 W
400 W
50 W
1200 W
100 W
400 W

7600 W

Voltage Drop Calculation


Vd

= Mv *I * L
1000

Mv

= Approximate Voltage Drop

= Vd *1000

I*L
L

= Length

=300 Mtr

= Current

= 13.3 A

Vd=Assume Maximum Permissible Voltage drop is 4% of 400 volt = 16 V


Mv

= 16*1000 =4.1mV
13.3*300

Suggestible cable size for Approximate Voltage drop at 4.1 Mv is 16 mm2 XLPE
cable.

Yours Sincerely

Lin Mathew
Projects Manager
0553314740