You are on page 1of 9

Page 28 of 36

DOCUMENT NO: PE-V6-367-100-N003

PROJECT: 1X 700 MW BELLARY TPS, UNIT-III


LT - MOTORS
DATASHEET
SL.
1.0

2.0

DESCRIPTION
LT Motors
GENERAL
i. Manufacturer & country of origin
ii. Equipment driven by motor
iii.Motor type (Squirrel cage/slip ring/DC etc.)
iv.Quantity
DESIGN & PERFORMANCE DATA
i. Frame
ii. Type of duty
iii. Type of enclosure and method of cooling.
Degree of protection
iv. Applicable standard to which motor generally conforms
v. Type of mounting
vi. Direction of rotation as viewed from Driving End
vii.Standard continuous rating at 40 deg C amb. temp. as per Indian
Standard (KW)
viii. Derated rating for specified normal condition ie 50 deg C ambient
temp (KW)
ix. Rated voltage (volts)
x. Permisible variation of
a. Voltage (Volts)
b. Frequency (Hz)
c. Combined voltage and frequency
xi. Min. permissible starting voltage(Volts)
xii. Rated speed at rated voltage and freq. ( rpm)
xiii. At rated Voltage and frequency
a. Full load current, Amp
b. No load current, Amp (Approx)
xiv. Power factor at
a. 100% load
b. No Load
c. Starting
xv. Efficiency at rated voltage and frequency. ( % )
a. 100% load
b. 75% load
c. 50% load
xvi. Starting current (amps) at
a. 100% voltage
b. 85% voltage
c. 80%voltage
xvii. Starting time with minimum permissble voltage (sec.)
a. Without driven equipment coupled
b. With driven equipment coupled
xviii. Safe stall time with 110% of rated voltage
a. From hot condition (sec)
b. From cold condition (sec)
xix. Torques
a. Starting torque at min.permissible voltage, % FLT
b. Pull up torque at rated voltage, % FLT
c. Pull out torque(% FLT)
d. Min.accelerating torque (kg.m) avl.
e. Rated torque (kg.m)
xx. Stator winding resistance per phase (ohms at 20 Deg.c) - approx.
xxi. GD2 value of motors ( kg- sq m)
xxii. No.of permissible successive starts when & motor is in hot
condition & cold condition
xxiii.
a. Locked rotor KVA input
b. Locked roter KVA/KW

VENDOR DOC. NO. FPL/990-60/PS


BHEL DOC NO.: PE-V6-367-100-N003

ABB
BOILER FILL PUMP
Squirrel Cage
1 NO.
M2BA315MLA4K
S1
TEFC
IP55
IS-325-1996
B3
Bi-directional
NOT APPLICABLE AS THE MOTORS ARE DESIGNED FOR 50 Deg.C AMBIENT
TEMPERATURE
132
415V
+/-10%
+5/-5%
10%
80 % of Rated Voltage
1485
216
61
0.89
0.04
0.2
95.5
95.5
94.5
1296
1102
1037
0.5 SECS
1.06 SECS
28
57
134%
200%
240%
> 10% of Full load torque
86.5
13.5
2 hot & 3 cold starts

932
7.06

DOCUMENT NO: PE-V6-367-100-N003

Page 29 of 36

BOILER FILL PUMP

Equipment driven by motor


xiv.Bearings
a. Type, DE / NDE
b. Manufacturer
c. Self lubricated or forced lubricated
d. Recommended lubricants
e. Guaraneed Life in hours
f. whether Dial type thermometer provided
g. Oil pressure Gauge/switch
i. Range
ii. Contact nos & ratings
iii. Accuracy
xxv. Vibration
a. Velocity (mm/s)
b. Displacement (Microns)
xxvi. Noise level (dB)
xxvii.Maximum Power requirement of driven equipment(KW)
CONSTRUCTION FEATURES
i. stator winding insulation
a. Class & type
b. Tropicalised (Yes/No)
c. Temperature rise over specified max.
i. cold water temperature of 38 Deg
ii. Ambient air 50 Deg C
d. Method of temperature measurement
e. stator winding connection
f. Number of terminals brought out.
ii. Type of terminal box for
a. stator leads
b. space heater
c. temperature detector
d. Instrument switch etc.
iii. For main terminal box
a. Location

3.0

Ball / Ball
SKF
SELF LUBRICATED
LITHIUM BASED GREASE
40,000 HRS
NOT APPLICABLE FOR LT MOTORS
NOT APPLICABLE FOR LT MOTORS

IS 12075
IS 12065
109.62

F limited to class B
YES
N.A.
70 Deg. C
Resistance
Delta
SIX
Detachable, Non-Phase Segregated, Stud type
Detachable
Not Applicable for LT Motors
Not Applicable for LT Motors
On R.H.S. as viewed from Driving End of motor

b. Entry of cables
c. Recommended cable size
d. Fault level (MVA)
iv. Temperature detector for stator winding
type
Nos provided
Location
Make
Resistance value at 0 deg.C (ohms)
v. Space heaters
a. Number
b. Location
c. Power requirement (W)
vi. Paint shade
vii. weight of ( approx. )
a. Motor stator (KG),.
b. Motor rotor (KG)
c. Total weight (KG)
viii. Cable Gland shall be heavy duty double compression type and nickel
cromium
plated
brass
cable duty
glaand
confirming
ix Cable Lugs
shall
be heavy
tinned
copperto BS-6121
4.0
CHARECTERISTIC CURVES
i. Torque Slip charecteristic of the motor
ii. Caliberation charecteristic of platinum type resistence temperature
detector
iii.
Caliberation charecteristic of platinum BTD
iv. Thermal withstand charecteristic
v. Starting current Vs Time
vi. Starting current Vs Speed
vii. Negative sequence current Vs Speed
viii. P.F. and Eff. Vs Load
NOTE : ALL DATA EXCEPT STARTING CURRENT ARE SUBJECT TO TOLERANCE AS PER IS-325' 1996
Additional Information
1
2
3
4
5
6

Method of Starting
Starting Current % FLC
Grounding Terminals
Whether Motors stall at 70 % voltage
Power Factor @ 75 % / 50 %
Safe stall time
HOT (SECS)
COLD (SECS)

Refer to GAD
2R x 3C x 240 Sqmm
50 KA for 0.25 sec with BREAKERprotection
Not Applicable for LT Motors

2
Wdg. Overhang
50 W *2
631 OF IS-5
720
390
1110
OK
OK
Enclosed
Not Applicable for LT Motors
Not Applicable for LT Motors
Enclosed
Enclosed
Enclosed
Not Applicable for LT Motors
Enclosed

DOL
600 % Inclusive of IS tolerance
2 on body 1 on TB
NO
0.85/0.77
80 %
100%
53
34
108
70

Page 30 of 36
DOCUMENT NO: PE-V6-367-100-N003

Load Current & Speed v/s Time

1600

1400

1400

1200
1000

1000
800
800
600
600

Current [A]

Speed [r/min]

1200

400

400

200

200
0

0
0

0.1

0.6

0.5

0.4

0.3

0.2

time [s]
Speed

Current

calculated catalog values, binding data on request


Date
19/10/12
GD2 motor [kgm2]
Rating[kW]

13.5
132.00

Full load torque(Nm)


Full load speed[r/min]

Motor Type

M2BA315MLA4k

849

FLC in Ampre

216.0

1485

Voltage (volts)

415

1296.0

0.58

(1.06)

Current at start[A]
GD2 Load[kgm2] at
Motorspeed

4.70

starttime[s]
(80%D)

(53.1)
Project

Ref

Page 31 of 36

DOCUMENT NO: PE-V6-367-100-N003

TORQUE & CURRENT / SPEED CURVES

6.00

2.50

5.00

2.00

1.50
3.00
1.00

Torque [T/Tn]

Current [I/In]

4.00

2.00

0.50

1.00

0.00
0

200

400

600

800

1000

1200

1400

0.00
1600

Speed [r/min]
I/In at Un

T/Tn at Un

Load T/Tn

calculated catalog values, binding data on request


Date
19/10/12
Full load torque(Nm)
GD2 motor [kgm2]
13.5
Rating[kW]

132.00

Full load speed[r/min]

T/Tn at 80%UnD

M2BA315MLA4k
849

FLC in Ampre

216.0

1485

Voltage (volts)

415

1296.0

0.58

(1.06)

Current at start[A]
GD2 Load[kgm2] at
Motorspeed

Project

4.70

Ref

starttime[s]
(80%D)

(53.1)

Page 32 of 36
DOCUMENT NO: PE-V6-367-100-N003

LOAD PERFORMANCE CURVES

1.40

1.000
0.900

1.20

0.600

0.80

0.500
0.60

0.400
0.300

I/In

1.00

0.700

Slip % /

Power Factor

/ Efficiency

0.800

0.40

0.200
0.20
0.100
0.000
0.00
0.000 0.200 0.400 0.600 0.800 1.000 1.200 1.400
P/Pn
Cosphi

Effcy.

Slip

I/In

M2BA315MLA4k

Date

19/10/12

Rating [kW]

132

Full load speed


[min-1]

1485

Voltage [volts]

415

FLC [amps]

216.0

Full load torque


[Nm]

848.8

Frequency [Hz]

50

CUSTOMER

REF

Page 33 of 36

DOCUMENT NO: PE-V6-367-100-N003

Thermal withstand curve

10000
HOT
COLD

Time, sec

1000

100

10

1
200

600

400

800

% Current

Voltage,%

CUSTOMER

100

M2BA315MLA4k
REF

DOCUMENT NO: PE-V6-367-100-N003

Page 34 of 36

DOCUMENT NO: PE-V6-367-100-N003

Page 35 of 36

DOCUMENT NO: PE-V6-367-100-N003

Page 36 of 36