Professional Documents
Culture Documents
1.INTRODUCTION:
The transformer is a vital apparatus in the electrical equipment in every stage viz.
Generation, transmission, distribution and utilization of electricity. Failure of a transformer in
the chain causes interruption in electricity supply and dislocation of all the works going on.
Care and maintenance of the transformer therefore requires attention from time to time to
avoid sudden, unpredicted failure. If a developing defect is detected early, remedial action
can be taken immediately and service continuity of the transformer maintained.
The troubles which would occur in service, methods of detecting them early and
remedies & repairs to bring back the transformers in service are described below.
The transformer in service may fail according to nature of troubles developed in the
transformer itself or due to some external causes. The external causes may be excessive
overloading on the transformer, short circuits near the transformer, failure of other auxiliary
equipment nearby, failure of its controlling breaker, failure of protection to operate and so
on. Internal causes of failure are failures of transformer insulation, failure of winding due to
excessive heating, internal short circuits, failure of winding joints, ingress of moisture in the
oil and insulation, deterioration of insulating oil, and failure of other auxiliary internal
equipment, such as reactor of the tap changer, contacts of the tap changer etc.
Failure of transformer can also take place if proper care has not been taken during its
erection. While receiving the transformer, unloading, storing and assembling, the instructions
of the manufacturer should be followed strictly. If the transformer is received with oil inside,
all care as if the transformer is in service, is required with nitrogen gas. A very strict watch is
required on maintenance of pressure and purity of gas, all the time the transformer is stored.
The auxiliary equipment such as radiators, conservator, piping, explosion vent are to be
stored with proper care. Conservator and radiators should be maintained airtight. The HT and
LT bushings should be immediately tested and H. T. bushings stored vertically. Similarly while
assembling the transformer every equipment such as H. T. & L. T. bushings of the
transformer windings, oil tap changer, diverter tank, connections of lead with bushing etc.
should be tested separately according to standards specified.
If the erection and commissioning is done properly, maintenance is required on the
transformer to judge the performance in service. It consist of regular inspection, testing and
reconditioning wherever necessary.
2. Factors affecting the life of the transformer : (i.e. factors responsible for degradation of
insulation.)
The normal expected life of a power transformer is about 35 years. Life of a power
transformer essentially means life of its insulation system comprising mainly : i) Solid
dielectric [paper, varnish, cloth, pressboard]; ii) Liquid dielectric [mineral oil].
A.EffectofMoisture
Transformer oil readily absorbs moisture from the air. This water in oil decreases the
dielectric strength of the oil as well as that of the insulating paper which absorbs and stores
the moisture due to higher affinity of water to paper than to oil.
254
B.EffectofOxygen
Oxygen may be present inside the transformer due to air remaining in oil, air pockets
trapped in the winding etc. The oxygen reacts on the cellulose of the insulating paper, and
the decomposition products of the cellulose lead to the formation of organic acids which
dissolve in oil and consequently form sludge. This sludge blocks the free circulation of the oil.
Thus the adverse effect of oxygen, which may be aggravated by catalytic action between
hot oil and bare copper, increases the operating temperature.
C.EffectofSolidImpurities/Dirtetc.
The dielectric strength of oil is appreciably diminished by even minor quantities of solid
impurities present in the oil. New transformers may contain particles of insulating materials
and other solid impurities. It is therefore a good practice to filter the oil after it has been in
service for a short time, especially for the units of higher-voltage class.
D.EffectofVarnishes
Some varnishes, particularly of the oxidizing type, enter readily and react with the
transformer oil and precipitate sludge on the windings. Synthetic varnishes having acidinhibiting properties generally delay the natural formation of acid and sludge in the oil. This
factor needs consideration during maintenance.
E.EffectofSlacknessofWinding
Slackness of windings may cause a failure due to repeated movement of coils, which
may wear the conductor at some places and lead to an inter-turn failure. The coils may also
get displaced under load conditions or momentary short circuits, which may cause electric
and magnetic unbalance and produce even greater displacement. It is therefore a good
practice to lift the core and windings of a transformer and correct any slackness, by
tightening the tie rods or pressure screws, during the first inspection.
F.AgingofInsulation
The aging of insulating materials is defined as irreversible negative change of
pertinent property. The quality of insulation declines during the aging process, to different
extents, depending upon various operating conditions, due to both physical and chemical
effects. The dielectric strength of the conductor insulation deteriorates extremely slowly. If
the same is not mechanically disturbed much. However, mechanical properties (tensile
strength) deteriorate more significantly in the course of time, and are hence taken as the
criteria to determine aging of paper.
G.OperatingTemperature
If the sustained operating temperature of the insulation exceeds the normal operating
temperature limit of 980C (hot spot temperature), there will be a shortening of life of the
transformer. In this condition, loading procedure as per IS-1972 define the life of material in
the insulating system as influenced by temperature alone, which may also be affected by
mechanical and electrical stresses.
3. MAINTENANCE OF TRANSFORMERS i) Transformers require only a little care as far as day
to day work is concerned Maximum temperature of oil corresponding to load and atmosphere
condition, oil level in the
255
electrical load conditions, and transformer hum etc. are the factors requiring regular
observation. ii) The transformer in service should not be subjected to overvoltage and
overload. Incoming
voltage, and taps should be correctly adjusted. iii) Every transformer has a cooling
system to limit the temperature rise of the transformer. The loading of transformer in KVA
depends on the temperature rise and therefore the cooling system should be maintained in
good condition. If ventilation fans do the cooling they must be available at the set value of
temperature as recommended by the manufacturer. For the transformer oil systems, cooled
by water, sufficient quantity of clean water should be available. Coolers also should be
maintained clean. Watch should be kept for leakage if any in the oil cooler. Alarms for
stoppage of oil and water flow should be maintained in working order. Instructions available
for the ventilation and cooling of the transformer should be strictly followed. All small
naturally cooled transformers should be installed at well ventilated places. Permissible
continuous overloading for a short period and overloading during emergency is determined by
the normal running temperature and therefore the transformer should be run at temperature
as low as possible. iv) General maintenance of the transformer demands cleanliness of the
surrounding yard and the transformer with all its auxiliaries, leakages of oil should be
attended as quickly as possible. Silicagel in breathers should be replaced as soon as it
indicates wetness by change of colour. All the silicagel breathers are provided with sealing oil
and the latter should be replaced from time to time. Foundation and fixing should be checked
for firmness. Checking performance of radiators, cooling system equipment, earthing of the
transformer, temperature-indicating instruments, signals and protection equipment of
transformers should be done regularly. v) The current transformer, potential transformer
lightening arrestor, isolators, circuit breakers installed for the transformers should also be
maintained in order. Current transformers and potential transformers also require equal care
as the main transformer. Contact resistance of isolators & circuit breaker will also effect the
performance of the transformer. All these equipment should be maintained in order.
vi) Due to leakage in the transformer, oil topping up is necessary. Lot of research and
experiments are going on, regarding mixing of oils. The results indicate that the oil of two
different sources though conforming to the same standards should not be mixed as the
sludging properties of the oil are considerably affected by mixing. Topping up of oil should
therefore, be done by the original grade of the oil as far as possible. If the mixing up of two
grades is unavoidable, the two grades of oils should be tested thoroughly before mixing.
Topping up with mixed oil should be undertaken only when oil topped up is small in comparison
to total transformer oil content, if the results of test show similarity of characteristics.
Recommendationsformaintenance:A.General:
No work shall be done on any of the transformers unless it is disconnected from
external circuits and all windings have been fully earthed. Naked lights and flames should be
kept well
256
away from the transformer while doing maintenance. Oil level should be reduced below tank
cover while opening nuts and bolts on cover and before unsealing the tank, radiators,
257
unscrewing the vent screw, oil level comes in gauge glass centre otherwise remains
258
checked for satisfactory level. Test tap be kept earthed after the test is over. Bushing
arcing horn gap be adjusted properly as per operating voltages. Oil level in bushing gauge
glass be properly maintained with transformer oil of the same grade and quality.
I.Externalconnectionsincludingearthing:
All connections should be tight. If they appear balckened or corroded, unbolt the
connection and clean down to the bright metal with emery paper. Remake the connections
and give it a heavy coating of grease. It is particularly important that heavy current carrying
connections should be properly maintained.
Before opening the transformer at site (i.e. untanking the active part), Manufacturer
specific instructions be made available and followed scrupulously with care.
J.Gasket:
Check the transformer for leakages periodically. The bolts should be tightened evenly
around the joints to avoid uneven pressure. Broken or leaking gaskets should be replaced as
soon as possible with proper jointing & fixing.
K.Rollers:
After the transformer has been in service for a long period, roller should be examined
carefully. They should be greased and rotated to see that they turn freely.
L.Paintwork:
During storage and service, the paint work should be critically inspected atleast once
a year and where necessary painting and retouching be carried out. If the metal surface is
exposed and becomes rusty or greasy due to delay in touching work, the surface must be
thoroughly cleaned before repainting with primer and final paint. Paint as mentioned in the
General Arrangement drawing of transformer should be used. In case paint of another
chemical base is to be used, paint manufacturer should be consulted for compatibility with
existing paint.
M.RecommendedMaintenanceSchedulefortransformers:
The maintenance schedule given below is to be used as a general guide under normal
conditions. The frequency of inspection should also be determined by the size of the
transformer and local climatic conditions.
N.MaintenanceSchedule:
The maintenance schedule given in Annexture is a good indication of the attention
required to be given to the transformer under normal conditions.
4.TYPESOFDAMAGESINFAILEDTRANSFORMERS:
The types of damages generally noticed in failed transformers are as follows: i) Cut in
delta (HT) formation; ii) Cut in star (LT) formation; iii) Damage to winding (HT or LT or both);
iv) Damage in LT bushing stem; v) Defect in tap changer; Puncture in explosion vent
diaphragm; vi) Defect in breather;
259
vii) Flash over of bushing; viii) Buldge in tank; ix) Choke in radiator tubes; x) Deteriorated oil.
xvi) Remove the air through vent plug of the diverter switch before you energize the
transformer. xvii) Check the oil level in the diverter switch and if found less, top up
with fresh oil conforming
to IS: 335. xviii) Check the gearbox oil level, if less, top up with specified oil. xix)
Examine and replace the burnt or worn out contacts as per Maintenance Schedule. xx) Check
all bearings and operating mechanism and lubricate them as per schedule. xxi) Open the
equalizing valve between tank and OLTC, wherever provided at the time of
filling the oil in the tank. xxii) Connect gas cylinder with automatic regulator if
transformer is to be stored for long, in
order to maintain positive pressure. xxiii) Fill the oil in the transformer/ reactor at the
earliest opportunity at site and follow
storage instructions. xxiv) Check the door seals of marshalling Box. Changes the
rubber lining if required. xxv) Equalize the diverter compartment of the OLTC by connecting
equalizing pipe between
flange joints provided on the tap changer head.
6. DONTS FOR POWER TANSFORMER/ REACTOR i) Do not energize without thorough
investigation of the transformer/ reactor, whenever
any alarm of protection has operated. ii) Do not re-energize the transformer/ reactor,
unless the Buchholz gas is analyzed. iii) Do not re-energize the transformer/ reactor without
conducting all precommissioning
checks. The results must be comparable with results at works. iv) Do not handle the
off-circuit tap switch when the transformer is energized. v) Do not energies the transformer,
unless the off-circuit tap switch handle is in locked
position. vi) Do not leave off circuit tap switch handle unlocked. vii) Do not leave
tertiary terminals unprotected outside the tank, connect them to tertiary
lightning arrestors protection scheme, when connected to load. viii) Do not allow WTI/
OTI temperature to exceed 650C during dryout of transformer, and
filter machine temperature beyond 700C. ix) Do not parallel transformers that do not
fulfil the condition of paralleling. x) Do not use low capacity lifting jacks on transformer/
reactor for jacking. xi) Do not move the transformer/ reactor with bushings mounted. xii) Do
not overload the transformer other than the specified limits as per IS : 6600. xiii) Do not
change the settings of WTI and OTI alarm and trip frequently. The setting
should be done as per the site condition. xiv) Do not leave red pointer behind the
black pointer in OTI and WTI. xv) Do not leave any connection loose. xvi) Do not meddle with
the protection circuits. xvii) Do not allow conservator oil level to fall below 14 level. xviii) Do
not allow oil level in the bushings to fall below minimum level xix) Do not leave marshalling box
doors open, they must be locked. xx) Do not switch off the heater in marshalling box except
to be periodically cleaned.
261
xxi) Do not allow dirt and dust deposits on bushings, they should be periodically cleaned. xxii)
Do not allow unauthorized entry near the transformer/ reactor. xxiii) Do not leave ladder
ANNEXTURE
NO.FREQ.OFITEMSTOBEINSPECTIONACTIONREQUIRED
INSPECTIONINSPECTEDNOTESIFINSPECTIONSHOWS
UNSATISFACTORYCONDITIONS
1 Hourly Ambient Temp. - 2 do Winding Temp. Check that temp. Shut down the transformer
rise is reasonable and investigate if either is
3 do Oil temperature persistently higher than normal.
4 do Load (amperes) Check against Note: An improper tap position
5 do Voltage rated figure can causeexcessive core loss.
6 Daily Oil level in Check against If low, top up with dry oil,
transformer & transformer oil examine transformer for leaks. on load tap temperature. changer
7 do Relief vent diaphragm - Replace if cracked or broken.
8 do Dehydrating breather Check colour of If silica gel is pink change by
the active agent. spare charge. Oil level in the oil filled Oil level should be
The old charge may be dehydrating breather. changing with reactivated for further use.
change in temp. of oil. Clear the Air path.
9 Quarterly Bushing Examine for cracks Clean or replace.
and dirt deposits.
10 do Oil in transformer Check for dielectric
and tap changer. strength and water Take suitable action to restore
content. quality of oil.
11 do Cooler fan and pump Lubricate bearings, Take suitable action to restore bearings
motors and check gear box. quality of oil. Replace burnt or operating mechanism Examine contacts
worn out contacts or other parts.
check manual control & interlocks.
12 do On load tap changer Lubricate bearings, Replace burnt or worn out
driving mechanism check gear box oil contacts or other parts.
level and examine contacts.
13 do On load tap changer Check all circuits automatic control independently.
Check step by step switch operation including limit switches.
263